Ⅱ、 PID FUNCTION.............................................................................................................................................2
VIII、 XC-E3AD4PT2DA.................................................................................................................................36
1、Basic Characteristic
XC series PLC have not only strong functions of logic dispose 、data operation、high speed disposing
etc. but also functions of A/D 、 D/A convert 、 PID adjustment ; With using expansions of analog input
module 、 analog output module 、 temperature control module etc, XC series PLC are widely used in the
control system of temperature、flow、liquid level、pressure.
2、Module’s Name
3、Exterior Size
4、General Specification
When carry on processing the screws or layout project, please protect the scraps falling into the modules
Before connecting, please confirm again module’s specification and connected device
When connecting, please check if the connection is fastness, cable breaking off will cause data incorrect,
short circuit and other fault! Installation, layout should only be carried after cutting all power.
Ⅱ、PID Function
2、Parameter’s usage
Usage of four parameters: Proportion parameter(Kp)、Integral parameter(Ki)、Differential
parameter(Kd)、Control proportion band(Diff)
Kp—parameter P is proportion parameter, mainly reflect system’s wrap. When wrap occurs, carry on control to
decrease this wrap.
Ki—parameter I is integral parameter, mainly used to eliminate whisht difference, improving system’s no
difference degree.
Kd-- parameter D is differential parameter, mainly used to control signal’s changing trend, decrease system’s
shake.
Diff—Control bound means in the assigned bound, carry on PID control, out the bound, do not carry on PID
control.
3、 Control characteristic
The bound of PID adjustment is, when the testing value is low than QD-Diff, controller output with the
full scale; when the testing value is larger than QD+Diff, the controller stop output; in the bound of(QD-
Diff,QD+Diff), carry on PID adjustment.
1.Specification
Specialty:
14 bits high precision analog input
8 channels analog input : The first
four channels current input
(0~20mA 、 4~20 mA two kinds) ;
The left 4 channels voltage input
(0~5V、0~10V two kinds)
As special function module of XC, 7
models could be connected at most.
With PID adjustment function
XC series analog module doesn’t engross I/O units, the converted data is directly transferred into PLC
register. Channels’ correspond PLC register ID is:
Input、output ID list
Register’s ID of expansion 1:
Channel AD signal PID output PID start/stop The set value PID Parameters: Kp,
value control bit Ki, Kd, control bound
Diff, dead bound
“Death”
0CH ID100 ID108 Y100 QD100 Kp:QD108
1CH ID101 ID109 Y101 QD101 Ki:QD109
2CH ID102 ID110 Y102 QD102
3CH ID103 ID111 Y103 QD103 Kd:QD110
4CH ID104 ID112 Y104 QD104 Diff:QD111
5CH ID105 ID113 Y105 QD105 Death:QD112
6CH ID106 ID114 Y106 QD106
7CH ID107 ID115 Y107 QD107
Register’s ID of expansion 2:
Channel AD signal PID output PID start/stop The set value PID parameters:Kp,
value control bit Ki, Kd, control bound
Diff, dead bound
“Death”
0CH ID200 ID208 Y200 QD200 Kp:QD208
1CH ID201 ID209 Y201 QD201 Ki:QD209
2CH ID202 ID210 Y202 QD202
3CH ID203 ID211 Y203 QD203 Kd:QD210
4CH ID204 ID212 Y204 QD204 Diff:QD211
5CH ID205 ID213 Y205 QD205 Death:QD212
6CH ID206 ID214 Y206 QD206
7CH ID207 ID215 Y207 QD207
Register’s ID of expansion 3:
Channel AD signal PID output PID start/stop The set value PID parameters:Kp,
value control bit Ki, Kd, control bound
Diff, dead bound
“Death”
0CH ID300 ID308 Y300 QD300 Kp:QD308
1CH ID301 ID309 Y301 QD301 Ki:QD309
2CH ID302 ID310 Y302 QD302
3CH ID303 ID311 Y303 QD303 Kd:QD310
4CH ID304 ID312 Y304 QD304 Diff:QD311
5CH ID305 ID313 Y305 QD305 Death:QD312
6CH ID306 ID314 Y306 QD306
7CH ID307 ID315 Y307 QD307
Register’s ID of expansion 4:
Channel AD signal PID output PID start/stop The set value PID parameters:Kp,
value control bit Ki, Kd, control bound
Diff, dead bound
“Death”
0CH ID400 ID408 Y400 QD400 Kp:QD408
1CH ID401 ID409 Y401 QD401 Ki:QD409
2CH ID402 ID410 Y402 QD402
3CH ID403 ID411 Y403 QD403 Kd:QD410
4CH ID404 ID412 Y404 QD404 Diff:QD411
5CH ID405 ID413 Y405 QD405 Death:QD412
6CH ID406 ID414 Y406 QD406
7CH ID407 ID415 Y407 QD407
Register’s ID of expansion 5:
Channel AD signal PID output PID start/stop The set value PID parameters:Kp,
value control bit Ki, Kd, control bound
Diff, dead bound
“Death”
0CH ID500 ID508 Y500 QD500 Kp:QD508
1CH ID501 ID509 Y501 QD501 Ki:QD509
2CH ID502 ID510 Y502 QD502
3CH ID503 ID511 Y503 QD503 Kd:QD510
4CH ID504 ID512 Y504 QD504 Diff:QD511
5CH ID505 ID513 Y505 QD505 Death:QD512
6CH ID506 ID514 Y506 QD506
7CH ID507 ID515 Y507 QD507
Register’s ID of expansion 6:
Channel AD signal PID output PID start/stop The set value PID parameters :
value control bit Kp、Ki、Kd、contr
ol bound Diff 、 dead
bound “Death”
0CH ID600 ID608 Y600 QD600 Kp:QD608
1CH ID601 ID609 Y601 QD601 Ki:QD609
2CH ID602 ID610 Y602 QD602
3CH ID603 ID611 Y603 QD603 Kd:QD510
4CH ID604 ID612 Y604 QD604 Diff:QD611
5CH ID605 ID613 Y605 QD605 Death:QD512
6CH ID606 ID614 Y606 QD606
7CH ID607 ID615 Y607 QD607
Register’s ID of expansion 7:
Channel AD signal PID output PID start/stop The set value PID parameters:Kp,
value control bit Ki, Kd, control bound
Diff, dead bound
“Death”
0CH ID700 ID708 Y700 QD700 Kp:QD708
1CH ID701 ID709 Y701 QD701 Ki:QD709
2CH ID702 ID710 Y702 QD702
3CH ID703 ID711 Y703 QD703 Kd:QD710
4CH ID704 ID712 Y704 QD704
5CH ID705 ID713 Y705 QD705 Diff:QD711
6CH ID706 ID714 Y706 QD706 Death:QD712
7CH ID707 ID715 Y707 QD707
Description:
Start signal(Y):when Y is 0, close PID control, when be 1 , start PID control
Parameter P:Proportion parameter, mainly reflex system’s difference, carry on control as soon as
difference occurs to improve the system’s no difference degree.
Parameter I:Integral parameter. Mainly used to remove whisht, improve the system’s no difference
degree.
Parameter D:Differential parameter, mainly used to control signal’s changing trend,minish system’s
shake.
Control bound Diff:In the assigned bound, carry on PID control. Beyond the bound, no PID control.
Dead area Death:When the current PID control value compares with the preceding PID control value. If
the difference between them is less than the set dead bound’s value, the module will
abnegate the current PID control value, send the preceding PID control value to the
PLC main unit.
Each parameter’s reference value:Kp=20~100;Ki=5~20;Kd=200~700;DIFF=100~200
1)Expansion’s 0CH~3CH channels have two modes to select: current 0~20mA 、4~20mA , 4CH~7CH
channels have two modes to select, voltage 0~5V 、 0~10V. Set via special FLASH data register FC inside
PLC. See the following table:
Note:As showed in the preceding table, each register set 4 channels’ mode, each register has 16 bits. From
low bit to high bit, every 4 bits separately set 4 channels’ mode.
Channel 3 Channel 2
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8
00: 1/2 filter - 0:0~20mA 00: 1/2 filter - 0:0~20mA
01: not filter 1:4~20mA 01: not filter 1:4~20mA
10: 1/3 filter 10: 1/3 filter
- -
11: 1/4 filter 11: 1/4 filter
Register FD8251:
Channel 5 Channel 4
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
00: 1/2 filter - 0:0~10V 00: 1/2 filter - 0:0~10V
01: not filter 1:0~5V 01: not filter 1:0~5V
10: 1/3 filter 10: 1/3 filter
- -
11: 1/4 filter 11: 1/4 filter
Channel 7 Channel 6
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8
00: 1/2 filter - 0:0~10V 00: 1/2 filter - 0:0~10V
01: not filter 1:0~5V 01: not filter 1:0~5V
10: 1/3 filter 10: 1/3 filter
- -
11: 1/4 filter 11: 1/4 filter
E.g. : 1 ) Set module 1’s No. 3 、 No.2 、 No.1 、 No.0 channel’s working mode separately as
0~20mA、4~20mA、0~20mA、4~20mA, filters are all 1/2 filter, data in FD8250 is 0101H
2 ) Set module 1’s No. 7 、 No.6 、 No.5 、 No.4 channel’s working mode separately as
0~10V、0~5V、0~10V、0~5V, all the four channels don’t filter, data in FD8251 is 4545H
4.Exterior connection
About exterior connection, you should note the following two items:
When connect+24V power outside, please use the 24V power on PLC main unit to avoid interfere.
To avoid interfere, please use the shield cable and single point grounding with the shield layer.
Layout chart:
5.Analog/digital convert chart
The relationship between input analog and converted digital quantity is showed in the following chart:
6.Programming
END
MOV ID108 D1000 Write channel 0’s PID value into register D1000
END
Ⅳ、Analog input/output module XC-E4AD2DA
1.Specification
Characteristic:
4 channels 14 bits analog input and 2
channels 12 bits analog output
4 channels selectable voltage
0~5V 、 0~10V , current
0~20mA 、 4~20mA input and 2
channels selectable voltage
0~5V 、 0~10V , current
0~20mA 、 4~20mA output. Set via
host machine.
As special function module of XC, 7
modules could be connected at most
4 channels A/D have PID adjustment
function
[Extend cable]: Realize data transfer via the connection of extend cable and PLC extend port
[Extend port]:Connect with other expansions
2.The assignment of input/output ID
XC series analog modules do not engross I/O units, the converted data is directly transferred into PLC
register, analog output is also directly offered by PLC register.
Register’s ID of expansion 1:
Channel AD signal PID output PID start/stop The set value PID parameter : Kp,
value control bit Ki, Kd, control bound
Diff, dead bound
Death
0CH ID100 ID104 Y100 QD102 Kp:QD106
1CH ID101 ID105 Y101 QD103 Ki:QD107
Kd:QD108
2CH ID102 ID106 Y102 QD104
Diff:QD109
3CH ID103 ID107 Y103 QD105 Death:QD110
Channel DA signal - - - -
4CH QD100 - - -
5CH QD101 - - -
Register’s ID of expansion 2:
Channel AD PID output PID start/stop The set value PID parameter : Kp,
value control bit Ki, Kd, control bound
Diff, dead bound
Death
0CH ID200 ID204 Y200 QD202 Kp:QD206
1CH ID201 ID205 Y201 QD203 Ki:QD207
Kd:QD208
2CH ID202 ID206 Y202 QD204
Diff:QD209
3CH ID203 ID207 Y203 QD205 Death:QD210
Channel DA signal - - - -
4CH QD200 - - -
5CH QD201 - - -
Register’s ID of expansion 3:
Channel AD signal PID output PID start/stop The set value PID parameter : Kp,
value control bit Ki, Kd, control bound
Diff, dead bound
Death
0CH ID300 ID304 Y300 QD302 Kp:QD306
1CH ID301 ID305 Y301 QD303 Ki:QD307
Kd:QD308
2CH ID302 ID306 Y302 QD304
Diff:QD309
3CH ID303 ID307 Y303 QD305 Death:QD310
Channel DA signal - - - -
4CH QD300 - - -
5CH QD301 - - -
Register’s ID of expansion 4:
Channel AD signal PID output PID start/stop The set value PID parameter : Kp,
value control bit Ki, Kd, control bound
Diff, dead bound
Death
0CH ID400 ID404 Y400 QD402 Kp:QD406
1CH ID401 ID405 Y401 QD403 Ki:QD407
Kd:QD408
2CH ID402 ID406 Y402 QD404
Diff:QD409
3CH ID403 ID407 Y403 QD405 Death:QD410
Channel DA signal - - - -
4CH QD400 - - -
5CH QD401 - - -
Register’s ID of expansion 5:
Channel AD signal PID output PID start/stop The set value PID parameter :
value control bit Kp、Ki、Kd、contr
ol bound Diff 、 dead
bound Death
0CH ID500 ID504 Y500 QD502 Kp:QD506
1CH ID501 ID505 Y501 QD503 Ki:QD507
Kd:QD508
2CH ID502 ID506 Y502 QD504
Diff:QD509
3CH ID503 ID507 Y503 QD505 Death:QD510
Channel DA signal - - - -
4CH QD500 - - -
5CH QD501 - - -
Register’s ID of expansion 6:
Channel AD signal PID output PID start/stop The set value PID parameter :
value control bit Kp、Ki、Kd、contr
ol bound Diff 、 dead
bound Death
0CH ID600 ID604 Y600 QD602 Kp:QD606
1CH ID601 ID605 Y601 QD603 Ki:QD607
Kd:QD608
2CH ID602 ID606 Y602 QD604
Diff:QD609
3CH ID603 ID607 Y603 QD605 Death:QD610
Channel DA signal - - - -
4CH QD600 - - -
5CH QD601 - - -
Register’s ID of expansion 7:
Channel AD signal PID output PID start/stop The set value PID parameter :
value control bit Kp、Ki、Kd、contr
ol bound Diff 、 dead
bound Death
0CH ID700 ID704 Y700 QD702 Kp:QD706
1CH ID701 ID705 Y701 QD703 Ki:QD707
Kd:QD708
2CH ID702 ID706 Y702 QD704
Diff:QD709
3CH ID703 ID707 Y703 QD705 Death:QD710
Channel DA signal - - - -
4CH QD700 - - -
5CH QD701 - - -
Description:
Start signal(Y):When Y is 0, close PID control; when being 1, start PID control
Parameter P:proportion parameter, mainly reflect system’s difference, control as soon as difference
occurs to decrease this difference.
Parameter I:Integral parameter, mainly used to remove the whisht and improve the system’s no
difference degree
Parameter D:differential parameter, mainly control signal’s changing trend and decrease the system’s
shake.
Temp. control bound Diff : in the assigned bound, carry on PID control, beyond that bound, no PID
control
Each parameter’s reference value:Kp=20~100;Ki=5~20;Kd=200~700;DIFF=100~200
1)Expansion’s input/output all have options of voltage 0~5V、0~10V, current 0~20mA、4~20mA modes.
Via setting of special FLASH data register FD in PLC. See the following table:
Module Channel’s ID
Take 1# expansion as example :
0CH~3CH 4CH~5CH
1# FD8250 FD8251 low byte FD8250 H O O O O
expansion 0CH
2# FD8258 FD8259 low byte 1CH
expansion 2CH
3# FD8266 FD8267 low byte 3CH
expansion FD8251 H O O O O
4# FD8274 FD8275 low byte 4CH
expansion 5CH
5# FD8282 FD8283 low byte
expansion
6# FD8290 FD8291 low byte
expansion
7# FD8298 FD8299 low byte
expansion
Note:As shown in the preceding table, every register set 4 channels mode, each register has 16 bits, from low
to high, every 4 bits set separately 4 channels mode.
Each channel’s working mode is assigned by correspond register’s 4 bits. Each bit’s definition is showed in the
following table:
Channel 1 Channel 0
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
00: 1/2 filter 0: voltage 0:0~10V 00: 1/2 filter 0: voltage 0:0~10V
01: not filter input 1:0~5V 01: not filter input 1:0~5V
10: 1/3 filter 10: 1/3 filter
1: current 0:0~20mA 1: current 0:0~20mA
11: 1/4 filter input
11: 1/4 filter input
1:4~20mA 1:4~20mA
Channel 3 Channel 2
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8
00: 1/2 filter 0: voltage 0:0~10V 00: 1/2 filter 0: voltage 0:0~10V
01: not filter input 1:0~5V 01: not filter input 1:0~5V
10: 1/3 filter 10: 1/3 filter
11: 1/4 filter 1: current 0:0~20mA 11: 1/4 filter 1: current 0:0~20mA
input 1:4~20mA input 1:4~20mA
Channel 5 Channel 4
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
00: 1/2 filter 0: voltage 0:0~10V 00: 1/2 filter 0: voltage 0:0~10V
01: not filter input 1:0~5V 01: not filter input 1:0~5V
10: 1/3 filter 10: 1/3 filter
1: current 0:0~20mA 1: current 0:0~20mA
11: 1/4 filter input
11: 1/4 filter input
1:4~20mA 1:4~20mA
E,g. : 1 ) If set working mode 0~20mA 、 4~20mA 、 0~10V 、 0~5V of module 1’s channel 3 、 channel
2、channel 1、channel 0, filters are all 1/2 filter, value in FD8250 is 2301H
4.Exterior connection
When carry on exterior connection, please note the following two items:
When connect+24V power outside, please choose 24V power on PLC main unit to avoid interfere.
To avoid interfere, please use shield cable and single point grounding with the shield layer.
Module’s 0~20mA or 4~20mA output need 24V power from outside, according to the analog output
register QD’s value, the module adjusts the loop circuit’s current, but the module itself doesn’t produce
current.
The relationship between output digital and its correspond analog data is showed in the following chart:
0~5V analog output 0~10V analog output
When input data exceed K4095, D/A converted output analog data keep 5V、10V or 20mA.
6.Programming
E.g.1)Real time read 4 channels data, write 2 channels data (take expansion 1 as example)
M8000
MOV ID100 D0 Write channel 0’s data into data register D0
MOV D10 QD100 Write data into data register D10 and give channel 4
MOV D11 QD101 Write data into data register D10 and give channel 5
END
MOV ID104 D1000 Write channel 0’s PID output value into register D1000
END
Characteristic:
12 bits high precision analog output
4 channels selectable voltage
0~5V 、 0~10V , current 0~20mA 、
4~20mA output
As special function module of XC, 7
modules could be connected
[Extend cable]:Realize data transfer via connecting of extend cable and PLC extend port
2.Assignment of Output ID
XC series analog module does not engross I/O units, the converted data is directly transferred into PLC
register. The output channel’s correspond PLC register ID is:
Output ID list
Channel No.1 unit No.2 unit No.3 unit No.4 unit No.5 unit No.6 unit No.7 unit
0CH QD100 QD200 QD300 QD400 QD500 QD600 QD700
1CH QD101 QD201 QD301 QD401 QD501 QD601 QD701
2CH QD102 QD202 QD302 QD402 QD502 QD602 QD702
3CH QD103 QD203 QD303 QD403 QD503 QD603 QD703
Each channel’s working mode is assigned by the correspond register’s 4 bits. Each bit’s definition is listed in
the following table:
Channel 1 Channel 0
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
- 0:Voltage 0:0~10V - 0: Voltage 0:0~10V
input 1:0~5V input 1:0~5V
1:current 0:0~20mA 1:Current 0:0~20mA
input 1:4~20mA input 1:4~20mA
Channel 3 Channel 2
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8
- 0: Voltage 0:0~10V - 0: Voltage 0:0~10V
input 1:0~5V input 1:0~5V
1: current 0:0~20mA 1: current 0:0~20mA
input 1:4~20mA input 1:4~20mA
4.Exterior connection
When carry on exterior connection, please note the following two items:
When connect+24V power outside, please choose 24V power on PLC main unit to avoid interfere.
To avoid interfere, please use shield cable and single point grounding with the shield layer.
Module’s 0~20mA or 4~20mA output need 24V power from outside, according to the analog output
register QD’s value, the module adjusts the loop circuit’s current, but the module itself doesn’t produce
current.
5.Analog digital convert chart
The relationship between PLC’s output digital and its correspond analog data is showed in the following
chart:
0~5V analog output 0~10V analog output
When the output data exceed K4095, D/A converted output analog data keep 5V、10V or 20mA
6.Programming
M8000
MOV D10 QD100
Write data into data register D10 and give channel 0
MOV D11 QD101
Write data into data register D11 and give channel 1
MOV D12 QD102
Write data into data register D12 and give channel 2
MOV D13 QD103
Write data into data register D13 and give channel 3
END
Ⅵ、Pt100 temperature PID control module XC-E6PT-P
1.Specification
Characteristic:
Item Content
Analog input signal Pt100 platinum thermo-resistance
Temperature testing -100℃~350℃
bound
Digital output bound -1000~3500,16 bits with sign bit, binary
Control precision ±0.5℃
Distinguish ratio 0.1℃
Integrate precision ±0.8%(relative to the max value)
Convert speed 100ms×6 channels
Analog using power DC24V±10%,50mA
Install format Fixed with M3 screws or directly installed on orbit of DIN46277 (Width: 35mm)
Exterior size 63mm×102mm×73.3mm
[Extend cable]:Realize data transfer via the connection of extend cable and PLC extend port.
Description:
Start signal(Y):When Y is 0, close PID control; when being 1, start PID control
Parameter P:proportion parameter, mainly reflect system’s difference, control as soon as difference
occurs to decrease this difference.
Parameter I:Integral parameter, mainly used to remove the whisht and improve the system’s no
difference degree
Parameter D:differential parameter, mainly control signal’s changing trend and decrease the system’s
shake.
Temp. control bound Diff : in the assigned bound, carry on PID control, beyond that bound, no PID
control
Each parameter’s reference value:Kp=20~100;Ki=5~20;Kd=200~700;DIFF=100~200
1)Every input of expansion has option of filter, set via special FLASH data register FD in PLC.
Seethe following chart:
Module channel’s ID
Take 1# module as example:
0CH~3CH 4CH~5CH
FD8250 H O O O O
1#module FD8250 FD8251low byte
0CH
2# module FD8258 FD8259 low byte
1CH
3# module FD8266 FD8267 low byte
2CH
4# module FD8274 FD8275 low byte
3CH
5# module FD8282 FD8283 low byte FD8251 H O O O O
6# module FD8290 FD8291 low byte 4CH
7# module FD8298 FD8299 low byte 5CH
Each channel’s filter mode is assigned via correspond register’s 4 bits! Each bit’s definition is showed in the
following table:
Register FD8250:
Channel 2 Channel 1
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
00:1/2 filter - - 00:1/2 filter - -
01:not filter 01:not filter
10:1/3 filter - - 10:1/3 filter - -
11:1/4 filter 11:1/4 filter
Channel 4 Channel 3
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8
00:1/2 filter - - 00:1/2 filter - -
01:not filter 01:not filter
10:1/3 filter - - 10:1/3 filter - -
11:1/4 filter 11:1/4 filter
Register FD8251:
Channel 5 Channel 4
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
00:1/4 filter - - 00:1/4 filter - -
01:不 filter 01:不 filter
10:1/2 filter - - 10:1/2 filter - -
11:1/3 filter 11:1/3 filter
When leave the factory, the defaulted value is 0, the initial filter format is 1/2 filter.
4.Exterior connection
About outside layout, you should note the following two items:
When carry on+24V power, please use 24V power on PLC main unit to avoid interfere.
To avoid interfere, please take shield measure with the signal cable.
Input connection:
COM0 COM1 COM2 Y3 Y5
Y0 Y1 Y2 Y4
0123
45
Y
PWR
AI
A0 A1 A2 A3 A4 A5
C0 C1 C2 C3 C4 C5
Output terminals
Transistor output terminals, please choose DC5V~30V flat power.
Circuit insulation
Between PLC’s interior circuit and output transistor, use optical insulation. Each public module is also
separate.
Response time
The time from PLC drive (or cut) optical coupling device to transistor ON/OFF, no more than 0.2ms.
Output current
Each point has electricity 0.8A, but to avoid temperature rising, please use as every 4 points 1.2A or
every 8 points 2.0A
Open circuit leak current
Below 0.1mA
FEND
Ⅶ、K type thermocouple temperature PID control module XC-E6TC-P
1.Specification
Characteristic:
Items Content
Analog input signal K type thermocouple
Temperature testing bound 0℃~1000℃
Digital output bound 0~10000,16 bits with sign bit, binary
Control precision ±0.5℃
Distinguish ratio 0.1℃
Integrate precision ±0.8% (compare with the max value)
Convert speed 100ms×6 channels
Power for analog using DC24V±10%,50mA
Install format Fixed with M3 screws or directly installed on orbit of DIN46277 (Width:
35mm)
Exterior size 63mm×102mm×73.3mm
[Extend cable]:Realize data transfer via the connection of extend cable and PLC extend port
Description:
Start signal(Y):When Y is 0, close PID control; when being 1, start PID control
Parameter P:proportion parameter, mainly reflect system’s difference, control as soon as difference
occurs to decrease this difference.
Parameter I:Integral parameter, mainly used to remove the whisht and improve the system’s no
difference degree
Parameter D:differential parameter, mainly control signal’s changing trend and decrease the system’s
shake.
Temp. control bound Diff : in the assigned bound, carry on PID control, beyond that bound, no PID
control
Each parameter’s reference value:Kp=20~100;Ki=5~20;Kd=200~700;DIFF=100~200
Every input of expansions has filter option, set via special FLASH data register FD inside PLC. See the
following chart:
Module Channel’s ID
Take 1# module as example :
0CH~3CH 4CH~5CH
1# module FD8250 FD8251 Low byte FD8250 H O O O O
2# module FD8258 FD8259 Low byte 0CH
3# module FD8266 FD8267 Low byte 1CH
4# module FD8274 FD8275 Low byte 2CH
5# module FD8282 FD8283 Low byte 3CH
FD8251 H O O O O
6# module FD8290 FD8291 Low byte 4CH
7# module FD8298 FD8299 Low byte 5CH
Each channel’s filter mode is assigned by correspond register’s 4 bits. Each bit’s definition is showed in the
following table:
Register FD8250:
Channel 1 Channel 0
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
00:1/4 filter - - 00:1/4 filter - -
01:not filter 01:not filter
10:1/2 filter - - 10:1/2 filter - -
11:1/3 filter 11:1/3 filter
Channel 3 Channel 2
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8
00:1/4 filter - - 00:1/4 filter - -
01:not filter 01:not filter
10:1/2 filter - - 10:1/2 filter - -
11:1/3 filter 11:1/3 filter
Register FD8251:
Channel 5 Channel 4
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
00:1/4 filter - - 00:1/4 filter - -
01:not filter 01:not filter
10:1/2 filter - - 10:1/2 filter - -
11:1/3 filter 11:1/3 filter
When leave the factory, their defaulted value is 0, i.e. the initial filter format is 1/4 filter
4.Exterior connection
About the exterior connection, you should pay attention to the following two items:
When connect with+24V power outside, please use the 24V power on PLC main unit to avoid interfere
To avoid interfere, shield measure is necessary for the signal cables
Input method:
COM0 COM1 COM2 Y3 Y5
Y0 Y1 Y2 Y4
0123
45
Y
PWR
AI
Output terminal
For transistor output terminals, flat please use power of DC5V~30V.
Circuit insulation
Between PLC interior circuit and output transistor, carry on optical insulation with optical coupling
device. Each public modules are separate.
Response time
The time form PLC drive (or cut) optical coupling circuit to transistor’s ON/OFF, no more than 0.2ms
Output circuit
Each point’s current 0.8A. But to restrict the increase of temperature,, please use in the condition of
every 4 points 1.2A or every 8 points 2.0A
Open circuit leak current
Below 0.1mA.
MOV K150 QD109 Set channel 0’s proportion band Diff as 150
(At 650, carry on PID operation)
M0
Y100 Start / stop channel 0
FEND
VIII、XC-E3AD4PT2DA
1.Specifications
Specilities:
3 channels 14 bits current input 、 4
channels PT100 temperature input and 2
channels 12 bits voltage output
3 channels current 0~20mA 、 4~20mA
input (selectable) and 2 channels voltage
0~5V、0~10V output (selectable), set via
the software
Pt resistor input (PT100)
3 channels A/D and 4 channels PT input,
with PID adjustment function
[Extend Cable]: Via the connection of the extend cable and PLC’s extend port, realize data transfer
Channel DA Signal - - - -
0CH QD100 - - -
1CH QD101 - - -
Channel DA Signal - - - -
0CH QD200 - - -
1CH QD201 - - -
Channel DA Signal - - - -
0CH QD300 - - -
1CH QD301 - - -
Channel DA Signal - - - -
0CH QD400 - - -
1CH QD401 - - -
Channel DA Signal - - - -
0CH QD500 - - -
1CH QD501 - - -
Channel DA Signal - - - -
0CH QD600 - - -
1CH QD601 - - -
Channel DA Signal - - - -
0CH QD700 - - -
1CH QD701 - - -
Description:
Start signal (Y): when Y is 0, close PID control, when be 1 , start PID control
Parameter P:Proportion parameter, mainly reflex system’s difference, carry on control as soon
as difference occurs to improve the system’s no difference degree.
Parameter I:Integral parameter. Mainly used to remove whisht, improve the system’s no
difference degree.
Parameter D:Differential parameter, mainly used to control signal’s changing trend,minish
system’s shake.
Control bound Diff : In the assigned bound, carry on PID control. Beyond the bound, no PID
control.
Dead area Death:When the current PID control value compares with the preceding PID control
value. If the difference between them is less than the set dead bound’s value,
the module will abnegate the current PID control value, send the preceding
PID control value to the PLC main unit.
Each parameter’s reference value:Kp=20~100;Ki=5~20;Kd=200~700;DIFF=100~200
- Output CH 1(PT)
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
- - - - - 0 :0~10V
1 :0~5V
4.External Connection
0V
AI2+
AI1+
AI1-AI0+
VO0+
VO1+
AI2-
24V+
VO0-
AI0-
VO1-
AI0 AI1 AI2 VO0 VO1
C0 C1 C2 C3 C4
A
PWR
B0 A1 C1 B2 A3 C3
A0 C0 B1 A2 C2 B3 PT100
PT100
PT100
PT100
The relationship of the output digital quantity and its correspond analog quantity is shown below:
0~5V analog output 0~10V analog output
When the output value is larger than K4095, D/A converted analog value will remain 5V、10V.
6.Program
E.g. 1)Real time read data from 7 channels, write data to 2 channels (take module 1 as the example)
M8000 Write AD value in CH0 to data register D0
MOV ID100 D0
MOV ID102 D2
Write AD value in CH2 to data register D2
MOV ID103 D3
Write temperature value in CH3 to data register D3
END
MOV D4000 QD102 Write the set AD value from CH0 into register D4000
MOV ID107 D1000 Write CH 0’s PID value into register D1000
END
Analog Input Module XC-E4AD
1.Specification
Specification:
4CH 14 bits analog input
4CH voltage (0~5V 、 0~10V),
current (0~20mA、4~20mA) input
selectable, set via the software.
As expansion of XC series PLC,
the PLC CPU unit can connect 7
modules
4CH A/D has PID adjustment
function
[Expansion Cable]: Realize data transfer via the connection of expansion cable and PLC expansion port.
[Expansion Port]: Connect with other expansion module
2.Assignment of Input/Output ID
XC series expansions do not occupy the I/O units, the converted value is delivered to PLC register directly.
Analog output is also offered by PLC register.
Register ID of expansion 1:
Channel AD Signal PID Output PID Start/Stop The Set Value PID Parameters: Kp,
Value Control Bit Ki, Kd, Control Range
Diff, Dead Range
“Death”
0CH ID100 ID104 Y100 QD102 Kp------- QD106
Ki------- QD107
1CH ID101 ID105 Y101 QD103 QD108
Kd-------
2CH ID102 ID106 Y102 QD104 QD109
Diff------
QD110
3CH ID103 ID107 Y103 QD105 Death----
Register ID of expansion 2:
Channel AD Signal PID Output PID Start/Stop The Set Value PID Parameters: Kp,
Value Control Bit Ki, Kd, Control Range
Diff, Dead Range
“Death”
0CH ID200 ID204 Y200 QD202 Kp------- QD206
Ki------- QD207
1CH ID201 ID205 Y201 QD203 QD208
Kd-------
2CH ID202 ID206 Y202 QD204 QD209
Diff------
QD210
3CH ID203 ID207 Y203 QD205 Death----
Register ID of expansion 3:
Channel AD Signal PID Output PID Start/Stop The Set Value PID Parameters: Kp,
Value Control Bit Ki, Kd, Control Range
Diff, Dead Range
“Death”
0CH ID300 ID304 Y300 QD302 Kp------- QD306
Ki------- QD307
1CH ID301 ID305 Y301 QD303 QD308
Kd-------
2CH ID302 ID306 Y302 QD304 QD309
Diff------
QD310
3CH ID303 ID307 Y303 QD305 Death----
Register ID of expansion 4:
Channel AD Signal PID Output PID Start/Stop The Set Value PID Parameters: Kp,
Value Control Bit Ki, Kd, Control Range
Diff, Dead Range
“Death”
0CH ID400 ID404 Y400 QD402 Kp------- QD406
Ki------- QD407
1CH ID401 ID405 Y401 QD403 QD408
Kd-------
2CH ID402 ID406 Y402 QD404 QD409
Diff------
QD410
3CH ID403 ID407 Y403 QD405 Death----
Register ID of expansion 5:
Channel AD Signal PID Output PID Start/Stop The Set Value PID Parameters: Kp,
Value Control Bit Ki, Kd, Control Range
Diff, Dead Range
“Death”
0CH ID500 ID504 Y500 QD502 Kp------- QD506
Ki------- QD507
1CH ID501 ID505 Y501 QD503 QD508
Kd-------
2CH ID502 ID506 Y502 QD504 QD509
Diff------
QD510
3CH ID503 ID507 Y503 QD505 Death----
Register ID of expansion 6:
Channel AD Signal PID Output PID Start/Stop The Set Value PID Parameters: Kp,
Value Control Bit Ki, Kd, Control Range
Diff, Dead Range
“Death”
0CH ID600 ID604 Y600 QD602 Kp------- QD606
Ki------- QD607
1CH ID601 ID605 Y601 QD603 QD608
Kd-------
2CH ID602 ID606 Y602 QD604 QD609
Diff------
QD610
3CH ID603 ID607 Y603 QD605 Death----
Register ID of expansion 7:
Channel AD Signal PID Output PID Start/Stop The Set Value PID Parameters: Kp,
Value Control Bit Ki, Kd, Control Range
Diff, Dead Range
“Death”
0CH ID700 ID704 Y700 QD702 Kp------- QD706
Ki------- QD707
1CH ID701 ID705 Y701 QD703 QD708
Kd-------
2CH ID702 ID706 Y702 QD704 QD709
Diff------
QD710
3CH ID703 ID707 Y703 QD705 Death----
Description:
Start signal (Y): when Y is 0, close PID control, when be 1 , start PID control
Parameter P: Proportion parameter, mainly reflex system’s difference, carry on control as soon as
difference occurs to improve the system’s no difference degree.
Parameter I:Integral parameter. Mainly used to remove whisht, improve the system’s no difference
degree.
Parameter D:Differential parameter, mainly used to control signal’s changing trend,minish system’s
shake.
Control bound Diff:In the assigned bound, carry on PID control. Beyond the bound, no PID control.
Dead area Death:When the current PID control value compares with the preceding PID control value. If
the difference between them is less than the set dead bound’s value, the module will
abnegate the current PID control value, send the preceding PID control value to the
PLC main unit.
Each parameter’s reference value: Kp=20~100; Ki=5~20; Kd=200~700; DIFF=100~200
3.Setting of working mode
1 ) Expansion’s input mode can be voltage 0~5V 、 0~10V or current 0~20mA 、 4~20mA , Set via
special FLASH data register FD inside PLC. See the following table:
Module Channel’s ID
0CH~3CH
1# expansion FD8250 Take 1# expansion as example :
2# expansion FD8258 FD8250 H O O O O
3# expansion FD8266 0CH
4# expansion FD8274 1CH
5# expansion FD8282 2CH
6# expansion FD8290 3CH
7# expansion FD8298
Note:As shown in the preceding table, every register set 4 channels mode, each register has 16 bits, from low
to high, every 4 bits set separately 4 channels mode.
Each channel’s working mode is assigned by correspond register’s 4 bits. Each bit’s definition is showed in the
following table:
Channel 1 Channel 0
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
00: 1/2 filter 0: voltage 0:0~10V 00: 1/2 filter 0: voltage 0:0~10V
01: not filter input 1:0~5V 01: not filter input 1:0~5V
10: 1/3 filter 10: 1/3 filter
1: current 0:0~20mA 1: current 0:0~20mA
11: 1/4 filter input
11: 1/4 filter input
1:4~20mA 1:4~20mA
Channel 3 Channel 2
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8
00: 1/2 filter 0: voltage 0:0~10V 00: 1/2 filter 0: voltage 0:0~10V
01: not filter input 1:0~5V 01: not filter input 1:0~5V
10: 1/3 filter 10: 1/3 filter
11: 1/4 filter 1: current 0:0~20mA 11: 1/4 filter 1: current 0:0~20mA
input 1:4~20mA input 1:4~20mA
E.g. : 1) If set working mode 0~20mA 、 4~20mA 、 0~10V 、 0~5V of module 1’s channel 3 、 channel
2、channel 1、channel 0, filters are all 1/2 filter, value in FD8250 is 2301H
4.Exterior connection
When carry on external connection, please note the following two items:
When connect+24V power outside, please choose 24V power on PLC main unit to avoid interfere.
To avoid interfere, please use shield cable and single point grounding with the shield layer.
E.g.1 Real time read the 4 channels data, write 2 channels data (take expansion 1 as example)
M8000
MOV ID100 D0
MOV ID101 D1 0 D0
MOV ID102 D2 1 D1
MOV ID103 D3
输入第
Write 2 通道的数据写入数据寄存器
data from CH3 into data register D3 D2
MOV ID104 D1000 Write channel 0’s PID output value into register D1000
END
VIII、XC-E3AD4PT2DA
VIII 、XC-E3AD4PT2DA
1.Specifications
Specilities:
3 channels 14 bits current input 、 4
channels PT100 temperature input and 2
channels 12 bits voltage output
3 channels current 0~20mA 、 4~20mA
input (selectable) and 2 channels voltage
0~5V、0~10V output (selectable), set via
the software
Pt resistor input (PT100)
3 channels A/D and 4 channels PT input,
with PID adjustment function
[Extend Cable]: Via the connection of the extend cable and PLC’s extend port, realize data transfer
Channel DA Signal - - - -
0CH QD100 - - -
1CH QD101 - - -
Channel DA Signal - - - -
0CH QD200 - - -
1CH QD201 - - -
Channel DA Signal - - - -
0CH QD300 - - -
1CH QD301 - - -
Channel DA Signal - - - -
0CH QD400 - - -
1CH QD401 - - -
Channel DA Signal - - - -
0CH QD500 - - -
1CH QD501 - - -
Channel DA Signal - - - -
0CH QD600 - - -
1CH QD601 - - -
Channel DA Signal - - - -
0CH QD700 - - -
1CH QD701 - - -
Description:
Start signal (Y): when Y is 0, close PID control, when be 1 , start PID control
Parameter P:Proportion parameter, mainly reflex system’s difference, carry on control as soon
as difference occurs to improve the system’s no difference degree.
Parameter I:Integral parameter. Mainly used to remove whisht, improve the system’s no
difference degree.
Parameter D:Differential parameter, mainly used to control signal’s changing trend,minish
system’s shake.
Control bound Diff : In the assigned bound, carry on PID control. Beyond the bound, no PID
control.
Dead area Death:When the current PID control value compares with the preceding PID control
value. If the difference between them is less than the set dead bound’s value,
the module will abnegate the current PID control value, send the preceding
PID control value to the PLC main unit.
Each parameter’s reference value:Kp=20~100;Ki=5~20;Kd=200~700;DIFF=100~200
- Output CH 1(PT)
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
- - - - - 0 :0~10V
1 :0~5V
4.External Connection
0V
AI2+
AI1+
AI1-AI0+
VO0+
VO1+
AI2-
24V+
VO0-
AI0-
VO1-
AI0 AI1 AI2 VO0 VO1
C0 C1 C2 C3 C4
A
PWR
B0 A1 C1 B2 A3 C3
A0 C0 B1 A2 C2 B3 PT100
PT100
PT100
PT100
5.Analog/Digital convert Diagram
The relationship of the input analog quantity and the converted digital quantity is shown below:
0~20mA analog input 4~20mA analog input
The relationship of the output digital quantity and its correspond analog quantity is shown below:
0~5V analog output 0~10V analog output
When the output value is larger than K4095, D/A converted analog value will remain 5V、10V.
E.g. 1)Real time read data from 7 channels, write data to 2 channels (take module 1 as the example)
M8000 Write AD value in CH0 to data register D0
MOV ID100 D0
MOV ID102 D2
Write AD value in CH2 to data register D2
MOV ID103 D3
Write temperature value in CH3 to data register D3
END
E.g.2) Application of PID (Take CH0 of module 1 as the example)
M8000
MOV ID100 D10 Write AD value from CH0 into data register D10
MOV D4000 QD102 Write the set AD value from CH0 into register D4000
MOV ID107 D1000 Write CH 0’s PID value into register D1000
END
\
IX、XC-E2DA
IX 、XC-E2DA
1. Specifications
Characteristic:
● 12 bits high precision analog
input.
● 2 channels selectable voltage
0 to 5V, 0 to 10 V, currents
are 0 to 20mA, 4 to 20 mA
output (selectable)
● As special function module
of XC series, 7 modules
could be connected at most
When the output value is larger than K4095, D?A converted analog value will remain 5V, 10V or 20mA.
6. Program
eg.1) Real time write data to 2 channels
Write register D10’s value into specification channel 0
Tel: (510)85134136
Fax: (510)85111290