Chilled Water System Sequence of Operation
Chilled Water System Sequence of Operation
Comparison of primary and secondary chilled water flow rate shall be the preferred method of deciding
Sequence of Operation:
A. The comparison of primary and secondary chilled water flow rate shall be the preferred method
1. Start an additional chiller when the secondary loop flow exceeds 95% of the primary loop flow
Another possible control sequence can be to calculate the building tonnage using the measured
secondary loop flow rate and supply and return water temperature of secondary loop, according
2. Backup method: (To be used when above method fails to generate start command)
This method shall start an additional chiller whenever reverse flow is sensed by the bi-
directional flow meter in the decouple pipe. (Reverse flow means when chilled water flows from
If the backup method is invoked, the DDC shall alarm and print a statement notifying the user
that a lag chiller was started using a backup method and the cause needs to be investigated.
Anytime the lag chiller is started, the system shall printout the following parameters
difference.
d. The total chiller capacity on line before the lag chiller was started.
1. The primary loop flow minus the design flow of the most recently started chiller exceeds the
2. Backup method: This method stop the most recently started chiller when the temperature
drop across the primary loop the building load can be carried without this chiller i.e. the
delta-T is less than 5 F. If the backup method is invoked, the DDC shall alarm and print a
statement notifying the user that the lag chiller was dropped off line using the backup
C. The DDC system shall be programmed to stage chillers of different capacities and accommodate
user assignment of the order in which the multiple chillers are to be staged. The system shall
also be programmed to permit the user to designate any chiller as being “out of service “without
effecting system’s ability to stage the remaining chillers automatically based on secondary loop
load.
D. The automatic chiller staging process does not attempt to start any chiller the user has
designated “Out of service” but shall start the next chiller in the user defined lead/lag sequence
of operation.
E. The DDC system shall start the next chiller in the user defined sequence in the event a required
chiller fails.
load.
2. The secondary chilled water pumps are energized through action of H-O-A switch
located on the VFD cover when in hand position and by DDC when in auto position. In
In auto position, pump speed is controlled by DDC to maintain set differential pressure
as sensed differential pressure is located at the top of the riser. The two pumps shall be
alternated and staged on depending on the demand when the load is sensed through
the VFD interface on the two pumps drop below 40% per pump, one pumps will be de-
energized with one pump running if the load on one pump exceeds 95 % of the full load