Auto Recloser Is An Inbuilt Function of REC650 (Bay Control Unit)

The document describes the auto recloser function of a REC650 bay control unit. It contains three sections: (1) the auto recloser operation for 3-phase faults, including timing parameters and logic gates; (2) the auto recloser start logic when the bay is in normal or transfer condition; (3) the auto recloser blocking logic under different fault conditions or equipment status. The auto recloser is used to automatically reclose the circuit breaker after a fault to restore power quickly, but will be blocked under permanent faults or out-of-sync conditions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
286 views3 pages

Auto Recloser Is An Inbuilt Function of REC650 (Bay Control Unit)

The document describes the auto recloser function of a REC650 bay control unit. It contains three sections: (1) the auto recloser operation for 3-phase faults, including timing parameters and logic gates; (2) the auto recloser start logic when the bay is in normal or transfer condition; (3) the auto recloser blocking logic under different fault conditions or equipment status. The auto recloser is used to automatically reclose the circuit breaker after a fault to restore power quickly, but will be blocked under permanent faults or out-of-sync conditions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Auto Recloser Function

≡ Auto Recloser is an inbuilt function of REC650 ( Bay Control Unit)

Fucntion Description IEC 61850 Identification IEC 60617 Identification ANSI/IEEE C37.2 Device Number

Auto Recloser for 3 Phase


SMBRREC O->l 79
Operation

Operation Description Value Used Logic Gate Description


Open time/ Dead Time 1 Sec And Gate (&) :- The AND gate is an electronic circuit
Reclaim Time 25 Sec that gives a high output (1) only if all its inputs are
Max Wait time for Sync check OK 30 Sec high.
Min time that CB must be Closed before new
5 Sec
sequence allows OR Gate:- The OR gate is an electronic circuit that
Max Trip Pulse Duration 0.2 Sec gives a high output (1) if one or more of its inputs are
Number of Shots 1 high

Auto Recloser Start Logic when Bay is in Normal Condition

REL 650 (Line Distance Prot. Relay)

Zone -1 Fault REC 650( Bay Control Unit)

Zone 2 Start
OR

Carrier Received

Carrier Selector &


Switch 'IN' Position

Carrier Channel
Healthy
Auto Recloser Start
&

REC 650( Bay Control Unit)

CBREADY( CB Ready for Reclosing Cycle i.e.


operating gear/mechanism charged)

CBPOS(Ensure that the CB was closed when line


fault occurred)

Blocking or Inhibit Signal shall notbe present &

Bay on Normal (NIT Switch is in Normal Position)

Synchocheck OK

Avik Bhattacharya 19/03/2019 15:20Hrs.


Auto Recloser Function
≡ Auto Recloser is an inbuilt function of REC650 ( Bay Control Unit)

Fucntion Description IEC 61850 Identification IEC 60617 Identification ANSI/IEEE C37.2 Device Number

Auto Recloser for 3 Phase


SMBRREC O->l 79
Operation

Operation Description Value Used Logic Gate Description


Open time/ Dead Time 1 Sec And Gate (&) :- The AND gate is an electronic circuit
Reclaim Time 25 Sec that gives a high output (1) only if all its inputs are
Max Wait time for Sync check OK 30 Sec high.
Min time that CB must be Closed before new
5 Sec
sequence allows OR Gate:- The OR gate is an electronic circuit that
Max Trip Pulse Duration 0.2 Sec gives a high output (1) if one or more of its inputs are
Number of Shots 1 high

Auto Recloser Start Logic when Bay is in Transfer Condition

REL 650 (Line Distance Prot. Relay)

Zone -1 Fault REC 650( Bay Control Unit)

Zone 2 Start
OR

Carrier Received

Carrier Selector &


Switch 'IN' Position

Carrier Channel
Healthy
Auto Recloser Start
&

REC 650( Bay Control Unit)

CBREADY( CB Ready for Reclosing Cycle i.e.


operating gear/mechanism charged)

CBPOS(Ensure that the CB was closed when line


fault occurred)

Blocking or Inhibit Signal shall notbe present &

Bay on Transfer (NIT Switch is in INTER/TRANSFER


position)

Synchocheck OK

Avik Bhattacharya 19/03/2019 15:20 Hrs.


Auto Recloser Blocking Logic

A/R Unsuccessful under these conditions:


REL 650 (Line Distance Prot. Relay) - Permanent fault
- During dead time faults
SOTF Trip - Out of synchronism

CB Open

Permit 3 PH Trip

Carrier Out/Fail

OC/EF Trip

GR A/B Trip relay


optd

Overvoltage Trip
OR

UndervoltageTrip

Manual CB Trip

Manual CB close

Distance Delayed Trip


(Z3,Z4)
Line REC 650
DT Received ( Bay Control Unit)

Z1,Z2,Z3,Z4
(PH-PH) Trip
Auto Recloser Block
&

Line Panel REC 650( Bay Control Unit) Bay in Normal


OR

GR A/B Trip relay


faulty

SF6 Gen Lockout

Loss of SF6 Alarm

TBC REC 650


TBC Panel ( Bay Control Unit)
REB 670
Busbar prot Trip
&
Auto Recloser Block

REC650 Bay in Transfer


OR
SF6 Gen Lockout

Loss of SF6 Alarm

Avik Bhattacharya 19/03/2019 15:20 Hrs.