SENLAN SB200 - VARIABLE SPEED DRIVE PARAMETER SETUP FOR ADVANCED SLEEP/WAKE PID PRESSURE CONTROL

0: Control Panel (EXT Exinguished) Set this to 0 if you are using the
Command Execution Channel
F0-02 1: Terminal (EXT Illuminated) 0 x 1 0 2 control panel or 1 if you are using
Options
2:Communication Control (EXT Flashing) the terminals FWD and GND
F0-08 Lower Frequency Limit 0.00Hz ~ F0-07 "Upper Frequency Limit" 0.00Hz x 0.00Hz
0: Both clockwise and anti-cockwise direction is applicable
F0-09 Direction Lock 1: Clockwise direction lock 0 o 1 0 2
2: Anti-clockwise direction lock
Set this according to the voltage
F2-13 Max. Output Voltage 150 ~ 500V 380V x 400V 150 500
on the motors plate
Depend Depends on inverter
F3-00 Rated Power 0.40 ~ 500.00kW s on x 0.4 500
model No.
inverer
F3-01 Number of Poles 2 ~ 48 4.00% x 4.00% 2 48

Depend Depends on inverter Set all these parameters according


F3-02 Rated Current 0.5 ~ 1200.0A s on x 0.5 1200
model No. to the motors plate
inverer
F3-03 Rated Frequency 1.00 ~ 650.00Hz 50.0Hz% x 50.0Hz% 1 650

Depend Depends on inverter


F3-04 Rated Rotation Speed 125 ~ 40000r/min s on x 125 40000
model No.
inverer
Output Functions of Relay Set this to activate an external
F5-02 0 ~ 59 ; refer to the following table of definitions of digital output functions 6 x 1 0 59
Output T1 cooling fan

Output Functions of Relay


F5-03 0 ~ 59 ; refer to the following table of definitions of digital output functions 24 x 6 0 59 Set this to activate a fault output
Output T2

Set this to 1 in the beginning and


until you have the system running
0: PID control is not selected
properly and have determined the
1: PID control is selected
F7-00 PID control function options 0 x 3 0 3 lowest frequency against a closed
2: PID is selected for frequency settings modification
system. Then change to 3 once all
3: PID control is selected for frequency settings of constant pressure water supply
settings have been made in F8
group

0: F7-04
1: AI1
2: AI2
3: AI3
Set this to 0 if you are using F7-04
4: UP/DOWN adjustment
F7-01 Channel Setting Options 0 x 1 0 9 as your refernce. Set this to 1 if
5: PFI
you are using an external POT
6: Communication Settings
7: AI-AI2
8: AI1 + AI2
9: Panel potentiometer

0: AI1
1: AI2
2: AI3
3: AI1 - AI2
4: AI1 + AI2
5: √AI1
F7-02 Feedback Channel Option 0 x 1 0 11
6: √AI2
7: √AI1-AI2
8: √AI1 + √AI2
9 PFI
10: MAX (AI1~AI3)
11: MIN(AI1~AI3)

F7-03 PID Reference Value 0.00 ~ 100.00 (transducer measurement range) 10 o 100 0 100

Set this to the system pressure you


F7-04 PID Digital Settings -F7-03 ~ F7-03 5 o 40
require

F7-06 Integral Time 1 0.01 ~ 10.00s 20.00s o 0.5s 0 10

0 = Nothing
1 = Alarm (only) [AL.FBL1 for analogue input 1, AL.FBL2 for analogue input 2, AL.FBL3 for analogue
input 3]
Analogue Input Feedback 2 = Error and deceleration shutdown and alarm AL.FBL [Er.FBL1 for analogue input 1, Er.FBL2 for
Software Revision V1.24

F7-29 0 o 2
Abnormality analogue input 2, Er.FBL3for analogue input 3]
3 = Error and free shutdown [Er.FBL1 for analogue input 1, Er.FBL2 for analogue input 2, Er.FBL3for
analogue input 3]

Set the minimum pressure the


Analogue Input Feedback
F7-30 0.00 ~ 100.00% (0.00% = Ignore) 50% o 1% system must always have when
Abnormality Level (%)
running. Dry run protection.
Analogue Input Feedback
F7-31 Set in seconds from 0 to 3600 60 o 45
Abnormality Time (s)

0: Water supply function is not selected


1: Common PI-regulated constant-pressure water supply
F8-00 Water Supply Mode Options 2: Water level control 0 x 1 0 4
3: Pumps are started by one in the sequence base on water pump capacity
4: Firefighting water supply

Units Digit: No. of variable-frequency cyclic switchover pumps 1 ~ 5


Tens Digit: No. of auxiliary pumps : 0 ~ 4
Hundreds Digit 0: Direct startup 1: Startup by soft starter
Thousands Digit: Sleeping and sleeping pump options
Water Pump Settings and 0: The sleep pump is not selected
F8-01 00001 x 03001
Sleeping Otions 1: The sleeping pump works at a variable frequency
2: The sleeping pump works at a line frequency
3: The main pump is in sleeping mode
Ten thousand Digit: Drainage pump Options
0: Drainage pump not under control 1: Drainage pump under control
SENLAN SB200 - VARIABLE SPEED DRIVE PARAMETER SETUP FOR ADVANCED SLEEP/WAKE PID PRESSURE CONTROL

Set this frequency 0.5Hz above the


lowest frequency you read when
F8-20 Sleeping Frequency 1.00 ~ 50.00Hz 40.00Hz o 40.00Hz 1 50
the system is working against a
closed system

Set this time before the system


will go to sleep once pressure is
F8-21 Sleeping Latency time 1.0 ~ 1800.0s 60.0s o 60.0s 1 1800 equal to the reference value and
the frequency is below F8-21
above

F8-22 Wakeup deviation settings -F7-03 ~ F7-03 -0.20 o -0.20 Try this with the factory default

F8-23 Wake Up Time delay 0.1 ~ 300.0s 30.0s o 30.0s 0.1 300

Monitoring Parameter Option


FC-02 -1 ~ 50; -1 means void; 0 ~ 50 mean FU-00 ~ FU-50 1 o 01 -1 50 Working Frequency
1

Monitoring Parameter Option


FC-03 -1 ~ 50; -1 means void; 0 ~ 50 mean FU-00 ~ FU-50 -1 o 02 -1 50 Frequency Setting (Reference)
2

Monitoring Parameter Option


FC-04 -1 ~ 50; -1 means void; 0 ~ 50 mean FU-00 ~ FU-50 -1 o 04 -1 50 DC Bus Voltage
3

Monitoring Parameter Option


FC-05 -1 ~ 50; -1 means void; 0 ~ 50 mean FU-00 ~ FU-50 -1 o 05 -1 50 AC Output Voltage
4

Monitoring Parameter Option


FC-06 -1 ~ 50; -1 means void; 0 ~ 50 mean FU-00 ~ FU-50 -1 o 07 -1 50 Output Current
5

Monitoring Parameter Option


FC-07 -1 ~ 50; -1 means void; 0 ~ 50 mean FU-00 ~ FU-50 -1 o 13 -1 50 Rotational Speed
6

Monitoring Parameter Option


FC-08 -1 ~ 50; -1 means void; 0 ~ 50 mean FU-00 ~ FU-50 -1 o 14 -1 50 AI1 Reading (Potentiometer)
7

Operation Monitoring
FC-09 -1 ~ 50; -1 means void; 0 ~ 50 mean FU-00 ~ FU-50 0 o 08 -1 50 AI2 Reading (Transducer)
Parameter Option 1

Operation Monitoring
FC-10 -1 ~ 50; -1 means void; 0 ~ 50 mean FU-00 ~ FU-50 2 o 00 -1 50 Nothing
Parameter Option 2

Operation Monitoring
FC-11 -1 ~ 50; -1 means void; 0 ~ 50 mean FU-00 ~ FU-50 4 o -1 -1 50 Nothing
Parameter Option 3

Operation Monitoring
FC-12 -1 ~ 50; -1 means void; 0 ~ 50 mean FU-00 ~ FU-50 -1 o -1 -1 50 Nothing
Parameter Option 4

0: Hz 1: A 2: V 3: % 4: kW 5: s 6: rpm 7:
Units of PID Settings and
FC-15 mps 8: m 9: mA 10: mV 11: Pa 12:kPa 13: oC 14: kg/cm2 14 o 14 0 16 Optional
Feedback Values
15: mmH2O 16: Mpa