LS25 S Manual PDF
LS25 S Manual PDF
LS25 S Manual PDF
AIR COMPRESSOR
LS25S
200-350HP/
149-261KW
AIR-COOLED & WATER-COOLED
STANDARD AND 24KT
OPERATOR’S
MANUAL AND
PARTS LIST
KEEP FOR
FUTURE
REFERENCE
Part Number 02250137-621
©Sullair Corporation
AIR CARE
SEMINAR TRAINING
Sullair Air Care Seminars are 3-day courses that provide hands-on instruction in the proper operation, mainte-
nance and service of Sullair equipment. Individual seminars on Industrial compressors and compressor electrical
systems are presented at regular intervals throughout the year at a dedicated training facility at Sullair’s corporate
headquarters in Michigan City, Indiana.
Instruction includes discussion of the function and installation of Sullair service parts, troubleshooting of the most
common problems, and actual equipment operation. The seminars are recommended for maintenance and serv-
ice personnel.
Section 1 Page
SAFETY 1 1.1 GENERAL
1 1.2 PERSONAL PROTECTIVE EQUIPMENT
1 1.3 PRESSURE RELEASE
2 1.4 FIRE AND EXPLOSION
2 1.5 MOVING PARTS
2 1.6 HOT SURFACES, SHARP EDGES AND SHARP CORNERS
3 1.7 TOXIC AND IRRITATING SUBSTANCES
3 1.8 ELECTRICAL SHOCK
3 1.9 LIFTING
4 1.10 ENTRAPMENT
Section 2
DESCRIPTION 5 2.1 INTRODUCTION
5 2.2 DESCRIPTION OF COMPONENTS
5 2.3 SULLAIR COMPRESSOR UNIT,
FUNCTIONAL DESCRIPTION
6 2.4 COMPRESSOR COOLING AND LUBRICATION SYSTEM,
FUNCTIONAL DESCRIPTION
8 2.5 COMPRESSOR DISCHARGE SYSTEM,
FUNCTIONAL DESCRIPTION
10 2.6 CONTROL SYSTEM, FUNCTIONAL
DESCRIPTION
13 2.7 AIR INLET SYSTEM, FUNCTIONAL
DESCRIPTION
Section 3
SPECIFICATIONS 15 3.1 SULLAIR SERIES LS25S SPECIFICATIONS
15 3.2 LUBRICATION GUIDE- STANDARD COMPRESSORS
15 3.3 LUBRICATION GUIDE- 24KT COMPRESSORS
15 3.4 APPLICATION GUIDE
15 3.5 LUBRICATION CHANGE RECOMMENDATIONS
AND MAINTENANCE
TABLE OF CONTENTS
Section 4
INSTALLATION 45 4.1 MOUNTING OF COMPRESSOR
45 4.2 VENTILATION AND COOLING
45 4.3 SERVICE AIR PIPING
45 4.4 COUPLING ALIGNMENT CHECK
45 4.5 FLUID LEVEL CHECK
46 4.6 FLUID PIPING (REMOTE AIR-COOLED OPTION ONLY)
47 4.7 ELECTRICAL PREPARATION
47 4.8 MOTOR ROTATION DIRECTION CHECK
Section 5
SUPERVISOR 48 FIGURE 5-1 SUPERVISOR CONTROL PANEL
Section 6
COMPRESSOR
OPERATION 49 6.1 INTRODUCTION
49 6.2 PURPOSE OF CONTROLS
50 6.3 INITIAL START-UP PROCEDURE
51 6.4 SUBSEQUENT START-UP PROCEDURE
51 6.5 SHUTDOWN PROCEDURE
Section 7
MAINTENANCE 53 7.1 GENERAL
53 7.2 DAILY OPERATION
53 7.3 MAINTENANCE AFTER INITIAL 50 HOURS
OF OPERATION
53 7.4 MAINTENANCE AFTER 1000 HOURS
53 7.5 FLUID CHANGE
53 7.6 SEPARATOR MAINTENANCE
53 7.7 PARTS REPLACEMENT AND ADJUSTMENT
PROCEDURES
53 FLUID FILTER MAINTENANCE
54 AIR FILTER MAINTENANCE
55 SEPARATOR ELEMENTS REPLACEMENT
56 OIL RETURN/SIGHT GLASS MAINTENANCE
56 DIFFERENTIAL PRESSURE REGULATOR
ADJUSTMENT
57 PRESSURE REDUCING REGULATOR
57 DRIVE COUPLING INSTALLATION AND ALIGNMENT
(200-350HP/ 149-261KW)
59 7.8 TROUBLESHOOTING
TABLE OF CONTENTS
Section 7
MAINTENANCE
(Continued) 59 7.9 TROUBLESHOOTING GUIDE
Section 8
ILLUSTRATION AND
PARTS LIST 63 8.1 PROCEDURE FOR ORDERING PARTS
63 8.2 RECOMMENDED SPARE PARTS LIST-
200-250HP/ 149-186KW
65 8.3 RECOMMENDED SPARE PARTS LIST-
300-350HP/ 224-261KW
66 8.4 MOTOR, COMPRESSOR, FRAME AND PARTS
68 8.5 AIR INLET SYSTEM
70 8.6 INLET VALVE
72 8.7 FLUID COOLING SYSTEM- AIR-COOLED
200-250HP/ 149-186KW
76 8.8 FLUID COOLING SYSTEM- AIR-COOLED
300-350HP/ 224-261KW
80 8.9 WATER COOLER PIPING- 200-350HP/ 149-261KW
82 8.10 AIR PIPING SYSTEM- AIR-COOLED 200-250HP/
149-186KW
86 8.11 AIR PIPING SYSTEM- WATER-COOLED300-350HP/
224-261KW
88 8.12 AIR PIPING SYSTEM- REMOTE-COOLED 200-250HP/
149-186KW
90 8.13 AIR PIPING SYSTEM- AIR-COOLED 300-350HP/
224-261KW
94 8.14 AIR PIPING SYSTEM- WATER-COOLED 300-350HP/
224-261KW
96 8.15 AIR PIPING SYSTEM- REMOTE-COOLED 300-350HP/
224-261KW
98 8.16 AIR PIPING SYSTEM- 24KT 350HP/ 261KW
102 8.17 FLUID PIPING SYSTEM- AIR-COOLED
200-250HP/ 149-186KW
104 8.18 FLUID PIPING SYSTEM- WATER-COOLED
200-250HP/ 149-186KW
106 8.19 FLUID PIPING SYSTEM- REMOTE-COOLED
200-250HP/ 149-186KW
110 8.20 FLUID PIPING SYSTEM- AIR-COOLED
300-350HP/ 224-261KW
112 8.21 FLUID PIPING SYSTEM- WATER-COOLED
300-350HP/ 224-261KW
TABLE OF CONTENTS
Section 8
ILLUSTRATION AND
PARTS LIST (Cont.) 114 8.22 FLUID PIPING SYSTEM- REMOTE-COOLED
300-350HP/ 224-261KW
116 8.23 SUMP AND PARTS 200-250HP/ 149-186KW
118 8.24 SUMP AND PARTS 300-350HP/ 224-261KW
120 8.25 COMPRESSOR SPIRAL VALVE
ACTUATOR (OPTIONAL)
122 8.26 ZERO-LOSS MOISTURE DRAIN (OPTIONAL)
124 8.27 PNEUMATIC CONTROLS
130 8.28 CONTROL BOX- SOLID STATE
132 8.29 CONTROL BOX- FULL VOLTAGE
134 8.30 CONTROL BOX- WYE-DELTA
136 8.31 ENCLOSURE- AIR-COOLED
200-250HP/ 149-186KW
140 8.32 ENCLOSURE- AIR-COOLED
300-350HP/ 224-261KW
144 8.33 ENCLOSURE- WATER-COOLED
200-350HP/ 149-261KW
148 8.34 DECAL GROUP
154 8.35 DECAL LOCATIONS- AIR-COOLED/OPEN
156 8.36 DECAL LOCATIONS- WATER-COOLED/OPEN
158 8.37 DECAL LOCATIONS- ENCLOSURES
160 8.38 DECAL LOCATIONS- CONTROL BOX INTERIOR
162 8.39 WIRING DIAGRAM- AIR-COOLED FULL VOLTAGE
WITH SUPERVISOR CONTROLLER
163 8.40 WIRING DIAGRAM- WATER-COOLED FULL VOLTAGE
WITH SUPERVISOR CONTROLLER
164 8.41 WIRING DIAGRAM- WYE-DELTA AIR- AND REMOTE-
COOLED WITH SUPERVISOR CONTROLLER
165 8.42 WIRING DIAGRAM- WYE-DELTA WATER-COOLED
WITH SUPERVISOR CONTROLLER
166 8.43 WIRING DIAGRAM- SOLID STATE AIR- AND REMOTE-
COOLED WITH SUPERVISOR CONTROLLER
167 8.44 WIRING DIAGRAM- SOLID STATE WATER-COOLED
WITH SUPERVISOR CONTROLLER
Section 1
SAFETY
1.1 GENERAL the service air outlet and the shut-off (throttle)
Sullair Corporation and its subsidiaries design and valve, either at the compressor or at any other point
manufacture all of their products so they can be along the air line, when an air hose exceeding 1/2”
operated safely. However, the responsibility for (13mm) inside diameter is to be connected to the
safe operation rests with those who use and main- shut-off (throttle) valve, to reduce pressure in case
tain these products. The following safety precau- of hose failure, per all applicable Federal, State and
tions are offered as a guide which, if conscientious- Local codes, standards and regulations.
ly followed, will minimize the possibility of accidents B. When the hose is to be used to supply a mani-
throughout the useful life of this equipment. fold, install an additional appropriate flow-limiting
The compressor should be operated only by those valve between the manifold and each air hose
who have been trained and delegated to do so, and exceeding 1/2” (13mm) inside diameter that is to be
who have read and understood this Operator’s connected to the manifold to reduce pressure in
Manual. Failure to follow the instructions, proce- case of hose failure.
dures and safety precautions in this manual can C. Provide an appropriate flow-limiting valve at the
result in accidents and injuries. Read this manual beginning of each additional 75 feet (23m) of hose
prior to startup. in runs of air hose exceeding 1/2” (13mm) inside
NEVER start the compressor unless it is safe to do diameter to reduce pressure in case of hose failure.
so. DO NOT attempt to operate the compressor D. Flow-limiting valves are listed by pipe size and
with a known unsafe condition. Tag the compressor rated CFM. Select appropriate valves accordingly,
and render it inoperative by disconnecting and lock- in accordance with their manufacturer’s recommen-
ing out all power at source or otherwise disabling its dations.
prime mover, so others who may not know of the
unsafe condition, cannot attempt to operate it until E. DO NOT use air tools that are rated below the
the condition is corrected. maximum rating of the compressor. Select air tools,
air hoses, pipes, valves, filters, and other fittings
Install, use and operate the compressor only in full accordingly. DO NOT exceed manufacturer’s rated
compliance with all pertinent regulations and all safe operating pressures for these items.
applicable Federal, State, and Local codes, stan-
dards and regulations. F. Secure all hose connections by wire, chain or
other suitable retaining devices to prevent tools or
DO NOT modify the compressor and/or controls in hose ends from being accidentally disconnected
any way except with written factory approval. and expelled.
While not specifically applicable to all types of com- G. Open fluid filler cap only when compressor is not
pressors with all types of prime movers, most of the running and is not pressurized. Shut down the com-
precautionary statements contained herein are pressor and bleed the sump (receiver) to zero inter-
applicable to most compressors and the concepts nal pressure before removing the cap.
behind these statements are generally applicable to
all compressors. H. Vent all internal pressure prior to opening any
line, fitting, hose, valve, drain plug, connection or
1.2 PERSONAL PROTECTIVE EQUIPMENT other component, such as filters and line oilers, and
Prior to installing or operating the compressor, own- before attempting to refill optional air line anti-icer
ers, employers and users should become familiar systems with antifreeze compound.
with, and comply with, all applicable regulations and
any applicable Federal, State and Local codes, I. Keep personnel out of line with and away from the
standards, and regulations relative to personal pro- discharge opening of hoses or tools or other points
tective equipment, such as eye and face protective of compressed air discharge.
equipment, respiratory protective equipment, equip- J. Use air at pressures less than 30 psig (2.1 bar)
ment intended to protect the extremities, protective for cleaning purposes, and then only with effective
clothing, protective shields and barriers and electri- chip guarding and personal protective equipment.
cal protective equipment, as well as noise exposure K. DO NOT engage in horseplay with air hoses as
administrative and/or engineering controls and/or death or serious injury may result.
personal hearing protective equipment.
L. DO NOT tamper with sump and unit (if provid-
1.3 PRESSURE RELEASE ed) relief valves. Check the relief valve as recom-
A. Install an appropriate flow-limiting valve between mended in the Maintenance Section of this manual
1
Section 1
SAFETY
or at a minimum of at least weekly to make sure it al that may be damaged by heat or that may sup-
is not blocked, clogged, obstructed or otherwise port combustion and is in close proximity, prior to
disabled. DO NOT change the factory setting of the attempting weld repairs.
relief valve. H. Keep suitable fully charged fire extinguisher or
M. If the compressor is installed in an enclosed extinguishers nearby when servicing and operating
area, it is necessary to vent the relief valve to the the compressor.
outside of the structure or to an area of non-expo- I. Keep oily rags, trash, leaves, litter or other com-
sure. bustibles out of and away from the compressor.
1.4 FIRE AND EXPLOSION J. DO NOT operate the compressor without proper
flow of cooling air or water or with inadequate flow
of lubricant or with degraded lubricant.
When installing a Base Load Transfer (BLT)
System, remove jumpers between 16-17 & 18-19
K. DO NOT attempt to operate the compressor in
(Dual Control Compressors) so the other com- any classification of hazardous environment unless
pressor does not backfeed defeating the shut- the compressor has been specially designed and
down circuitry. manufactured for that duty.
A. Clean up spills of lubricant or other combustible 1.5 MOVING PARTS
substances immediately, if such spills occur. A. Keep hands, arms and other parts of the body
B. Shut off the compressor and allow it to cool. and also clothing away from couplings, fans and
Then keep sparks, flames and other sources of igni- other moving parts.
tion away and DO NOT permit smoking in the vicin- B. DO NOT attempt to operate the compressor with
ity when checking or adding lubricant or when refill- the fan, coupling or other guards removed.
ing air line anti-icer systems with antifreeze com- C. Wear snug-fitting clothing and confine long hair
pound. when working around this compressor, especially
C. DO NOT permit fluids, including air line anti-icer when exposed to hot or moving parts.
system antifreeze compound or fluid film to accu- D. Keep access doors, if any, closed except when
mulate on, under, or around acoustical material, or making repairs or adjustments.
on any external surfaces of the air compressor or
on internal surfaces of the enclosure. Wipe down E. Make sure all personnel are out of and/or clear of
using an aqueous industrial cleaner or steam-clean the compressor prior to attempting to start or oper-
as required. If necessary, remove acoustical mate- ate it.
rial, clean all surfaces and then replace acoustical F. Disconnect and lock out all power at source and
material. Any acoustical material with a protective verify at the compressor that all circuits are de-
covering that has been torn or punctured should be energized to minimize the possibility of accidental
replaced immediately to prevent accumulation of start-up or operation, prior to attempting repairs or
liquids or fluid film within the material. DO NOT use adjustments. This is especially important when
flammable solvents for cleaning purposes. compressors are remotely controlled.
D. Disconnect and lock out all power at source prior G. Keep hands, feet, floors, controls and walking
to attempting any repairs or cleaning of the com- surfaces clean and free of fluid, water, or other liq-
pressor or of the inside of the enclosure, if any. uids to minimize the possibility of slips and falls.
E. Keep electrical wiring, including all terminals and 1.6 HOT SURFACES, SHARP EDGES AND SHARP
pressure connectors in good condition. Replace CORNERS
any wiring that has cracked, cut abraded or other- A. Avoid bodily contact with hot fluid, hot coolant,
wise degraded insulation, or terminals that are hot surfaces and sharp edges and corners.
worn, discolored or corroded. Keep all terminals
and pressure connectors clean and tight. B. Keep all parts of the body away from all points of
air discharge.
F. Keep grounded and/or conductive objects such
as tools away from exposed live electrical parts C. Wear personal protective equipment including
such as terminals to avoid arcing which might serve gloves and head covering when working in, on or
as a source of ignition. around the compressor.
G. Remove any acoustical material or other materi- D. Keep a first aid kit handy. Seek medical assis-
tance promptly in case of injury. DO NOT ignore
2
Section 1
SAFETY
small cuts and burns as they may lead to infection. tained in full compliance with all applicable Federal,
1.7 TOXIC AND IRRITATING SUBSTANCES State and Local codes, standards and regulations,
A. DO NOT use air from this compressor for respi- including those of the National Electrical Code, and
ration (breathing) except in full compliance with any also including those relative to equipment ground-
Federal, State or Local Codes or regulations. ing conductors, and only by personnel that are
trained, qualified and delegated to do so.
B. Keep all parts of the body and any hand-held
Death or serious injury can result from inhaling tools or other conductive objects away from
compressed air without using proper safety exposed live parts of electrical system. Maintain dry
equipment. footing, stand on insulating surfaces and DO NOT
contact any other portion of the compressor when
B. DO NOT use air line anti-icer systems in air lines making adjustments or repairs to exposed live parts
supplying respirators or other breathing air utiliza- of the electrical system. Make all such adjustments
tion equipment and DO NOT discharge air from or repairs with one hand only, so as to minimize the
these systems in unventilated or other confined possibility of creating a current path through the
areas. heart.
C. Operate the compressor only in open or ade- C. Attempt repairs in clean, dry and well lighted and
quately ventilated areas. ventilated areas only.
D. Locate the compressor or provide a remote inlet D. DO NOT leave the compressor unattended with
so that it is not likely to ingest exhaust fumes or open electrical enclosures. If necessary to do so,
other toxic, noxious or corrosive fumes or sub- then disconnect, lock out and tag all power at
stances. source so others will not inadvertently restore
E. Coolants and lubricants used in this compressor power.
are typical of the industry. Care should be taken to E. Disconnect, lock out, and tag all power at source
avoid accidental ingestion and/or skin contact. In prior to attempting repairs or adjustments to rotating
the event of ingestion, seek medical treatment machinery and prior to handling any ungrounded
promptly. Wash with soap and water in the event of conductors.
skin contact. Consult the compressor operator’s
manual lubrication section for information pertaining F. Dry test all shutdown circuits prior to starting the
to compressor fluid fill. compressor after installation.
3
Section 1
SAFETY
or swinging of the compressor once it has been lift- mum practical speeds.
ed clear of the ground. N. Make sure pallet-mounted compressors are firm-
F. DO NOT attempt to lift in high winds. ly bolted or otherwise secured to the pallet prior to
G. Keep all personnel out from under and away attempting to forklift or transport them. NEVER
from the compressor whenever it is suspended. attempt to forklift a compressor that is not secured
to its pallet, as uneven floors or sudden stops may
H. Lift compressor no higher than necessary. cause the compressor to tumble off, possibly caus-
I. Keep lift operator in constant attendance whenev- ing serious injury or property damage in the
er compressor is suspended. process.
J. Set compressor down only on a level surface O. DO NOT use the lifting eye bolt on the compres-
capable of safely supporting at least its weight and sor motor, if supplied, to lift the entire compressor
its loading unit. package.
K. When moving compressors by forklift truck, uti- 1.10 ENTRAPMENT
lize fork pockets if provided. Otherwise, utilize pal- A. If the compressor enclosure is large enough to
let if provided. If neither fork pockets or pallet are hold a person and if it is necessary to enter it to per-
provided, then make sure compressor is secure form service adjustments, inform other personnel
and well balanced on forks before attempting to before doing so, or else secure and tag the access
raise or transport it any significant distance. door in the open position to avoid the possibility of
L. Make sure forklift truck forks are fully engaged others closing and possibly latching the door with
and tipped back prior to lifting or transporting the personnel inside.
compressor. B. Make sure all personnel are out of compressor
M. Forklift no higher than necessary to clear obsta- before closing and latching enclosure doors.
cles at floor level and transport and corner at mini-
4
Section 2
DESCRIPTION
2.1 INTRODUCTION trol system and Supervisor ControllerTM, micro-
Refer to Figures 2-1A and 2-1B. Your new Sullair processor system and starter all mounted on a
lubricated rotary screw air compressor provides you structural steel frame
with a unique experience in improved reliability and On air-cooled models, a fan draws air over the fan
greatly reduced maintenance. motor and forces it through the combined aftercool-
Compared to other types of compressors, the er and fluid cooler, thereby removing the heat of
Sullair rotary screw is unique in its mechanical reli- compression from the cooling fluid.
ability and lack of “wear”. The compressor requires On water-cooled models, fluid is piped into a water-
absolutely no inspection of its internal parts. cooled heat exchanger where the heat of compres-
By reading through Section 6, you will notice the sion is removed from the fluid. A fan is used to sup-
easy process of caring and maintaining this Sullair ply sufficient ventilating air to compressors
manufactured product. Should any questions arise equipped with an optional enclosure.
which cannot be answered in this text, call your Both air-cooled and water-cooled versions have
nearest Sullair representative or the Sullair easily accessible items such as the fluid filters and
Corporation Service Department. control valves. The inlet air filters are also mounted
2.2 DESCRIPTION OF COMPONENTS for easy access and servicing.
Refer to Figures 2-1A and 2-1B. The components 2.3 SULLAIR COMPRESSOR UNIT, FUNCTIONAL
and assemblies of the air compressors are clearly DESCRIPTION
shown. The complete package includes compres- Sullair air compressors feature the Sullair compres-
sor, electric motor, compressor inlet system, sor unit, a positive displacement fluid lubricated-
compressor discharge system, compressor type compressor. This unit provides continuous air
cooling and lubrication system, capacity con- compression to meet your needs.
Figure 2-1A Sullair Series LS25S Rotary Screw Compressor (Air-cooled Version)
5
Section 2
DESCRIPTION
Figure 2-1B Sullair Series LS25S Rotary Screw Compressor (Water-cooled Version)
Fluid is injected into the compressor unit where it 2.4 COMPRESSOR COOLING AND LUBRICATION
mixes directly with the air as the internal rotors turn, SYSTEM, FUNCTIONAL DESCRIPTION
compressing the air. The fluid flow has three basic Refer to Figures 2-2, 2-3, 2-4, 2-5A, 2-5B, 2-5C and
functions: 2-5D. The cooling and lubrication system con-
1. As coolant, it controls the rise of air temperature sists of a fluid cooler, full flow fluid filter and
normally associated with the heat of compression. thermal valve.
2. Seals the clearance between the rotors and the The pressure in the receiver/sump causes fluid flow
stator and also between the rotors themselves. by forcing the fluid from the high pressure area of
the sump to an area of lower pressure in the com-
3. Acts as a lubricating film between the rotors pressor unit.
allowing one rotor to directly drive the other, which
is an idler. After the air/fluid mixture is discharged Fluid flows from the receiver/sump to the thermal
from the compressor unit, the fluid is separated valve. The thermal valve is fully open to the com-
from the air. At this time, the air flows to the serv- pressor unit when the discharge temperature is
ice line and the fluid is cooled in preparation for re- below 170°F (77°C) for all compressors, except
injection. water-cooled 24KT models, which is fully open up
to 195°F (91°C). The fluid passes through the ther-
mal valve, the main fluid filter and directly to the
compressor unit.
With a Sullair compressor, there is no mainte-
nance or inspection of the internal parts of the
As the discharge temperature rises above 170°F
compressor unit permitted in accordance with (77°C) for all compressors (195°F [91°C] for water-
the terms of the warranty. cooled 24KT models), due to the heat of compres-
6
Section 2
DESCRIPTION
Figure 2-2 Compressor Piping and Instrument Diagram (200 -350HP/ 149-261KW)
7
Section 2
DESCRIPTION
Figure 2-3 Compressor Cooling and Lubrication System (Air-cooled)
8
Section 2
DESCRIPTION
Figure 2-4 Compressor Discharge System (Air-cooled)
ControllerTM microprocessor control monitors the air in the service line from bleeding back into the
condition of the separator elements by reading the receiver on shutdown and during operation of the
differential pressure on the digital display. At a dif- compressor in an unloaded condition.
ferential of 10 psig (0.7 bar), or greater, the opera- A pressure relief valve (located on the wet side of
tor will be told to service the separator elements. At the separator) is set to open if the sump pressure
this time, separator element replacement is neces- exceeds the rated pressure of the tank.
sary.
All Sullair compressor models are equipped with
high pressure shutdown protection to shut down the
compressor at 20-35 psi above rated pressure. This
Calibration of dP1 is required at start-up. Consult
Supervisor manual.
prevents the pressure relief valve from opening
under normal conditions, thereby preventing fluid
The receiver is an ASME pressure vessel. A combi- loss through the pressure relief valve. The
nation minimum pressure/check valve, located Supervisor will shut down the compressor if the dis-
downstream from the separator, assures a mini- charge temperature reaches 235°F (113°C).
mum receiver pressure of 50 psig (3.4 bar) during
full load operation. This pressure is necessary for
proper air/fluid separation and proper fluid circula-
DO NOT remove caps, plugs, and/or other com-
tion while supplying air to the system. This valve ponents when compressor is running or pres-
also acts as a check valve preventing compressed surized.
9
Section 2
DESCRIPTION
Figure 2-5A Control System- START Stage (200-350HP/ 149-261KW)
Stop compressor and relieve all internal pressure ic inlet valve. The functional description of the con-
before doing so. trol system is described below in four distinct phas-
Fluid is added to the sump via a capped fluid filler es of compressor operation. The following applies
opening, placed low on the receiver tank to prevent to LS25S Series compressors ranging from 200
over-filling of the sump. Two sight glasses enable through 350HP/ 149-261KW. For explanatory pur-
the operator to visually monitor the sump fluid level. poses, this description applies to any compressor
with an operating range of 100 to 110 psig (6.9 to
2.6 CONTROL SYSTEM, FUNCTIONAL DESCRIP- 7.6 bar). A compressor with any other pressure
TION range would operate in the same manner except for
Refer to Figures 2-5A, 2-5B, 2-5C and 2-5D. The the stated pressures.
purpose of the compressor control system is to reg-
ulate the amount of air being compressed to match START MODE - 0 TO 50 PSIG (0 TO 3.4 BAR)
the amount of compressed air being used. When the compressor (ON) pad is depressed,
The capacity control system consists of a pneumat- the sump pressure will quickly rise from 0 to 50 psig
10
Section 2
DESCRIPTION
Figure 2-5B Control System MODULATION Stage (200-350HP/ 149-261KW)
(0 to 3.4 bar). During this period, both of the pres- rises above 50 psig (3.4 bar), the minimum pres-
sure regulators and the solenoid valve are closed sure valve opens, allowing compressed air to flow
and the pneumatic inlet valve is inoperative. The into the service line. From this point on, the line air
internal spring holds the inlet valve fully closed to pressure is continually monitored by the Supervisor.
reduce motor torque for starting. After eight (8) sec- A load signal is provided through a pressure reduc-
onds the solenoid valve will open, opening the inlet ing regulator set at 70 psig (4.8 bar) to maintain the
valve, and the compressor will run at full rated inlet valve in an open position. The inlet valve will
capacity. The rising compressor air pressure is iso- remain in the full load position as long as the com-
lated from the service line in this phase by the min- pressor is running at 100 psig (6.9 bar) or below.
imum pressure valve set at approximately 50 psig MODULATION - 100 TO 110 PSIG (6.9 TO 7.6
(3.4 bar). BAR)
FULL LOAD MODE - 50 TO 100 PSIG (3.4 TO 6.9 As air demand drops below the rated capacity of the
BAR) compressor, the line pressure will rise above 100
When the compressed air pressure in the sump psig (6.9 bar). As the air pressure exceeds 100 psig
11
Section 2
DESCRIPTION
Figure 2-5C Control System FULL LOAD Stage (200-350HP/ 149-261KW)
(6.9 bar), the differential pressure regulator con- used, the service line pressure continues to rise.
trolling the inlet valve opens. This allows the air When it exceeds 110 psig (7.6 bar), Supervisor
pressure into the unload chamber of the inlet valve, energizes the solenoid valve, applying pressure to
which starts partially closing the inlet valve, provid- the unload chamber of the inlet valve, which fully
ing modulation. During this period, the pressure closes the valve. Simultaneously, the solenoid valve
rises approximately from 100 to 110 psig (6.9 to 7.6 sends a pneumatic signal to the blowdown valve.
bar). When equipped with optional spiral valve, the The blowdown valve opens the sump to the atmos-
differential pressure regulator controlling the spiral phere. This reduces the sump pressure to approxi-
valve will operate to unload the spiral valve from mately 25 psig (1.7 bar), which results in low horse-
100-105 psi (6.9-7.2 bar) with the inlet valve acting power consumption. The check valve in the air
from 105-110 psig (6.9 -7.6 bar). service line prevents line pressure from returning to
UNLOAD MODE - IN EXCESS OF 110 PSIG (7.6 sump while the compressor is running in the
BAR) unloaded mode. The inlet valve remains in the
When a relatively small amount or no air is being unload position.
12
Section 2
DESCRIPTION
Figure 2-5D Control System UNLOAD Stage (200-350HP/ 149-261KW)
When the line pressure drops back to 100 psig (6.9 ulation can be disabled in the Supervisor
bar) due to an increase in the air demand, ControllerTM in the “Control Parameters” menu. If
Supervisor de-energizes the solenoid valve remov- modulation is disabled, the unload pressure must
ing air pressure from the unload chamber, opening be reset to the rated load pressure of the machine.
the inlet valve. The blowdown valve closes, and the For example, an L model rated for 100 psig full load
inlet valve opens. operation and 110 psig unload must have the
AUTOMATIC OPERATION unload pressure reset to 100 psig. This ensures
For applications with varied periods of time when that the motor will not run in an overload condition.
there are no air requirements, Supervisor’s Auto 2.7 AIR INLET SYSTEM, FUNCTIONAL DESCRIP-
mode allows the compressor to shut down (time TION
delayed) when no compressed air requirement is Refer to Figure 2-6. The compressor inlet system
present and restart as compressed air is needed. consists of a dry-type air filter, a vacuum switch
LOAD/ NO LOAD OPERATION and an air inlet valve.
If applications call for load/no load operation, mod- The vacuum switch, located in the compressor
13
Section 2
DESCRIPTION
Figure 2-6 Compressor Air Inlet System Supervisor control system, indicates the condition
of the air filter. When the message “AIR FILTER
MAINT RQD” is displayed, maintenance is required.
The pneumatic-type air inlet valve directly controls
the amount of air intake to the compressor (Section
2.6).
14
Section 3
SPECIFICATIONS
3.1 SULLAIR SERIES LS25S SPECIFICATIONS
60 HZ MODEL LENGTH WIDTH HEIGHT (I) WEIGHT
(AC & WC) (IN) (IN) (IN) (LB)
154 78 86 (II)
For noise level information, please contact the Sullair Factory Service Department.
15
Section 3
SPECIFICATIONS
Figure 3-2 Identification- LS25S 200-250HP/ 149-186KW Air-cooled (Typical)
02250136-148R01
16
Section 3
SPECIFICATIONS
Figure 3-3 Identification- LS25S 200-250HP/ 149-186KW Water-cooled (Typical)
02250136-151R01
17
Section 3
SPECIFICATIONS
Figure 3-4 Identification- LS25S 200-250HP/ 149-186KW Remote-cooled (Typical)
02250136-150R01
18
Section 3
SPECIFICATIONS
Figure 3-5 Identification- LS25S 200-350HP/ 149-261KW EES (Typical)
02250136-149R00
19
Section 3
SPECIFICATIONS
Figure 3-6 Identification- LS25S 300-350HP/ 224-261KW Air-cooled (Typical)
02250136-156R00
20
Section 3
SPECIFICATIONS
Figure 3-7 Identification- LS25S 300-350HP/ 224-261KW Water-cooled (Typical)
02250136-159R00
21
Section 3
SPECIFICATIONS
Figure 3-8 Identification- LS25S 300-350HP/ 224-261KW Remote-cooled (Typical)
02250136-158R01
22
Section 8
ILLUSTRATIONS AND PARTS LIST
Figure 3-9 Identification- LS25S 300-350HP/ 224-261KW EES (Typical)
02250136-157R01
23
Section 3
SPECIFICATIONS
Figure 3-10 Piping and Instrumentation Diagram- LS25SC-200/250 Remote-cooled Supervisor with Pneumatic
Control
02250136-141R03
24
Section 3
SPECIFICATIONS
Figure 3-10 Piping and Instrumentation Diagram- LS25SC-200/250 Remote-cooled Supervisor with Pneumatic
Control
key part
number description number quantity
25
Section 3
SPECIFICATIONS
Figure 3-10 Piping and Instrumentation Diagram- LS25SC-200/250 Remote-cooled Supervisor with Pneumatic
Control
02250136-141R03
26
Section 3
SPECIFICATIONS
Figure 3-10 Piping and Instrumentation Diagram- LS25SC-200/250 Remote-cooled Supervisor with Pneumatic
Control (Continued)
key part
number description number quantity
27
Section 3
SPECIFICATIONS
Figure 3-11 Piping and Instrumentation Diagram- LS25SC-300/350 Remote-cooled Supervisor with Pneumatic
Control
02250136-142R03
28
Section 3
SPECIFICATIONS
Figure 3-11 Piping and Instrumentation Diagram- LS25SC-300/350 Remote-cooled Supervisor with Pneumatic
Control
key part
number description number quantity
29
Section 3
SPECIFICATIONS
Figure 3-11 Piping and Instrumentation Diagram- LS25SC-300/350 Remote-cooled Supervisor with Pneumatic
Control
02250136-142R03
30
Section 3
SPECIFICATIONS
Figure 3-11 Piping and Instrumentation Diagram- LS25SC-300/350 Remote-cooled Supervisor with Pneumatic
Control (Continued)
key part
number description number quantity
31
Section 3
SPECIFICATIONS
Figure 3-12 Piping and Instrumentation Diagram- LS25SC-200/350 ACAC Supervisor with Pneumatic Control
02250136-143R02
32
Section 3
SPECIFICATIONS
Figure 3-12 Piping and Instrumentation Diagram- LS25SC-200/350 ACAC Supervisor with Pneumatic Control
33
Section 3
SPECIFICATIONS
Figure 3-12 Piping and Instrumentation Diagram- LS25SC-200/350 ACAC Supervisor with Pneumatic Control
02250136-143R02
34
Section 3
SPECIFICATIONS
Figure 3-12 Piping and Instrumentation Diagram- LS25SC-200/350 ACAC Supervisor with Pneumatic Control
(Continued)
35
Section 3
SPECIFICATIONS
Figure 3-13 Piping and Instrumentation Diagram- LS25SC-200/350 WCAC Supervisor with Pneumatic Control
02250136-144R02
36
Section 3
SPECIFICATIONS
Figure 3-13 Piping and Instrumentation Diagram- LS25SC-200/350 WCAC Supervisor with Pneumatic Control
37
Section 3
SPECIFICATIONS
Figure 3-13 Piping and Instrumentation Diagram- LS25SC-200/350 WCAC Supervisor with Pneumatic Control
02250136-144R02
38
Section 3
SPECIFICATIONS
Figure 3-13 Piping and Instrumentation Diagram- LS25SC-200/350 WCAC Supervisor with Pneumatic Control
(Continued)
39
Section 3
SPECIFICATIONS
Figure 3-14 Piping and Instrumentation Diagram- LS25SC-200/350 WCAC Supervisor with Pneumatic Control &
Parallel Piping
02250136-145R02
40
Section 3
SPECIFICATIONS
Figure 3-14 Piping and Instrumentation Diagram- LS25SC-200/350 WCAC Supervisor with Pneumatic Control &
Parallel Piping
41
Section 3
SPECIFICATIONS
Figure 3-14 Piping and Instrumentation Diagram- LS25SC-200/350 WCAC Supervisor with Pneumatic Control &
Parallel Piping
02250136-145R02
42
Section 3
SPECIFICATIONS
Figure 3-14 Piping and Instrumentation Diagram- LS25SC-200/350 WCAC Supervisor with Pneumatic Control &
Parallel Piping (Continued)
43
NOTES
44
Section 4
INSTALLATION
4.1 MOUNTING OF COMPRESSOR Table 4-1 Ventilation Requirements below indicates
A foundation or mounting capable of supporting the the ventilation requirements necessary to keep the
weight of the compressor, and rigid enough to main- compressor running at a normal operating temper-
tain the compressor frame level and the compres- ature. The fan air requirement is the volume of air
sor in alignment is required. The compressor frame which must flow through the compressor and/or
must be leveled and secured with foundation bolts, cooling package for proper ventilation. The speci-
and full uniform contact must be maintained fied heat rejection requirement is the amount of
between the frame and foundation. It is recom- heat that is radiated by the compressor. This heat
mended that the frame be grouted to the founda- must be removed to assure a normal operating tem-
tion. The compressor unit and driver must be perature. With air-cooled compressors it is possible
aligned after installation as specified in the to use this heat for space heating, providing exces-
Operator’s Manual. No piping loads shall be trans- sive pressure drop is not created across the fan.
mitted to the compressor or the cooling package at Consult a Sullair office for assistance in utilizing this
the external connections. heat.
4.2 VENTILATION AND COOLING DO NOT install a water-cooled or an air-
For air-cooled compressors, select a location to cooled/aftercooled compressor without adequate
permit sufficient unobstructed air to flow in and out freeze protection where it will be exposed to tem-
of the compressor cooling package to keep the perature less than 32°F(0°C).
operating temperature stable. The minimum dis- 4.3 SERVICE AIR PIPING
tance that the compressor should be from sur- Service air piping should be installed as shown in
rounding walls is three (3) feet (914mm). To prevent Figure 4-1. A shut-off valve should be installed to
excessive ambient temperature rise, it is imperative isolate a compressor from the service line if
to provide adequate ventilation. required. Also notice that the service line should be
For water-cooled compressors, it is necessary to equipped with water legs and condensate drains
check the cooling water supply. The water system throughout the system.
must be capable of supplying the following flows: 4.4 COUPLING ALIGNMENT CHECK
MODEL-HP/KW WATER FLOW (GPM) In preparation for the factory test, the coupling sup-
plied with your compressor is properly aligned for
LS25S 200HP/149KW 44
operation. Refer to Coupling Alignment procedure
LS25S 250HP/187KW 54
explained in the Maintenance section of this manu-
LS25S 300HP/225KW 65
al.
LS25S 350HP/260KW 76
4.5 FLUID LEVEL CHECK
Your air compressor is also supplied with the prop-
er amount of fluid. However, it is necessary to
check the fluid level at installation. The level is
Water flow requirements are based on 80°F to checked by looking at the sight glass located on the
85°F (27°C to 29°C) water inlet temperature.
sump. If the sump is properly filled, the coolant level
Recommended water pressure range is 40 to 75 should fill 1/2 of the upper sight glass when the
psig (2.8 to 5.2 bar). Water flow rates will vary compressor is shutdown. When the oil level falls
with operating conditions. For rates based on below the center of the lower sight glass, fluid must
criteria other than that listed, consult your local
Sullair representative. be added.
45
Section 4
INSTALLATION
Figure 4-1 Service Air Piping (Typical Installation)
4.6 FLUID PIPING (REMOTE AIR-COOLED OPTION (usually lowest ambient). If the pressure drop is in
ONLY) excess of 10 psig (0.7 bar), a pump should be
To allow de-pressurization of the cooling package installed. Consult the Sullair Service Department for
and connecting piping between the compressor and recommendations.
the cooling package upon shutdown of the com- It is recommended that shutoff valves be installed in
pressor, a 1/2”(13 mm) de-pressurization line must the supply and return piping to facilitate compressor
be installed between the top of the fluid cooler and component’s maintenance.
the sump tank connection which is located on the
fluid supply and return line connection bracket. This Because of the variability in installations, the fluid
line must be maintained at a higher level than the necessary to fill the supply and return piping for the
supply and return piping for the fluid cooler. fluid cooler is not part of the standard scope of sup-
ply for the compressor. The fluid necessary to fill
The supply and return piping for the fluid cooler this piping may be ordered from the nearest Sullair
must be adequately sized to prevent excessive representative or the representative from whom the
pressure drop. The total pressure drop in the supply compressor was purchased. To assist in determin-
and return piping and associated fittings and ing the amount of fluid necessary to fill the piping,
valves, not including the cooler, shall not exceed 10 the following chart may be used.
psig (0.7 bar) at the worst case operating condition
46
Section 4
INSTALLATION
GALLONS/LITERS OF FLUID
PIPE SIZE PER 12 INCHES/304.8MM OF PIPE control panel, press STOP , then press
2 .1635/.62 START .
2 1/2 .2555/.97
3 .368/1.39
4 .6542/2.48
6 1.4719/5.57 Since some solid state starters have built-in power
monitoring, a dry run will only indicate compres-
4.7 ELECTRICAL PREPARATION sor overload when machine has this type of
Interior electrical wiring is performed at the factory. starter.
Required customer wiring is minimal, but should be
by a qualified electrician in compliance with OSHA, 5. Reconnect the three (3) motor leads and jog the
National Electrical Code, and any other applicable motor for a direction of rotation check, as
state or local electrical code concerning isolation explained in Section 4.8.
switches, fuse disconnects, etc. Sullair provides a 6. Verify all directions of rotations on all auxiliary
wiring diagram for use by the installer. motors.
A few electrical checks should be made to help 4.8 MOTOR ROTATION DIRECTION CHECK
assure that the first start-up will be trouble free. After the electrical wiring has been done, it is nec-
essary to check the direction of the motor rotation.
With the control system in MANUAL mode, press
Lethal shock hazard inside.
the and pads in succession to bump start
Disconnect all power at source, before opening
or servicing starter or control panel.
the compressor. When looking at the motor from the
end opposite the compressor unit, the shaft should
1. Check incoming voltage. Be sure that the incom- be turning clockwise on all gear driven models, and
ing voltage is the same voltage that the com- counterclockwise on direct drive models. If the
pressor was wired for. motor shaft is not turning in the proper direction,
2. Check starter and overload heater sizes (see disconnect the power to the starter and exchange
Electrical Parts in Parts Manual). any two of the three power input leads, then re-
3. Check all electrical connections for tightness. check rotation. A “Direction of Rotation” decal is
located on the coupling guard between the motor
4. “DRY RUN” the electrical controls by disconnect-
and compressor to show proper motor/compressor
ing the three (3) motor leads from the starter.
rotation.
Pull out the EMERGENCY STOP button on the
47
Section 5
SUPERVISOR
Figure 5-1 Supervisor Control Panel
48
Section 6
COMPRESSOR OPERATION
6.1 INTRODUCTION pose, location, and use.
While Sullair has built into the LS25S Series pack- 6.2 PURPOSE OF CONTROLS
age a comprehensive array of controls and indica- All Supervisor Controller related functions and indi-
tors to assure its proper operation, the user should cators are presented in the Supervisor Controller
recognize and interpret readings which call for Manual, so please refer to that manual for further
service or indicate the onset of a malfunction. information. Additional indicators and functions
Before starting the unit, the user should become included in the package are as follows:
familiar with the controls and indicators-their pur-
THERMAL O/L RESET Momentarily pushing this button, found on the starter’s ther-
mal overload element housing, re-closes the starter’s con-
tacts after a current overload takes place. Please be aware
that the elements must be allowed to cool sufficiently before
resetting.
SPIRAL VALVE Internally bypasses and controls the air flow capacity of the
compressor, in order to match air supply to the demand.
Maintains a maximum pilot pressure of 70 psig (4.8 bar).
PRESSURE REGULATOR
(LOAD CHAMBER)
PRESSURE REGULATOR Opens a pressure line between the sump and the inlet unload
(UNLOAD CHAMBER) chamber, allowing the inlet valve to regulate air delivery
according to air demand. Works in conjunction with solenoid
valve #3.
SOLENOID VALVE #1 Electrically actuated, 3-way valve which controls the flow of
pneumatic logic signals. Used throughout package to:
•Open the blowdown valve.
•Pressurize the unload port/close the inlet valve during shut-
down operation.
•Open the (optional) spiral valve.
SOLENOID VALVE #2 Opens when the Wye-delta timer closes; closes when the
Wye-delta timer is open. Opens a pressure line between the
sump and inlet load chamber allowing the inlet valve to deliv-
er air. This prevents any air system loss and de-pressurizes
the controls when the compressor is shut off.
SOLENOID VALVE #3 Opens pressure line between sump and inlet unload chamber
for modulation.
Serves to control machine during sequencing with multiple
machines. Designates whether machine is at full load or mod-
ulating.
49
Section 6
COMPRESSOR OPERATION
CONTROL OR INDICATOR (CONT.) PURPOSE (CONT.)
PNEUMATIC INLET VALVE Blocks the reverse flow of air/fluid through the compressor
unit during shutdown, and opens to allow air intake to the
compressor during normal load.
Maintains 50 psig (3.5 bar) in the receiver tank when the
MINIMUM PRESSURE VALVE
compressor is running loaded. Also incorporates a check
valve, which prevents compressed air backflow from the sys-
tem when unloaded or shutdown.
PRESSURE RELIEF VALVE Vents the sump vessel to atmosphere before the com-
pressed air pressure exceeds rated tank pressure. Its oper-
ation indicates fault with the Supervisor operation unload
pressure set too high or failure of solenoid valve #1.
BLOWDOWN VALVE ASSEMBLY Vents the sump vessel to atmosphere during unloading and
shutdown.
THERMAL MIXING VALVE Bypasses fluid flow around the cooler until the fluid reaches
a temperature of 170°F, 77°C (195°F for water cooled KT and
> 150 psi/ 10.3 bar). Useful for fast warm-up during start.
Maintains a minimum temperature during periods of low load
or low ambient temperatures.
FLUID STOP VALVE Blocks the flow of cooler fluid to the sump during shutdown,
(remote-cooler package only) thus preventing the overfill of fluid in the sump.
SUMP SIGHT GLASSES Indicates level of lubricant in the sump. Located on the sump
side, fluid level should be maintained at a level between the
high and low sight glass.
SEPARATOR RETURN LINE SIGHT Indicate fluid flow in the separator return lines. Large flow
GLASSES should be visible during full load operation; little to no flow
during unloaded operation. Sluggish flow during full load
operation indicates the need to clean the strainers fitted to
the return lines.
WATER PRESSURE SWITCH De-energizes the starter, via the Supervisor, if the water pres-
sure falls below 10 psig (0.7 bar). This switch is not
adjustable. Used on water-cooled packages only.
DRAIN VALVES Lubricant sump drain valve.
6.3 INITIAL START-UP PROCEDURE described in the Installation Section have been
The following procedure should be used to make made.
the initial start-up of the compressor. 4. Open the shut-off valve to the service line.
1. Read the preceding pages of this manual thor- 5. Check for possible leaks in piping.
oughly.
6. Slowly close the shut-off valve to assure proper
2. Jog motor to check for correct rotation of fan nameplate pressure unload setting is correct.
(refer to Section 4.8). The compressor will unload at nameplate pres-
3. Be sure that all preparations and checks sure. If adjustments are necessary, see Control
50
Section 6
COMPRESSOR OPERATION
System Adjustments. 6.4 SUBSEQUENT START-UP PROCEDURE
7. Observe the operating temperature. If the oper- On subsequent start-ups, check that the proper
ating temperature exceeds 200°F (93°C) [215°F level is visible in the fluid sight glass and simply
(102°C) for water-cooled 24KT and > 150 psi], press the START or AUTO MODE button.
the cooling system and installation environment When the compressor is running, observe the
should be checked. instrument panel and maintenance indicators.
8. Open shut-off valve to the service line. 6.5 SHUTDOWN PROCEDURE
9. Reinspect the compressor for temperature and To shut the compressor down, simply press the
leaks the following day.
STOP button.
51
NOTES
52
Section 7
MAINTENANCE
7.1 GENERAL 7.5 FLUID CHANGE
As you proceed in reading this section, it will be Standard models are filled with the long life lubri-
easy to see that the Maintenance Program for the cant Sullube.
air compressor is quite minimal yet important. The Sullube should be changed under the following con-
use of the service indicators provided for the fluid fil- ditions, whichever occurs first:
ter, air filter and fluid separator, will alert you when
service maintenance is required. When the mainte- 1. Every 8000 hours.
nance message is displayed by the Supervisor 2. Once a year.
ControllerTM, maintenance for that specific item is 3. As indicated by fluid analysis.
required. See instructions for each item in Section A fluid sample at every 1000 hours is recommend-
7.7, Parts Replacement and Adjustment proce- ed. For a free Sullube analysis, send fluid to:
dures. Dow Chemical
7.2 DAILY OPERATION Lubricant Technology Center
Prior to starting the compressor, it is necessary to Building B-1605
check the fluid level in the sump. Should the level Freeport, TX 77541
be low, simply add the necessary amount. If the To facilitate this, a sample bottle is included with the
addition of fluid becomes too frequent, a simple compressor.
problem has developed which is causing this
7.6 SEPARATOR MAINTENANCE
excessive loss. See the Troubleshooting Section
Replace the separator elements when a message is
(7.8) under Excessive Fluid Consumption for a
displayed or after one (1) year, whichever comes
probable cause and remedy.
first. The separator elements must be replaced. DO
After a routine start has been made, observe the NOT clean the separator elements.
Supervisor control panel and be sure it monitors the
7.7 PARTS REPLACEMENT AND ADJUSTMENT
correct readings for that particular phase of opera-
PROCEDURES
tion. After the compressor has warmed up, it is rec-
ommended that a general check of the overall com- FLUID FILTER MAINTENANCE
pressor and Supervisor be made to assure that the Refer to Figure 7-1. The fluid filter (P/N 02250128-
compressor is running properly. 717) is located schematically after the thermal
valve. When servicing the fluid filter, shut the com-
pressor down, be sure all pressure has been
DO NOT remove caps, plugs, and/or other com-
released, then follow the instructions below. For
ponents when compressor is running or pres-
surized. Figure 7-1 Fluid Filter (P/N 02250128-717)
Stop compressor and relieve all internal pres-
sure before doing so.
7.3 MAINTENANCE AFTER INITIAL 50 HOURS OF
OPERATION
After the initial 50 hours of operation, a few mainte-
nance requirements are needed to rid the system of
any foreign materials if any. Perform the following
maintenance operations to prevent unnecessary
problems.
1. Clean the return line strainers.
2. Clean the return line orifices.
3. Change the fluid filter element.
4. Clean the control line filters.
7.4 MAINTENANCE AFTER 1000 HOURS
After 1000 hours of operation, it will be necessary to
perform the following:
1. Clean the return line strainers.
2. Replace the fluid filter element.
*Repair Kit P/N 02250121-657
53
Section 7
MAINTENANCE
element replacement order kit number 02250121- sary. When removing the primary element, always
657. check the secondary element for visible dirt, grease
1. Drain the fluid from the canister by removing the or damage. The secondary element must be
bottom drain plug changed after every sixth primary element change.
DO NOT clean the secondary element.
2. Loosen the spin-on canister using a wrench on
the bottom canister hex. ELEMENT REMOVAL
3. Pull the canister away from the filter head. The 1. Clean the exterior of the air filter housing.
filter element will be attached to the head. 2. Remove the cover assembly by loosening the
4. Separate the element from the head. wingnut securing it.
5. Remove the canister seals. 3. Pull the element assembly out of the housing.
6. Thoroughly clean the filter head and canister in 4. On the inside of the element, you will notice a
solvent. wingnut which fastens the element to the hous-
ing. Remove the wingnut and pull the primary
7. Lubricate the new seals with the same type of element out.
fluid used in the compressor and position each
seal in its appropriate place. 5. Loosen and remove the hex nut securing the sec-
ondary element. Remove the secondary ele-
8. Slide the element into the canister. ment.
9. Thread the canister and element back on the fil- 6. Inspect the secondary element and replace if
ter head. necessary.
AIR FILTER MAINTENANCE 7. Clean the interior of the housing by using a damp
Refer to Figure 7-2. Air filter maintenance should cloth. DO NOT blow dirt out with compressor air.
be performed when the air filter maintenance mes-
sage is displayed. The air filter is equipped with a 8. Install the new secondary element and replace
primary element and a secondary element. As pre- the sealing washer and hex nut.
viously stated, the Supervisor will alert you as to 9. With the secondary element in place, replace the
when the primary element maintenance is neces- primary element.
54
Section 7
MAINTENANCE
Figure 7-3 Separator Element Replacement shine through the element, revealing any holes.
2. Inspect all gaskets and gasket contact surfaces
of the housing. Should faulty gaskets be evident,
correct the condition immediately.
3. If the clean element is to be stored for later use,
it must be stored in a clean, closed container.
4. After the element has been installed, inspect and
tighten, if necessary, all air inlet connections
prior to resuming operation.
PRIMARY ELEMENT REPLACEMENT
1. Place the element in position over secondary ele-
ment. Replace the sealing washer and wingnut.
Tighten the wingnut so as to fully seat the ele-
ment gasket.
2. Install the cover/element assembly and replace
the wingnut.
SEPARATOR ELEMENTS REPLACEMENT
Refer to Figure 7-3. The separator elements must
be changed when “Separator Maintenance
Required” message is displayed, or once a year
whichever occurs first. Follow the procedure
explained below for separator element replace-
ment.
PROCEDURE FOR 200-350HP/149-261KW ELE-
MENT REPLACEMENT
1. Relieve all pressure from the separator and all
compressor lines prior to disconnecting any
pipes, tubing, etc.
2. Disconnect all piping connected to the separator
cover to allow removal (return lines, service
lines, etc.).
200-250HP/ 149-186KW: 3. Loosen and remove the twelve (12) 3/4” x 3” hex
*Primary Replacement Element P/N 250034-122 head capscrews from the cover plate.
**Secondary Replacement Element P/N 02250131-225 4. Lift the cover plate from the separator using a
3/4” jackscrew under the lifting arm post. The lid
300-350HP/ 224-261KW: can be pivoted to the side supported by the lift-
*Primary Replacement Element P/N 250034-124
ing arm.
**Secondary Replacement Element P/N 250034-130 5. Remove the primary and secondary separator
elements.
DO NOT strike the element against any hard sur- 6. Scrape the old gasket material from the cover
face to dislodge dust. This will damage the sealing and flange on the sump being careful not to let
surfaces and possibly rupture the element. the scraps fall in the sump.
DO NOT “blow” dirt out of the interior of the filter 7. Inspect the separator tank for rust, dirt, etc.
housing. This may introduce dust downstream of
8. Reinsert the separator elements with gaskets
the filter. Instead, use a clean damp cloth.
attached into the sump taking care not to dent
DO NOT oil the element. them against the tank opening. DO NOT remove
ELEMENT INSPECTION grounding staples. Check between separator
1. Place a bright light inside the element to inspect element flange and tank for continuity after
for damage or leak holes. Concentrated light will torquing bolts. DO NOT use anti-seize com-
55
Section 7
MAINTENANCE
Figure 7-4 Oil Return/Sight Glass
56
Section 7
MAINTENANCE
Figure 7-5 Pressure Regulator Adjustments
Above 100 psig (6.9 bar), the optional spiral valve pressure reducing regulator to maintain 70 psig (4.8
regulator should allow pressure to flow into the bar) signal to open the inlet valve.
chamber of the spiral valve actuator. The spiral DRIVE COUPLING INSTALLATION AND ALIGN-
valve should start to rotate at this time. MENT (200-350HP/ 149-261KW)
PRESSURE REDUCING REGULATOR Refer to Figures 7-6, 7-7 and 7-8. For coupling
When running with compressor loaded, adjust the installation and alignment, the tools required are a
straight edge, a measuring scale, one set of feeler
Figure 7-6 Drive Coupling (200-350HP/ 149-261KW) gauges, a set of standard Allen wrenches and one
set of standard socket wrenches.
TABLE 7-1
INSTALLATION DATA (200-350HP/149-261KW)
Max. Operating Misalignment
Tightening Coupling Parallel Angular
Torque Gap Offset
ft.-lbs./Nm inches/cm inches/cm inches/cm (I)
200 2.969 + .030 .010 .010
- .000
271Nm 7.5 + .08 .03 .03
- .000
(I) Angular misalignment in inches equals maximum A minus
minimum B as shown in Figure 7-7. DO NOT exceed val-
*Replacement Element P/N 046999 ues in Table above.
57
Section 7
MAINTENANCE
Figure 7-7 Drive Coupling Alignment rately to correct. Recheck the vertical offset.
STEP 4 INSTALL THE FLEXIBLE ELEMENT -
Position the motor and compressor keyways 180°
apart. Insert the flexible element between the two
hubs. The element should be compressed prior to
insertion. The element can be compressed by tight-
ening a suitably sized radiator hose clamp around
the outer edge of the element as shown in Figure 7-
8. Slide the ferry head capscrews with lockwashers
through the holes in the hubs and element. Tighten
the capscrews to 200 ft.-lbs. (271 Nm).
For installation and alignment of the drive coupling,
follow the steps explained below.
Capscrews are 3/4-10 x 4” LG ASTM A354 Grade
STEP 1 MOUNT HUBS - Mount the motor hub and BD yellow zinc di-chromate. DO NOT substitute
the compressor hub onto respective shaft. Position with any other bolts.
the hubs to establish the correct gap specified in After tightening the capscrews, tighten the shaft
Table 7-1 Installation Data. Secure each hub with a setscrews and remove the hose clamp from the
setscrew. flexible element. At this time, the coupling is ready
STEP 2 OFFSET ALIGNMENT - Clean any oil, for operation.
grease, dirt or paint from coupling faces and the
other surfaces of the drive flanges. Rotate shafts so
that a straight edge will rest squarely (or within the
0.010 inch maximum limit shown in Table 7-1
Installation Data) on both flanges and at a point 90° Figure 7-8 Parallel/ Angular Offset Alignment
away. The vertical offset alignment is adjusted by
the addition or removal of motor mounting shims.
Loosen the motor mounting bolts and slide the
motor sideways to correct the horizontal offset.
STEP 3 COUPLING GAP AND ANGULAR ALIGN-
MENT - Position the hubs to establish the proper
gap and angular alignment as indicated in Table 7-
1 Installation Data. To determine the angular mis-
alignment in inches, measure the maximum space
between the hub flanges and the minimum space
180° away, and then subtract. To adjust the hori-
zontal angular misalignment, loosen the motor
mounting bolts and adjust the motor position until
the angular alignment is within tolerance.
58
Section 7
MAINTENANCE
7.8 TROUBLESHOOTING A detailed visual inspection is worth performing for
The information contained in the Troubleshooting almost any problems which may prevent unneces-
chart is based upon both the actual applied situa- sary damage to the compressor. Always remember
tions and extensive testing at the factory. It contains to:
symptoms and usual causes for the described prob- a. Check for loose wiring.
lems. However DO NOT assume that these are the b. Check for damaged piping.
only problems that may occur. All available data c. Check for parts damaged by heat or an electrical
concerning the trouble should be systematically short circuit, usually apparent by discoloration or a
analyzed before undertaking any repair or compo- burnt odor.
nent replacement.
Should your problem persist after making the rec-
ommended check, consult your nearest Sullair rep-
For additional information on troubleshooting, resentative or the Sullair Corporation.
consult the Supervisor Controller manual.
Motor Starter Overloads Tripped Reset. Should trouble persist, check whether
motor starter contacts are functioning properly.
Low Incoming Line Voltage Check voltage. Should voltage check low, consult
power company.
59
Section 7
MAINTENANCE
7.9 TROUBLESHOOTING GUIDE (CONTINUED)
SYMPTOM PROBABLE CAUSE REMEDY
COMPRESSOR SHUTS DOWN HIGH TEMP T1 or T3 Message Displayed Cooling water temperature too high; increase
WITH AIR DEMAND PRESENT water flow (water-cooled only).
(CONTINUED)
Cooling water flow insufficient; check water lines,
valves (water-cooled only) and available water
pressure differential.
Low Water Pressure Check the cooling fan motor or water flow sys-
(FAN OL/LOW WATER display) tem.
COMPRESSOR WILL NOT BUILD Air Demand is Too Great Check service lines for leaks or open valves.
UP FULL DISCHARGE PRESSURE
Dirty Air Filter Check for filter maintenance message on supervi-
sor panel and change or clean element if
required.
LINE PRESSURE RISES ABOVE Leak in Control System Causing Loss of Check for leaks.
UNLOAD P2 PRESSURE SETTING Pressure Signals
ON THE SUPERVISOR
Defective Blowdown Valve Check that sump pressure is exhausted to the
atmosphere when in the OFF LOAD mode.
Repair or replace if necessary (kit available).
60
Section 7
MAINTENANCE
7.9 TROUBLESHOOTING GUIDE (CONTINUED)
SYMPTOM PROBABLE CAUSE REMEDY
LINE PRESSURE RISES ABOVE Plugged Control Line Filter Clean or repair if necessary.
UNLOAD P2 PRESSURE SETTING
ON THE SUPERVISOR (CONT.)
EXCESSIVE FLUID CONSUMP- Clogged Return Line Strainer or Orifice Clean strainer (screen with o-ring replacement kit
TION available)
Clean orifice.
Leak in the Lubrication System Check all pipes, connections and components.
PRESSURE RELIEF VALVE Defective Pressure Relief Valve Replace pressure relief valve.
OPENS REPEATEDLY
LIQUID WATER IN COMPRESSED Water Vapor Condensation From Cooling Remove the water vapor from compressed air
AIR SERVICE LINE and Compression Occurs Naturally prior to distribution through the air system. Check
operation of aftercooler and moisture separator.
Install a compressed air dryer sized for the flow
and dryness level required. (Note: Filters may also
be required to remove particulates, liquid oil
aerosols or for oil vapor removal. Change car-
tridges as recommended by the filter manufactur-
er.) Check all drain traps routinely to insure their
proper operation. Maintain them regularly.
61
NOTES
62
Section 8
ILLUSTRATION AND PARTS LIST
8.1 PROCEDURE FOR ORDERING PARTS
Parts should be ordered from the nearest Sullair Representative or the Representative from whom the com-
pressor was purchased. If for any reason parts cannot be obtained in this manner, contact the factory directly
at the address or phone numbers listed below.
When ordering parts always indicate the Serial Number of the compressor. This can be obtained from the Bill
of Lading for the compressor or from the Serial Number Plate located on the compressor. For compressor unit
parts only, order parts by the unit serial number place located on the compressor unit.
For ordering parts other than those pertaining to the compressor unit, use serial number located on nameplate
mounted on control panel.
63
Section 8
ILLUSTRATION AND PARTS LIST
8.2 RECOMMENDED SPARE PARTS LIST - 200-250HP/ 149-186KW (CONTINUED)
DESCRIPTION KIT NUMBER QTY
64
Section 8
ILLUSTRATION AND PARTS LIST
8.3 RECOMMENDED SPARE PARTS LIST- 300-350HP/ 224-261KW
DESCRIPTION KIT NUMBER QTY
65
Section 8
ILLUSTRATION AND PARTS LIST
8.4 MOTOR, COMPRESSOR, FRAME AND PARTS
02250134-871R00
66
Section 8
ILLUSTRATION AND PARTS LIST
8.4 MOTOR, COMPRESSOR, FRAME AND PARTS
key part
number description number quantity
(I) There is an exchange program whereby a remanufactured compressor unit can be obtained from Sullair
distributors or the factory at less cost than the owner could repair the unit. For information regarding
the unit exchange program, contact your nearest Sullair representative or the Sullair Corporation.
The shaft seal is not considered part of the compressor unit in regard to the two year warranty.
The normal Sullair parts warranty applies. For shaft seal repairs order repair kit no. 067329-001.
(II) For maintenance on drive coupling element, order drive coupling replacement no. 046999.
(III) Motor and motor support may vary. Consult factory with machine serial number.
67
Section 8
ILLUSTRATION AND PARTS LIST
8.5 AIR INLET SYSTEM
02250134-881R01
68
Section 8
ILLUSTRATION AND PARTS LIST
8.5 AIR INLET SYSTEM
key part
number description number quantity
(I) For maintenance on inlet valve no. 02250137-084, order repair kit with o-rings and springs no.
02250141-645, or rebuild kit no. 02250141-648.
When performing maintenance on the inlet valve, gasket no. 040422 and gasket no. 041079 may also
need to be replaced.
(II) For maintenance on air filter no. 250006-718, order primary replacement element no. 250007-838, and
secondary replacement element no. 250007-839.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
69
Section 8
ILLUSTRATION AND PARTS LIST
8.6 INLET VALVE
02250137-085R00
70
Section 8
ILLUSTRATION AND PARTS LIST
8.6 INLET VALVE
key part
number description number quantity
(I) For maintenance on inlet valve no. 02250137-084, order repair kit with o-rings and springs no.
02250141-645, or rebuild kit no. 02250141-648.
When performing maintenance on the inlet valve, gasket no. 040422 and gasket no. 041079 may also
need to be replaced.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
71
Section 8
ILLUSTRATION AND PARTS LIST
8.7 FLUID COOLING SYSTEM- AIR-COOLED 200-250HP/ 149-186KW
02250134-080R02
72
Section 8
ILLUSTRATION AND PARTS LIST
8.7 FLUID COOLING SYSTEM- AIR-COOLED 200-250HP/ 149-186KW
key part
number description number quantity
73
Section 8
ILLUSTRATION AND PARTS LIST
8.7 FLUID COOLING SYSTEM- AIR-COOLED 200-250HP/ 149-186KW
02250134-080R02
74
Section 8
ILLUSTRATION AND PARTS LIST
8.7 FLUID COOLING SYSTEM- AIR-COOLED 200-250HP/ 149-186KW (CONTINUED)
key part
number description number quantity
(I) This item may vary with machine. Consult factory with machine serial number.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
75
Section 8
ILLUSTRATION AND PARTS LIST
8.8 FLUID COOLING SYSTEM- AIR-COOLED 300-350HP/ 224-261KW
02250128-959R02
76
Section 8
ILLUSTRATION AND PARTS LIST
8.8 FLUID COOLING SYSTEM- AIR-COOLED 300-350HP/ 224-261KW
key part
number description number quantity
77
Section 8
ILLUSTRATION AND PARTS LIST
8.8 FLUID COOLING SYSTEM- AIR-COOLED 300-350HP/ 224-261KW
02250128-959R02
78
Section 8
ILLUSTRATION AND PARTS LIST
8.8 FLUID COOLING SYSTEM- AIR-COOLED 300-350HP/ 224-261KW (CONTINUED)
key part
number description number quantity
32 bushing (I) - 1
33 capscr, hex gr5 1/2-13 x various len (I) - 4
34 bushing (I) - 1
35 motor (I) - 1
(I) This item may vary with machine. Consult factory with machine serial number.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
79
Section 8
ILLUSTRATION AND PARTS LIST
8.9 WATER COOLER PIPING- 200-350HP/ 149-261KW
80
Section 8
ILLUSTRATION AND PARTS LIST
8.9 WATER COOLER PIPING- 200-350HP/ 149-261KW
key part
number description number quantity
(I) This item may vary with machine. Consult factory with machine serial number.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
81
Section 8
ILLUSTRATION AND PARTS LIST
8.10 AIR PIPING SYSTEM- AIR-COOLED 200-250HP/ 149-186K
02250137-569R02
82
Section 8
ILLUSTRATION AND PARTS LIST
8.10 AIR PIPING SYSTEM- AIR-COOLED 200-250HP/ 149-186K
key part
number description number quantity
(I) For maintenance on water separator no. 02250111-105, consult factory for replacement parts.
(II) For maintenance on minimum pressure check valve no. 250033-821, order repair kit no. 250018-262.
(III) For maintenance on blowdown valve no. 409783, order repair kit no. 001667.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
83
Section 8
ILLUSTRATION AND PARTS LIST
8.10 AIR PIPING SYSTEM- AIR-COOLED 200-250HP/ 149-186K
02250137-569R02
84
Section 8
ILLUSTRATION AND PARTS LIST
8.10 AIR PIPING SYSTEM- AIR-COOLED 200-250HP/ 149-186K (CONTINUED)
key part
number description number quantity
85
Section 8
ILLUSTRATION AND PARTS LIST
8.11 AIR PIPING SYSTEM- WATER-COOLED 200-250HP/ 149-186KW
02250137-571R02
86
Section 8
ILLUSTRATION AND PARTS LIST
8.11 AIR PIPING SYSTEM- WATER-COOLED 200-250HP/ 149-186KW
key part
number description number quantity
(I) For maintenance on water separator no. 02250111-105, consult factory for replacement parts.
(II) For maintenance on minimum pressure check valve no. 250033-821, order repair kit no. 250018-262.
(III) For maintenance on blowdown valve no. 409783, order repair kit no. 001667.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
87
Section 8
ILLUSTRATION AND PARTS LIST
8.12 AIR PIPING SYSTEM- REMOTE-COOLED 200-250HP/ 149-186KW
02250137-570R02
88
Section 8
ILLUSTRATION AND PARTS LIST
8.12 AIR PIPING SYSTEM- REMOTE-COOLED 200-250HP/ 149-186KW
key part
number description number quantity
(I) For maintenance on minimum pressure check valve no. 250033-821, order repair kit no. 250018-262.
(II) For maintenance on blowdown valve no. 409783, order repair kit no. 001667.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
89
Section 8
ILLUSTRATION AND PARTS LIST
8.13 AIR PIPING SYSTEM- AIR-COOLED 300-350HP/ 224-261KW
02250137-572R00
90
Section 8
ILLUSTRATION AND PARTS LIST
8.13 AIR PIPING SYSTEM- AIR-COOLED 300-350HP/ 224-261KW
key part
number description number quantity
(I) For maintenance on water separator no. 02250111-105, consult factory for replacement parts.
(II) For maintenance on minimum pressure check valve no. 250033-821, order repair kit no. 250018-262.
(III) For maintenance on blowdown valve no. 409783, order repair kit no. 001667.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
91
Section 8
ILLUSTRATION AND PARTS LIST
8.13 AIR PIPING SYSTEM- AIR-COOLED 300-350HP/ 224-261KW
02250137-572R00
92
Section 8
ILLUSTRATION AND PARTS LIST
8.13 AIR PIPING SYSTEM- AIR-COOLED 300-350HP/ 224-261KW (CONTINUED)
key part
number description number quantity
93
Section 8
ILLUSTRATION AND PARTS LIST
8.14 AIR PIPING SYSTEM- WATER-COOLED 300-350HP/ 224-261KW
02250137-575R00
94
Section 8
ILLUSTRATION AND PARTS LIST
8.14 AIR PIPING SYSTEM- WATER-COOLED 300-350HP/ 224-261KW
key part
number description number quantity
(I) For maintenance on water separator no. 02250111-105, consult factory for replacement parts.
(II) For maintenance on minimum pressure check valve no. 250033-821, order repair kit no. 250018-262.
(III) For maintenance on blowdown valve no. 409783, order repair kit no. 001667.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
95
Section 8
ILLUSTRATION AND PARTS LIST
8.15 AIR PIPING SYSTEM- REMOTE-COOLED 300-350HP/ 224-261KW
02250137-574R00
96
Section 8
ILLUSTRATION AND PARTS LIST
8.15 AIR PIPING SYSTEM- REMOTE-COOLED 300-350HP/ 224-261KW
key part
number description number quantity
(I) For maintenance on minimum pressure check valve no. 250033-821, order repair kit no. 250018-262.
(II) For maintenance on blowdown valve no. 409783, order repair kit no. 001667.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
97
Section 8
ILLUSTRATION AND PARTS LIST
8.16 AIR PIPING SYSTEM- 24KT 350HP/261KW
02250137-580R00
98
Section 8
ILLUSTRATION AND PARTS LIST
8.16 AIR PIPING SYSTEM- 24KT 350HP/261KW
key part
number description number quantity
(I) For maintenance on water separator no. 02250111-105, consult factory for replacement parts.
(II) For maintenance on minimum pressure check valve no. 250033-821, order repair kit no. 250018-262.
(III) For maintenance on blowdown valve no. 409783, order repair kit no. 001667.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
99
Section 8
ILLUSTRATION AND PARTS LIST
8.16 AIR PIPING SYSTEM- 24KT 350HP/261KW
02250137-580R00
100
Section 8
ILLUSTRATION AND PARTS LIST
8.16 AIR PIPING SYSTEM- 24KT 350HP/261KW (CONTINUED)
key part
number description number quantity
101
Section 8
ILLUSTRATION AND PARTS LIST
8.17 FLUID PIPING SYSTEM- AIR-COOLED 200-250HP/ 149-186KW
02250135-894R01
102
Section 8
ILLUSTRATION AND PARTS LIST
8.17 FLUID PIPING SYSTEM- AIR-COOLED 200-250HP/ 149-186KW
key part
number description number quantity
(I) For maintenance on coreless filter no. 02250121-658, order replacement filter no. 02250139-995.
(II) For maintenance on thermal valve (175ºF), order repair kit no. 02250105-553.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
103
Section 8
ILLUSTRATION AND PARTS LIST
8.18 FLUID PIPING SYSTEM- WATER-COOLED 200-250HP/ 149-186KW
02250135-895R01
104
Section 8
ILLUSTRATION AND PARTS LIST
8.18 FLUID PIPING SYSTEM- WATER-COOLED 200-250HP/ 149-186KW
key part
number description number quantity
(I) For maintenance on thermal valve (175ºF), order repair kit no. 02250105-553.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
105
Section 8
ILLUSTRATION AND PARTS LIST
8.19 FLUID PIPING SYSTEM- REMOTE-COOLED 200-250HP/ 149-186KW
02250135-896R01
106
Section 8
ILLUSTRATION AND PARTS LIST
8.19 FLUID PIPING SYSTEM- REMOTE-COOLED 200-250HP/ 149-186KW
key part
number description number quantity
(I) For maintenance on thermal valve (175ºF), order repair kit no. 02250105-553.
(II) For mainteinance on fluid stop vavle no. 02250113-668, order repair kit no. 02250116-697.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
107
Section 8
ILLUSTRATION AND PARTS LIST
8.19 FLUID PIPING SYSTEM- REMOTE-COOLED 200-250HP/ 149-186KW
02250135-896R01
108
Section 8
ILLUSTRATION AND PARTS LIST
8.19 FLUID PIPING SYSTEM- REMOTE-COOLED 200-250HP/ 149-186KW (CONTINUED)
key part
number description number quantity
109
Section 8
ILLUSTRATION AND PARTS LIST
8.20 FLUID PIPING SYSTEM- AIR-COOLED 300-350HP/ 224-261KW
02250134-950R00
110
Section 8
ILLUSTRATION AND PARTS LIST
8.20 FLUID PIPING SYSTEM- AIR-COOLED 300-350HP/ 224-261KW
key part
number description number quantity
(I) For maintenance on thermal valve (170ºF) no. 02250120-955, order repair kit no. 02250120-957.
(II) For maintenance on coreless filter no. 02250128-717, order replacement kit no. 02250121-657.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
111
Section 8
ILLUSTRATION AND PARTS LIST
8.21 FLUID PIPING SYSTEM- WATER-COOLED 300-350HP/ 224-261KW
02250135-878R00
112
Section 8
ILLUSTRATION AND PARTS LIST
8.21 FLUID PIPING SYSTEM- WATER-COOLED 300-350HP/ 224-261KW
key part
number description number quantity
(I) For maintenance on thermal valve (170ºF) no. 02250120-955, order repair kit no. 02250120-957.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
113
Section 8
ILLUSTRATION AND PARTS LIST
8.22 FLUID PIPING SYSTEM- REMOTE-COOLED 300-350HP/ 224-261KW
02250135-879R01
114
Section 8
ILLUSTRATION AND PARTS LIST
8.22 FLUID PIPING SYSTEM- REMOTE-COOLED 300-350HP/ 224-261KW
key part
number description number quantity
(I) For maintenance on (170ºF) thermal valve no. 02250120-955, order repair kit no. 02250120-957.
(II) For maintenance on oil stop valve no. 02250122-004, order repair kit no. 001684.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
115
Section 8
ILLUSTRATION AND PARTS LIST
8.23 SUMP AND PARTS 200-250HP/ 149-186KW
02250135-451R01
116
Section 8
ILLUSTRATION AND PARTS LIST
8.23 SUMP AND PARTS 200-250HP/ 149-186KW
key part
number description number quantity
(I) Consult Oil Return Sight Glass Maintenance information in Section 7, and Figure 7-4 for maintenance
and repair kit on oil return/sight glass sub-assembly.
(II) For maintenance on separator elements, order (primary) replacement kit no. 250034-122, and (second-
ary) replacement kit no. 02250131-225.
(III) This item may vary with machine. Consult factory with machine serial number.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
117
Section 8
ILLUSTRATION AND PARTS LIST
8.24 SUMP AND PARTS 300-350HP/ 224-261KW
02250134-913R00
118
Section 8
ILLUSTRATION AND PARTS LIST
8.24 SUMP AND PARTS 300-350HP/ 224-261KW
key part
number description number quantity
(I) Consult Oil Return Sight Glass Maintenance information in Section 7, and Figure 7-4 for maintenance
and repair kit on oil return/sight glass sub-assembly.
(I) For maintenance on separator elements, order (primary) replacement kit no. 250034-124, and (second-
ary) replacment kit no. 250034-130.
(II) This item may vary with machine. Consult factory with machine serial number.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
119
Section 8
ILLUSTRATION AND PARTS LIST
8.25 COMPRESSOR SPIRAL VALVE ACTUATOR (OPTIONAL)
120
Section 8
ILLUSTRATION AND PARTS LIST
8.25 COMPRESSOR SPIRAL VALVE ACTUATOR (OPTIONAL)
key part
number description number quantity
(I) For maintenance on air cylinder no. 250016-183, order diaphragm repair kit no. 608311-001.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
121
Section 8
ILLUSTRATION AND PARTS LIST
8.26 ZERO-LOSS MOISTURE DRAIN (OPTIONAL)
02250131-040R02
122
Section 8
ILLUSTRATION AND PARTS LIST
8.26 ZERO-LOSS MOISTURE DRAIN (OPTIONAL)
key part
number description number quantity
123
Section 8
ILLUSTRATION AND PARTS LIST
8.27 PNEUMATIC CONTROLS
02250138-038R01
124
Section 8
ILLUSTRATION AND PARTS LIST
8.27 PNEUMATIC CONTROLS
key part
number description number quantity
(I) For maintenance on reducing pressure regulator no. 02250046-568, order repair kit no. 02250055-911.
(II) For maintenance on back pressure control regulator no. 02250052-358, order repair kit no. 048409.
(III) For maintenance on control air filter no. 02250112-032, order repair kit no. 02250112-031.
(IV) For maintenance on solenoid valve no. 02250125-657, order repair kit no. 02250125-829(valve), and
replacement coil no. 02250125-861.
(V) For maintenance on solenoid valve no. 02250125-667, order repair kit no. 02250125-826(valve), and
replacement coil no. 02250125-858.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
125
Section 8
ILLUSTRATION AND PARTS LIST
8.27 PNEUMATIC CONTROLS
02250138-038R01
126
Section 8
ILLUSTRATION AND PARTS LIST
8.27 PNEUMATIC CONTROLS (CONTINUED)
key part
number description number quantity
(VI) For maintenance on differential pressure regulator no. 406929, order repair kit no. 041742.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
127
Section 8
ILLUSTRATION AND PARTS LIST
8.27 PNEUMATIC CONTROLS
02250138-038R01
128
Section 8
ILLUSTRATION AND PARTS LIST
8.27 PNEUMATIC CONTROLS (CONTINUED)
key part
number description number quantity
(VII) This item may vary with machine. Consult factory with machine serial number.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
129
Section 8
ILLUSTRATION AND PARTS LIST
8.28 CONTROL BOX- SOLID STATE
02250122-005R04
130
Section 8
ILLUSTRATION AND PARTS LIST
8.28 CONTROL BOX- SOLID STATE
key part
number description number quantity
1 enclosure 02550108-859 1
2 door 02550109-465 1
3 bezel 02250089-302 1
4 beze; gasket 02550090-872 1
5 I/0 module 02250141-089 1
6 display module 02250119-330 1
7 display gasket 02250048-822 2
8 primary fuse 305 amp 250026-648 1
9 secondary fuse 5 amp 250019-751 1
10 univ. 250 va trans 02250083-189 1
11 power supply 24v 0250120-644 1
12 relay 45496 1
13 relay base 46467 1
14 ground bus 02550110-334 1
15 ground bar 02550101-721 1
16 240A IT starter 02250122-042 1
17 304A IT starter 02250120-789 -
18 360A IT starter 02250120-792 -
19 420A IT starter 02250122-043 -
20 500A IT starter 02250122-044 -
21 650A IT starter 02250120-645 -
22 850A IT starter 02250122-046 -
23 display label 02250130-344 1
24 E-stop decal 02550086-259 1
25 E-stop operator 02550085-504 1
26 contact block 250027-125 1
27 plate 02550086-265 1
131
Section 8
ILLUSTRATION AND PARTS LIST
8.29 CONTROL BOX- FULL VOLTAGE
02250122-511R04
132
Section 8
ILLUSTRATION AND PARTS LIST
8.29 CONTROL BOX- FULL VOLTAGE
key part
number description number quantity
1 enclosure 02550108-859 1
2 door 02550109-465 1
3 bezel 02250129-958 1
4 bezel gasket 02550090-872 1
5 I/O module 02550141-089 1
6 transformer 24v 02250135-283 1
7 primary fuse 3.5 amp 250026-648 2
8 secondary fuse 5 amp 250019-751 1
9 univ. 250 va trans 02250083-188 1
10 univ. 350 va trans 02250083-190 -
11 primary fuse 4 amp 250026-649 -
12 secondary fuse 6 a 250019-762 -
13 ground bus 02550110-334 1
14 ground bar 02550101-721 1
15 display module 02550119-330 1
16 display label 02550130-344 1
17 starter9 size 5 250038-284 1
18 starter9 size 5dp 02250113-513 -
19 starter9 size 6 250038-285 -
20 display module gasket 02250048-822 2
21 E-stop operator 02250085-504 1
22 contact block I-NC 250027-125 1
23 E-stop decal 02250086-259 1
24 plate 02250086-265 1
133
Section 8
ILLUSTRATION AND PARTS LIST
8.30 CONTROL BOX- WYE-DELTA
02250122-516R08
134
Section 8
ILLUSTRATION AND PARTS LIST
8.30 CONTROL BOX- WYE-DELTA
key part
number description number quantity
135
Section 8
ILLUSTRATION AND PARTS LIST
8.31 ENCLOSURE- AIR-COOLED 200-250HP/ 149-186KW
02250128-119R01
136
Section 8
ILLUSTRATION AND PARTS LIST
8.31 ENCLOSURE- AIR-COOLED 200-250HP/ 149-186KW
key part
number description number quantity
137
Section 8
ILLUSTRATION AND PARTS LIST
8.31 ENCLOSURE- AIR-COOLED 200-250HP/ 149-186KW
02250128-119R01
138
Section 8
ILLUSTRATION AND PARTS LIST
8.31 ENCLOSURE- AIR-COOLED 200-250HP/ 149-186KW (CONTINUED)
key part
number description number quantity
139
Section 8
ILLUSTRATION AND PARTS LIST
8.32 ENCLOSURE- AIR-COOLED 300-350HP/ 224-261KW
02250128-122R01
140
Section 8
ILLUSTRATION AND PARTS LIST
8.32 ENCLOSURE- AIR-COOLED 300-350HP/ 224-261KW
key part
number description number quantity
141
Section 8
ILLUSTRATION AND PARTS LIST
8.32 ENCLOSURE- AIR-COOLED 300-350HP/ 224-261KW
02250128-122R01
142
Section 8
ILLUSTRATION AND PARTS LIST
8.32 ENCLOSURE- AIR-COOLED 300-350HP/ 224-261KW (CONTINUED)
key part
number description number quantity
143
Section 8
ILLUSTRATION AND PARTS LIST
8.33 ENCLOSURE- WATER-COOLED 200-350HP/ 149-261KW
02250128-124R02
144
Section 8
ILLUSTRATION AND PARTS LIST
8.33 ENCLOSURE- WATER-COOLED 200-350HP/ 149-261KW
key part
number description number quantity
145
Section 8
ILLUSTRATION AND PARTS LIST
8.33 ENCLOSURE- WATER-COOLED 200-350HP/ 149-261KW
02250128-124R02
146
Section 8
ILLUSTRATION AND PARTS LIST
8.33 ENCLOSURE- WATER-COOLED 200-350HP/ 149-261KW (CONTINUED)
key part
number description number quantity
147
Section 8
ILLUSTRATION AND PARTS LIST
8.34 DECAL GROUP
148
Section 8
ILLUSTRATION AND PARTS LIST
8.34 DECAL GROUP
key part
number description number quantity
149
Section 8
ILLUSTRATION AND PARTS LIST
8.34 DECAL GROUP
150
Section 8
ILLUSTRATION AND PARTS LIST
8.34 DECAL GROUP (CONTINUED)
key part
number description number quantity
151
Section 8
ILLUSTRATION AND PARTS LIST
8.34 DECAL GROUP
152
Section 8
ILLUSTRATION AND PARTS LIST
8.34 DECAL GROUP (CONTINUED)
key part
number description number quantity
(I) ISO decal may vary per machine. To determine the proper part number of this decal, consult factory
with machine serial number.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
153
Section 8
ILLUSTRATION AND PARTS LIST
8.35 DECAL LOCATIONS- AIR-COOLED/OPEN
154
Section 8
ILLUSTRATION AND PARTS LIST
8.35 DECAL LOCATIONS- AIR-COOLED/OPEN
key part
number description number quantity
(I) This decal is used with 24KT fluid option fill only.
(II) ISO decal may vary per machine. To determine the proper part number of this decal, consult factory with
machine serial number.
(III) Fluid decal will vary per machine fill. To determine the compressor’s proper fill decal, consult factory
with machine serial number.
(IV) This decal is used with actuator option only.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
155
Section 8
ILLUSTRATION AND PARTS LIST
8.36 DECAL LOCATIONS- WATER-COOLED/OPEN
156
Section 8
ILLUSTRATION AND PARTS LIST
8.36 DECAL LOCATIONS- WATER-COOLED/OPEN
key part
number description number quantity
(I) This decal is used with 24KT fluid option fill only.
(II) ISO decal may vary per machine. To determine the proper part number of this decal, consult factory with
machine serial number.
(III) Fluid decal will vary per machine fill. To determine the compressor’s proper fill decal, consult factory
with machine serial number.
(IV) This decal is used with actuator option only.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
157
Section 8
ILLUSTRATION AND PARTS LIST
8.37 DECAL LOCATIONS- ENCLOSURES
158
Section 8
ILLUSTRATION AND PARTS LIST
8.37 DECAL LOCATIONS- ENCLOSURES
key part
number description number quantity
(I) ISO decal may vary per machine. To determine the proper part number of this decal, consult factory
with machine serial number.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR
159
Section 8
ILLUSTRATION AND PARTS LIST
8.38 DECAL LOCATIONS- CONTROL BOX INTERIOR
160
Section 8
ILLUSTRATION AND PARTS LIST
8.38 DECAL LOCATIONS- CONTROL BOX INTERIOR
key part
number description number quantity
161
Section 8
ILLUSTRATION AND PARTS LIST
8.39 WIRING DIAGRAM- AIR-COOLED FULL VOLTAGE WITH SUPERVISOR CONTROLLER
02250136-109R03
162
Section 8
ILLUSTRATION AND PARTS LIST
8.40 WIRING DIAGRAM- WATER-COOLED FULL VOLTAGE WITH SUPERVISOR CONTROLLER
02250136-114R02
163
Section 8
ILLUSTRATION AND PARTS LIST
8.41 WIRING DIAGRAM- WYE-DELTA AIR- AND REMOTE-COOLED WITH SUPERVISOR CONTROLLER
02250136-108R03
164
Section 8
ILLUSTRATION AND PARTS LIST
8.42 WIRING DIAGRAM- WYE-DELTA WATER-COOLED WITH SUPERVISOR CONTROLLER
02250136-113R02
165
Section 8
ILLUSTRATION AND PARTS LIST
8.43 WIRING DIAGRAM- SOLID STATE AIR- AND REMOTE-COOLED WITH SUPERVISOR CONTROLLER
02250136-107R02
166
Section 8
ILLUSTRATION AND PARTS LIST
8.44 WIRING DIAGRAM- SOLID STATE WATER-COOLED WITH SUPERVISOR CONTROLLER
02250136-112R02
167
WORLDWIDE SALES AND SERVICE
SULLAIR CORPORATION
3700 East Michigan Boulevard
Michigan City, Indiana 46360 U.S.A.
www.sullair.com
Telephone: 1-800-SULLAIR (U.S.A. Only)
or 1-219-879-5451
Fax: (219) 874-1273
PARTS DEPARTMENT
Fax: (219) 874-1835
www.sullair.com/parts.shtm
SERVICE DEPARTMENT
Fax: (219) 874-1205
www.sullaircompressors.com