100% found this document useful (1 vote)
82 views

Generator Protection

This document provides an overview of common protections used for generators, including: 1) Abnormal operating condition protections like loss of synchronism, abnormal frequency, and over excitation. 2) Stator and rotor protections like stator phase faults, overfluxing, and negative sequence. 3) System protections including out of step, backup, synchronizing, and inadvertent energizing protections. 4) Other protections for conditions like reverse power, loss of field, over voltage, and thermal overload. Diagrams and explanations are given for each protection type.

Uploaded by

stmeu
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
82 views

Generator Protection

This document provides an overview of common protections used for generators, including: 1) Abnormal operating condition protections like loss of synchronism, abnormal frequency, and over excitation. 2) Stator and rotor protections like stator phase faults, overfluxing, and negative sequence. 3) System protections including out of step, backup, synchronizing, and inadvertent energizing protections. 4) Other protections for conditions like reverse power, loss of field, over voltage, and thermal overload. Diagrams and explanations are given for each protection type.

Uploaded by

stmeu
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 23

Generator Protection

Some Review Slids


What a Generator looks like

Generator Protection

2
Generator

3
Generator Protection Review

Abnormal Operating Conditions


• Loss of Synchronism
• Abnormal Frequency
• Over excitation
• Field Loss
• Inadvertent Energizing
• Breaker Failure
• Loss of Prime Mover Power
• Open Circuits

4
Abnormal Operating Conditions

Overexcitation
Over Open
Power Loss of Field
Loss of Field Circuits
Overexcitation
Overexcitation

Exciter
The
"Wild"
G Power
System
Abnormal
Inadvertent Frequency
Abnormal Energizing,
Frequency Pole Flashover
Loss of
Reverse Breaker Synchronism
Power Failure

5
Generator Stator Phase Fault
Protection (87G)

6
Over fluxing Protection (V/Hz) (24)
Causes:
• As voltage rises above rating leakage flux increases
• Leakage flux induces current in transformer support structure causing rapid localized heating.
Volts per Hertz Limiter and Protection:
• used to protect generator and step-up transformer from damage due to excessive magnetic flux resulting from low
frequency and/or overvoltage
• excessive magnetic flux, if sustained, can cause overheating and damage the unit transformer and the generator
core
• V/Hz limiter (or regulator) controls the field voltage so as to limit the generator voltage when V/Hz exceeds a
preset value
• V/Hz protection trips the generator when V/Hz exceeds the preset value for a specified time
Over fluxing Protection (V/Hz) (24) Ct.
• Over excitation (Fluxing) occurs when the V/Hz ratio exceeds 105% at FL and
110% at no load
• V/Hz relays set at 110% with a 5 – 10 sec delay
• Generator overvoltage can occur without exceeding V/Hz relay setting due to
large over speed on hydro generator
81O/U (Over/Under Frequency Protection)
Over Frequency :
• Significant load rejection
• Should use for protection against possible over speeding condition
• Can cause Overvoltage on hydro turbines
Under frequency:
• Over load condition
• Loss of Generation
• Can cause Over excitation
• Can cause turbine blade fatigue
Out of Step Protection (78)
• High peak currents and off-frequency operation can occur when a generator losses
synchronism.
• Causes winding stress, high rotor iron currents, pulsating torques and mechanical
resonances.
• It will protect generator against pole slipping.
Negative Sequence Protection (46)
Causes:
• Unbalance load condition
• Unbalance fault
Effect:
• Negative sequence current interacts with normal positive sequence current to induce a double frequency current (120 Hz)
• Current (120 Hz) is induced into rotor causing surface heating
• Generator has established short-time rating, 𝐾 = 𝐼2 𝑡
Where
K=Manufacturer Factor (the larger the generator the smaller the K value)
I= Negative sequence current
• Protects generator from excessive heating in the rotor due to unbalanced stator currents
• Rotor temperature rise proportion to I
System Backup Protection (51V, 21)
• Common practice to provide protection for faults inside and outside of the generator zone of
protection
• It will use as back up for 87G
• Distance relay (21) set to include generator step up transformer and reach beyond, into the
system (zone 1 for internal faults and zone 2 for external faults)
• Time delays must be coordinated with those of the system protection to assure that system
protection will operate before back up
• Control or restraining function in 51V used to prevent or desensitize the overcurrent relay
from tripping until the generator voltage is reduced by a fault (80% of nominal voltage)
Synchronizing (25)
• Improper synchronizing of a generator to a system may result in damage to the generator step-up
transformer and any type of generating unit.
• The damage incurred may be slipped couplings, increased shaft vibration, a change in bearing alignment,
loosened stator windings, loosened stator laminations and fatigue damage to shafts and other mechanical
parts.
• In order to avoid damaging a generator during synchronizing, the generator manufacturer will generally
provide synchronizing limits in terms of breaker closing angle and voltage matching:
• Breaker closing angle: within ± 10 elect. degrees
• Voltage matching: 0 to +5%
• Frequency difference < 0.067 Hz
Reverse Power (32)
• Prevents generator from motoring on loss of prime mover
• From a system standpoint, motoring is defined as the flow of real power into the
generator acting as a motor.
• With current in the field winding, the generator will remain in synchronism with the
system and act as a synchronous motor.
• A power relay set to look into the machine is therefore used on most units.
• The sensitivity and setting of the relay is dependent upon the type of prime mover
involved.
Reverse Power (32) Ct.
Pickup setting should be below the following motoring limits:
• Gas : 50% rated power; time < 60 s
• Diesel : 25% rated power; time < 60 s
• Hydro turbines : 0.2% - 2% rated power; time < 60 s
• Steam turbines : 0.5% - 3% rated power; time < 30 s
Loss of Field Loss of Field (40)
CAUSES
• Field open circuit
• Field short circuit
• Accidental tripping of field breaker
• Regulator control failure
• Loss of main exciter
• If the field breaker is opened, the generator will act as an induction generator (receive
reactive power from the grid).
Split Phase Differential (50DT)
• Most turbine generators have single turn stator windings. If a generator has stator
windings with multi-turn coils and with two or more circuits per phase, the split-
phase relaying scheme may be used to provide turn fault protection.
• In this scheme, the circuits in each phase of the stator winding are split into two
equal groups and the currents of each group are compared.
• A difference in these currents indicates an unbalance caused by a single turn fault.
Split-Phase Differential Phase Differential
Split Phase Differential (50DT) Ct.
• Scheme detects turn to turn fault not involving ground.
• Generator must have two or more windings per phase to apply scheme.
• Used widely on salient-pole hydro generators. Used on some steam generators.
• Difference between current on each phase indicates a turn to turn fault.
• Need to have separate pick-up levels on each phase to accommodate practice of
removal of shorted terms.
Inadvertent Off Line Generator Protection (50/27)(50AE)
Protects against closing of the generator breaker while machine is not spinning / on turning gear
Causes:
• Operating errors
• Breaker head flashover
• Control circuit malfunctions
• Combination of above
Inadvertent energizing is a serious industry problem:
• Damage occurs within seconds
• Conventional generator protection will not provide protection
Generator Response and Damage to Three -Phase Inadvertent
Energizing
• Generator behaves as an induction motor
• Rotating flux induced into the generator rotor
• Resulting rotor current is forced into negative sequence path in rotor body
• Machine impedance during initial energizing is equivalent to its negative sequence
impedance
• Rapid rotor heating occurs 𝐾 = 𝐼2𝑡
Over-Voltage (59)
• Generator overvoltage may occur without necessarily exceeding the V/Hz limits of
the machine.
• Protection for generator overvoltage is provided with a frequency-compensated (or
frequency insensitive) overvoltage relay.
• The relay should have both an instantaneous unit and a time delay unit with an
inverse time characteristic.
• Two definite time delay relays can also be applied.
Large Machine Protection
IEEE C37.102

• Unit Connected
• High Z Grounded

32 Reverse Power
40 Loss of Excitation
46 Negative Sequence
49 Thermal Overload
51V voltage restraint
51G Ground overcurrent
64 Ground Relay
87 Differential

22
References

• IEEE generator protection guide

23

You might also like