SunSpec PV System Performance Assessment v2
SunSpec PV System Performance Assessment v2
1
Metrics and methods to assess performance
of existing systems to aid bankability of
PV asset class
Determining and evaluating system performance based on
actual weather and actual system characteristics is
critical to developing creditability for PV as an asset
class.
takeholders of existing photovoltaic (PV) ROI due to significantly lower annual energy
4
Fig. 1.2 - Performance Assessment Map showing
applicability of recommendations covered by this report
Cost Effective
Approaches to
Proprietary Proprietary Proprietary Performance
Maximum
2% to 5%
Uncertainty:
Utility billing, PPI, Utility billing, PPI, Utility billing, PPI, SunSpec
PR w/o adjustments PR w/o adjustments PR w/o adjustments Performance
Assessment
Focus
The recommendations were developed to be applicable to fixed flat panel PV module technology.
5
Current Industry this metric is Performance Ratio and it is
used regularly to compare systems.
Performance Metrics – However, it may result in incorrect
Literature Survey conclusions if the systems being
The review of currently used performance compared are in different locations with
metrics included information from NREL, different irradiance and temperature.
Sandia, IEC, equipment suppliers, and other
Performance metrics can first be divided
organizations. Some metrics appropriately
into instantaneous, short-term, and long-
use a ratio of actual performance divided by
term assessment periods. Various
expected performance, called Performance
degradation mechanisms and intermittent
Index (PI). Some methods have established
anomalies develop and occur over long-term
acceptance criteria which define the
periods so both periods are needed to
minimum output and are used primarily
complete an assessment. Instantaneous
during commissioning. Inputs used in
output is based on power and is denoted by
calculating expected performance included
kW (power). A long-term assessment
as-build system component ratings and
period, such as weekly, monthly, or annually
technology, irradiance, ambient temperature,
is based on energy and yield, and is denoted
wind, mounting, module temperature, and
by kWh (energy).
typical condition dependent derate factors.
Performance metrics can also be divided
The condition dependent derate factors are
into absolute and relative values. An
difficult to determine and they have a large
absolute value can be used to evaluate a
influence on the performance calculation,
system by comparing it to industry-wide
and also introduce significant uncertainty
values resulting in a figure of merit for the
into the calculations.
system. A relative performance metric can
In principle, performance assessment could be used to trend a specific system using
be based on any of the following: trend plots of the metric and associated
parameters. Both the absolute and relative
Actual output divided by actual solar
metrics provide input to troubleshooting of
input. This metric is representative of
degraded systems. Measurement
overall system efficiency and a normal
uncertainty and error analysis should be
system would have a value on the order
used to define a tolerance band to avoid
of 0.1, largely dependent on the module
reaching inappropriate conclusions.
efficiency. No analytical PV model is
needed in this case. This metric has Some metrics, such as Yield and
limited use most likely due to the Performance Ratio are independent of a PV
negative perception of a low value model, whereas Performance Index is the
around 0.1. actual performance divided by the calculated
Actual output divided by expected expected performance and is therefore
output. This metric is largely dependent dependent upon an accurate PV model.
on the system design, quality of Initial review of industry practice found
installation, and the accuracy of the PV various performance metrics as shown in
model. A normal system would be on Table 2.1 in the Appendix.
the order of 1.0. This metric is used and
can be based on either power or energy.
Actual output normalized divided by
actual input normalized. An example of
6
Yield Summary of Effective
The standard Yield metric is considered to Performance Metrics
be the “bottom-line” indication of how well The industry has used various metrics, often
a system is performing since the purpose of with similar names but different calculation
the system is to maximize energy output for methods, or with different names and similar
a given system size; however, it does not calculation methods. Some metrics and
account for weather conditions or design and calculations presented in technical papers
can only be applied for a consistent are not effective for the purpose intended.
assessment period (such as annually). Since As the industry has evolved, data has
Yield increases proportionally with hours of become more available, and analyses easier
operation, insolation, and lower temperature, to perform; newer methods have been
a high yield due to unusually high insolation proposed and used. Based on evaluation of
can be misleading and potentially even mask these various metrics, those that are
a case of a degrading system. Conversely, a considered appropriate for assessments are
system with an unusually low insolation summarized in Table 2.2.
may be incorrectly judged to have poor
performance. If systems are being In general, performance assessment is the
compared using Yield, the hours of process of measuring or monitoring actual
operation, insolation, and cell temperature performance and comparing it to expected
should be equivalent for a fair comparison. performance.
The basic Yield equation is shown below as Either the actual performance or the
equation 1: expected performance must be adjusted to
account for the actual weather and derate
factor conditions. One approach is to adjust
the actual system kW AC output “up” to
STC (e.g. apply a ratio of 1000 W/m2 /
The value of a system ultimately comes Gactual) and compare this to the expected
down to annual AC energy output relative to STC system output from PV model
system cost. Therefore, Yield is a measure calculations.The other approach is to adjust
of system value rather than performance. the STC output from PV model calculations
Performance Index “down” to the actual condition (e.g. apply a
ratio of Gactual / 1000 W/m2). The second
Performance Index (PI) as typically used by approach is appropriate and more commonly
the industry represents the ratio of actual used by the industry.
output (either power or energy) of a system
divided by the expected output. The Performance Index (PI) is typically the
expected output was calculated using an direct ratio of actual output divided by
accepted PV model, such as the NREL expected output, and is obviously different
System Advisor Model (SAM), or a than a ratio of output divided by input such
regression model, therefore, the accuracy as is used in an efficiency equation.
and uncertainty of the PI value is dependent Performance Ratio (PR), as defined by
on the accuracy and uncertainty of the NREL and IEC, is a normalized version of
model. output divided by input so its value is not
similar to a system efficiency of around 10%
but rather is around 70%. The normalizing
7
approach of including the DC STC rating
and irradiation ratio, effectively converts the
PR to a ratio of actual output divided by a
“rough estimate” of expected output. If
compensation factors in addition to actual
irradiation are added to PR, such as
temperature, balance of system losses, etc.,
it converts PR to a ratio with expected value
in the denominator and is then similar to PI.
The simple algebra is shown later.
Energy Performance Index (EPI) is a ratio of
actual kWh AC divided by expected kWh
AC using actual climate data over the
assessment period as input to an accepted
PV system model, such as SAM with all
relevant derate parameters included, or as
input to a “trained” regression model.
“Trained” refers to the process of using
actual system historical data to solve for
regression equation coefficients. Therefore,
EPI (either SAM or Regression methods)
incorporates the most complete metric for
performance assessment.
In the paragraphs that follow, the four
metrics which are considered to be
appropriate for performance assessment are
discussed.
8
Table 2.2- Summary of Performance Metrics
Acronyms:
PI = Performance Index, ratio of actual divided by expected
PPI = Power Performance Index, instantaneous actual power divided by expected power
PR = Performance Ratio
CPR = Temperature compensated Performance Ratio
EPI = Energy Performance Index
kWhAC = AC Energy at system output at utility meter
kWDC = DC rating of array at standard test conditions (STC)
SAM = System Advisor Model, from NREL
KTemp = Temperature compensation factor based on (TCell-TSTC)
kWhSun = Total in-plane solar irradiance
Performance Ratio which could potentially be misinterpreted as
a degrading system. Hourly data also has
Performance Ratio (PR), as defined by variation from morning to afternoon that is
IEC61724 and NREL, is a metric commonly difficult to interpret.
used, however one shortcoming in the basic
PR is that normal temperature variation The seasonal variation of PR can be
influences PR and is not included in the illustrated using PVWATTS to represent an
basic equation. Specifically, cases with low actual system to calculate monthly AC kWh
temperature and moderate irradiation (such and monthly irradiation. A 100kW system
as late winter) result in higher PR and cases with latitude tilt in Sacramento was
with high temperature and moderate arbitrarily selected and analyzed resulting in
irradiation (such as late summer) will result the plot shown in Figure 2.1. It would
in lower PR. A normally operating system appear that the system performance was
typically has a declining PR in the spring, degrading February through July.
9
Figure 2.1 – Basic PR Seasonal Variation Without Temperature Correction
Both the numerator and denominator are summations of the measured increment data over the
assessment period. The assessment period can be daily, weekly, monthly, annually. Calculation
of hourly PR is a problem since some hours of the day with zero irradiance result in division by
zero and is undefined. Since hourly data is commonly available, hourly PR was calculated and
plotted for interest.
10
Analysis of hourly data required filtering to eliminate hours with zero irradiance. The Excel
filter function was used in various scenarios such as to include mid-day hours and for irradiance
greater than a defined value, such as 600 kWh/m2. Effectively, this was a “mid-day flash test”.
Filtering levels raise questions and doubts about the calculated PR value; therefore it is preferred
to calculate daily or longer periods. The Excel function of SUMIFS is useful to calculate the
total values for the period, and AVERAGEIFS is useful to calculate average values such as daily
temperature if temperature correction is being used in CPR.
11
hourly calculations weight the compensation factor by the irradiance or energy output for the
hour, or to use factors based on average annual ambient temperature.
Other factors besides temperature also affect PR and are also outside the control of the owner,
such as design, shading, degradation, balance of system, and could be included as compensation
factors; however the basis for estimating these factors to compensate PR is impractical.
Therefore, if compensation other than temperature is desired, it is more practical to calculate
Long-Term Energy Performance Index (EPI) using actual irradiation and temperature in one of
the accepted models, such as SAM or regression model.
If the purpose of the assessment is only to evaluate a specific system, trend analysis using a
temperature compensated PR is reasonable because it is not influenced by the accuracy and/or
uncertainty of a PV model.
Compensation for factors such as cell temperature, KTemp, can be applied to the basic PR to
adjust the DC power rating from Standard Test Conditions (STC), however since temperature
varies continuously with irradiance and weather, an averaging technique must be performed at
each time increment (such as, hourly) and used to calculate a daily average temperature.
Typical hourly data includes night hours when the energy production and irradiance are zero.
Dividing by zero is undefined; therefore, Daily PR should be calculated using the SUMIF
function in Excel to sum the hourly values to obtain the daily sum of kWhAC and kWhSun. A
daily PR would then be obtained using equation (3). Hourly PR values vary from zero to a
maximum either before or after noon depending on conditions and are considered to be of little
use for performance assessment. Averaging hourly PR to obtain daily PR was tried and not
recommended versus summation of the hourly kWhAC and kWhSun values for the day.
Because irradiance and temperature change continuously, it would be beneficial to use a time
increment less than an hour, however for practicality an average hourly temperature is
considered acceptable unless the assessment is for a large critical system. The 2004 King paper,
suggests that hourly averages is acceptable for most assessments, although other experts say
hourly average under-predicts performance due to the thermal lag when irradiance increases.
If additional compensation factors are of interest to be included, such as balance of system
losses, angle of incidence, soiling, shading, long-term degradation, etc, it is more practical to
include them in the Energy Performance Index (EPI) using an accepted PV model, such as SAM,
to incorporate the compensation factors rather than complicating PR.
12
Figure 2.2 –PR Without and With Temperature Compensation
13
Energy Performance Index (EPI) – SAM or equal:
When compensation factors are added to the PR equation, the equation is equivalent to
Performance Index of actual energy divided by expected energy for the assessment period.
Note that the PR equation which includes compensation for temperature or other factors is
identical to the equation for Energy Performance Index (EPI), based on the following algebra:
This equation is of the form of the Power Performance Index (PPI) presented later, however in
this case it is in terms of energy and is EPI.
Acceptable models (e.g. SAM) inherently include “compensation factors” as part of the model.
It is necessary to input actual weather data in a climate file. In the case of SAM, actual hourly
data for GHI, DNI, DHI, dry-bulb temperature, and wind speed can be incorporated into TMY3
format file and read by SAM. Other parameters included in the TMY3 file, such as dew-point,
relative humidity, pressure, and albedo can be assumed to be acceptable from the original TMY3
file for the specific location.
The rate of change of the compensation factors affects the time frame over which the summation
is performed.
When calculating the expected energy output, System Advisor Model (SAM), or equal, requires
actual weather conditions to be formatted in a Typical Meteorological Year format.
14
Procedure:
1. Download a TMY3 file in the vicinity of the PV array.
2. Click and open the function “Create a TMY3 File”
3. Obtain one year of hourly data for actual weather conditions at the PV array.
4. In order to calculate the Direct Normal Irradiance (DNI), the Direct Insolation Solar Code
(DISC) model developed by Dr. E. Maxwell of the National Renewable Energy
Laboratory, available on-line can be used.
5. The Diffuse Horizontal Irradiance (DHI) was also calculated through DISC data. Using
the DNI, and ϴz zenith angle, calculated by DISC, and the relationship between GHI, the
direct horizontal irradiance (dHI), and DHI, were able to be calculated.
Where:
6. Using the SAM Create a TMY3 Function, create a TMY3 file for your PV system.
7. Input system design characteristics and assumed derate factors into SAM and calculate an
expected hourly generation (kWhAC).
8. Calculate an hourly performance index using the measured energy generated and
expected energy generation from SAM.
9. Apply a filter removing all hours where less than a threshold was generated.
A plot of EPI is provided below from the 600kW PV system applying the above method. It
shows a potential performance problem in late summer that could be investigated, such as
soiling.
15
Figure 2.4: Daily EPI-SAM for One Year Using Actual Weather and SAM
16
The process to calculate EPI is:
1. Obtain hourly metered kWhAC for assessment period.
2. Sum hourly kWhAC, for each day using Excel SUMIF.
3. Calculate DNI, DHI, DiffHI from GHI using NREL DISC, or use POA data if available.
4. Calculate POA irradiance using Isotropic Sky model.
5. Calculate coefficient matrix using polynomial equation.
6. Use matrix pseudo-inverse to calculate hourly kWhAC .
7. Sum hourly kWhAC for day using Excel SUMIF.
8. Calculate EPI for day, plot daily trend.
Using the regression analysis method, the estimated daily energy can be calculated for
comparison to the actual, Figure 2.5 shows how the calculated and actual compare.
Figure 2.5: Plot Showing Agreement of Regression Equation
Different variables in the general regression equation were tried, such as inverter efficiency
which played a role to reduce the uncertainty. By analyzing weather data, it was found that at
high ambient temperatures the inverter shuts down even though the insolation was optimal for
high power output. Hourly data was used to determine the regression coefficients from the
general regression equation. The POA irradiance was calculated using the NREL- DISC program
using GHI data.
17
Using the general regression model and adding the inverter efficiency to the equation as a new
parameter reduced the uncertainty. With this new parameter, the uncertainty with a GHI greater
than 800 (W/m²) is 4.1%.
Figure 2.6: Plot Showing Result of Regression Method with 4% error bars.
Quarterly data was also used to see if any anomalies or trends existed. Quarterly data would be
used to define a regression equation for a particular season. Further work is needed on this topic
to fully assess its usefulness.
The same technique and method was used for 15-minute data. The reduction of averaging over a
longer period of time (for an hour) was the motive for using 15 minute data so that there would
be less averaging involved. For 15-minute data there were more wild points to be considered,
however, by taking into account more variables, 5% uncertainty was achieved.
The data has a range of points. There are more than 10,000 data points which have been graphed
on this chart and there are many more wild points that need to be taken into account. Yet, the
regression was able to predict the outcome within 5% of the actual power output.
For the year of 2011, the chart below shows the EPI obtained. The confidence is high in this case
since the generic model described above was altered to include more variables.
P = A + T H B + H C +H²D + TE +N F +T NG +DH
18
Figure 2.7: Plot Showing Wild Points Adversely Affecting EPI .
Anomalies were found as illustrated in Figure 2.8, whereby irradiance, cell temperature, and
system output varied counter intuitive to known PV principles.
19
Fig. 2.8 Data Anomalies Which Are Inconsistent With PV Operating Principles:
Between 12:20 and 12:30 - Irradiance decreases, cell temp constant, power increases
Between 13:10 and 13:30 - Irradiance decreases, cell temp increases, power increases
Between 13:50 and 14:00 - Irradiance large decrease, cell temp small decrease, power increases
Uncertainty estimates for the measured data were based on literature consensus. Uncertainty for
calculations was based on principles of propagation of uncertainty, such as using square-root-
sum-of-squares combination when products were calculated.
Power Performance Index (PPI)
The Power Performance Index (PPI) is the instantaneous actual AC kW power output divided by
the instantaneous expected AC kW power output. The instantaneous expected AC power
depends on many factors, including the instantaneous irradiance and cell junction temperature,
the module technology including STC ratings and spectral and angular response, and the derate
factors. The actual irradiance absorbed by the module cells (referred to as “effective irradiance”
by Sandia) can depend on a number of factors, including the POA irradiance just above the glass
surface, incident angle, glass coatings, soiling, encapsulant, etc.
A desirable module temperature measurement results in the average cell junction temperature
20
across the array under test. The average cell temperature depends on a number of factors,
including ambient temperature, irradiance, wind speed and direction, mounting geometries, etc.
Uncertainty results from the specific model used to calculate the expected power. Neglecting
some of the factors mentioned above increases uncertainty, but generally simplifies the
calculations and measurements. A detailed PPI analysis could be performed using SAM or other
PV design software to calculate the expected power output considering all relevant factors. A
simple model for the calculation of expected output uses the rated DC STC power (P) times
adjustment factors (Ks) which include instantaneous irradiance and temperature, and is called the
PKs method in this article. The actual power is then compared to the resulting expected power in
the PPI ratio.
Latency between the irradiance and temperature measurements and the actual power reading
should be minimized. Instantaneous measurements are ideal. If irradiance and temperature
measurements are taken manually, it is important to carefully timestamp actual power readings
and irradiance and temperature readings and note how steady the values are so that the actual
power value is correlated to the actual irradiance and actual temperature values. Experience has
shown that apparently clear sky conditions can result in significant variations of irradiance over a
short time. It should also be noted that the uncertainty in the actual power reading shown on an
inverter can vary from inverter to inverter. A revenue grade AC power meter is usually the best
method.
Instructions for Calculating Power Performance Index (PPI) using the PKs method
1. Visually inspect system - Determine as-built configuration, identify conditions affecting
performance, estimate typical derate factors per PVWATTS description or similar
documentation and combine to obtain derate K factor (KDerate).
2. Measure Plane of Array (POA) irradiance. If only horizontal data is available (GHI),
convert to POA using NREL DISC spreadsheet to calculate DNI, DHI and use Isotropic
model to convert to POA irradiance. Note that converting from GHI to POA will
introduce error into the irradiance measurement, especially at steep incident angles seen
early or late in the day. The Isotropic model formula is:
4. Measure module backside temperature and add an offset to account for temperature
difference between backside and cells, such as 3°C × KIrrad, per King 2004 paper shown
below. If backside temperature is not available, you can measure ambient temperature
and calculate cell temperature using Sandia model or NOCT value on module datasheet
21
using one of the following formulas. Note, this method will generally be less accurate
than directly measuring the backside temperature.
5. Calculate temperature K factor (KTemp) for temperature relative to STC using the
following formula, where μ is the power temperature coefficient and is a negative
number, such as typically - 0.005/°C.
7. Measure actual AC output power (kW) or use inverter displayed value at a time which is
correlated with the irradiance and module temperature measurements.
8. Calculate ratio of measured actual AC power to expected power, define values as Power
Performance Index (PPI)
9. Estimate uncertainty values for measured and calculated values (apply propagation of
uncertainty method using square root sum squares of each relative uncertainty in %).
10. Evaluate PI. If PI = 1.0 ± uncertainty, short-term system performance is acceptable,
proceed to Long Term Assessment.
Uncertainty of PPI
As noted above, the uncertainty associated with the PPI is highly dependent on the model used to
determine the expected power and the methods used for determining instantaneous irradiance
and module cell temperature. The PKs method trades-off uncertainty for simplicity. This
method results in an uncertainty of 10-15%. More sophisticated measurements and models will
reduce the uncertainty of the expected power and therefore reduce the uncertainty of the PPI.
Some industry tools and models have been shown to have uncertainty less than 5%. To reach
22
such accuracy levels requires care. For example, a better method for determining the average
cell junction temperature across the array is to use the Voc of the array as described in IEC 904-
5. This is generally a better method than backside temperature measurements plus offset or
calculations that take into account wind speed because in general it is nearly impossible to
determine the typically non-uniform distribution of wind flow over an array. It should be noted
that the Voc method has limitations at low irradiance values.
Accurate irradiance measurements can be achieved by using a matched reference cell or a model-
corrected reference cell oriented in the POA. This will give a good estimate of the effective
irradiance actually absorbed by the cell, taking into account angular and spectral response, glass
coatings etc and will generally be superior to inexpensive irradiance meters. These kinds of
irradiance meters are fairly accurate when oriented directly at the sun to give the direct normal
irradiance, however direct normal readings are only valid when the sun is directly normal to the
plane of array which in practice is only a few times during the year. Therefore angle-response
effects are not accounted for like when a reference cell is used oriented in the POA.
23
investment decisions. Use PR, CPR and/or EPI depending on the level of effort and level
of uncertainty.
Additional work is recommended to develop specific procedures for each of the four metrics
summarized above and for making Excel spreadsheets available for general use. Additional
long-term data should be analyzed to investigate the ability of metrics to meet the stated
purposes, and to determine best practices for obtaining reliable inputs with currently available
industry products such as monitoring systems and IV curve tracers. An industry standard would
also be useful to improve consistency in calculating and interpreting these performance metrics
across the industry.
Acknowledgements
Contributors to the work summarized in this report included SJSU students: Harikrishna
Patadiya, and Uriel Rosas, and SunSpec Performance Committee members: Willard MacDonald,
Laks Sampath, Mike Balma, Tim Keating, and David McFeely.
The SunSpec Alliance wishes to acknowledge SolarTech, where this project was initiated by the
same team, and originally published Version 1 of the document. The project was moved to the
SunSpec Alliance in 2013.
24
Table 2.1- Commonly Used Performance Metrics
METRIC CALCULATION REFERENCE
Yield kWh / kWDC STC NREL/CP-520-37358
Performance Ratio (kWh/ kWDC STC ) / (H/GSTC) IEC61724
Performance Ratio kWh / (sunhours × area × efficiency) SMA
(EActual / EIdeal) * 100%
Performance Ratio SolarPro, Taylor & Williams
EIdeal is temp. and irrad. compensated
Specific Production MWhAC / MWDC STC SolarPro, Taylor & Williams
(100 * Net production / total incident
Performance Ratio NREL/TP-550-38603
solar radiation) / rated PV module eff.
Performance Factor ISC,G*RSC*FFR*ROC*VOC,T Sutterlueti
Performance Index kWmeasured / kWexpected SolarPro, Sun Light & Power
Actual Power / (Rated power * irrad adj.
Performance Index * temp adj * degradation adj * soiling adj Townsend
* BOS adj)
Output Power Ratio kWmeasured / kWpredicted SolarPro, Sun Light & Power
Output power kW > CF-6R-PV Table CEC Commissioning
Output power kW > 95% expected SRP Arizona Utility
Specific Production MWhAC / MWDC-STC SolarPro, Taylor & Williams
Acceptance Ratio kWactual / kWexpected Literature
Inverter comparison kWh of multiple similar inverters Qualitative
String comparison Imp, Vmp of multiple parallel strings Qualitative
Utility billing Monthly comparison Qualitative
Performance Ratio,
(kWh/ kWDC *KTemp) / (H/ GSTC) Proposed in this report
temp. comp. (CPR)
Energy Performance kWh AC actual / SAM AC Expected
Proposed in this report
Index (EPI) using actual weather data
Power Performance
kWAC / (kWDC *KIrrad*KTemp*KDerate ) Proposed in this report
Index (PPI)
25
Sample of Excel Spreadsheets to calculate Performance Ratio (CPR)
PR ADJUSTMENT FACTOR DEVELOPMENT
Arizona Game & Fish 191 kW system live site data used to find PR adjustment factors to result in a PR value that has
minimal variation with time, irradiance, and temp, when in normal condition. Decrease in PR would then be due to degradation.
Plots on next tab shows results. System DC Rated Power (kW) = 191 Used only for comparison:
Input Site Data = Cut-off irrad (kW/M^2) = 0.75 NOCT (C)= 47
Output for plots = Power Temp. Coefficient (W/C) =-0.005 Wind (m/s) = 2
Daily PR
Average
using Daily PR
Hourly Measured Total Total Sum of
Hourly AC Average Total Power using
Irradianc Average Daily AC Daily Power
ID y m d t Energy Ambient Time Week Hourly PR Daily times Power
e Cell Energy Insolation times
(kWh) Temp. (C) Energy Hourly PR Weighted
(kW/M^2 Temp. (C) (kWh) (kWh/M^2) Hourly PR
and Average
)
Insolation
1 2011 2 13 0:00 0 0.004 12.664 7.747 0.00 1 0 0 0 0 0 0 0
2 2011 2 13 1:00 0 0.004 12.711 7.649 0.04 1 0 0 0 0 0 0 0
3 2011 2 13 2:00 0 0.004 11.68 6.487 0.08 1 0 0 0 0 0 0 0
4 2011 2 13 3:00 0 0.004 11.069 6.128 0.13 1 0 0 0 0 0 0 0
5 2011 2 13 4:00 0 0.004 11.33 6.604 0.17 1 0 0 0 0 0 0 0
6 2011 2 13 5:00 0 0.004 11.268 5.119 0.21 1 0 0 0 0 0 0 0
7 2011 2 13 6:00 0 0.004 10.469 3.426 0.25 1 0 0 0 0 0 0 0
8 2011 2 13 7:00 4.24 0.152 9.838 6.476 0.29 1 0 0 0.14595 0 0.618827 0 0
9 2011 2 13 8:00 41.732 0.549 11.617 18.17 0.33 1 0 0 0.39791 0 16.60556 0 0
10 2011 2 13 9:00 85.684 0.851 15.261 30.12 0.38 1 0 0 0.527091 0 45.16328 0 0
11 2011 2 13 10:00 125.876 1.069 18.872 46.435 0.42 1 0 0 0.616441 0 77.59508 0 0
12 2011 2 13 11:00 133.224 1.155 21.793 52.784 0.46 1 0 0 0.603851 0 80.4474 0 0
13 2011 2 13 12:00 129.68 1.117 23.064 52.186 0.50 1 844.996 7.584 0.607782 0.583265 78.81712 505.3351 0.598033
14 2011 2 13 13:00 111.624 0.931 23.454 43.163 0.54 1 0 0 0.627665 0 70.06247 0 0
15 2011 2 13 14:00 94.496 0.76 22.913 35.236 0.58 1 0 0 0.650893 0 61.50675 0 0
16 2011 2 13 15:00 79.572 0.641 23.137 34.701 0.63 1 0 0 0.649832 0 51.70844 0 0
17 2011 2 13 16:00 33.172 0.284 22.582 25.096 0.67 1 0 0 0.611318 0 20.27863 0 0
18 2011 2 13 17:00 5.696 0.067 20.232 16.015 0.71 1 0 0 0.444441 0 2.531536 0 0
19 2011 2 13 18:00 0 0.004 18.415 11.741 0.75 1 0 0 0 0 0 0 0
20 2011 2 13 19:00 0 0.002 17.76 10.554 0.79 1 0 0 0 0 0 0 0
26
Sample of Excel Spreadsheet to calculate Energy Performance Index (EPI-SAM)
Daily EPI-SAM
1.6
1.4
1.2
1
0.8
Daily EPI
0.6
0.4
0.2
0
0 100 200 300 400
27
Sample of Excel Spreadsheet to calculate Energy Performance Index (EPI-Regression)
28