ASHRAE Method Air Flow: Air Temp Water Temp
ASHRAE Method Air Flow: Air Temp Water Temp
ASHRAE Method Air Flow: Air Temp Water Temp
7
air flow
Wp= A(0.0887+0.07815v)/Y(pw-pa)
total
area =A= Pool 1035 1100 m2
c1 = 0.0887
c2 = 0.07815
Y = latent heat required to change water to vapour
at surface water temperature kJ/kg 2436.92 kJ/kg
simplified formula
Wp = 4.0E-5 x A (Pw-Pa)xFa 0.082973 kg / sec l/s = 25608.95
l/s = 29816
200000 w 5.589876
c1 = 0.0887
c2 = 0.07815
Y = latent heat required to change water to vapour
at surface water temperature kJ/kg 2436.92 kJ/kg
simplified formula
Wp = 4.0E-5 x A (Pw-Pa)xFa 0.075574 kg / sec l/s = 17494.02
l/s = 19827
c1 = 0.0887
c2 = 0.07815
Y = latent heat required to change water to vapour
at surface water temperature kJ/kg 2436.92 kJ/kg
simplified formula
Wp = 4.0E-5 x A (Pw-Pa)xFa 0.068175 kg / sec l/s = 11836
l/s = 14022
Tldb = 12.7
Tadp 9
Tedb 46
BF = 0.1
Moisture
BF = (Wla-Wadp)/(Wea-Wadp)
Wla = 0.0081
Wadp = 0.0071
Wea = 0.0162
BF = 0.10989