Dse6010 Mkii Dse6020 Mkii Data Sheet
Dse6010 Mkii Dse6020 Mkii Data Sheet
Dse6010 Mkii Dse6020 Mkii Data Sheet
DSEGenset
ELECTRO-MAGNETIC COMPATIBILITY
AUTO START AND AUTO MAINS FAILURE BS EN 61000-6-2
EMC Generic Immunity Standard for
CONTROL MODULES the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
FEATURES
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
The DSE6010 MKII Auto Start Electronic J1939 (CAN) and non- Using the DSE Configuration Suite
Control Module and the DSE6020 electronic MPU and alternator PC Software the controller is easy TEMPERATURE
MKII Auto Mains (Utility) Failure sensing engine support for diesel, to use and configure which allows BS EN 60068-2-1
Ab/Ae Cold Test -30 oC
Control Module are suitable for a gas and petrol engines all in one alteration of operating parameters, BS EN 60068-2-2
wide variety of single gen-set variant. With a number of flexible sequences, timers and alarms. Bb/Be Dry Heat +70 oC
applications. inputs, outputs and protections, the VIBRATION
modules can be easily adapted to BS EN 60068-2-6
Monitoring engine speed, oil suit a wide range of applications. AVAILABLE VARIANTS Ten sweeps in each of three
major axes
pressure, coolant temperature, 5 Hz to 8 Hz at +/-7.5 mm,
6010-03 Auto Start with real time clock
frequency, voltage, current, power Through USB Communication both 8 Hz to 500 Hz @ 2 GN
and fuel level, the modules give modules can be configured using 6010-04 Auto start with real time clock and HUMIDITY
comprehensive engine and the DSE Configuration Suite PC heated display BS EN 60068-2-30
alternator protection. This is Software or through the module's Db Damp Heat Cyclic 20/55 oC
at 95% RH 48 Hours
indicated on a large back-lit LCD front panel editor. 6020-03 Auto Mains Failure with real time BS EN 60068-2-78
icon display via an array of warning, clock Cab Damp Heat Static 40 oC
at 93% RH 48 Hours
electrical trip and shutdown alarms. 6020-04 Auto Mains Failure with real time
clock and heated display SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 GN in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the optional sealing gasket.
6 4 4
DSE6010/20 MKII
7
OTHER
MAINS (UTILITY) DC OUTPUT GENERATOR / DC OUTPUT GENERATOR CHARGE FUEL & START ELECTRONIC
SENSING 1 OF 4 LOAD CURRENT 1 OF 4 SENSING ALTERNATOR OUTPUTS ENGINES &
(DSE6020 MKII) (Flexible with CAN) MAGNETIC PICK-UP
VOLTS VOLTS
+ D+
+ W/L +
DSEGenset
DSE6010/20 MKII
SPECIFICATION
DC SUPPLY
FREQUENCY RANGE
3.5 Hz to 75 Hz
INPUTS
DIGITAL INPUTS A to F
Negative switching
ANALOGUE INPUTS A to C
Configurable as:
0 Ω to 480 Ω
Negative switching digital input
ANALOGUE INPUT D
Configurable as:
Negative switching digital input
KEY BENEFITS KEY FEATURES • Support for 0-10 V & 4-20 mA 0 V to 10 V
0 Ω to 480 Ω
4 mA to 20 mA
• Automatically transfers between • Large back-lit icon display oil pressure sensors
mains (utility) and generator • Heated display option available • Configurable staged loading
(DSE6020 MKII only) • Fully configurable via the fascia outputs OUTPUTS
OUTPUT A (FUEL)
• Hours counter provides accurate or PC using USB • CAN, MPU and alternator 10 A short term, 5 A continuous,
information for monitoring and communication speed sensing in one variant at supply voltage
maintenance periods • Efficient power save mode • 3 engine maintenance alarms
OUTPUT B (START)
• User-friendly set-up and button • 3 phase generator sensing • Engine speed protection 10 A short term, 5 A continuous,
layout for ease of use • 3 phase mains (utility) sensing • Engine hours counter at supply voltage
• Multiple parameters are (DSE6020 MKII only) • Engine pre-heat
AUXILIARY OUTPUTS C, D, E & F
monitored simultaneously which • Generator/load power • Engine run-time scheduler 2 A DC at supply voltage
are clearly displayed on a large monitoring (kW, kV A, kV Ar, pf) • Engine idle control for starting &
back-lit icon display • Accumulated power monitoring stopping DIMENSIONS
OVERALL
• The module can be configured (kW h, kVA h, kVAr h) • Fuel pump control 216 mm x 158 mm x 43 mm
to suit a wide range of • Generator overload protection • Real time clock 8.5’’ x 6.2” x 1.5”
applications (kW) • Battery voltage monitoring
PANEL CUT-OUT
• Compatible with a wide range • Generator/load current • Start on low battery voltage 184 mm x 137 mm
of CAN engines, including tier 4 monitoring and protection • Configurable remote start input 7.2’’ x 5.3”
engine support • Breaker control via fascia • 1 alternative configuration
MAXIMUM PANEL THICKNESS
• Uses DSE Configuration Suite buttons • Comprehensive warning, 8 mm
PC Software for simplified • Fuel and start outputs, electrical trip or shutdown 0.3”
configuration configurable when using CAN protection upon fault condition
STORAGE TEMPERATURE RANGE
• Licence-free PC software • 4 configurable DC outputs • LCD and LED alarm indication
-40 °F to +185 °F
-40°C to +85°C
• IP65 rating (with optional • 4 configurable analogue/digital • Configurable event log (50)
gasket) offers increased inputs
OPERATING TEMPERATURE RANGE
resistance to water ingress • 6 configurable digital inputs
-22 °F to +158 °F
-30°C to +70°C
-40 °C to +70 °C
RELATED MATERIALS HEATED DISPLAY VARIANT
-40 °F to +158 °F
TITLE PART NO’S
DSE6010/20 MKII Installation Instructions 053-174
DSE6010/20 MKII Operator Manual 057-230
DSE6010/20 MKII Configuration Suite PC Manual 057-223 OPTIONAL PARTS
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-190/05/14 (2)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457