Schedulloae of Loads & Computations

The document outlines the schedule of loads and circuit protection for 16 circuits in a home. It lists each circuit's load description, voltage, volt-amperes, current, circuit protection type and rating, required feeder conductor size and type, and electrical grounding conductor size. The total connected load is calculated to be 96.77 amps. Based on this load calculation, the document recommends using a 100 amp, 100 amp fuse, 2-pole, 10,000 amp interrupting capacity main circuit breaker box with 2-38mm2 copper wires plus an 8.0mm2 copper grounding wire.

Uploaded by

Sinn Raven
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
613 views2 pages

Schedulloae of Loads & Computations

The document outlines the schedule of loads and circuit protection for 16 circuits in a home. It lists each circuit's load description, voltage, volt-amperes, current, circuit protection type and rating, required feeder conductor size and type, and electrical grounding conductor size. The total connected load is calculated to be 96.77 amps. Based on this load calculation, the document recommends using a 100 amp, 100 amp fuse, 2-pole, 10,000 amp interrupting capacity main circuit breaker box with 2-38mm2 copper wires plus an 8.0mm2 copper grounding wire.

Uploaded by

Sinn Raven
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

SCHEDULE OF LOADS AND

CIRCUIT PROTECTION
CKT NO. LOAD DESCRIPTION VOLT VA CURRENT (A)
AT AF
1 LIGHTING OUTLET 230 300 1.30 15 100
2 LIGHTING OUTLET 230 750 3.26 15 100
3 LIGHTING OUTLET 230 600 2.61 15 100
4 LIGHTING OUTLET 230 500 2.17 15 100
5 CONVENIENCE OUTLET 230 720 3.13 20 100
6 WATER HEATER (GFCI) 230 3500 15.22 30 100
7 WASHING MACHINE (GFCI) 230 500 2.17 20 100
8 REF OUTLET 230 800 3.48 20 100
9 3/4 HP WATER PUMP 230 1587 6.90 20 100
10 CONVENIENCE OUTLET 230 900 3.91 20 100
11 1.5 HP ACU 230 2300 10.00 30 100
12 1 HP ACU 230 1840 8.00 20 100
13 CONVENIENCE OUTLET 230 720 3.13 20 100
14 WATER HEATER (GFCI) 230 4500 19.57 30 100
15 1 HP ACU 230 1840 8.00 20 100
16 CONVENIENCE OUTLET 230 900 3.91 20 100
TOTAL CONNECTED LOAD 96.77
IF = 96.77 + 25% (10) = 99.27A USE: 1
2-
ADS AND COMPUTATIONS
CIRCUIT PROTECTION FEEDER CONDUCTOR
EGC CONDUIT
POLE kAIC TYPE SET SIZE & TYPE
2 10 MCB 1 2 - 2.0 mm2 THHN - 20 mm2 Ø PVC
2 10 MCB 1 2 - 2.0 mm2 THHN - 20 mm2 Ø PVC
2 10 MCB 1 2 - 2.0 mm2 THHN - 20 mm2 Ø PVC
2 10 MCB 1 2 - 2.0 mm2 THHN - 20 mm2 Ø PVC
2 10 MCB 1 2 - 3.5 mm2 THHN 1- 3.5 mm2 THHW 20 mm2 Ø PVC
2 10 MCB 1 2 - 3.5 mm2 THHN 1- 3.5 mm2 THHW 20 mm2 Ø PVC
2 10 MCB 1 2 - 3.5 mm2 THHN 1- 3.5 mm2 THHW 20 mm2 Ø PVC
2 10 MCB 1 2 - 5.5 mm2 THHW 1- 5.5 mm2 THHW 20 mm2 Ø PVC
2 10 MCB 1 2 - 3.5 mm2 THHN 1- 3.5 mm2 THHW 20 mm2 Ø PVC
2 10 MCB 1 2 - 3.5 mm2 THHN 1- 3.5 mm2 THHW 20 mm2 Ø PVC
2 10 MCB 1 2 - 3.5 mm2 THHW 1- 3.5 mm2 THHW 20 mm2 Ø PVC
2 10 MCB 1 2 - 5.5 mm2 THHW 1- 3.5 mm2 THHW 20 mm2 Ø PVC
2 10 MCB 1 2 - 3.5 mm2 THHN 1- 5.5 mm2 THHW 20 mm2 Ø PVC
2 10 MCB 1 2 - 3.5 mm2 THHN 1- 3.5 mm2 THHW 20 mm2 Ø PVC
2 10 MCB 1 2 - 5.5 mm2 THHW 1- 3.5 mm2 THHW 20 mm2 Ø PVC
2 10 MCB 1 2 - 3.5 mm2 THHN 1- 3.5 mm2 THHW 20 mm2 Ø PVC

USE: 100AT, 100AF, 2P, 10kAIC, MCCB


2 - 38 mm2 THHN Copper Wire + 8.0 mm2 THHW Copper Wire (EGC)