Calculation For Fire Size - Smoke Spill System Location Production A3 & A4 Production C3 & C4
Calculation For Fire Size - Smoke Spill System Location Production A3 & A4 Production C3 & C4
Calculation For Fire Size - Smoke Spill System Location Production A3 & A4 Production C3 & C4
Assume smoke temperature < 250oC 250 250 250 250 deg C 250 250 250 250 250 250 deg C
(under sprinklered actions)
523 523 523 523 deg K 523 523 523 523 523 523 deg K
Smoke volume, V 19.25 19.25 19.25 19.25 m3/s 25.31 25.31 25.31 25.31 25.31 25.31 m3/s
Overall air change (sprinklered) 5.7 ACH 5.8 ACH
Assume smoke temperature < 250oC 250 250 250 250 deg C 250 250 250 250 250 250 deg C
(unsprinklered)
523 523 523 523 deg K 523 523 523 523 523 523 deg K
Allowable Smoke temperature rise 217 217 217 217 deg C 217 217 217 217 217 217 deg C
Allowable Smoke temperature rise with 325.5 325.5 325.5 325.5 deg C 325.5 325.5 325.5 325.5 325.5 325.5 deg C
building structure absorb up to one third
of the energy of the fire
Required smoke layer height 4.32 4.32 4.32 4.32 m 4.32 4.32 4.32 4.32 4.32 4.32 m
Resultant Mass of smoke, MR 30.72 30.72 30.72 30.72 kg/s 30.72 30.72 30.72 30.72 30.72 30.72 kg/s
Smoke volume, V 43.76 43.76 43.76 43.76 m3/s 43.76 43.76 43.76 43.76 43.76 43.76 m3/s
Overall air change (sprinklered) 12.9 ACH 12.4 ACH
Equations :