Transformer Sizing Calculation

This document provides calculations to size a transformer for a 1500kW motor. It determines that a 5MVA transformer with voltages of 11kV and 6.6kV and an impedance of 7.15% would be suitable. The calculations show that this transformer would allow a voltage drop of 18.18% at startup, within the permissible 20% limit. Therefore, the selected 5MVA transformer rating is suitable to run the 1500kW motor at direct online (DOL) mode.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (9 votes)
5K views2 pages

Transformer Sizing Calculation

This document provides calculations to size a transformer for a 1500kW motor. It determines that a 5MVA transformer with voltages of 11kV and 6.6kV and an impedance of 7.15% would be suitable. The calculations show that this transformer would allow a voltage drop of 18.18% at startup, within the permissible 20% limit. Therefore, the selected 5MVA transformer rating is suitable to run the 1500kW motor at direct online (DOL) mode.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

PROJECT: BSP BF-8 DOCUMENT NO REV

DESIGNED CHECKED
TITLE: Transformer Sizing Calculation

Motor Details
Rating 1500 KW
Voltage 6.6 KV
PF 0.85
Eff. 0.92
Permissible Voltage Drop at Motor Terminal* 20 %

Upstream Details
SC Capacity (11KV SWBD) 200 MVA

Parameter Basis / Formula Value

Base MVA (MVAB) 5


Base Voltage (KVB) 6.6
Base Current (IB) MVAB × 1000 / (√3×VB) 437.40

Source Impedance (Zs) MVAB / ISC 0.025


Trafo Impedance (ZTr) (%Z / 100) × (MVAB / Act MVA) 0.0715
Total Impedance (ZT ) (ZS + ZTr) 0.0965

Short Circuit Current = ISC (IB / ZT) 4532.64

Short Circuit Capacity of Trafo (KVAsc) (√3×VL×ISC) 51813.47

Motor Starting KVA (KVAst) (6×KWmotor)/(cosφ × η) 11508.95

Voltage Drop at Trafo Terminal during Starting (KVAST × 100)/(KVAST+KVASC) 18.18

NOTE:
1. *As Per cl No GS-03,Cl No 1.02.06, Sec-04, Point No 6,iV (Page 55of 205)
2. Hence the Selected Transformer capacity 5MVA is suitable to for 1500KW Motor running at DOL mode
DATE
13.05.2011
SHEET
A4

Selected Trafo Details


Rating 5 MVA
Voltage 11 KV
6.6 KV
Impedance 7.15 %

Unit Symbol

MVA
KV
A

P.U
P.U
P.U

KVA

KVA

at DOL mode