EAMII0001 Axial Flow Valves 9710 7 032713A
EAMII0001 Axial Flow Valves 9710 7 032713A
EAMII0001 Axial Flow Valves 9710 7 032713A
Pilot regulator
Inlet pressure 100 bar
Applications
The use of pilot regulators adds precision and flexibility to pressure regulation. This pi- • Spring loaded
lot regulator is used to pressure balance a main valve diaphragm for positive posi-
• Modular design
tioning of the main line valve with respect to flow. It will provide fast, accurate and sta-
ble pressure regulation. It is also used for spring loaded regulators where the outlet • Provide fast, accurate, stable pressure
pressure exceeds the practical limits of spring loading. All forged parts of this pilot are control
brass for maximum strength. The unit is approved as part of the AFV by DVGW accord-
• Operating temperature -20 °C to +60 °C
ing to the Pressure Equipment Directive 97/23/EC (PED) in conjunction with EN 334.
Registration number: CE-0085BN0509. Types
• Type Z and Z 138 load limit regulator
Type ZSC pilot regulator: Type ZSC has double diaphragms which decouples control pres-
used to maintain the inlet pressure
sure and pilot outlet pressure giving accurate control. It is designed for applications where
for a control pilot
a secondary control pressure is used to operate the main valve.
• Type ZSC 100 and ZSC 320-100
Type ZSC 150 back pressure and relief service: The ZSC 150 is a normally closed pilot used for secondary pressure control
opening on increasing pressure applied to it external sense connection or can be used as
a differential device, when the upper chamber is connected to a second pressure. • Type ZSC 150 and ZSC 320-150
used for back pressure and relief
Type Z pilot regulator: Type Z pilot has a single diaphragm and controls its own output service
pressure. It is used for maintaining the inlet pressure for a control pilot. This reduces the
inlet pressure dependency of the control system and is especially recommended for instal-
lations where large pressure reductions are required, and where there is a considerable
variation in the inlet pressure.
Ordering example:
Type
Size of orifice
Inlet pressure
Outlet pressure or spring range/number
Pressure ratings
Maximum allowable operating pressure MOP 100 bar
Maximum outlet pressure 22.4/41.4 bar
– see spring range (ZSC 100/ZSC 320-100)
Z/ZSC: Pilot regulator, inlet pressure 100 bar
Materials
Body Brass EN 12164
Sense chamber Brass EN 12164
D Valve seat Buna N
Diaphragm Buna N
O rings Buna N
H2
H1
Load limit regulator Z, pilot regulator ZSC 100 and relief pilot ZSC 150
73030222
70 – 350 mbar Green 71411 P010
0.14 – 0.7 bar Brown/blue 71411 P043
0.2 – 2.1 bar Yellow 71411 P011
0.7 – 5.2 bar Red 71411 P012
1.7 – 10.4 bar Blue 71411 P014
6,9 – 15.5 bar White 71411 P009
13.8 – 22.4 bar White/red 71411 P046
All rights reserved
max. inlet pressure 100 bar
Spare Parts
Load limit regulator Z 138, Spare Part Set Order No.
pilot regulator ZSC 320-100 and relief pilot ZSC 320-150
Spare set Z / ZSC 73914 K010
Your contacts
Germany United Kingdom Belgium Singapore
Elster GmbH Elster Metering Ltd. Elster NV/SA Elster-Instromet Sdn. Bhd. (Singapore Branch)
Steinern Str. 19 - 21 Elster Instromet Rijkmakerlaan 9 160 Paya Lebar Road
55252 Mainz-Kastel 4 Pate Road 2910 Essen #04-01 Orion@Paya Lebar
T +49 6134 605 0 Melton Mowbray T +32 3 670 0700 Singapore 409022
F +49 6134 605 223 Leicestershire, LE13 0RG F +32 3 667 6940 T +65 6247 7728
www.elster-instromet.com T +44 1 664 567 797 www.elster-instromet.com F +65 6247 7729
[email protected] F 44 1 664 410 254 [email protected] [email protected]
www.elster-instromet.com
Z ZSC EN02 [email protected]
A30.09.2011