EC3-X33 Superheat Controller and ECD-002 Keypad/Display Unit
Description Electrical Installation
EC3-X33 is a universal superheat controller used in conjunction • Refer to the electrical wiring diagram for electrical connections.
with Emerson Electrical Control Valves EX4...EX8. • Do not apply voltage to the controller before completion of wir-
ing.
• Ground the metal housing with a 1/4 in spade connector.
• Important: Keep controller and sensor wiring well separated from
mains wiring. Minimum recommended distance 1.2 in.
Warning: Use a class II category transformer for 24VAC power
supply. Do not ground the 24VAC lines. We recommend to use
individual transformers for EC3 controller(s) and for 3rd party
controllers to avoid possible interference or grounding problems
in the power supply. Connecting any EC3 inputs to mains voltage
www.emersonclimate.com/flowcontrols
11911 Adie Road P.O. Box 411400 St. Louis MO 63141 USA CUSTOMER SERVICE (314) 569-4666
ECD-002 Display/Keypad Unit Wiring
(LEDs and Button Functions)
Blinking: valve is opening
ON: valve is fully open
Blinking: valve is closing Parameters setting/saving
ON: valve is fully closed
Next parameter/
ON: demand value (higher)
OFF: no demand
ON: alarm
OFF: no alarm Next parameter/
Prg & Sel (5 sec) value (lower)
Manual reset for
blinking alarm codes Selecting/confirming
EX8 ≤ 5.2 seconds J: Third party controller (can use the analog output signal from
EC3)
u9 Sec.
Dimensions
EC3-X33 2.9
ECD-002
4.1
1.42
Cutout 2.8 x 1.1 in
.2 1.44
3.1
5.4 2.5
Main parameters (must be checked and modified if necessary) Optional parameters
Factory Field (recommended factory setting for majority of applications)
Code Parameter description & choices Min Max Setting Setting Factory Field
H5 Password 1 199 12 Code Parameter description & choices Min Max Setting Setting
u0 System Refrigerant 0 7 1 uu Start valve opening (%) 10 100 50
0 = R22; 1 = R134a; 2 = R507; 3 = R404A; 4 = R407C; u9 Start opening duration (second) 1 30 5
5 = R410A; 6 = R124; 7 = R744 (subcritical application) uL Low superheat alarm function 0 2 1
uP Installed pressure sensor type 0 1 0 0 = disable (for flooded evaporator)
0 = PT4-07M (for R22/R134a/R507/R404A/R407C/R124) 1 = enable auto reset 2 = enable manual reset
1 = PT4-18M (for R410A) Cut-out at 1°F (if it maintains 1 min.); Cut-in immediately at 6°F
2 = PT4-30M (for R744, subcritical) u5 Superheat set-point (°F)
ut Installed valve type 1 5 5 If uL enabled (auto or manual) 5.4 54 10.8
1 = EX4; 2 = EX5; 3 = EX6; 4 = EX7; 5 = EX8 If uL disabled 0.9 54 10.8
u2 MOP function 0 1 1
Mounting of ECD-002 0 = disable 1 = enable
ECD-002 can be installed at any time also during operation. u3 MOP set-point (°F) saturation temperature * * X
• ECD-002 can be mounted in Factory setting is according to selected refrigerant (u0):
panels with 2.8x1.1 in cutout +55°F for R22 +59°F for R134a +45°F for R507
• Push controller into panel cut- +45°F for R404A +59°F for R407C +59°F for R410A
out.(1) +122°F for R124 +23°F for R744
• Make sure that mounting lugs are ┌┘5 Units conversion (only for u3, u5, ┌┘1) 0 1 0
0 = °C, K, bar 1 = °F, R, psig
flush with outside of controller
(Psig values are divided by 10. Example: Display 12.5 is 125 psig)
housing
┌┘1 Value to show 0 4 0
• Insert allen key into front panel 0 = Measured superheat (F) 1 = Measured evaporator pressure (psi)
holes and turn clockwise. Mount- 2 = Valve opening (%) 3 = Measured coil-out temp. (°F)
ing lugs will turn and gradually 4 = calculated evaporating temperature (°F) from the pressure
move towards panel (2) b1 Battery error management, when battery 0 3 2
• Turn allen key until mounting lug is defective (EC3-X33 only), see below:
barely touches panel. Then move Alarm Reset possibility after
other mounting lug to the same Value Display Alarm Relay Valve recovery/replacement
0 – – Regulating –
position (3)
1 Ab – Regulating –
• Tighten both sides very carefully
2 Ab Signalling Fully close Auto
until keypad is secured. Do not 3 Ab Signalling Fully close Manual
over tighten as mounting lugs will (blinking)
break easily.
* Min. and Max. setting values are dependant to selected type of refrigerant.
Error/Alarm Handling
Alarm Related Alarm Requires manual reset
code Description parameter relay Valve What to do? after resolving alarm
E0 Pressure transmitter error - Signalling Fully close Check wiring connection and measure the signal 4 to 20 mA No
E1 Temperature sensor error - Signalling Fully close Check wiring connection and measure the resistance of sensor No
AΠ EX4…EX8 electrical - Signalling - Check wiring connection and measure the resistance of winding No
connection error
AL Low superheat (<1°F) uL: 1 Signalling Fully close Check wiring connection and operation of valve No
AL blinking uL: 2 Signalling Fully close Yes
Ab b1: 1 - Regulating Battery potentially does not have enough charge to close valve in case -
Ab Battery error b1: 2 Signalling Fully close of main power supply interruption. May occur temporarily with new -
Ab blinking b1: 3 Signalling Fully close controllers or after long storage but should disappear when battery is Yes
charged sufficiently. If Ab remains active even when battery is charged,
battery may be defective and should be replaced.
Er Data error display – - - - Data send to the display is out of range. Check temperature No
out of range and pressure sensor.
Note: When multiple alarms occur, the highest priority alarm is displayed until being cleared, Message
then the next highest alarm is displayed until all alarms are cleared. Only then will param- — No data to display
eters be shown again. The display will show an “—” at start up and when no data is sent to ECD-002
0 2 4
EC3-X33
2a 4a
0V
24 V AC
2b
1 4b
5 sec.
0 = R22
1 = R134a
2 = R507 1 = EX4
1a 3 = R404A 2 = EX5
12x 4 = R407C R 410A 3 = EX6
5 = R410A 4 = EX7
6 = R124 5 = EX8
7 = R744
2 4c
1b
4d
1c 3
1d 4e
1-199 3a EC3-X33
3b
88
24 V
1e 24 V AC
0 = PT4-07S
(R22/R134a/R507/R404A/R407C/R124)
1 = PT4-18S (R410A)
2 = PT4-30S (R744)
3c
Display of Data:
EX4, EX5 Ts
EX6, EX7 R22
EX8