S400 Servo Drive Quick Start Guide en
S400 Servo Drive Quick Start Guide en
Quickstart Guide
Version 12.2014
2
Minimum Wiring for Drive Operation
ENC
1
2
3
Enable
24V ON
PC
1 +
2
RES -
4 24V DC
5
Motor-Power
safety or
functionality of
your application,
Feedback
Feedback
3
Connect
l Connect the interface cable to a serial interface on your PC and to the serial in-
terface X6 of the servo amplifier. USB to serial converter can be used optionally.
l Switch on the 24 V logic power supply for the servo amplifier.
l Wait about 30 seconds, until the front display of the servo amplifier displays the
current rating (e.g. for 3 amps). If the mains power supply voltage is
switched on, too, a leading P is displayed (e.g. for Power, 3 amps).
If a fault code ( ) or a warning ( ) or a status message ("." or "_"
or "E" or "S") appears in the display, you will find the description and hints for
trouble shooting in the instructions manual. If there is fault, fix the problem.
Double-Click the Drive.exe icon on your Windows desktop to start the
software.
4
The software tries to com-
municate with the drive
and to upload the param-
eters. If it's not success-
ful, you receive this error
message:
- wrong interface chosen
- wrong connector chosen at the servo amplifier
Frequent causes: - interface is used by another software
- 24 V auxiliary voltage for the servo amplifier not working
- interface cable broken or wrong wiring
Click OK to remove the error message. Detect and remove the error source. Restart
the software.
If communication works, the drive selection screen appears:
Now parameters are transmitted from the servoamplifier to the computer. Then you
see the start screen.
Make sure, that the amplifier is disabled (Input HW-Enable connector X1 pin 3
must be 0 V or open)!
5
Important Screen Elements
Help Function
The Online-Help gives detailed information to all parameters the servo amplifier can
work with.
Tool Bar
Save to EEPROM,
required if you changed parameters.
Reset (coldstart),
required if you changed important configuration parameters.
Status Bar
6
Basic Setup
On the start screen click "Basic Setup" button.
Regen Resistor: Change only if you use an external regen resistor. Most applica-
tions don't need an external regen resistor
Max. Mains Voltage: Select the nominal mains AC voltage
Mains Phase Missing: You can select either warning "n05" or error "F19" in case of
phase loss. The setting "F19" disables the output stage, "n05" is just a message.
Units: Acceleration, Velocity, Position
Select usable units for your application referring to the moved load.
Address: Adjust for master amplifier only (= highest address of the drive system, see
instructions manual: "Setup/Multi-Axis Systems")
Leave all other fields unchanged. Click OK.
7
Motor (synchronous)
On the start screen click "Motor" button.
Motor Type: Select Synchronous Motor. If you use a linear motor or an induction
motor, please contact our support department.
Number-Name: Click the list to start uploading the motor parameter table, which is
stored in the servo amplifier. Search and select the connected motor. If your motor is
not listed, please contact our support department.
Leave all other fields unchanged.
Click OK.
8
If your motor has a built-in brake, click
"Yes", otherwise "No".
9
Feedback
On the start screen, click "Feedback" button.
Feedback Type:
Select the feedback type used.
Leave all other fields unchanged.
10
Save Parameters and Restart
You are going to finish setup and you have changed several basic parameters.
Depending on the parameters you changed, two possible reactions can occur:
Configuration parameters changed
A warning appears, that you have to restart the amplifier. This is called "coldstart".
Click "YES". The parameters are saved to the amplifier's EEPROM automatically
and a reset command restarts the amplifier (takes a few seconds). For example, this
happens after motor or feedback selection.
Other parameters changed
No warning appears. Parameters are saved in the volatile RAM only.
Save the parameters to the EEPROM of the servo amplifier manually by clicking the
symbol in the tool bar. A coldstart of the amplifier is not necessary.
11
Jogging the Motor (Speed Control)
Be aware that the actual position of the load permits the subsequent moving
operations. The axis could move to the hardware limit-switch or the mechanical
stop. Make sure that a jerk or a fast acceleration of the load cannot cause any
damage.
l Switch on the power supply for the drive.
l Hardware-Enable: +24 VDC to Enable [connector X1 pin 3].
12
l Select Service-Mode "Speed F6", then click "Parameter" button
The opmode is switched to "0" and the output stage is enabled automatically.
The symbol's color changes to green as long as the function is active.
l The function is active until you click the "Stop" button or press F9.
l The output stage can be disabled by pressing function key F12.
13
Status
Actual warnings and errors are listed on the Status screen, which can be accessed
on the start screen by clicking the "Status" button. This button monitors the current
status of the amplifier and can appear with different text.
The Reset button can be used to clear some actual error messages. A description of
errors/warnings can be found in the online help.
Now you have setup and tested the basic functions of the drive successfully.
14
Monitor
Documents
You need access to these documents (located on the product CD-ROM, you can
download the latest editions from our website):
l Instructions Manual (Assembly, Installation, Setup)
l CANopen communication profile
Depending on the installed fieldbus interface, you need one of these documents:
l PROFIBUS DP communication profile
l SERCOS communication profile
l EtherCAT communication profile
You need Acrobat Reader to read the PDFs, an installation link is on every screen of
the product CD-ROM.
15
Technical changes which improve the performance of the equipment may be
made without prior notice!