Gplv2 Manual en 2
Gplv2 Manual en 2
1
Table of Contents
1. Introduction
2. Installation
3. Main Features
4. Home
5. Alarms
6. Configuration
7. History
8. Service
9. Download Manuals
10. Language
GPLV2-Manual-EN v2.1.0.0
Table of Contents
Introduction...................................................................................................................................................................... 5
Types of Limited Service Fire Pump Controllers ....................................................................................................... 5
Methods of Starting/Stopping ..................................................................................................................................... 5
Installation ....................................................................................................................................................................... 7
FCC Regulations and Radio Standards Specification (RSS) Rules .......................................................................... 7
Location ...................................................................................................................................................................... 7
Mounting .................................................................................................................................................................... 8
Storage ....................................................................................................................................................................... 8
Wiring and Connections ............................................................................................................................................. 8
Water Connections ..................................................................................................................................................... 8
Electrical Wiring ......................................................................................................................................................... 8
Electrical Connections................................................................................................................................................ 8
Energy Consumption.................................................................................................................................................. 8
Sizing.......................................................................................................................................................................... 8
Incoming Power Connections .................................................................................................................................... 8
Motor Connections ..................................................................................................................................................... 9
Terminal Strip Descriptions ......................................................................................................................................10
Quick Start-Up Guide ...............................................................................................................................................11
Main Features ...............................................................................................................................................................16
The ViZiTouch ..........................................................................................................................................................16
First Setup ................................................................................................................................................................16
ViZiTouch: Manual Rebooting Method .....................................................................................................................16
Home .............................................................................................................................................................................17
Home (Menu) ...........................................................................................................................................................17
Screen Saver ...........................................................................................................................................................19
Alarms ...........................................................................................................................................................................20
Alarms (Menu) ..........................................................................................................................................................20
Configuration .................................................................................................................................................................23
Config (Menu) ..........................................................................................................................................................23
NumPad Page ..........................................................................................................................................................24
Date and Time Page ................................................................................................................................................24
User Login Page / KeyPad Page .............................................................................................................................25
Advanced Configuration Page .................................................................................................................................26
Update Program Page .............................................................................................................................................26
Sensor Selection ......................................................................................................................................................27
Alarms ......................................................................................................................................................................29
Control Timers ..........................................................................................................................................................31
Inputs........................................................................................................................................................................31
Outputs .....................................................................................................................................................................32
Factory Settings .......................................................................................................................................................33
3
I/O Card Info .............................................................................................................................................................34
Network ....................................................................................................................................................................34
Interlock Lockout ......................................................................................................................................................35
Reboot ViZiTouch ....................................................................................................................................................35
History ...........................................................................................................................................................................36
History (Menu) ..........................................................................................................................................................36
Events Page .............................................................................................................................................................37
Pressure Curves ......................................................................................................................................................37
Power Curves ...........................................................................................................................................................38
Saved Logs ..............................................................................................................................................................39
Pump Curves ...........................................................................................................................................................40
Statistic .....................................................................................................................................................................41
All Time Statistics .....................................................................................................................................................41
First Service Statistics ..............................................................................................................................................42
Last Service Statistics ..............................................................................................................................................43
Download .................................................................................................................................................................43
Service ..........................................................................................................................................................................44
Download Manuals ........................................................................................................................................................44
Language ......................................................................................................................................................................44
Technical Documents ....................................................................................................................................................44
4
Introduction
Model GPL limited service fire pump controllers are designed to start an electric motor driven fire pump. It can
either start the fire pump manually through the local start pushbutton or automatically through the sensing of a
pressure drop in the sprinkler system. The fire pump controller is supplied with a pressure transducer. The fire
pump can be stopped manually with the local stop pushbutton or automatically after the expiration of a field
programmable timer. In both cases, stopping is only allowed if all starting causes have disappeared.
Methods of Starting/Stopping
The controllers are available as combination automatic / non-automatic with provision for manual or automatic
shutdown (an automatic shutdown is only possible after an automatic start).
METHODS OF STARTING
AUTOMATIC START
The controller will start automatically on low pressure detection by the pressure sensor when the pressure drops
below the cut-in threshold.
MANUAL START
The motor can be started by pressing the START push button, regardless of the system pressure.
EMERGENCY START
The motor can be started manually by using the emergency push button. This button can be maintained in a
closed position.
Important: to avoid damaging the contactor, it is recommended to start the motor in this manner:
1) Shutdown the main power by using the main disconnect means,
2) Push the emergency button and lock it in closed position,
3) Turn the power back on by using the main disconnect means.
SEQUENTIAL START
In case of a multiple pump application, it may be necessary to delay the automatic (pressure drop) starting of each
motor to prevent simultaneous starting of all motors.
5
FLOW START, HIGH ZONE START
The pump can be started by opening/closing a contact on the FLOW/ZONE START/STOP input.
WEEKLY START
The engine can be started (and stopped) automatically at the preprogrammed time.
TEST START
The motor can be started manually by pressing the run test button.
METHODS OF STOPPING
MANUAL STOP
Manual stop is done by pressing the priority STOP push button. Note that pressing the stop push button will
prevent the motor from restarting as long as the button is pressed, plus a two second delay.
AUTOMATIC STOP
Automatic stop is possible only after an automatic start and this function has been activated. When this function is
enabled, the motor is automatically stopped 10 minutes after the restoration of the pressure (above the cut-out
threshold) given that no other run cause is present.
EMERGENCY STOP
The emergency stop is always possible in any starting condition and is done by using the main disconnecting
means located on the door.
6
Installation
The GPL electric fire pump controller is cULus listed, FM certified and is intended to be installed in accordance with
the latest edition of the Standard of the National Fire Protection Association for the Installation of Centrifugal Fire
Pumps, NFPA20 (Centrifugal Fire Pumps) and
*Only American and Canadian applicable codes have been considered during the design of the controllers and
the selection of components.
Except in some cases, the controller is also seismic approved and has been tested in accordance with the ICC-ES
AC156, IBC 2015 & CBC 2016 standards. Proper installation, anchoring and mounting is required to validate this
compliance report. Refer to this manual and drawings to determine the seismic mounting requirements and location
of the center of gravity (you may need to contact factory). The equipment manufacturer is not responsible for the
specification and performance of anchorage systems. The structural engineer of record on the project shall be
responsible for anchorage details. The equipment installation contractor shall be responsible for ensuring the
requirements specified by the structural engineer of record are satisfied. If detailed seismic installation calculations
are required, please contact the manufacturer for the performance of this work.
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following
two conditions: (1) this device may not cause interference, and (2) this device must accept any interference,
including interference that may cause undesired operation of the device.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
“Changes or modifications not expressly approved by the party responsible for compliance could void the user's
authority to operate the equipment.”
Location
The controller shall be located as close as practical to the motor it controls and shall be within sight of the motor.
The controller shall be located or protected so that it will not be damaged by water escaping from the pump or pump
connections. Current carrying parts of the controller shall be not less than 12 in. (305 mm) above the floor level.
Working clearances around the controller shall comply with NFPA 70, National Electrical Code, Article 110 or
C22.1, Canadian Electrical Code, Article 26.302 or other local codes.
7
The controller is suitable for use in locations subject to a moderate degree of moisture, such as a damp basement.
The pump room ambient temperature shall be between 39°F (4°C) and 104°F (40°C).
The standard controller enclosure is rated NEMA 2. It is the installer's responsibility to insure that either the
standard enclosure meets the ambient conditions or that an enclosure with an appropriate rating has been
provided. Controllers must be installed inside a building and they are not designed for outside environment. The
paint color may change if the controller is exposed to ultraviolet rays for a long period of time.
Mounting
The fire pump controller shall be mounted in a substantial manner on a single incombustible supporting structure.
Wall mounted controllers shall be attached to the structure or wall using all four (4) mounting ears provided on the
controller with hardware designed to support the weight of the controller at a height not less than 12 in. (305 mm)
above floor level. Floor mounted controllers shall be attached to the floor using all holes provided on the mounting
feet with hardware designed to support the weight of the controller. The mounting feet provide the necessary 12 in.
(305 mm) clearance for current carrying parts. For seismic applications, the mounting arrangement should be rigid
wall and base only. The structural engineer of record on the project shall be responsible for anchorage details.
Storage
If the controller is not installed and energized immediately, Tornatech recommend following the instructions from the
chapter 3 of the NEMA ICS 15 standard.
Electrical Wiring
The electrical wiring between the power source and the fire pump controller shall meet the latest edition of NFPA
20, NFPA 70 National Electrical Code Article 695 or C22.1 Canadian Electrical Code, Section 32-200 or other local
codes. Electrical wiring shall be typically sized to carry at least 125% of the full load current (FLC or FLA) of the fire
pump motor.
Electrical Connections
A licensed electrician must supervise the electrical connections. The dimension drawings show the area suitable for
incoming power and motor connections. No other location shall be used. Only watertight hub fittings shall be used
when entering the cabinet to preserve the NEMA rating of the cabinet. The installer is responsible for adequate
protection of the fire pump controller components against metallic debris or drilling chips. Failure to do so may
cause injuries to personnel, damage the controller and subsequently void warranty.
Energy Consumption
Standby power: 10W
Sizing
Incoming power terminals on the controller are suitable to accept wire based on that selection with insulation not
less than 60°C. (Refer to terminal diagram for terminal sizes.)
The electrical wiring between the fire pump controller and the pump motor shall be in rigid, intermediate, or liquid
tight flexible metal conduit or Type MI cable and meet the requirements of NFPA 70 National Electrical Code or
C22.1 Canadian Electrical Code or other local codes.
The number of conductors required is :
- For 3 phases motor: 3 wires plus a ground sized at 125% of full load current.
- For single phase motor: 2 wires plus a ground sized at 125% of full load current.
9
Terminal Strip Descriptions
10
Quick Start-Up Guide
The rating label is the most important label. It must be read carefully to ensure the compatibility between the
controller and the installation.
Verify that the controller is installed securely on the wall, or optionally on the mounting stand.
Make sure to drill holes for the motor and power connections and run the cables inside the panel, all in accordance
with the specifications in order to minimize interference with other equipment.
Verify and/or install the proper water connections for the water input and the drain. They must be securely installed
and tightened. Refer to the silkscreen markings on the plastic cover.
11
Connect the input power and the motor on their respective terminals. Secure with the appropriate torque as
indicated on the torque label and verify all connections. Secure the door in closed position then put the circuit
breaker disconnecting means in ON position. Verify the readings on the controller main screen.
Once the controller has booted up, the “First Start Up” page appears. The controller will automatically detect and
display the frequency of the power source. It is then possible to manually choose the frequency of the voltage.
Press “User Login” and enter a valid authorization code. Once logged in, press “Power”.
Verify that the normal voltage shown at L1-L2, L2-L3 and L1-L3 (nominal) is the same as what is written on the fire
pump controllers nameplate. The fire pump controller will validate the nominal voltage automatically versus what it
has been built for.
12
Press “Motor Rotation”
Press the “Start” button to start the electric motor and validate that the electric motor is rotating in the correct
direction. If it is not rotating in the correct direction adjus the motor connections as per below. Press the “Stop”
button to stop the electric motor.
Interchange the connection of the wires coming from the motor that are connected to T1 and T2 on the M1
contactor.
Once the motor rotation has been checked, go back to the controller start-up page and press the “Verify pressure”
button.
WARNING!
On a Wye-Delta closed transition starter, if the transition from Wye to Delta occurs (after 5 to 8 seconds depending
on the motor HP), the manual stop push button will be disabled for 80 seconds. To stop the engine before the end of
the 80 second delay, use the disconnecting mean handle.
Press “Pressure”.
- Verify that the pressure reading on the screen matches with the calibrated pressure gauge installed on the sensing
line.
- Choose the desired units of measurement for pressure reading.
13
- Adjust, if required, the range of the digital pressure gauge at Max. Pres.
- Insert the Cut-Out and Cut-In pressure values of the fire pump.
- Insert, if so desired, the Cut-Out and Cut-In pressure values of the jockey pump.
Note: The jockey pump Cut-Out and Cut-In values must be set at the jockey pump controller itself. Inserting these
values at the Fire Pump Controller is only for pressure recording data purposes.
Go back to the controller start-up page and press the “Other Configuration” button. Enter the time and date. Select
the “Automatic shutdown” and the duration the pump will keep running after the automatic stop if an automatic stop
is desired. Select the frequency at which the periodic test will occur, the day of the week, the hour and the duration
of the test. Also, enter the duration of the Manual Run Test.
From the “Home” page, verify that the displayed values are correct.
14
The “First Start up” is now completed. The controller is fully installed and configured.
15
Main Features
The ViZiTouch
Warning
After 2 years of service, the Vizitouch battery may become less efficient and could lose the time after a shutdown.
First Setup
The First Setup must be done prior to using the controller. Completing the First Setup is the only way to access the
homepage and enable the automatic mode of the controller.
16
Home
Home (Menu) Home
1
2
3
4
5
6
7
The home page displays all controller statuses and important values of the controller. This includes all voltages,
currents, pressures, motor state and status, as well as all timers and motor starting sequences.
A: Navigation bar: Pressing this icon will open a navigation menu on the left side of the screen:
D: Motor power voltage. Each box represents an individual phase voltage between the two adjacent lines.
F: Motor contacts. An animation shows the contactor opened or closed depending on the signal sent to the main
coil.
17
G: The electric motor. It will be grey if the motor is stopped, green if a “Motor Run” signal is detected and red if a
“Fail to start” has occurred. Pressing on the motor will redirect the user to the “Last Service Statistics” page, which
monitors all relevant statistics concerning the controller since the last service.
H: The motor configuration symbol shows how the motor is wired to the contactor(s). This symbol is used to show if
the motor is in a starting configuration (Wye wiring, for example) or in a permanent running configuration (i.e. delta
wiring)
I: Representation of the motor starting or stopping cause. The reason why the motor is running will be displayed in a
message box. Possible choices include, but are not limited to:
FLOW: Automatic motor starting activated by a signal in the FLOW/ZONE START/STOP input.
HIGH ZONE: Automatic motor starting activated by a signal in the FLOW/ZONE START/STOP input.
RUN TEST: Automatic motor starting activated by the run test push button.
This message can also indicate the reason why the motor is not running despite the fact that a request is being
made. Possible choices include, but are not limited to:
LOCKED ROTOR CURRENT (not on GPL models): A locked rotor current alarm has not been cleared on the
alarms page and prevents the motor from starting.
LOW PRESSURE: A low suction pressure prevents the motor from running, This functionality is optional.
LOW WATER: A low water reservoir level prevents the motor from running, This functionality is optional.
LOW ZONE: A not running lower zone controller prevents the motor from running. This functionality is optional.
J: Timers. The sequential start timer (on-delay) will start timing upon an Automatic start request (pressure drop,
deluge valve or remote auto signal). The motor will only start if the request stays active for the duration of this timer.
The “Duration” of the run period timer (off –delay) for automatic shutdown will start timing once the start request
disappears. The pump will stop at the expiration of this timer if the starting reason is no longer present. If a periodic
test has been programmed, the remaining time will be displayed. If a manual run test has been energized, the
remaining time will be displayed.
K: The discharge pressure gauge. It allows for a precise reading of the actual system pressure.The Cut-In (between
the yellow and the red section) and the Cut-Out (between the green and the yellow section) set point values are
indicated on the gauge. These values will also be represented by a red and green line on the gauge, allowing a
quick comparison between the actual pressure and the set points. The actual pressure is shown in the centre of the
18
gauge along with the unit of measure (psi, bar etc). The maximum allowable pressure is also indicated on the
gauge and will scale the gauge accordingly. A full screen image of the gauge will appear by pressing anywhere on
the gauge.
L: Status Bar. The Status Bar appears across the bottom of the display. It displays three statuses that describe the
primary configuration of the controller: Pressure actuated or Non-pressure Actuated, Automatic Controller or Non-
automatic, Manual or Automatic Shutdown.
If an alarm or a warning is active, a colored rectangle will appear over the Status Bar and will display the error
message. This notification will be yellow for a warning and red for an alarm. If more than one error is active, the
display will alternate between the error messages. The messages will disappear when the alarm or warning starting
cause is no longer present.
Screen Saver
After 5 minutes of inactivity on the ViZiTouch, the screen will dim it's brightness to 25%. After 10 minutes of
inactivity on the ViziTouch, the “Black Screen” screen saver will activate. Its goal is to expand the lifetime of the
LCD screen. The screen saver will be instantly deactivated if the engine is running or if an alarm is activated. To
manually deactivate it, simply touch the screen or any membrane button. After deactivation, the screen saver will
always redirect to the “Home” page. It will also log off any user by resetting the security level to 0 and save any new
modifications to the settings.
19
Alarms
Alarms (Menu) Configuration > Advanced > Alarms
Displays the list of currently active and occurred alarms. An alarm is called ACTIVE when its triggering condition is
still valid. An alarm is called OCCURRED when its triggering condition has been active, but is no longer true.
Alarms representing serious concerns are colored RED. Alarms representing simple warnings are colored
YELLOW. Pressing on the RESET button will reset OCCURRED alarms only. Alarms ending with ** are available
on transfer switch models only.
- Alternate Power Phase Reversal**: Activates when the phase order on the alternate power does not match the
correct value of the controller. Each time a service is acknowledged on the ViZiTouch, the controller synchronises
the correct phase order to the one detected on the normal power.
- Phase Loss N1: This alarm is activated if the first phase of the normal power connection does not meet the
qualification criteria.
- Phase Loss N2: Activates if the second phase of the normal power connection does not meet the qualification
criterions.
- Phase Loss N3: Activates if the third phase of the normal power connection does not meet the qualification
criterions.
20
- Loss of power: Activates when a complete loss of normal power is detected.
- Fail to start: Activates if there is and under-current draw of two phases when the motor should be running. A 20
seconds factory set delay is used to give the motor enough time to start before signalling this alarm.
- Transfer Switch Trouble**: Activates upon detection of any of the following incoherent transfer switch data:
The alternate position and normal position limit switches are both activated. None of the alternate position or the
normal position limit switches is activated after a factory programmed delay. The voltage reading on the load side of
the motor contactor does not match the one of the reported input power position after a factory programmed delay.
- Service Required: Activates when service is due for the controller. This occurs when the date set in the service
page has passed or if no service has ever been done.
- Undercurrent: Activates when current is under 30% of FLA and motor has been running for 15 seconds.
- Under voltage: Activates when normal power voltage is below 80% of nominal voltage.
- Over voltage: Activates when normal power voltage is above 120% of nominal voltage.
- Phase Unbalanced: Activates when there is a difference of more than 30% of nominal voltage between the normal
power voltage readings.
- Ground Fault: Activates when the ground fault input current is above the factory set value after a factory set delay.
- PT Fault Detected: If an optional dual pressure sensor is installed, it will be activated if the two pressure
transducers show different readings. Further investigation is advised to determine what caused the different
readings. Note that the controller will always choose the lowest pressure reading to determine the actual system
pressure.
- Overpressure: Activates if the analog readout of the discharge pressure goes higher than the overpressure set
point in the discharge pressure sensor page.
- Underpressure: Activates if the analog readout of the discharge pressure goes lower than the “Under Pressure”
set point in the discharge pressure sensor page.
- Low Suction Pressure: Activates if the analog readout of the suction pressure is enabled and goes lower than the
low suction pressure set point in the suction pressure sensor page.
- Force start on flow: Activates if an external contact triggers flow switch input or if the analog readout of the flow is
enabled and goes higher than the “force start on flow set point” in the flow sensor page.
- Low Spare Temperature: Activates if the analog readout of the spare temperature input is enabled and is lower
than the low spare temperature set point in the “Spare temperature” sensor page.
- Water Reservoir Low: Activates if the “Water Reservoir Low” contact input is triggered or if the analog readout of
the water reservoir is enabled and is lower than the water reservoir low set point in the “Water Level” sensor page.
- Water Reservoir Empty: Activates if an external contact triggers the optional “Water Reservoir Empty” input.
- High Water Level: Activates if the optional “High Water Level” contact input is triggered or if the analog readout of
the water level is enabled and goes higher than the “High Water Level” set point in the “Water Level” sensor page.
- Io_expX-inX alarm: Activates if the specific expansion programmable input on the specific expansion board is
activated and triggered.
21
- High Motor Temperature: Activates when the optional high motor temperature contact is activated.
- Low ambient temperature: Activates when the ambient temperature is below the factory set value (5 Celsius).
- High ambient temperature: Activates when the ambient temperature is above the factory set value (40 Celsius).
- Control Voltage Not Healthy: Activates when the 24VAC power input to the IO cards is below the acceptable
functional range.
- Motor Trouble: Activates when a motor related alarm condition is present (overcurrent, undercurrent, fail to start or
ground fault).
- Pump Room Alarm: Activates when a pump room related alarm condition is present (overvoltage, undervoltage,
phase unbalanced).
- Flow Meter On: Activates when the optional flow meter input is activated.
- IO Electric Communication Error: Activates if no communication with the electric IO card could be established for
15 seconds. This alarm is critical and triggers the bell. If this alarm persists for more than 1 minute, the controller
will reboot to try to fix the problem.
- IO Transfer Switch Communication Error**: Activates if no communication with the transfer switch IO card could
be established for 15 seconds. This alarm is critical and triggers the bell. If this alarm persists for more than 1
minute, the controller will reboot to try to fix the problem.
- IO Expansion Communication Error: Activates if no communication with the Expansion IO card could be
established for 15 seconds.
- Pump on demand: Activates when the pressure is below the cut-in set-point on an automatic pressure actuated
controller.
22
Configuration
Config (Menu) Config
The main configuration page is used to setup all basic configuration parameters and provides a quick means of
changing the most common settings.
There are seven (7) access parameter boxes; Pressure, Periodic Test, Run Test, Automatic Shutdown, Date &
Time, Advanced and User Login. Each parameter requires a specific access level to set or change values.
User Login:
The padlock icon indicates the current authorization level. A locked padlock indicates that only basic settings can be
changed. Press on the padlock to enter an authorization code to unlock additional settings. An unlocked padlock
showing an authorization number indicates that some settings are unlocked. Press on the padlock again when you
have concluded your operation to logout and to save any changes made in the configuration.
Pressure:
The main pressure parameters can be set inside the box at the top of the page.
- Pressure reading: Can be selected as PSI, kPa, bar, FoH, or mH20.
- Input Device: Can be selected as Pressure transducer 1 or 2
- Maximum Pressure: Can be set between the Cut-Out value and 9999.
- Cut-Out: Can be set between the Cut-In value and the Maximum Pressure value. (The Cut-Out should be set
before the Cut-In).
- Cut-In: Can be set below the Cut-Out value.
Periodic Test:
The Periodic Test can be selected as “weekly”, “every other week” or “monthly”. The day of the week, the time of
day for the test and the test Duration can also be specified in this box.
Automatic Shutdown:
If enabled, the Automatic Shutdown will automaticly stop the pump after the demand dissapears. A timer between 1
and 1440 minutes can be selected.
23
Advanced:
Go to the advanced configuration pages.
NumPad Page
The NumPad is activated every time the user presses on a white square box representing a number that can be
set. On top of the NumPad, the current parameter is shown. The box at the top of the NumPad displays the range
of values accepted for that particular parameter. The box will turn red if the value entered is out of range. Pressing
the “X” button in the circle will set the value to zero “0”. Once a value that falls within the range is selected, the box
will turn blue. The button with a blue “X” inside a white arrow is used as a “backspace”. Pressing the “OK” button
will enter the new value and the screen will return to the previous page. Pressing anywhere outside the numpad
view will cancel the edition process and leave the value previously selected.
Select the Year by pressing inside the year box and enter the value, or use the left and right arrows to simply
decrement or increment the value. Likewise, select the month by pressing on the month box and select the value
from the list shown, or use the left and right arrows to cycle through the choices.
Once set, press on the proper day to select the actual day, if different. The time is set by pressing the two square
24
boxes under the clock; the left sets the hours and the right sets the minutes. Press the Update button to commit the
changes. A dialog box will appear to confirm the change “Date and Time”. The user may cancel the changes by
pressing the “Cancel” button. Please note that changing the date and time will have an effect on the logs
chronology.
The time zone can also be changed using the box in the bottom-right corner.
Shortly after being entered, each character will be displayed as an “*”. To view the whole password, press the eye
on the top left corner.
If the password is invalid for a consecutive number of times, the user will be redirected to the “Service Dealer” page,
allowing the user to communicate with the appropriate Service Dealer.
If the password is valid, the “Configuration” page will reload and the access security level will be shown inside the
lock. To log off, click on the lock and the user security level will return to “0”
25
Other KeyPads:
The KeyPad is activated every time the user presses on a grey rectangle box with white text representing a text that
can be set. The “X” button allows the user to cancel editing the value. The back arrow erases the last entered
character. Simply click the “OK” button once the value is set. This type of text field is mostly used to generate a
digital text indication for a custom alarm input.
This page is the portal to all the advanced configuration parameters of the ViZiTouch. Pressing on a tab will redirect
to the corresponding page.
This page is used to update the controller software. A USB key or a network connection with the software update is
needed.
26
Sensor Selection Config > Advanced > Sensors
All analog sensors, voltage sensors, a current sensor and a Ground fault sensor can be calibrated by accessing this
page. The Analog Input 1 is dedicated to the Pressure Transducer 1. The other Analog Input depends on the
controller options.
Every sensor, except the line Voltage and the Current sensor can be calibrated the same way. The Signal
destination, the Unit type, the Unit, the Min and Max value are variables that are set in factory but the calibration
can be made in the field.
There are three ways of calibrating a sensor that can be chosen in the windows below "Sensor value".
-Sensor value: Connect an external measurement tool that is already calibrated (like a Manometer to calibrate a
pressure sensor). Bring the system to calibrate to a low point. While looking at the measurement tool, press the
read button (the button with a circular arrow). The value that was displayed on the measurement tool when the read
button was pressed needs to be enter in the "Low" window below the Desired value. Repeat these steps with a high
value. Then press compute. For the PT1, only a high value is required.
-Theorical voltage: Use a graphic of the theorical sensor's voltage response (usually given in the datasheet of the
sensor). Enter a low point (value, voltage) and a high point. Then press compute.
For the pressure transducer PT1, the low point (zero) is automatically acquired during first power up. It can be re-
acquired by pressing the blue round arrow. The high point needs to be entered in order to calibrate the sensor.
To calibrate the line voltage sensor, use an external voltmeter that is already calibrated. With the control panel
under power:
- Read the voltage between L1 and L2, and press the first white box under “Sensor value”.
- Enter the voltages in the first white box below “Desired”.
- Read the voltage between L2 and L3, and press the second white box under “Sensor value”.
- Enter the voltages in the second white box below “Desired”.
- Read the voltage between L1 and L3, and press the third white box under “Sensor value”.
- Enter the voltages in the third white box below “Desired”.
- Press the “Compute” button.
28
To calibrate the current sensor, use an already calibrated current clamp. With the control panel under voltage and
the motor not powered, enter “0” in the white box under “Desired”. Press the higher “Read all” button. Start the
motor by pressing the manual start button on the ViZiTouch and wait for the motor to reach the full speed. Take a
reading with the current clamp on one line and press the lower “Read all” button. Enter the value taken with the
current clamp in the white box under “Desired”and at the right of “High”. Press Compute.
Important Notice!
Every analog sensor cable used for this controller should be shielded. The shield has to be grounded on the motor
side. Not complying to these recommendations may affect the controller good functioning and void its warranty.
Most alarms are not configurable in the field, but some are with the appropriate password level. If it's configurable,
the checkboxes will be in white. Otherwise the checkboxes will be grey. Also, the two last fields: Value Usage and
Analog Value are not always visible.
29
Start Test: The alarm can be tested using this button.This test will only announce the chosen alarm. It will activate
the bell if the alarm is audible and will activate any output relays associated with this alarm. The test will not activate
other common alarms or other components. To stop the testing, press the “Stop Test” button.
Alarm: Makes this signal an alarm (red display). Otherwise, it will be a warning (yellow display).
Annunciate when occurred: Check this box to keep activated any associated relay even when this alarm has
occurred.
Acknowledgeable: Check this box to make the alarm acknowledgeable. If an alarm is ackowledged, the alarm IO
board Output will stop being active. To acknowledge an alarm, go to the alarm list page and press the blue “Active”
status on the right of the alarm. The “Active” status should change to “Acknowledge”.
Timer On: It is the time delay between the triggering of the condition and the activation of the alarm.
Timer Off: It is the time delay between the stopping of the condition and the deactivation of the alarm.
Analog Value Usage: It is used to describe the activation range of the alarm. “Lower Than”, “Higher Than” and
“Between” can be selected. The corresponding value has to be entered.
Text: This field can be used to change the name of the alarm that will be displayed while this alarm is active. Note
that changing the factory set name of an alarm will disable any translation of this alarm to different languages.
30
Control Timers Config > Advanced > Control Timers
This page is for vizualisation purpose only. It allow the user to verify which signal is mapped on which controller's
input.
31
Outputs Config > Advanced > Outputs
This page is used to see the logic of the signals that will activate the Outputs on the IO board and to test those
Outputs. The TB6 output can also be configured from this page.
The first box from the top is used to change the name of the Output. For the output's logic, a combination of 5 digital
inputs can be selected. Each input can be an alarm or a signal from a list and can be inverted by pressing the
32
NO/NC contact symbol at the left of the screen. A logical AND or OR can combine the chosen inputs and the exit
can also be inverted by pressing the NO/NC contact symbol at the right of the screen.
Pressing the “Test” button, at the bottom of the screen, will change the state of the output for one second. Note:
activating some outputs may cause the motor to start.
This page is used to visualize the program version, the serial number and the model of the controller.
Some parameters can be changed on this page, but be careful, modifying a parameter will change the basic
operation of the controller. Afterwards the controller may no longer respect the NFPA standard.
- Automatic Controller: Enable automatic starting causes.
- Pressure Actuated Controller: Enable the automatic controller to start following a pressure drop.
It is possible to reload a past configuration by pressing the "reload configuration" button. Dates with an "*" are
settings following a "Service".
Do not change a parameter on this page without previously consulting a Tornatech representant.
33
I/O Card Info Config > Advanced > IO Card Info
This page is used to visualize the ViZitouch and the IO Card registers by pressing on the blue arrows on the right of
the screen. Expansion Cards can also be installed via this page.
This page displays the IP address, the Subnet Mask, the Default Gateway and the DNS1-2-3 of the controller. All
those parameter can be changed manually by checking the box on the upper left corner. To apply the change,
press on the blue arrow in the bottom right corner.
34
Interlock Lockout Config > Advanced > Interlock Lockout
This page is used to configure the Lockout input and the Interlock output parameters. To be active those options
need to be assigned to an Input or an Output on the IO board.
35
History
History (Menu) History
This page is used to access all data related to events, statistics, pressure history, power logs and the downloading
of this information via one of the two USB ports.
-Events: This button leads to the “Events” page, which displays the events from the most recent 500 logs. Each
event log contains the date and time of occurrence as well as a brief description of the event.
-Pressure/Power Curves: This button leads to the “Pressure Curves” / “Power Curves” page accordingly, which
displays all relevant pressure/power information from the most recent 500 logs.
-Saved Logs: This button leads to a page where past logs can be viewed.
-Statistics: This button leads to the “Statistics” page, which leads to “All Time Statistics”, “First Service Statistics”
and “Last Service Statistics” pages.
-Download: This button leads to the “Download” page, which allows the user to download information, including the
user manual, drawings, logs, statistics and configuration.
36
Events Page History > Events
The Events Page shows the events from the last 500 logs which occurred in chronological order. The first column is
the date, the second one is the time of occurrence and the third column is the “Event message”. To obtain a log that
is older than thoses events, visit the “Saved Logs”.
On this page, a graphic of the “System Pressure”, the “Cut-in”, the “Cut-Out”, the main pump “Engine Run” and the
“Jockey Pump Run” through time can be viewed. By pressing on the screen, the caption will disappear or will be
displayed. The time scale can be changed by pressing the time span desired on top of the screen (from 1 minute to
2 weeks). The blue arrows on both sides of the graphic are used to navigate through time. The blue button in the
bottom left corner leads to the table used to generate this graph.
37
This table allows viewing of the exact values used to generate the Pressure Curves with the precise time. Pressing
the blue button on the top left corner will return to the graph page.
On this page, a graphic of the 3 line voltages, the 3 line currents and the motor running through time can be viewed.
By pressing on the screen, the caption will disappear or will be displayed. The time scale can be changed by
pressing the time span desired on top of the screen (from 1 minute to 2 weeks). The blue arrows on both sides of
the graphic are used to navigate through time. The blue button in the bottom left corner leads to the table used to
generate this graph.
38
This table allows viewing of the exact values used to generate the Power Curves with the precise time. Press the
blue button on the top left corner to return to the graph page.
This page is used to access all past log files. Each log file is a CSV file containing the time, the date, the Cut-in, the
Cut-out, the system pressure, the 3 line voltages and currents, the engine run signal, the jockey pump run signal
and the log event message. Each file can contain up to 1 MB of data. The month and year are shown in the title.
Each time a CSV file is full, a new one is created with an incremented number in the title. Press on the file to
consult this content.
39
The logs are arranged chronologically. To select the displayed data, press on the filter icon in the top center of the
screen.
From this page, the selected values will be displayed. Press on “Log File” at the top left of the screen to go back to
the logs table.
40
Statistic History > Statistics
This page leads to 3 other Statistics pages: “All Time Statistics”, “First Service Statistics” and “Last Service
Statistics”.
All Time Statistics History > Statistics > All Time Statistics
41
First Service Statistics History > Statistics > First Service Statistics
This page allows the user to view the “First Setup Statistics”. The parameters are:
From:
- Since: Date of the first setup
- On Time: Time the controller spent On, in DAYS-HOURS:MINUTES-SECONDS
Motor:
- On Time: Time the motor spent On, in DAYS-HOURS:MINUTES-SECONDS
- Start Count: Number of times the motor has started
- Last Started On: Last time the motor started
Pressure:
- Minimum: Smallest pressure value
- Minimum Occurred On: Date the smallest value happened
- Maximum: Biggest pressure value
- Maximum Occurred On: Date the biggest value happened
- Average: Average pressure since first start-up
Temperature
- Minimum: Smallest temperature value
- Minimum Occurred On: Date the smallest value happened
- Maximum: Biggest temperature value
- Maximum Occurred On: Date the biggest value happened
- Average: Average temperature since first start-up
Jockey Pump Running
- On Time: Time the Jockey Pump spent On, in DAYS-HOURS:MINUTES-SECONDS
- Start Count: Number of times the Jockey Pump has started
- Last Started On: Last time the Jockey Pump started
42
Last Service Statistics History > Statistics > Last Service Statistics
This page allows the user to view the “Last Setup Statistics”. The parameters are the same as the ones from the
“First Setup Statistics” page but from the “Last Service”.
43
Service
Service
Informations on how to reach technical support, concerning the commissioning date, the last service date and the
next service due date is available on this page. It is the client responsibility to make sure that the proper
maintenance is done on the controller. A reminder for the “Service” can be selected from these options: OFF, ½
year, 1 year, 1 ½ years, 2 years and 3 years. The next service will be determined using the last service and the
chosen service interval. This service must be done by an accredited technician.
A proper password must be enter for the “Service Done” button to be available. This button should only be pressed
by an authorized person after a completed service.
The “Live View” page is where the user can grant or refuse the remote access demands.
The “Nameplate Information” page contains all the information found on the nameplate.
The Jockey Pump Cut-Out and Cut-In can be set on this page.
It is possible to install a custom Service card on this page. Contact Tornatech for more information.
44
Download Manuals
Pressing on the question mark will redirect to the download page. A pdf version of the manual can be downloaded
on an USB device.
45
Language
The language displayed on the ViZiTouch can be selected on this page.
46
Technical Documents
Patents
Country Title Grant No
CA Mechanical activator for contactor 2741881
US Mechanical activator for contactor US8399788B2
CA Mechanical activator for electrical contactor 165512
CA Mechanical activator for electrical contactor 165514
US Mechanical activator for electrical contactor D803794
US Mechanical activator for electrical contactor Patent pending
002955393-
EP Mechanical activator for electrical contactor 0001/2
AE Mechanical activator for electrical contactor Patent pending
AE Mechanical activator for electrical contactor Patent pending
CA Fire pump digital operator 163254
US Fire pump digital operator interface D770313
AE Fire pump digital operator interface Patent pending
EP Fire pump digital operator interface 002937250-0001
CA System and method for detecting failure in a pressure sensor of a fire pump system Patent pending
US System and method for detecting failure of a pressure sensor in a fire pump system Patent pending
47
Pre-Field Acceptance Test
TORNATECH MODEL GPL
WITH OR WITHOUT GPU TRANSFER SWITCH
ELECTRIC FIRE PUMP CONTROLLER
PRE- FIELD ACCEPTANCE TEST
CHECK LIST
Note: This document should be an official indication of whether or not the installation and general condition
of the equipment is adequate for a field acceptance test. This document should also aid the individual
responsible for executing the field acceptance test to decide whether or not to carry out the field acceptance
test of the equipment.
Installation Check List: YES NO
Verify that the nameplate of the Fire Pump Controller corresponds with the AC voltage
1
available.
Visual inspection for any damage to the exterior of the Fire Pump Controller. Make sure
2
the enclosure, alarm bell, selector switch, membrane and display are not damaged.
Verify that the Fire Pump Controller has been installed within sight of the pump and engine
3
or motor.
Verify that the Fire Pump Controller has been installed not less than 12 inches from the
4
floor of the mechanical room.
Verify that all electrical connections to the Fire Pump Controller are done using liquid tight
5
conduit and connectors.
With the Fire Pump Controller door open, visually inspect for any drill chips, dirt or foreign
6 objects in the bottom of the enclosure, loose wires, broken components and general
proper electrician workmanship.
Verify that the correct Normal Power AC voltage is supplied to the controller by taking a
7
voltage reading at the incoming terminals of the isolating switch (IS).
8 Verify that the motor leads are connected for the corresponding starting method.
Initial Power-Up Check List: YES NO
Controller door must be closed and latched with Normal Power Disconnecting Means
1 handle in the OFF position. If a Transfer Switch is supplied, its door must be closed and
latched with the Alternate Power Isolating Switch handle in the OFF position.
2 Verify that the Emergency Start Handle is in the OFF position.
3 Place the Disconnecting Means handle in the ON position.
Verify that the Normal Power voltage and hertz displayed on the digital screen are the
4
same as measured in point 7 of the Installation Checklist above.
5 Verify that there is no Phase Reversal Alarm.
Note: A manual or automatic start must only be executed if the motor and the pump have
YES NO
been cleared to be started by their respective official service technicians.
1 Place the Disconnecting Means handle in the ON position.
2 Push the START pushbutton. The motor will start.
Verify the motor rotation:
• If the motor rotation is correct, no adjustment is required.
3
• To correct the motor rotation, change motor connection leads 1 and 3 (A and C) at the
run contactor
Verify any alarms that would appear on the digital display screen. Correct any alarm
4
condition.
Set the Cut-Out and Cut-In settings by following the ViZiTouch documentation. You need
5 to be logged in to modify these settings. Verify the automatic start by dropping the system
pressure below the Cut-In setting.
Stop the motor by pressing the “STOP” membrane button. Note: the motor will only stop if
6
the system pressure is above the cut-out setting.
48
Tornatech Controller S/N: _________________________________________
_________________________________________
_________________________________________
Company: __________________________________________
Date: __________________________________________
Comments: ___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
49
Field Acceptance Test Report
TORNATECH MODEL GPL
WITH OR WITHOUT GPU TRANSFER SWITCH
ELECTRIC FIRE PUMP CONTROLLER
FIELD ACCEPTANCE TEST REPORT
Complete this first section if it was not completed during the Pre-Field Acceptance test
Note: A manual or automatic start must only be executed if the motor and the pump
YES NO
have been cleared to be started by their respective official service technicians.
1 Place the Disconnecting Means handle in the ON position.
2 Push the START pushbutton. The motor will start.
Verify the motor rotation:
• If the motor rotation is correct, no adjustment is required.
3
• To correct the motor rotation, change motor connection leads 1 and 3 (A and C) at
the run contactor
Verify any alarms that would appear on the digital display screen. Correct any alarm
4
condition.
Set the Cut-Out and Cut-In settings by following the ViZiTouch documentation. You
5 need to be logged in to modify these settings. Verify the automatic start by dropping
the system pressure below the Cut-In setting.
Stop the motor by pressing the “STOP” membrane button. Note: the motor will only
6
stop if the system pressure is above the cut-out setting.
Phase Reversal Verification YES NO
Verify or simulate phase reversal
Overcurrent Protection
Controller nameplate info Electric Motor nameplate info
1
FLC: __________A FLC: __________A
LRC: __________A LRC: __________A
Motor Starts
Normal Power YES NO
1 6 manual starts
2 6 automatic starts
3 6 Emergency Handle starts
4 1 remote/deluge valve start
Field Settings:
50
Alarm Contacts Connections:
Fire Pump Controller
_________________________________________
Company: __________________________________________
Date: __________________________________________
Company: __________________________________________
The undersigned witness has been made aware of the NFPA20 article 14.4 Periodic Inspection, Testing and
Maintenance which stipulates that “Fire pumps shall be inspected tested and maintained in accordance with
NFPA25 – Standard for the Inspection, Testing and Maintenance of Water Based Fire Protection Systems”
Comments: _____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
51
52