Floc Fault Locator: Issued: 6/2005 Version: A/08.07.2005
Floc Fault Locator: Issued: 6/2005 Version: A/08.07.2005
Fault locator
Issued: 6/2005
Version: A/08.07.2005
Contents
1. Introduction ................................................................................................ 3
1.1 Features................................................................................................ 3
1.2 Application ............................................................................................ 4
1.3 Input description ................................................................................... 5
1.4 Output description................................................................................. 5
2. Description of operation............................................................................ 6
2.1 Configuration ........................................................................................ 6
2.2 Rated frequency ................................................................................... 6
2.3 Measuring mode ................................................................................... 7
2.4 Operation criteria .................................................................................. 7
2.5 Fault type selection............................................................................... 8
2.6 Fault distance calculation ..................................................................... 9
2.7 Triggering the FLOC function.............................................................. 13
2.8 Result validity indicator for earth faults ............................................... 14
2.9 ALARM output..................................................................................... 15
2.10 Impedance settings............................................................................. 16
2.10.1 Modeling a non-homogeneous line ........................................... 18
2.10.2 Positive-sequence impedance values ....................................... 21
2.10.3 Zero-sequence impedance values ............................................ 22
2.11 Setting groups..................................................................................... 23
2.12 Registers............................................................................................. 23
2.13 Resetting............................................................................................. 23
4. Technical Data...........................................................................................35
2
Distribution Automation FLOC
1. Introduction
1.1 Features
• Impedance based fault locator function (ANSI: 21FL) for single terminal
systems (radial lines)
• Fault localization for short-circuits and earth faults
• Patented earth fault locator function suitable for effectively earthed and low
resistance/reactance earthed networks
• Validity indication of calculated fault distance for earth faults
• Fault distance calculation based on locally measured fundamental
frequency current and voltage phasors
• Load current compensation for earth faults and short circuit faults
• Line charging current compensation for earth faults
• Faulted phase identification by patented Phase Selection Logic (PSL)
• Distance to fault in form of impedance (primary ohms) and in kilometers or
miles
• Line type impedance variation modeling with three line sections with
independent impedance settings
• Two setting groups for changing network configurations or switching states
• External and internal triggering possibilities
• Possibility to set alarm limits for measured fault distance
3
FLOC Distribution Automation
1.2 Application
This document specifies the fault locator function used in products based on
the RED 500 Platform.
The fault locator function is designed for radially operated distribution systems.
It is applicable for locating short-circuits in all kinds of distribution networks.
Earth faults can be located in effectively earthed and low resistance/reactance
earthed networks.
For IEC symbols used in single line diagrams, refer to the manual “Technical
Descriptions of Functions, Introduction”, 1MRS750528-MUM.
4
Distribution Automation FLOC
5
FLOC Distribution Automation
2. Description of operation
2.1 Configuration
The FLOC function requires three phase currents and three phase-to-earth
voltages for operation. Phase currents can be measured with conventional
current transformers or Rogowski coils. Phase-to-earth voltages can be
measured with conventional voltage transformers or voltage dividers. The
measuring devices and the signal types for the analog channels are selected
and parameterized in a special dialog box of the graphic IEC configuration
tool. Binary inputs (the number of selectable analog inputs, binary inputs and
outputs depends on the hardware used) are parameterized in the same
programming environment.
When the analog channels and the binary inputs have been selected and
parameterized in the dialog box, the inputs and the outputs of the function
block can be configured in a graphic worksheet of the IEC configuration tool.
The phase currents IL1, IL2 and IL3 are connected to the corresponding IL1,
IL2 and IL3 inputs of the function block. The phase-to-earth voltages U1, U2
and U3 are connected to the corresponding UL1, UL2 and UL3 inputs of the
function block. The binary inputs are connected to the Boolean inputs of the
function block, and the outputs of the function block are connected to the
output signals in the same way.
The rated frequency of the relay or the feeder terminal is set via a dialog box
in the configuration tool. The global control parameter Rated frequency of the
relay can also be used for reading the rated frequency.
6
Distribution Automation FLOC
For phase-to-phase loops, the phase-to-phase (line) voltages and currents are
numerically derived from phase quantities within the function block using the
following equations:
I L12 = I L1 − I L 2 U L12 = U L1 − U L 2
I L 23 = I L 2 − I L 3 U L 23 = U L 2 − U L 3
I L 31 = I L 3 − I L1 U L 31 = U L 3 − U L1
The actual fault distance calculation consists of two steps. First the fault type
is determined using the inbuilt Phase Selection Logic (PSL), and then the fault
distance is calculated.
7
FLOC Distribution Automation
The identification of the faulty phase is compulsory for correct operation of the
fault locator function. This is because only one of the impedance measuring
elements (fault loops) provides the correct result for a specific fault type.
Three-phase fault is an exception and it could, in theory, be calculated with
any of the fault loops. The fault loops for each fault type are:
The fault loop used in the fault distance calculation is indicated in the outputs
as FLTLOOP.
8
Distribution Automation FLOC
RFLOOP = R1 + RN + Rfault
XFLOOP = X1 + XN
RF = Rfault
Figure 2. Fault loop impedance for phase-to-earth fault impedance loops (1, 2 or
3)
Fault loops 12, 23 and 31 are used for phase-to-phase short circuit faults as
well as in the case of a phase-to-phase-to-earth fault, if the individual earth
faults locate at the same feeder. Fault loops 12, 23 and 31 measure the
following impedances, which at the same time are the outputs of the FLOC
function (Figure 3):
RFLOOP = R1 + Rfault/2
XFLOOP = X1
RF = Rfault/2
9
FLOC Distribution Automation
Note that for fault loops 12, 23 and 31, the estimated fault resistance is half of
the total physical fault resistance between phases. This is illustrated in Figure
5.
Figure 3. Fault loop impedance for phase-to-phase fault impedance loops (12,
23 or 31)
Fault loop 123 is used exclusively for the three-phase short circuit fault and it
measures the following impedances, which at the same time are the outputs of
the FLOC function (Figure 4):
RFLOOP = R1 + Rfault
XFLOOP = X1
RF = Rfault
Figure 4. Fault loop impedance for a three-phase fault impedance loop (123)
10
Distribution Automation FLOC
11
FLOC Distribution Automation
Figure 5. Illustration of how a physical fault resistance is connected in different fault loops
Note that for fault loops 12, 23 and 31 the estimated fault resistance, RF, is
half of the total physical fault resistance between phases.
The FLOC function employs independent algorithms for each fault types in
order to achieve optimal performance.
For fault loops 1, 2 and 3, the fault distance algorithm compensates for
loading, in order to provide higher accuracy in case of faults with fault
resistance. The algorithm also compensates for the influence of line charging
capacitances. For correct operation there should not be any zero-sequence
current sources, e.g. earthing transformers, in front of the relay location.
For fault loops 12, 23 and 31, the fault distance algorithm compensates for
loading, in order to provide higher accuracy in case of faults with fault
resistance.
Fault loop 123 also compensates for loading in order to provide higher
accuracy in case of faults with fault resistance. The fault distance estimate is
calculated using positive sequence quantities, which reduces the influence of
line parameter asymmetry. This is advantageous especially in case of non-
transposed (asymmetric) lines.
For load compensation, the fault distance algorithm utilizes so-called delta (∆)
quantities, which describe the change in measured quantities due to the fault:
∆x = xfault - xpre-fault
The setting Delay time is used for generating the pre-fault quantities to be
used in load compensation. See Section 2.7 Triggering the FLOC function for
trigger mode details.
12
Distribution Automation FLOC
The fault distance estimate is obtained when the FLOC function is triggered.
The actual trigger time is saved in the registers. The trigger method is defined
with the control parameter Trigger mode, with the following settings:
Internal In case of internal triggering, the input TRIGG1 is not used for
triggering, but the trigger signal is created internally by the
Phase Selection Logic (PSL). The actual triggering moment
depends on the setting Delay time and it occurs (Delay time -
40 ms) after the PSL has recognized a fault condition.
Continuous The function outputs are continuously updated at the task time
interval. This trigger mode can be utilized during secondary
testing of the function block. The TRIGG output can be
monitored, in order to see when external or internal triggering
has occurred.
13
FLOC Distribution Automation
Fault localization is a challenging task. There are many factors, which may
deteriorate the accuracy of the calculated fault distance estimate. The most
important factors are:
• Fault resistance. The smaller the fault resistance, the more accurate
the result is likely to be. The accuracy of the fault distance estimation
deteriorates if the resistive part of the fault loop impedance becomes
much larger than the reactive part due to large fault resistance.
14
Distribution Automation FLOC
The validity of estimated earth fault distance is judged and reported together
with the fault distance estimate. The VALIDITY output can have the following
values (the number inside the parenthesis equals the number displayed in the
output data):
The FLOC function contains an alarm output for calculated fault distance. If
the calculated fault distance FLTDIST is between the settings Low limit and
High limit, the output ALARM is set to TRUE.
The ALARM output can be utilized e.g. in regions with waterways or other
places where knowledge of certain fault locations is of high importance.
15
FLOC Distribution Automation
The impedance settings (R1A, X1A, R0A, X0A, etc.) are given in units of
primary ohm/pu and line section lengths in pu. Per unit, pu, can be whichever
unit the user prefers, allowing the user to give impedances in ohm/km and
length in km (i.e. pu = km), or impedances in ohm/mile and length in mile (i.e.
pu = mile). The resulting fault distance is also obtained in pu and thus it
matches the units entered for the line section lengths.
The inherent result from the fault distance calculation is the ohmic fault loop
impedance value ZFLOOP = RFLOOP+ j*XFLOOP+ RF, which can be utilized
as such in upper level fault localization applications (e.g. MicroSCADA, DMS).
As the fault distance calculation is based on the fault impedance loops as
described in Section 2.6, it is important that the used fault loop closely models
the impedances, through which the actual fault current flows. This means that
the user should always apply impedance settings (R1A, X1A, R0A, X0A, etc.),
which closely match the protected line in order to enable accurate fault
localization.
If the user wants to convert the estimated fault loop reactance into a physical
length in the relay terminal, an accurate conversion requires that the line
impedance non-homogeneity is taken into account (see Section 2.10.1). If the
conversion is not done in relay terminal, then the setting Line sections should
be set to 0. This disables the FLTDIST output. The electrical fault distance is
still calculated (ohmic fault loop impedance value) and it can be utilized in
upper level applications (e.g. in MicroSCADA and DMS).
16
Distribution Automation FLOC
The settings RL0F and XC0F are used for improving fault distance estimation
accuracy for earth faults. They provide compensation for charging capacitance
and leakage resistance for the estimated fault loop impedance. The setting
RL0F represents the leakage losses (resistive losses due to insulators etc.) of
the protected feeder in terms of resistance. XC0F represents the phase-to-
earth capacitive reactance of the protected feeder.
The XC0F setting can be based on datasheet value and the RL0F setting
value can be based on approximation.
XC0F = 1/(ω*C0F),
ω = 2*π*fn
17
FLOC Distribution Automation
If Line sections= 1, the longitudinal impedance settings R1A, X1A, R0A, X0A
and the parameter LengthA are enabled for the
conversion of the electrical fault distance into a physical
distance. This option should be used only in the case of a
homogeneous line, i.e. when the protected feeder
consists of only one conductor type.
18
Distribution Automation FLOC
The total line impedance for the 10 km line is R1 = 6.602 ohm (0.6602
ohm/km) and X1 = 3.405 ohm (0.3405 ohm/km). Figure 9 illustrates the
conversion error as a function of physical fault location, if only one impedance
setting would be used:
19
FLOC Distribution Automation
The previous example assumed a short-circuit fault and therefore only positive
sequence impedance settings were used. The results, however, also apply for
earth faults.
20
Distribution Automation FLOC
a
X 1 ≈ f n ⋅ 2π ⋅ 10 − 4 ⋅ 2 ⋅ ln en + 0.5 [Ω / km ]
r
where
ln = natural logarithm
21
FLOC Distribution Automation
The positive sequence impedance values for the lines are typically known or
can easily be obtained from datasheets. The zero sequence values on the
other hand are not so easy to obtain as they depend on actual installation
conditions and configurations. Sufficient accuracy can however be obtained
with rather simple calculations using the following equations (applies per
phase for symmetrically transposed three-phase aluminum overhead lines
without ground wires):
R0 [50 Hz ] ≈ R1 + 0.14804 [Ω / km ]
R0 [60 Hz ] ≈ R1 + 0.17765 [Ω / km ]
W
X 0 ≈ f n ⋅ 4π ⋅ 10 − 4 ⋅ 3 ⋅ ln + 0.25 [Ω / km ]
ren
where
ρ earth
W = 658 ⋅ [m ] = equivalent depth of the earth return path [m]
fn
1
2 3
( )
1 3
ren = r ⋅ a122 ⋅ a 23
2
⋅ a31 = equivalent radius for conductor bundle [m]
22
Distribution Automation FLOC
Two different groups of setting values, Group 1 and Group 2, are available for
changing network configurations and switching states. Switching between the
two groups can be done in the following three ways:
3) By means of the GROUP input signal when allowed via the parameter
Group selection (V2 = 2). When GROUP is FALSE, Group 1 is active. When
GROUP is TRUE, Group 2 is active.
2.12 Registers
The recording function can be blocked via the BLOCK input. Registers can be
reset with the RESET input signal. See Section 2.13 Resetting for further
information.
2.13 Resetting
The outputs and the registers can be reset either via the RESET input, or over
the serial bus or the local HMI.
Operation Registers
indicators
RESET input of the function block * X
Parameter F058V008 * X
General parameter F001V011 X
General parameter F001V012 X
General parameter F001V013 X X
Push-button C X
Push-buttons C + E (2 s) X
Push-buttons C + E (5 s) X X
* Local reset: resets the FLOC function block
23
FLOC Distribution Automation
3.1 General
• The data direction of the parameters defines the use of each parameter as
follows:
• The different event mask parameters (see section “Control Settings”) affect
the visibility of events on the HMI or on the serial communication (LON or
SPA) as follows:
For example, if only the events E3, E4 and E5 are to be seen on the HMI of
the relay terminal, the event mask value 56 (8 + 16 + 32) is written to the
“Event mask 1” parameter (F058V101).
24
Distribution Automation FLOC
X1A S2 0.000…999.999 ohm/pu 1.000 R/M Positive sequence line reactance, line section A
R0A S3 0.000…999.999 ohm/pu 4.000 R/M Zero sequence line resistance, line section A
X0A S4 0.000…999.999 ohm/pu 4.000 R/M Zero sequence line reactance, line section A
R1B S6 0.000…999.999 ohm/pu 1.000 R/M Positive sequence line resistance, line section B
X1B S7 0.000…999.999 ohm/pu 1.000 R/M Positive sequence line reactance, line section B
R0B S8 0.000…999.999 ohm/pu 4.000 R/M Zero sequence line resistance, line section B
X0B S9 0.000…999.999 ohm/pu 4.000 R/M Zero sequence line reactance, line section B
R1C S11 0.000…999.999 ohm/pu 1.000 R/M Positive sequence line resistance, line section C
X1C S12 0.000…999.999 ohm/pu 1.000 R/M Positive sequence line reactance, line section C
R0C S13 0.000…999.999 ohm/pu 4.000 R/M Zero sequence line resistance, line section C
X0C S14 0.000…999.999 ohm/pu 4.000 R/M Zero sequence line reactance, line section C
RL0F S16 1.0...9999999.9 ohm 700000.0 R/M Leakage resistance of the protected feeder
XC0F S17 0.1...99999.9 ohm 7000.0 R/M Phase-to-earth capacitive reactance of the protected
feeder
1)
Adaptive XC0F S18 0…1 - 0 R/M Reserved for future use
Zmaxload S20 0.000…9999.999 ohm 400.000 R/M Impedance corresponding to maximum three-phase
loading
1)
Adaptive XC0F 0 = Disabled; 1 = Enabled
25
FLOC Distribution Automation
X1A S42 0.000…999.999 ohm/pu 1.000 R/W Positive sequence line reactance, line section A
R0A S43 0.000…999.999 ohm/pu 4.000 R/W Zero sequence line resistance, line section A
X0A S44 0.000…999.999 ohm/pu 4.000 R/W Zero sequence line reactance, line section A
R1B S46 0.000…999.999 ohm/pu 1.000 R/W Positive sequence line resistance, line section B
X1B S47 0.000…999.999 ohm/pu 1.000 R/W Positive sequence line reactance, line section B
R0B S48 0.000…999.999 ohm/pu 4.000 R/W Zero sequence line resistance, line section B
X0B S49 0.000…999.999 ohm/pu 4.000 R/W Zero sequence line reactance, line section B
R1C S51 0.000…999.999 ohm/pu 1.000 R/W Positive sequence line resistance, line section C
X1C S52 0.000…999.999 ohm/pu 1.000 R/W Positive sequence line reactance, line section C
R0C S53 0.000…999.999 ohm/pu 4.000 R/W Zero sequence line resistance, line section C
X0C S54 0.000…999.999 ohm/pu 4.000 R/W Zero sequence line reactance, line section C
RL0F S56 1.0...9999999.9 ohm 700000.0 R/W Leakage resistance of the protected feeder
XC0F S57 0.1...99999.9 ohm 7000.0 R/W Phase-to-earth capacitive reactance of the protected
feeder
1)
Adaptive XC0F S58 0…1 - 0 R/W Reserved for future use
Zmaxload S60 0.000…9999.999 ohm 400.000 R/W Impedance corresponding to maximum three-phase
loading
1)
Adaptive XC0F 0 = Disabled; 1 = Enabled
26
Distribution Automation FLOC
X1A S72 0.000…999.999 ohm/pu 1.000 R/W Positive sequence line reactance, line section A
R0A S73 0.000…999.999 ohm/pu 4.000 R/W Zero sequence line resistance, line section A
X0A S74 0.000…999.999 ohm/pu 4.000 R/W Zero sequence line reactance, line section A
R1B S76 0.000…999.999 ohm/pu 1.000 R/W Positive sequence line resistance, line section B
X1B S77 0.000…999.999 ohm/pu 1.000 R/W Positive sequence line reactance, line section B
R0B S78 0.000…999.999 ohm/pu 4.000 R/W Zero sequence line resistance, line section B
X0B S79 0.000…999.999 ohm/pu 4.000 R/W Zero sequence line reactance, line section B
R1C S81 0.000…999.999 ohm/pu 1.000 R/W Positive sequence line resistance, line section C
X1C S82 0.000…999.999 ohm/pu 1.000 R/W Positive sequence line reactance, line section C
R0C S83 0.000…999.999 ohm/pu 4.000 R/W Zero sequence line resistance, line section C
X0C S84 0.000…999.999 ohm/pu 4.000 R/W Zero sequence line reactance, line section C
RL0F S86 1.0...9999999.9 ohm 700000.0 R/W Leakage resistance of the protected feeder
XC0F S87 0.1...99999.9 ohm 7000.0 R/W Phase-to-earth capacitive reactance of the protected
feeder
1)
Adaptive XC0F S88 0…1 - 0 R/W Reserved for future use
Zmaxload S90 0.000…9999.999 ohm 400.000 R/W Impedance corresponding to maximum three-phase
loading
1)
Adaptive XC0F 0 = Disabled; 1 = Enabled
27
FLOC Distribution Automation
Delay time V4 0.10...300.00 s 1.00 R/W Parameter used for generating the pre-fault quantities to be
used in load compensation, see Section 0 for details
4)
Trigger mode V5 0…2 - 0 R/W Trigger mode, see Section 0 for details
High limit V6 0.001…999.999 pu 999.999 R/W High alarm limit for calculated distance, see Section 2.9 for
details
Low limit V7 0.001…999.999 pu 0.001 R/W Low alarm limit for calculated distance, see Section 2.9 for
details
5)
Reset registers V8 0…1 - 0 W Resetting of outputs and registers
Event mask 1 V101 0...255 - 42 R/W Event mask 1 for event transmission (E0 ... E7)
Event mask 2 V103 0...255 - 42 R/W Event mask 2 for event transmission (E0 ... E7)
Event mask 3 V105 0...255 - 42 R/W Event mask 3 for event transmission (E0 ... E7)
Event mask 4 V107 0...255 - 42 R/W Event mask 4 for event transmission (E0 ... E7)
1)
Operation mode 0 = Not in use; 1 = In use
2)
Group selection 0 = Group 1; 1 = Group 2; 2 = GROUP input
3)
Active group 0 = Group 1; 1 = Group 2
4)
Trigger mode 0 = External; 1 = Internal; 2 = Continuous
5)
Reset registers 0 = 0; 1 = Reset
28
Distribution Automation FLOC
Fault loop R O3 0.000...9999.999 ohm 0.000 R/M Fault loop resistance in primary
ohms
Fault loop X O4 0.000...9999.999 ohm 0.000 R/M Fault loop reactance in primary
ohms
29
FLOC Distribution Automation
3.3.3.1 General
All the information required for later fault analysis is recorded when the
recording function is triggered. As trigger mode can either be Internal, External
or Continuous, the triggering output TRIGG indicates the actual triggering
moment (time stamp). The data of last three operations (Operation 1...3) are
stored and the values of the most recent operation always replace the data of
the oldest operation. The registers are updated in the following order:
Operation 1, Operation 2, Operation 3, Operation 1, Operation 2…
The time stamp indicates the rising edge of the TRIGG signal.
The status data of the Active group parameter is recorded at the moment of
recording. The Active group parameter indicates the setting group valid for
the recorded data. Blocking will block recording as well as changes to output.
30
Distribution Automation FLOC
Fault resistance V204 0.000...9999.999 ohm 0.000 R/M Fault resistance in primary ohms
Fault loop R V205 0.000...9999.999 ohm 0.000 R/M Fault loop resistance in primary ohms
Fault loop X V206 0.000...9999.999 ohm 0.000 R/M Fault loop reactance in primary ohms
UL1 fault V211 0.00...999.99 kV 0.00 R/M Phase voltage UL1 during fault
UL2 fault V212 0.00...999.99 kV 0.00 R/M Phase voltage UL2 during fault
UL3 fault V213 0.00...999.99 kV 0.00 R/M Phase voltage UL3 during fault
IL1 fault V214 0.0...20000.0 A 0.0 R/M Phase current IL1 during fault
IL2 fault V215 0.0...20000.0 A 0.0 R/M Phase current IL2 during fault
IL3 fault V216 0.0...20000.0 A 0.0 R/M Phase current IL3 during fault
UL1 pre-fault V217 0.00...999.99 kV 0.00 R/M Pre-fault phase voltage UL1
UL2 pre-fault V218 0.00...999.99 kV 0.00 R/M Pre-fault phase voltage UL2
UL3 pre-fault V219 0.00...999.99 kV 0.00 R/M Pre-fault phase voltage UL3
IL1 pre-fault V220 0.0...20000.0 A 0.0 R/M Pre-fault phase current IL1
IL2 pre-fault V221 0.0...20000.0 A 0.0 R/M Pre-fault phase current IL2
IL3 pre-fault V222 0.0...20000.0 A 0.0 R/M Pre-fault phase current IL3
Angle UL1 fault V223 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL1 during fault
Angle UL2 fault V224 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL2 during fault
Angle UL3 fault V225 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL3 during fault
Angle IL1 fault V226 -180.0...180.0 ° 0.0 R/M Phase angle of current IL1 during fault
Angle IL2 fault V227 -180.0...180.0 ° 0.0 R/M Phase angle of current IL2 during fault
Angle IL3 fault V228 -180.0...180.0 ° 0.0 R/M Phase angle of current IL3 during fault
Angle UL1 preflt V229 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL1 pre-fault
Angle UL2 preflt V230 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL2 pre-fault
Angle UL3 preflt V231 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL3 pre-fault
Angle IL1 preflt V232 -180.0...180.0 ° 0.0 R/M Phase angle of current IL1 pre-fault
Angle IL2 preflt V233 -180.0...180.0 ° 0.0 R/M Phase angle of current IL2 pre-fault
Angle IL3 preflt V234 -180.0...180.0 ° 0.0 R/M Phase angle of current IL3 pre-fault
1)
VALIDITY 0 = N/A; 1 = High; 2 = Moderate; 3 = Poor
2)
Output ALARM 0 = Not active; 1 = Active
3)
Active group 0 = Group 1; 1 = Group 2
31
FLOC Distribution Automation
Fault resistance V304 0.000...9999.999 ohm 0.000 R/M Fault resistance in primary ohms
Fault loop R V305 0.000...9999.999 ohm 0.000 R/M Fault loop resistance in primary ohms
Fault loop X V306 0.000...9999.999 ohm 0.000 R/M Fault loop reactance in primary ohms
UL1 fault V311 0.00...999.99 kV 0.00 R/M Phase voltage UL1 during fault
UL2 fault V312 0.00...999.99 kV 0.00 R/M Phase voltage UL2 during fault
UL3 fault V313 0.00...999.99 kV 0.00 R/M Phase voltage UL3 during fault
IL1 fault V314 0.0...20000.0 A 0.0 R/M Phase current IL1 during fault
IL2 fault V315 0.0...20000.0 A 0.0 R/M Phase current IL2 during fault
IL3 fault V316 0.0...20000.0 A 0.0 R/M Phase current IL3 during fault
UL1 pre-fault V317 0.00...999.99 kV 0.00 R/M Pre-fault phase voltage UL1
UL2 pre-fault V318 0.00...999.99 kV 0.00 R/M Pre-fault phase voltage UL2
UL3 pre-fault V319 0.00...999.99 kV 0.00 R/M Pre-fault phase voltage UL3
IL1 pre-fault V320 0.0...20000.0 A 0.0 R/M Pre-fault phase current IL1
IL2 pre-fault V321 0.0...20000.0 A 0.0 R/M Pre-fault phase current IL2
IL3 pre-fault V322 0.0...20000.0 A 0.0 R/M Pre-fault phase current IL3
Angle UL1 fault V323 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL1 during fault
Angle UL2 fault V324 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL2 during fault
Angle UL3 fault V325 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL3 during fault
Angle IL1 fault V326 -180.0...180.0 ° 0.0 R/M Phase angle of current IL1 during fault
Angle IL2 fault V327 -180.0...180.0 ° 0.0 R/M Phase angle of current IL2 during fault
Angle IL3 fault V328 -180.0...180.0 ° 0.0 R/M Phase angle of current IL3 during fault
Angle UL1 preflt V329 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL1 pre-fault
Angle UL2 preflt V330 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL2 pre-fault
Angle UL3 preflt V331 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL3 pre-fault
Angle IL1 preflt V332 -180.0...180.0 ° 0.0 R/M Phase angle of current IL1 pre-fault
Angle IL2 preflt V333 -180.0...180.0 ° 0.0 R/M Phase angle of current IL2 pre-fault
Angle IL3 preflt V334 -180.0...180.0 ° 0.0 R/M Phase angle of current IL3 pre-fault
1)
VALIDITY 0 = N/A; 1 = High; 2 = Moderate; 3 = Poor
2)
Output ALARM 0 = Not active; 1 = Active
3)
Active group 0 = Group 1; 1 = Group 2
32
Distribution Automation FLOC
Fault resistance V404 0.000...9999.999 ohm 0.000 R/M Fault resistance in primary ohms
Fault loop R V405 0.000...9999.999 ohm 0.000 R/M Fault loop resistance in primary ohms
Fault loop X V406 0.000...9999.999 ohm 0.000 R/M Fault loop reactance in primary ohms
UL1 fault V411 0.00...999.99 kV 0.00 R/M Phase voltage UL1 during fault
UL2 fault V412 0.00...999.99 kV 0.00 R/M Phase voltage UL2 during fault
UL3 fault V413 0.00...999.99 kV 0.00 R/M Phase voltage UL3 during fault
IL1 fault V414 0.0...20000.0 A 0.0 R/M Phase current IL1 during fault
IL2 fault V415 0.0...20000.0 A 0.0 R/M Phase current IL2 during fault
IL3 fault V416 0.0...20000.0 A 0.0 R/M Phase current IL3 during fault
UL1 pre-fault V417 0.00...999.99 kV 0.00 R/M Pre-fault phase voltage UL1
UL2 pre-fault V418 0.00...999.99 kV 0.00 R/M Pre-fault phase voltage UL2
UL3 pre-fault V419 0.00...999.99 kV 0.00 R/M Pre-fault phase voltage UL3
IL1 pre-fault V420 0.0...20000.0 A 0.0 R/M Pre-fault phase current IL1
IL2 pre-fault V421 0.0...20000.0 A 0.0 R/M Pre-fault phase current IL2
IL3 pre-fault V422 0.0...20000.0 A 0.0 R/M Pre-fault phase current IL3
Angle UL1 fault V423 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL1 during fault
Angle UL2 fault V424 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL2 during fault
Angle UL3 fault V425 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL3 during fault
Angle IL1 fault V426 -180.0...180.0 ° 0.0 R/M Phase angle of current IL1 during fault
Angle IL2 fault V427 -180.0...180.0 ° 0.0 R/M Phase angle of current IL2 during fault
Angle IL3 fault V428 -180.0...180.0 ° 0.0 R/M Phase angle of current IL3 during fault
Angle UL1 preflt V429 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL1 pre-fault
Angle UL2 preflt V430 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL2 pre-fault
Angle UL3 preflt V431 -180.0...180.0 ° 0.0 R/M Phase angle of voltage UL3 pre-fault
Angle IL1 preflt V432 -180.0...180.0 ° 0.0 R/M Phase angle of current IL1 pre-fault
Angle IL2 preflt V433 -180.0...180.0 ° 0.0 R/M Phase angle of current IL2 pre-fault
Angle IL3 preflt V434 -180.0...180.0 ° 0.0 R/M Phase angle of current IL3 pre-fault
1)
VALIDITY 0 = N/A; 1 = High; 2 = Moderate; 3 = Poor
2)
Output ALARM 0 = Not active; 1 = Active
3)
Active group 0 = Group 1; 1 = Group 2
33
FLOC Distribution Automation
3.3.4 Events
1. Fault detected
3. Fault alarm
The fault alarm signal indicates that the calculated fault distance
FLTDIST is between the settings Low limit and High limit. In this
case an event is sent. Fault loop (fault type) information is sent with the
event (possible only with the LON protocol).
4. BLOCK signal
The BLOCK input signal blocks the triggering of the FLOC function. If
the BLOCK input becomes active, an event is sent.
34
Distribution Automation FLOC
4. Technical Data
Operation accuracies Fault location accuracy: ±2.5% of the line length.
Actual fault location accuracy depends on the fault and the power
system characteristics as described in Section 2.8 “Result validity
indicator for earth faults”.
35