Instrument Transformers
Instrument Transformers
Instrument Transformers
TRANSFORMERS
INSTRUMENT
TRANSFORMERS
MEDIUM VOLTAGE
INSTRUMENT TRANSFORMERS
P1 P2 P1 P2
Unused
secondary
taps must be C1
1S1 1S2 left open.
S1 S2 Ck
S1 S2 S2 Left open Unused Ck tab
A must be earthed.
A C2
Test Voltages
Highest voltage for Rated power-frequency Rated lightning impulse
equipment Um (r.m.s.) withstand voltage (r.m.s.) withstand voltage (peak)
12 28 75
17,5 38 95
24 50 125
36 70 170
INDOOR CURRENT TRANSFORMERS
SUPPORT TYPE
CURRENT TRANSFORMERS
12 - 24 kV
Block Type Design
Standard: IEC 60044-1/6, VDE, ANSI, GOST
TECHNICAL DATA
Rated data
Operating voltage
[kV] 12 - 17,5 24
(maximum)
Maximum rated
[A] 2500 4000 [Icont 1 x In]
primary current
Rated short-time
[kA] max. 60 [1000 x In]
thermal current Ith [1s]
C
D A
40
600 <= In <1500A
184
M 12,23 deep
120 32
P1
K
80
40
P2
L
Dimensions (mm)
36 kV
Block Type Design
Standard: IEC 60044-1/6, VDE, ANSI, GOST
Rated data
Operating voltage
[kV] 36
(maximum)
Maximum rated
[A] 3000
primary current
Rated short-time
[kA] max. 60 [max. 1000 x In]
thermal current Ith [1s]
In <=600A
B
184
M12,23 deep 120 32
40
600< In <1500A
184
M12,23 deep
120 32
P1
K
F
P2
L
40
80
Dimensions (mm)
24 - 36 kV
Standard: IEC 60044-1/6, VDE, ANSI, GOST
TECHNICAL DATA
Type AK24 AK36
Rated data
Operating voltage
[kV] 24 36
(maximum)
Maximum rated
[A] 1500
primary current
Rated short-time
[kA] max. 60 [max. 1000 x In]
thermal current Ith [1s]
D A
B
M 12,23 deep
120
ø28
In <=600A
184
M 12,23 deep
120 32
P1
K
40
F
P2
L
600< In <1500A
Dimensions (mm)
A 178 190
B 280 360
C 244 244
D 122 122
E 287 255
F 178 225
G 200 160
H 150 200
1. When the secondary terminals are connected to the measuring or protection devices,
one of the terminals should be earthed for safety as seen in FIGURE VT-1
2. The base plate must be earthed.
3. The secondary circuits must not be short-circuited during operation. Otherwise the
voltage transformers will be thermally destroyed.
4. If any of the secondary windings of a voltage transformer, used for the purpose of
measuring, will not be used then it must be left open with one terminal connected to
earth as seen in FIGURE VT-2. However, even if the open-delta windings are not to be
used for detection of earth faults, they must be connected in an open delta circuit and an
appropriate resistor (depending on the voltage and thermal power rating of the secondary)
must be connected and open-delta circuit must be earthed only at one point as seen on
FIGURE VT-4. Please refer to the technical recommendations below.
5. For single phase transformers, the neutral terminal of the primary “ N ” must be
earthed in the earthed (neutral) systems as seen in FIGURE VT-3
A
R
B A N
S
a b a n
A B
da dn
dn da
Earth fault
a b winding resistor
da dn
Test Voltages
Highest voltage for Rated power-frequency Rated lightning impulse
equipment Um (r.m.s.) withstand voltage (r.m.s.) withstand voltage (peak)
12 28 75
17,5 38 95
24 50 125
36 70 170
INDOOR VOLTAGE TRANSFORMERS
SINGLE POLE
VOLTAGE TRANSFORMERS
12 - 24 - 36 kV
Single Pole Insulated
Block Type Design
Standard: IEC 60044-2, IEC 61869, VDE, ANSI, GOST
TECHNICAL DATA
Type VB12 VB24 VB36
Rated data
Highest voltage for equipment,
[kV] 12 - 17,5 24 36
Um [r.m.s.]
C A
D
B
A
Dimensions (mm)
36 kV
Single Pole Insulated
Standard: IEC 60044-2, IEC 61869-3, VDE, ANSI, GOST
TECHNICAL DATA
Type VK36
Rated data
Highest voltage for equipment,
[kV] 36
Um [r.m.s.]
C A
D
G H B
E F
Type VK36
Dimensions (mm)
A 245
B 390
C 320
D 160
E 435
F 250
G 300
H 225
INDOOR VOLTAGE TRANSFORMERS
DOUBLE POLE
VOLTAGE TRANSFORMERS
12 - 24 kV
Double Pole Insulated
Block Type Design
Standard: IEC 60044-2, IEC 61869-3, VDE, ANSI, GOST
TECHNICAL DATA
Type 2VB12 2VB24
Rated data
C
D A
L
K
B
A
F
B
G
E
Dimensions (mm)
A 148 178
B 220 280
C 280 290
D 14O 145
E 350 360
F 148 178
S 270 280
H 125 150
K 110 130
L 100 165
INDOOR VOLTAGE TRANSFORMERS
SINGLE POLE
VOLTAGE TRANSFORMERS
12 - 24 - 36 kV
With Fuse
Single Pole Insulated
Block Type Design
Standard: IEC 60044-2, IEC 61869-3, VDE, ANSI, GOST
TECHNICAL DATA
Type VBF12 VBF24 VBF36
Rated data
Highest voltage for equipment,
[kV] 12 - 17,5 24 36
Um [r.m.s.]
D A
B
K
H
Dimensions (mm)
K_EN_IT_OG_14R01