CHAPTER 5 - Protection
CHAPTER 5 - Protection
Power system protection is a branch of electrical power engineering that deals with
the protection of electrical power systems from faults through the isolation of faulted
parts from the rest of the electrical network. The objective of a protection scheme is to
keep the power system stable by isolating only the components that are under fault,
whilst leaving as much of the network as possible still in operation. Thus, protection
schemes must apply a very pragmatic and pessimistic approach to clearing system faults.
For this reason, the technology and philosophies utilized in protection schemes can often
be old and well-established because they must be very reliable.
• Current and voltage transformers to step down the high voltages and currents of
the electrical power system to convenient levels for the relays to deal with;
• Relays to sense the fault and initiate a trip, or disconnection, order;
• Circuit breakers to open/close the system based on relay and auto recloser
commands;
• Batteries to provide power in case of power disconnection in the system.
• Communication channels to allow analysis of current and voltage at remote
terminals of a line and to allow remote tripping of equipment.
1
Figure 1: Overccurrent protection schematic
For parts
p of a diistribution syystem, fusess are capable of both seensing and disconnectin
d ng
faultss.
Failures may
m occur in each parrt, such as insulation failure,
f falleen or brokeen
transm
mission lines, incorrect operation off circuit breaakers, short circuits
c and open circuits.
Proteection devicces are installed with the aims of
o protectionn of assets,, and ensurre
continnued supply
y of energy.
a) Instru
ument Tran
nsformers - Current traansformer & voltage traansformer arre
instrument transfoormer.
• A curren
nt transform
mer (CT) iss used for measuremennt of electriic
currents. When
W current in a circcuit is too high
h to directly apply to
t
measuringg instrumentts, a currennt transform
mer producees a reduceed
current accurately prooportional to the current in the circuuit, which caan
be convenniently conneected to meaasuring and recording innstruments. A
current traansformer also isolates the
t measurinng instrumennts from whaat
may be veery high volttage in the primary
p circcuit. Currentt transformerrs
are commonly used inn metering and
a protectivve relays in the electricaal
power induustry.
• Voltage transformers (VTs)
( or pottential transfformers (PTss) are anotheer
type of innstrument traansformer, used
u for meetering and protection in
i
high-voltaage circuits. They are deesigned to present
p negliigible load to
t
2
the supply being measured and to have a precise voltage ratio to
accurately step down high voltages so that metering and protective
relay equipment can be operated at a lower potential.
b) Relays - A relay is an electrical switch that opens and closes under the control
of another electrical circuit. In the original form, the switch is operated by an
electromagnet to open or close one or many sets of contacts. A protective
relay is a complex electromechanical apparatus, often with more than one coil,
designed to calculate operating conditions on an electrical circuit and trip
circuit breakers when a fault was found. Unlike switching type relays with
fixed and usually ill-defined operating voltage thresholds and operating times,
protective relays had well-established, selectable, time/current (or other
operating parameter) curves.
Such relays were very elaborate, using arrays of induction disks, shaded-pole
magnets, operating and restraint coils, solenoid-type operators, telephone-
relay style contacts, and phase-shifting networks to allow the relay to respond
to such conditions as over-current, over-voltage, reverse power flow, over-
and under- frequency, and even distance relays that would trip for faults up to
a certain distance away from a substation but not beyond that point. An
important transmission line or generator unit would have had cubicles
dedicated to protection, with a score of individual electromechanical devices.
The various protective functions available on a given relay are denoted by
standard ANSI Device Numbers. For example, a relay including function 51
would be a timed overcurrent protective relay.
3
Design and theory of these protective devices is an important part of the
education of an electrical engineer who specializes in power systems. Today
these devices are nearly entirely replaced (in new designs) with
microprocessor-based instruments (numerical relays) that emulate their
electromechanical ancestors with great precision and convenience in
application. By combining several functions in one case, numerical relays also
save capital cost and maintenance cost over electromechanical relays.
However, due to their very long life span, tens of thousands of these "silent
sentinels" are still protecting transmission lines and electrical apparatus all
over the world.
4
large currents or high voltages are usually arranged with pilot devices to sense
a fault current and to operate the trip opening mechanism. The trip solenoid
that releases the latch is usually energized by a separate battery, although
some high-voltage circuit breakers are self-contained with current
transformers, protection relays, and an internal control power source.
Once a fault is detected, contacts within the circuit breaker must open to
interrupt the circuit; some mechanically-stored energy (using something such
as springs or compressed air) contained within the breaker is used to separate
the contacts, although some of the energy required may be obtained from the
fault current itself. Small circuit breakers may be manually operated; larger
units have solenoids to trip the mechanism, and electric motors to restore
energy to the springs.
The circuit breaker contacts must carry the load current without excessive
heating, and must also withstand the heat of the arc produced when
interrupting the circuit. Contacts are made of copper or copper alloys, silver
alloys, and other materials. Service life of the contacts is limited by the
erosion due to interrupting the arc. Miniature circuit breakers are usually
discarded when the contacts are worn, but power circuit breakers and high-
voltage circuit breakers have replaceable contacts.
5
• Connecting capacitors in parallel with contacts in DC circuits
Finally, once the fault condition has been cleared, the contacts must again be
closed to restore power to the interrupted circuit.
The term transducer is commonly used in two senses; the sensor, used to detect a
parameter in one form and report it in another (usually an electrical or digital
signal), and an actuator may be described as opposite to a sensor-it converts
electrical signal into generally non-electrical energy. An example of a transducer
is a loudspeaker which converts an electrical signal into a variable magnetic field
and, subsequently, into acoustic waves.
b) Relay
6
on most lines having pilot relaying for primary protection. However, distance
relaying for ground-fault primary and back-up protection of transmission lines is
slowly replacing overcurrent relaying. Overcurrent relaying is used extensively
also at power-transformer locations for external-fault back-up protection, but
here, also, there is a trend toward replacing overcurrent with distance relays.
It is generally the practice to use a set of two or three overcurrent relays for
protection against inter-phase faults and a separate overcurrent relay for single-
phase-to-ground faults. Separate ground relays are generally favored because they
can be adjusted to provide faster and more sensitive protection for single-phase-
to-ground faults than the phase relays can provide. However, the phase relays
alone are sometimes relied on for protection against all types of faults. On the
other hand, the phase relays must sometimes be made to be inoperative on the
zero-phase-sequence component of ground-fault current. Overcurrent relaying is
well suited to distribution-system protection for several reasons. Not only is
overcurrent relaying basically simple and inexpensive but also these advantages
are realized in the greatest degree in many distribution circuits. Very often, the
relays do not need to be directional, and then no a-c voltage source is required.
Also, two phase relays and one ground relay are permissible. And finally, tripping
reactor or capacitor tripping may be used.
7
ii) Directional Relay - Directional overcurrent relays consist of a typical
overcurrent unit and a directional unit combined to operate together for a
predetermined phase-angle and magnitude of current. The current in one coil is
compared in phase-angle position with a voltage or current in another coil of that
unit. The reference current or voltage is called the polarization. The relay operates
only for current flow in one direction and will be insensitive to current flow in the
opposite direction.
8
Figure 3 shows the zones are overlapped to avoid the possibility of unprotected areas.
Without overlap the small area between two neighboring zones would not be located in
any zone and thus would not be protected.
ii) Speed - The function of automatic protection is to isolate faults from the power
system in a very much shorter time than could be achieved manually, even with a
great deal of personal supervision. The object is to safeguard continuity of supply by
removing each disturbance before it leads to widespread loss of synchronism, which
would necessitate the shutting down of plant.
9
fault. It will be noted that phase faults have a more marked effect on the stability of
the system than does a simple earth fault and therefore require faster clearance.
It will be seen that protective gear must operate as quickly as possible; speed,
however, must be weighed against economy. For this reason, distribution circuits for
which the requirements for fast operation are not very severe are usually protected by
time-graded systems, but generating plant and EHV systems require protective gear of
the highest attainable speed; the only limiting factor will be the necessity for correct
operation.
10
to an individual relay, it does not refer to a current or voltage setting but to the volt-
ampere consumption at the minimum operating current. A given type of relay
element can usually be wound for a wide range of setting currents; the coil will have
an impedance which is inversely proportional to the square of the setting current
value, so that the volt-ampere product at any setting is constant. This is the true
measure of the input requirements of the relay, and so also of the sensitivity. Relay
power factor has some significance in the matter of transient performance.
For D.C. relays the VA input also represents power consumption, and the burden
is therefore frequently quoted in watts.
The reliability of a power system has been discussed in earlier sections. Many factors
may cause protection failure and there is always some possibility of a circuit breaker
failure. For this reason, it is usual to supplement primary protection with other
systems to 'back-up' the operation of the main system and ensure that nothing can
prevent the clearance of a fault from the system. Back-up protection may be obtained
automatically as an inherent feature of the main protection scheme or separately by
means of additional equipment.
Time graded schemes such as over current or distance protection schemes are
examples of those providing inherent back-up protection. The faulty section is
normally isolated discriminatively by the time grading, but if the appropriate relay
fails or the circuit breaker fails to trip, the next relay in the grading sequence will
complete its operation and trip the associated circuit breaker, thereby interrupting the
fault circuit one section further back. In this way complete back-up cover is obtained.
One more section is isolated than is desirable but this is inevitable in the event of the
failure of a circuit breaker. Where the system interconnection is more complex, the
above operation will be repeated so that all parallel in feeds are tripped.
11
the main protective relays have failed, and will trip further back in the event of
circuit breaker failure.
Such back-up protection is inherently slower than the main protection and,
depending on the power system configuration, may be less discriminative. For the
most important circuits the performance may not be good enough, even as a back-up
protection, or, in some cases, not even possible, owing to the effect of multiple in
feeds. In these cases duplicate high speed protective systems may be installed. These
provide excellent mutual back-up cover against failure of the protective equipment,
but either no remote back-up protection against circuit breaker failure or, at best,
time delayed cover. Breaker fail protection can be obtained by checking that fault
current ceases within a brief time interval from the operation of the main protection.
If this does not occur, all other connections to the bus bar section are interrupted, the
condition being necessarily treated as a bus bar fault. This provides the required
back-up protection with the minimum of time delay, and confines the tripping
operation to the one station, as compared with the alternative of tripping the remote
ends of all the relevant circuits.
The extent and type of back-up protection which is applied will naturally be
related to the failure risks and relative economic importance of the system. For
distribution systems where fault clearance. Times are not critical, time delayed
remote back-up protection is adequate but for EHV systems, where system stability is
at risk unless a fault is cleared quickly, local back-up, as described above, should be
chosen.
Ideal back-up protection would be completely independent of the main
protection. Current trans-formers, voltage transformers, auxiliary tripping relays, trip
coils and D.C. supplies would be duplicated. This ideal is rarely attained in practice.
The following compromises are typical:
a. Separate current transformers (cores and secondary windings only) are
used for each protective system, as this involves little extra cost or
accommodation compared with the use of common current transformers
which would have to be larger because of the combined burden.
12
b. Common voltage transformers are used because duplication would involve
a considerable increase in cost, because of the voltage transformers them-
selves, and also because of the increased accommodation which would
have to be provided. Since security of the VT output is vital, it is desirable
that the supply to each protection should be separately fused and also
continuously supervised by a relay which will give an alarm on failure of
the supply and, where appropriate, prevent an unwanted operation of the
protection.
c. Trip supplies to the two protections should be separately fused.
Duplication of tripping batteries and of tripping coils on circuit breakers is
sometimes provided. Trip circuits should be continuously supervised.
d. It is desirable that the main and back-up protections (or duplicate main
protections) should operate on different principles, so that unusual events
that may cause failure of the one will be less likely to affect the other.
13
Example:
Draw the protective zones for the power system shown in figure 5. Which circuit
breaker should open for a fault at:
a) P1
b) P2
14
a) for a fault at P1, located in zone5, breakers B24 and B42 should open
b) for a fault at P2, located in the overlap region of zones 4 and 5, breakers B24, B42,
B21 and B23 should open.
Tutorial 1:
Tutorial 2:
15
Figure 8: Three types of power system connection
Figure 8 shows the three typical bus arrangements. Although the number of lines
connected to each arrangement varies widely in practice, four lines are shown for
convenience and comparison. Note that the required number of circuit breakers per line is
1 for the ring bus, 1 for the breakera dn half double bus and 2 for the double breaker
16
6.4 EXAMPLE OF PROTECTION APPLICATION
Figure 5: Photos by Abdul Kazia, which show lightning strikes hitting the Burj Dubai
on 29 April 2009
(the world's tallest building)
The greatest threat to a secure supply is the shunt fault or short circuit, which
imposes a sudden and sometimes violent change on system operation. The large
current which then flows, accompanied by the localized release of a considerable
quantity of energy, can cause fire at the fault location, and mechanical damage
17
throughout the system, particularly to machine and transformer windings. Rapid
isolation of the fault by the nearest switch-gear will minimize the damage and
disruption caused to the system. A power system represents a very large capital
investment. To maximize the return on this outlay, the system must be loaded as
much as possible. For this reason it is necessary not only to provide a supply of
energy which is attractive to prospective users by operating the system
Revenue for the supply authority. Absolute freedom from failure of the plant
and system network cannot be guaranteed. The risk of a fault occurring, however
slight for each item, is multiplied by the number of such items which are closely
associated in an extensive system, as any fault produces repercussions throughout the
net-work. When the system is large, the chance of a fault occurring and the
disturbance that a fault would bring are both so great that without equipment to
remove faults the system will become, in practical terms, inoperable.
The object of the system will be defeated if adequate provision for fault
clearance is not made. Nor is the installation of switchgear alone sufficient;
discriminative protective gear, designed according to the characteristics and
requirements of the power system, must be provided to control the switchgear.
18
19