Ocr: Relay1: Phase INST Ground INST
Ocr: Relay1: Phase INST Ground INST
OCR: Relay1
MFR: ABB Tag #: CT Base kV If (kA)
Model: 50B Phase: 2000/5
GND: 2000/5
OC Level: OC1
Range Setting
Phase INST Pickup 0.8 - 8 Sec - 5A 5.000
Ground INST Pickup 0.2 - 2 Sec - 5A 2.000
OCR: Relay2
MFR: ABB Tag #: CT Base kV If (kA)
Model: REF 615 Phase: 75/1
GND: 75/1
OC Level: OC1
Range Setting
Phase TOC IEC Very Inverse
Pickup (Tap) 0.05 - 5 xCT Sec 1.060
Time Dial 0.250
Ground TOC IEC Very Inverse
Pickup (Tap) 0.01 - 5 xCT Sec 0.100
Time Dial 0.050
OCR: Relay3
MFR: ALSTOM Tag #: CT Base kV If (kA)
Model: P127 Phase: 75/1
GND: 75/1
OC Level: OC1
Range Setting
Phase TOC IEC - Very Inverse
Pickup (Tap) 0.1 - 25 xCT Sec 1.200
Time Dial 0.300
Ground TOC IEC - Very Inverse
Pickup (Tap) 0.002 - 1 xCT Sec 0.200
Time Dial 0.025