Wcee2012 1411 PDF
Wcee2012 1411 PDF
Wcee2012 1411 PDF
Seismic
Static Pushover
Design and
Analysis
Simulation
for Seismic Design
of RC Buildings
A.Q. Bhatti
National University of Sciences and Technology (NUST), Islamabad,
Pakistan
H.Varum
University of Aveiro, Portugal
SUMMARY
Seismic retrofitting of already constructed buildings is one of the most effective methods of decreasing
the risk. However the seismic performance of the structure may not be improved by Strengthening
unless the professional engineer selects an appropriate modifying technique based on seismic
evaluation of the already constructed structures. In this paper nonlinear static pushover analysis has
been performed for the said building. The demand spectrum of ATC 40 procedure for this building
was compared with real site based demand spectra. The simulation has been compared with and
without strengthened structure. The plastic hinges of the building have been plotted for different safety
margins.
1. INTRODUCTION
A component based procedure developed for seismic rehabilitation of already constructed buildings
shall be used for a Tier3 Evaluation (ASCE/SEI 31-03). Analysis procedures for such kind of detailed
evaluation include linear and nonlinear methods of static or dynamic analysis. These procedures
include ATC 40, FEMA 356 & many other procedures. FEMA 356 is the recommended design
procedure for evaluation of existing buildings. Acceptance criteria for these kind of detailed
procedures for different performance levels depend on strength, stiffness and ductility properties of
elements & components evaluated from laboratory testing and analytical procedures. Such kind of
component based detailed evaluation methods should be used in accordance with the authority having
jurisdiction (Bhatti et al., 2011a, 2011b). If linear analysis procedure is adopted, the analysis should
implicitly and/or explicitly recognize nonlinear behavior. Force levels which are used for analysis in
the provisions for seismic evaluation of already constructed existing buildings shall be multiplied by
0.75 factor when used in a Tier 3 Evaluation phase as these methods are intended for design. In Tier 1
and 2 Evaluations, this reduction factor is taken into account in various factors including material
strength and m factor. The use of reduction factor is verified by following points.
1. The reduction factor reduce the earthquake shaking from conservative level followed in design
to one that is trusted to be more accurate for evaluating existing building.
2. The actual strength of element and/or components will be greater than used in procedure.
3. An existing building does not necessarily need to have the same level of safety as newly
constructed building since the remaining useful life of a existing building is obviously less
than a new building.
A building fulfilling all provisions for the seismic evaluation of existing buildings shall be considered
compliant with this section. The section properties are shown in Table 1.
Figure 1. 3D Finite Element Model Figure 2. Real Picture of Building in Pakistan for
which Seimic evaluation is performed
Beam – B1 (width x height) 12” x 18” Top 5 # 6, Bot 5-#6 (Stirrup #3@6”)
6 # 6 bars
Column – C1 12” x 16”
(Stirrups #3@6”)
6#6 bars
Column – C2 9” x 16”
(Strirrups # 3@6”
Slab Thickness = 6 “
2. METHODS OF ANALYSIS
Analysis of the Structure should be carried out using one of the methods discussed above. Linear
procedures are considered to be adequate when the expected nonlinearity level is low. This is
measured by finding the ratio of component demand to capacity (DCRs) (< 2.0).
The procedures which recognize the nonlinear behavior of the structural components in
earthquake are considered to give the most accurate results. Nonlinear analysis procedures should be
selected for complex and/or irregular buildings and for case where performance level is high. For the
Buildings with any of the following characteristics should not be evaluated by linear analysis methods.
In SAP2000 a frame is drawn as a line element having elastic properties and nonlinear force
displacement properties of individual frame elements are assigned (Computers and Structures Inc,
2000). The braced and unbraced frames are shown in Fig. 4 and Fig. 5. The pushover curves for the
braced and unbraced frame are shown in Fig. 6 and Fig. 8 respectively.
Figure 4. Formation of Hinges for Unbraced Figure 5. Formation of Hinges for braced Structure
Structure
In the above figure, Point A shows to unloaded states and point B shows yielding of the element.
The ordinate at C corresponds to optimum strength & on x-axis at C it shows the deformation at which
significant decrease in strength starts. The line from C to D shows the starting failure of the
component/element. The resistance from D to E shows that the frame elements sustain only gravity
loads. After point E the maximum deformation occurs. Gravity loads are no more sustained.
Figure 6. Pushover curve of Unbraced Structure Figure 7. ATC 40 Response Spectrum capacity
For Unbraced Structure
Figure 8. Pushover curve of braced Structure Figure 9. ATC 40 Response Spectrum Capacity
For Braced Structure
There are 3 types of hinges in SAP2000 (Edward L Wilson, 2000). They are default hinges, generated
hinges & user defined hinges as shown in Fig. 4 and Fig. 5. Only user defined hinges & default hinges
should be assigned to the frame elements or components. When the said hinge properties (user defined
or default) are assigned to a frame element/components, the program creates automatically generated
hinge properties. Default hinge properties of the frame elements could not be changed & it depends on
the section. The default hinge properties which are assigned to the frame elements for steel and
concrete members are on the basis of ATC-40 for braced and unbraced frame as shown in Fig. 7 and
Fig. 9 & FEMA-273 criteria.
In pushover analysis approach the target displacement for a MDOFS is usually estimated in
terms of displacement demands in correspondence with the equivalent SDOFS.
Lateral loads show the distribution of forces due to inertia imposed on the building during an
earthquake. The distribution of forces due to inertia varies with the extremity of Earthquake & with
the increasing time during earthquake. Commonly used lateral force patterns are uniform, elastic first
mode, “code" distributions and a single concentrated horizontal force at the top of structure. Multi-
modal load pattern derived from Square Root of Sum of Squares (SRSS) story shears is also used to
consider at least elastic higher mode effects for long period structures. These loading patterns usually
favor certain deformation modes that are triggered by the load pattern and miss others that are initiated
and propagated by the ground motion and inelastic dynamic response characteristics of the structure.
The invariant load patterns cannot account for the redistribution of inertia forces due to
progressive yielding and resulting changes in dynamic properties of the structure. Also, fixed load
patterns have limited capability to predict higher mode effects in post-elastic range. The underlying
approach of this technique is to redistribute the lateral load shape with the extent of inelastic
deformations.
5. CONCLUSION
In this research paper seismic evaluation of already existing buildings is carried out based using ASCE
31-03 provisions in order to understand the procedure in insight. ASCE 31-03 is based in 3 tiers of
increasing performance detail and reducing conservativism for safety. Prior to the evaluation of Tier 1
the performance level desired (Life Safety or Immediate Occupancy) the seismicity region (low,
moderate and/or high) & the structure type is evaluated. Detailed nonlinear static (pushover) is
performed. The time history analysis is considered to be the most accurate method to evaluate the
force & deformation demand at various frame elements/components of the building. However time
history analysis is limited for its use because dynamic behavior is very sensitive to modeling and
characteristics of ground motion. Inelastic static analysis or pushover analysis is recommended method
for evaluating seismic performance because of its simplicity.
REFERENCES
ASCE SEI/ASCE 7-05. (2005). Minimum Design Loads for Building and Other Structures, American Society of
Civil Engineers, Reston, VA.
BCP. (2007). Seismic Provision for Building Code of Pakistan. Ministry of Housing and Works Government of
Pakistan Islamabad.
Bhatti A.Q, Hassan SZ, Rafi Z, Khatoon Z, Ali Q. (2011a). Seismic Hazard Analysis of Islamabad Pakistan.
Journal of Asian Earth Sciences. 42:3,468-478
Bhatti A.Q, Kishi N. and Tan KH. (2011b). Impact resistant behaviour of an RC slab strengthened with FRP
sheet. Material and Structures. 44:10:1855-1864
Computers and Structures Inc. (CSI). (1998). SAP2000 Three Dimensional Static and Dynamic Finite Element
Analysis and Design of Structures V7.40N. Berkeley, California.
Computers and Structures Inc CSI. (1995). ETABS Extended Three Dimensional Analysis of Building Systems
Non linear Version 9.5. Berkeley, California USA
Edward L Wilson. (2000). Three Dimensional Static and Dynamic analysis of Structures” 3rd Edition.
Computers and Structures, Inc. Berkeley, California, USA
NESPAK. (2006). Revision/Updation of Building Code of Pakistan, Stage 1, Recommendations for preliminary
seismic design parameters and criteria for seismic resistant design of buildings in Islamabad – Rawalpindi
area. Ministry of Housing and Works, Government of Pakistan National Engineering Services Pakistan
(Pvt.) Limited (NESPAK).