Static Calculation

This document provides a static pressure calculation for an HVAC system in the AL ABEER EDU CITY project. It details 30 sections of ductwork with varying sizes from 58x50 inches to 20x18 inches. It calculates the length, friction rate, and friction loss for each section. The total friction loss is calculated to be 1.36 inches of water column. With a 20% safety factor added, the external static pressure is calculated to be 1.63 inches of water column.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
243 views4 pages

Static Calculation

This document provides a static pressure calculation for an HVAC system in the AL ABEER EDU CITY project. It details 30 sections of ductwork with varying sizes from 58x50 inches to 20x18 inches. It calculates the length, friction rate, and friction loss for each section. The total friction loss is calculated to be 1.36 inches of water column. With a 20% safety factor added, the external static pressure is calculated to be 1.63 inches of water column.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

STATIC PRESSURE CALCULATION

Project : AL ABEER EDU CITY


Project HVAC : SIEMENS
MEP Contractor : VOLTAS LIMITED
Document No:
Unit Ref:/ Air Flow : AH-1-03/4200 CFM

SI NO Description Air Volume Duct Size (inch) L


CFM mtr.
FA duct
1 Straight Duct 33000 58x50 9.17
2 Elbow 33000 58x50 12.00
3 Taper 30800 56x50 0.30
4 Straight Duct 30800 54x50 2.15
5 Taper 28600 53x49 0.30
6 Straight Duct 28600 52x50 2.15
7 Taper 26400 51x49 0.30
8 Straight Duct 26400 50x48 2.15
9 Taper 24200 50x47 0.30
10 Straight Duct 24200 50x46 2.15
11 Taper 22000 49x45 0.30
12 Straight Duct 22000 48x44 2.15
13 Taper 19800 48x42 0.30
14 Straight Duct 19800 48x40 2.15
15 Taper 17600 46x40 0.30
16 Straight Duct 17600 44x40 2.15
17 Taper 15400 44x38 0.30
18 Straight Duct 15400 44x36 2.15
19 Taper 13200 40x36 0.30
20 Straight Duct 13200 40x36 2.15
21 Taper 11000 40x32 0.30
22 Straight Duct 11000 40x32 2.15
23 Taper 8800 38x31 0.30
24 Straight Duct 8800 36x30 2.15
25 Taper 6600 34x28 0.30
26 Straight Duct 6600 32x26 2.15
27 Taper 4400 30x24 0.30
28 Straight Duct 4400 28x22 2.15
29 Taper 2200 24x20 0.30
30 Straight Duct 2200 20x18 2.15

AHU
GRILLE 2200
External static - Inches
Safety - 20 %
External static in mm of water column.
LATION

Length or Fricion Rate Friction Loss


Equivalent (INCH/100ft) (INCH)
Length (ft)

30.1 0.059 0.018


39.4 0.059 0.023
1.0 0.053 0.001
7.0 0.059 0.004
1.0 0.056 0.001
7.1 0.059 0.004
1.0 0.052 0.001
7.1 0.059 0.004
1.0 0.051 0.001
7.1 0.059 0.004
1.0 0.05 0.000
7.1 0.059 0.004
1.0 0.051 0.001
7.1 0.059 0.004
1.0 0.052 0.001
7.1 0.059 0.004
1.0 0.052 0.001
7.1 0.059 0.004
1.0 0.057 0.001
7.1 0.059 0.004
1.0 0.046 0.000
7.1 0.059 0.004
1.0 0.042 0.000
7.1 0.059 0.004
1.0 0.04 0.000
7.1 0.059 0.004
1.0 0.04 0.000
7.1 0.059 0.004
1.0 0.029 0.000
7.1 0.059 0.004
0.0 0.000
0.0 0.000
0.0 0.000
0.0 0.000
0.0 1.181
0.0 0.072
1.36
1.63
n. 41.4