HT9610P0100 Room Unit of Communicating Fan Coil Thermostat Honeywell

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

HT9610P0100

Room Unit of Communicating Fan Coil Thermostat


2-pipe/4-pipe fan coil control
PRODUCT DATA

• Stylish and elegant blue backlight


• 2-pipe/4-pipe integrated into one unit with easy
configuration
• Big LCD display with English and icons
• Manual or automatic fan speed selection
• Onboard or Remote temperature sensor option
• Cycle per Hour (CPH) function
• Adjustment of display room temperature
• Temperature unit either °C or °F
• User setting can be kept when power off
• Lock or unlock keys or part of keys in Installer Set-
up
• Heat and cool setpoint limitation for energy saving

APPLICATION TECHNICAL SPECIFICATIONS


HT961 communicating thermostats are designed for Power Communicating lines
application of 3-speed fan and valves in fan coil Control algorithm PI, On/off output
system and available in BACnet MS/TP protocol. Accuracy ± 1 °C @ 21 °C
HT961 Series thermostats can be easily integrated Setpoint range 10 ~ 32 °C
into a building automation system based on the Display range 0 ~ 37 °C
BACnet MS/TP platform. Installation Panel mounting or
Installed on 86×86 mm
HT961 communicating thermostat adopts two-piece or US 2×4 inch. junction box
solution consisting of two devices: driver and room unit. Protection class IP 20
Room unit provides user interface and control Operation temperature 0 ~ 49 °C (32 to 120°F)
algorithm for thermostats. This document contains Shipping temperature -29 ~ 55 °C (-20 to 130°F)
specification of room unit. For driver, please refer to Relative humidity 5 ~ 90 %
the data sheet of “HT961xD Series Driver of Action Type Action type 1
Communicating Fan Coil Thermostat”. Pollution Degree 2
Rated impulse Voltage 2500V
FEATURES Maximum Temperature
for Relay Wire 155°C
• Two-wire connection for both power and
Wire Diameter
communication
(Recommendation) 1-1.5mm
• Slim design, direct installation on 86 size box

1
Working current for the whole prod 4(3)A Fan Output
4A: When the load of the thermostat is resistance 4A: When the load is is resistance
3A: When the load of the thermostat is Inductance 2A: When the load is inductance

MODEL SUMMARY
Power Manual/Automatic
Model UI Type Backlight Application Ventilation
Supply Fan
FCU on/off Communication
HT9610P0100 Horizontal Blue Y Y
2/4-pipe Bus

Fan Operation
APPEARANCE Fan can be selected as
manual or automatic 3-
speed operation. In
Manual mode, the fan is
switched to the selected
speed via control
outputs of the driver.
While in automatic
mode, fan speed
depends on the difference between room temperature
and setpoint, valve will be closed and meanwhile, fan
will be closed either.
LCD DISPLAY
Fan speed is high or off
Difference between RT and SP

COOL
4F
Fan speed is medium or off
2F
Fan speed is low or off
Setpoint
Fan speed is low or off
-2F
Fan speed is medium or off
-4F

HEAT
Fan speed is high or off

Fan speed ramping control algorithm

FUNCTION Temperature Display


Valve Control The displayed temperature can be set to acquired
room temperature or setpoint. The setting can be
Room unit acquires the
made during Installer Set-Up process.
room temperature via
its integrated sensor or Room temperature and setpoint can be display
external temperature simultaneously.
sensor and maintains
the setpoint by Cycle per Hour (CPH)
delivering on/off valve
control commands In order to get a more accurate temperature control,
output. CPH function may enable the thermostat to open the
valve for several times per hour even the temperature
is close to setpoint (difference less than ½ P-band).
The default value is 4 for heating and 3 for cooling and
can be changed in Installer Set-Up process.

2
Backlight
Ventilation Mode
Any key press will activate the backlight. Backlights
will timeout 8 seconds after last key press. When in Press mode button to enter ventilation mode. In
Installer Set-up and Installer test mode, the backlight ventilation mode, no output for valve while the fan will
will timeout 60 seconds after last key press. operate according to selected fan speed.

Onboard and Remote Temperature Sensor On/Off Mode


HT9610P0100 room unit provides control either Pressing power
depending on the acquired room temperature or the button can switch
return air temperature. It can be selected in Installer between on and off
Set-Up process. The model of remote temperature mode.
sensor is NTC20K.

Keypad Lock

Keypad lock can be set in ISU with default status is all


keys available. You may change into mode button DIMENSIONS (mm)
locked out, fan and mode buttons locked out, all
buttons locked out and all buttons locked out but
power button by changing the ISU.

OPERATING MODELS
The following operating modes are available:

Comfort Mode

In comfort mode, the setpoint can be changed by


pressing up and down button. Different applications
include cool only, heat only and manual heat/cool
changeover.