370013-063 ConfigGde Smartpack2 Smartpack-S Compack-Controllers 1v0 PDF
370013-063 ConfigGde Smartpack2 Smartpack-S Compack-Controllers 1v0 PDF
Smartpack S Controller
Compack Controller
Technical Support
+1 (800) 435-4872
[email protected]
www.eltek.com
2 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
Table of Contents
1. Overview ..........................................................................................5
Passwords ................................................................................................................................ 6
2. Direct Network Connection to the Controller .................................7
Requirements .......................................................................................................................... 7
Procedure ................................................................................................................................. 8
3. Setting Float Voltage ................................................................... 13
Setting Float Voltage through the Web Interface ..................................................... 13
Setting Float Voltage through the Display Panel ....................................................... 14
4. Setting Rectifier Current Limit ..................................................... 15
Setting the Rectifier Current Limit through the Web Interface ............................. 15
Setting the Rectifier Current Limit through the Display Panel ............................... 16
5. Setting Battery Charging Current Limit....................................... 17
Setting the Battery Charging Current Limit through the Web Interface ............. 17
Setting the Battery Charging Current Limit through the Display Panel .............. 18
6. Battery Discharge Testing ........................................................... 20
Setting Battery Discharge Testing through the Web Interface ............................. 21
Battery Discharge Testing through the Display Panel ............................................. 23
7. Battery Temperature Compensation ........................................... 25
Setting Battery Temperature Compensation through the Web Interface ......... 25
Setting Battery Temperature Compensation through the Display Panel ........... 27
8. Setting Alarms .............................................................................. 28
Input Alarms .......................................................................................................................... 29
Setting an Input Alarm through the Web Interface ................................................... 30
Setting an Input Alarm through the Display Panel ..................................................... 31
Output Alarm Relays ........................................................................................................... 32
Setting Output Relays through the Web Interface .................................................... 32
Setting Output Relays through the Display Panel ..................................................... 34
Alarm Setpoints.................................................................................................................... 34
Setting Alarm Battery Voltage Alarm through the Web Interface........................ 35
Setting Alarm Battery Voltage Alarm through the Display Panel ......................... 38
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 3
9. Alarm Relay Test .......................................................................... 41
Testing Output Relays through the Web Interface ................................................... 41
Testing Output Relays through the Display Panel ..................................................... 42
10. Setting Site Information (web only) ............................................. 43
To Set Site Information through the Web Interface .................................................. 43
11. Setting SNMP Communication (web only) ................................... 45
General SNMP Configuration ............................................................................................ 46
SNMP v3 Configuration: Web-based / SNMP-based ................................................. 46
SNMP Implementation ........................................................................................................ 55
4 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
1. Overview
This configuration guide provides instructions for the following Eltek controllers:
o Smartpack2 Master
o Smartpack S
o Compack
The procedures herein describe how to establish controller communication using a
computer and how to apply parameter settings through both the web interface and
display panel. Screenshots for the web interface are taken from the Compack
controller (unless otherwise noted). Screenshots for the display panel are taken
from the Smartpack2 Master controller.
For the Smartpack2 Master and Smartpack S controllers, setup can be performed
through either the web interface or display panel.
NOTICE: The Compack controller does not have a display panel and therefore
requires the use of a computer and an Ethernet connection for the web interface in
order to adjust parameters.
NOTICE: The Smartpack2 Master controller display must be unlocked in order to
enter the Main Menu. At the default status screen, press the UP arrow key, DOWN
arrow key, and then the ENTER key to unlock the screen and enter the Main Menu.
NOTICE: The Smartpack S controller's navigation keys are slightly different from
the Smartpack2 controller's keys in that the ENTER and CANCEL (X) keys also
function as the LEFT and RIGHT keys, respectively, as follows:
ENTER: A short press of this key navigates to the LEFT. A long press (or,
"press-and-hold") performs an ENTER or confirm action.
CANCEL (X): A short press of this key navigates to the RIGHT. A long press
performs a CANCEL or abort action.
Navigation Buttons
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 5
REVISION NOTE: This guide was written to Compack controller software revision
2.1.2 and Smartpack2 controller software revision 2.2. Some menus and options
may vary as later revisions are released.
Passwords
Passwords are required to edit fields and apply changes. The following are the
default passwords for each interface:
• Web interface: The administrative password required to make changes is
entered when logging in to the interface. By default, the credentials are:
User name: admin
Password: admin
• Display: The administrative password (PIN, in this case) is entered when
selecting a field to edit. By default, the PIN is 0003.
6 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
2. Direct Network Connection to the Controller
The following procedure describes the most reliable method for establishing a
direct connection between a computer and an Eltek controller, which facilitates
access through the web interface.
Requirements
NOTICE: Adjusting settings on the Compack controller requires the use of a
computer and an Ethernet connection. The Smartpack2 and Smartpack S
controllers can be configured using either the display panel or a connection to
a computer.
Before connecting to and accessing an Eltek controller by computer, the
following items and information must be collected:
o Make sure the User Guides for the controller and system are on hand. If
not, please visit the Eltek ShareFile site (https://eltek.sharefile.com) and
download the appropriate documents.
o Install the Eltek Network Utility (ENU) on the computer to be used. This
utility can be downloaded from the Internet (http://msm.eltek.com/enu).
o Identify the operating system of the computer to be used.
• Required Operating Systems: Microsoft® Windows XP or later
(Windows Vista, Windows 7, etc.)
o Identify the web browsers available on the computer to be used.
• Required Web Browsers: Internet Explorer 9 or later; or Mozilla Firefox
12.0 or later.
NOTICE: Internet Explorer 9 is not available for Windows XP. In this case,
Mozilla Firefox 12.0 or later should be downloaded to the computer to
ensure full functionality of the web interface.
The web interface is fully tested using Internet Explorer 9 and Firefox
12.0. Limited tests are also performed using Chrome, Safari and Opera
with success. However, no guarantee is given that full functionality is
achieved with these browsers.
o OPTIONAL: It may be advantageous in some cases to install Eltek's
PowerSuite program on the computer to be used, especially if the
computer is running Windows XP and it is not possible to install one of the
required web browsers. PowerSuite is on the CD provided with the
controller. It can also be downloaded from Eltek's FTP site
(ftp://ftp.eltek.com); please contact Eltek for the current credentials.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 7
NOTICE: PowerSuite is not covered in this guide. If necessary, please consult
the documentation provided on the CD as well as the online help file at
http://onlinedocs.eltek.com/wip4/mywip/powersuite; please contact Eltek
for the current credentials.
IMPORTANT: The following Eltek interfaces require the computer ports
specified to be available (i.e., not blocked by the local network administration
or IT group):
o Eltek Network Utility:
• UPD port 20034
• TCP port 80
o Web Interface:
• TCP port 80
• TCP port 443
o PowerSuite:
• UDP port 4002
Procedure
1. Connect an Ethernet cable (either cross-over or straight-through) to
the controller and computer Ethernet ports.
Ethernet Port Ethernet Port
Compack
Smartpack2 Master
Ethernet Port
Smartpack S
8 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
3. After the ENU program opens, click on the search button (magnifying
glass icon) in the upper left corner to find the controller. Wait for the
window to populate.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 9
o If YES, then skip to step 20.
o If NO, then the controller's IP address must be changed to be
closer to the IP address of the computer. Continue to the next
step.
7. On the computer, launch a "Command Prompt" window. This can be
done in one of two ways:
o Click the "Start" button, select "Run", type "cmd" in the text field,
and click the "OK" button.
o Click the "Start" button, select "All Programs", select
"Accessories", and then select "Command Prompt".
10 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
15. Type an address that is close to the IP address of the computer. The
first three numbers (or octets) should be exactly the same to ensure
that both the computer and controller are on the same network; the
last number (octet) should be different by a few digits.
For Example: If the computer's IPv4 address is 192.168.1.30, then use
the first three numbers (192.168.1) exactly as they appear for the
controller. For the last number, pick something close to the
computer's last number, like "35". The resulting IP address for the
controller in this example will be 192.168.1.35.
NOTICE: If an invalid address is entered, the box shows a red outline.
Leading zeros should be omitted.
16. Click the "Submit" button. There may be a "click" from the controller as
it reboots to apply the new IP address. Allow 30 seconds for the
controller to finish the reboot cycle.
17. Click the "Close" button of the "Ip configuration" window.
14 13
12 16 17
18. After the controller reboots, return to the main window of the ENU
program and click the search button again. The controller appears in
the list with the new IP address.
19. Select the controller and click the "Web Interface" button. The login
page appears. See Figure 4.
20. Click the "LOGIN" link.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 11
21. At the prompt, type in the username and password. The defaults are:
Username: admin
Password: admin
NOTICE: The username and password are case-sensitive. If these
credentials do not work, then they have been changed on site. Consult
site personnel and/or site documentation for the current credentials.
Controller connection is now established. Make sure to logout from the
controller when finished.
NOTICE: If the controller is to be connected to a local area network (LAN),
contact the local network administrator to determine if a static IP address is to
be assigned or if the IP address will be assigned dynamically (DHCP). Use the
"Ip configuration" window to set the controller IP configuration according to the
instructions from the network administrator. Refer to steps 11– 17 again if
necessary.
RECOMMENDATION: If connecting the controller to a LAN after setup, make
sure to check connectivity through the network!
For controllers with a display (Smartpack2, Smartpack S), the controller's IP
address can be found at the following location:
Main Menu > Sys.Config. > PowerSystem > General System Config. >
Agent IP Address
12 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
3. Setting Float Voltage
CAUTION: Refer to the battery manufacturer's documented specifications
for recommended float voltage per battery cell. It is the user's responsibility
to enter proper battery parameters.
NOTICE: Float voltage is calculated based on the voltage required per battery cell.
3, 4
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 13
Setting Float Voltage through the Display Panel
To set float voltage through the
display panel:
1. From the Main Menu, select
"Sys. Config".
2. Select "Power System".
3. Select "General System Config".
4. Select "Reference Voltage
[V/Cell]".
5. Enter the PIN. The default PIN
is 0003. Figure 8 - Setting Float Voltage
6. Enter the float voltage desired Through the Display Panel
per cell.
7. Press the [ENTER] key to save the change.
The float voltage is now set.
14 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
4. Setting Rectifier Current Limit
Rectifier current limit restricts total output current of all rectifiers.
3, 4
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 15
Setting the Rectifier Current Limit through
the Display Panel
To set rectifier current limit through the
display panel:
1. From the Main Menu, select "Sys.
Config".
2. Select "Rectifiers". This opens the
"RECTIFIER CONFIG." screen.
NOTICE: If there are multiple rectifier
bays connected to separate Smartpack2
Basic controllers, a screen appears that
says "Sel. Group(up/dwn):TOT"; simply
press [ENTER] again on this screen. If a Figure 10 - Setting Rectifier Current
multiple rectifier bay configuration does Limit through the Display Panel
not exist, the "RECTIFIER CONFIG." screen
appears automatically.
3. Select "Rect. CurrentLimit enable-On/Off?"
4. Enter the PIN. The default PIN is 0003.
5. Use the UP or DOWN arrow keys to place a check mark in the box.
6. Press the [ENTER] key to save the change.
7. Select "Rect. CurrentLimit value [A]".
8. Enter the current value desired.
9. Press the [ENTER] key to save the change.
Rectifier current limit is now set.
16 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
5. Setting Battery Charging Current Limit
Battery current limit restricts charge current. Eltek controllers have two separate
current limit parameters for different power situations: Mains (normal AC utility
service) and Generator (AC backup).
NOTICE: A shunt is required in order to use battery current limit.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 17
1
Figure 11 - Setting Battery Charging Current Limit through the Web Interface
18 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
7. Press the [ENTER] key to save the change.
8. Select "CurrentLimitValue [A] (MainsFeed)".
9. Enter the current value desired for when the system is on regular AC
utility service.
10. Press the [ENTER] key to save the change.
11. If a current limit setpoint is desired for AC generator power, then select
"CurrentLimitValue [A] (GenFeed)".
12. NOTICE: Normally the value for "Generator feed current limit" is lower
than "Mains feed current limit". If the "Generator" limit is not going to be
used, then simply put the same value here as the "Mains feed current
limit".
13. Enter the current value desired for when the system is on AC generator
back-up.
14. Press the [ENTER] key to save the change.
Battery charging current limit is now set.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 19
6. Battery Discharge Testing
CAUTION: Battery discharge testing requires the specifications from the
battery manufacturer. DO NOT proceed with battery testing of any kind
without having the documented specifications on hand. If unavailable, contact the
battery manufacturer directly. Eltek does not provide battery discharge
specifications.
There are two methods of executing battery discharge testing: Simplified and
Normal.
o The "Simplified" test does not use the battery table for reference (see page
22 for details on the battery table); instead, it relies on user-entered values
to determine whether the batteries are able to discharge for the entire
duration specified ("Max duration") or meet the amp-hour value ("Max
discharge") before falling to the voltage per cell specified in the "End voltage"
field. All three parameters are user-defined, but must be within the
specifications provided by the battery manufacturer. The test stops when
any one of the parameters mentioned above (Max duration, Max discharge, or
End voltage) is reached.
o The "Normal" test relies on the battery table for reference, using the battery
specifications to determine end voltage. The only editable parameter that
affects termination of the test is "Max duration".
NOTICE: Under "Normal Test", battery discharge results are evaluated only if the
test is stopped by reaching "End voltage". Results are discarded if a test is
terminated due to reaching "Max duration" or any other reasons (such as manually
stopping the test).
Other configurable parameters on the Battery Test Configuration page:
o "Guard time" is the number of hours that a battery test should be delayed
after a loss of AC input power.
o "Interval test" facilitates regular, periodic battery testing and also
accommodates the inhibiting testing during certain months (for example,
summer months).
o "Automatic test" initiates testing when AC input power is lost. Data is
recorded only if "End voltage" is reached.
o "Discontinuance test" is an advanced battery feature that is used to detect
defective or failed battery cells in unbalanced battery strings. It requires at
least two battery strings and a separate shunt in each string. The
Discontinuance Test is not covered in this document.
20 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
Setting Battery Discharge Testing through the
Web Interface
To set battery discharge testing through the web interface:
1. Click on the "System Conf." icon in the top menu bar.
2. In the left menu bar, click on "Battery" (below the "Power System"
heading).
3. Click on "Test".
4. Enter settings as required for the batteries. Refer to the descriptions of
the fields above.
5. Click on the save icon ("diskette") to save changes.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 21
Figure 14 - Battery Test Page (Normal test selected)
NOTICE: The battery table is located under the "Configuration" menu. To access
the battery table, choose System Conf. > Power System > Battery > Configuration >
[Edit battery table].
22 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
NOTICE: The battery table can be adjusted only through the web interface. It
cannot be changed through the display.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 23
Figure 17 - Battery Discharge Test (Page 2)
24 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
7. Battery Temperature Compensation
CAUTION: Battery temperature compensation requires specifications from the
battery manufacturer. DO NOT proceed without having the documented
specifications on hand. If unavailable, contact the battery manufacturer directly.
Eltek does not provide battery specifications.
Battery temperature compensation adjusts battery charging voltage after a
predefined temperature threshold has been exceeded. The reference voltage and
temperature slope are specifications provided by the battery manufacturer.
Maximum and minimum compensation voltage should also be defined to protect
load equipment.
The fields available are:
o Temperature Compensation – check the box to enable Temperature
Compensated Charging parameters. Clicking again on the box (uncheck)
disables the parameters.
o Minimum Compensation Voltage – minimum charging voltage per battery cell
(protects connected load equipment).
o Maximum Compensation Voltage – maximum charging voltage per battery
cell (protects connected load equipment).
o Reference Voltage – charging voltage per battery cell recommended by the
battery manufacturer at the reference temperature specified in the
“Reference Temperature” field.
o Reference Temperature – the reference temperature in degrees Celsius that
the battery manufacturer specifies for the charging voltage entered in the
“Reference Voltage” field.
o Temperature Slope – compensation factor in millivolts per degree Celsius per
battery cell recommended by the battery manufacturer
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 25
4. Enter settings as required for the batteries. See the descriptions of the
fields above.
5. Click on the save icon ("diskette") to save changes.
26 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
Setting Battery Temperature Compensation
through the Display Panel
To set battery temperature compensation through the display panel:
1. From the Main Menu, select "Sys.
Config".
2. Select "Battery".
3. Select "Battery Config".
4. Use the down arrow key to scroll
to "Temp. Compensation –
On/Off?"
This and the next five lines are for
temperature compensation (down
through "Max.CompensationVolt.
Figure 20 - Battery Temperature
[V/Cell]")
Compensation through the Display Panel
5. To enable Temperature
Compensation, select the box by pressing the [ENTER] key, then enter
the PIN. The default PIN is 0003.
6. Use the UP or DOWN arrow keys to place a check mark in the box.
7. Press the [ENTER] key to save the change.
8. Adjust the other parameters as desired. Refer to the parameter
descriptions above for details.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 27
8. Setting Alarms
Alarm settings are configured in the "Alarm Configuration" section of both the web
interface and display menus. Alarm or temperature inputs are assigned to alarm
groups. Alarm groups, in turn, are assigned to output relays. These assignments
are user-configurable. The diagram below (Figure 21) illustrates how inputs can be
assigned to alarm groups, and how alarm groups can be assigned to output relays.
The assignments in the diagram are just examples.
Alarm/Temperature Alarm Output
Input Terminals ELTEK CONTROLLER Relays
1 1
Alarm Group 1
2 2
Alarm Group 2
Input 3 3 Output
Alarm Group 3
4 4
5 5
Alarm Group X
6 6
The next two sections explain different parts of the diagram above (Figure 21).
INPUT ALARMS explains what the inputs are on the "Inputs" page of the controller
and how to assign them to alarm groups. OUTPUT ALARM RELAYS explains the
"Outputs" page of the controller, how to assign alarm groups to relays, and how to
rename alarm groups.
NOTICE: Each controller has different alarm input/output interfaces:
o The Compack controller has three inputs and three output relays; they are
located on the top of the controller.
o The Smartpack2 controller does not have any input/output terminals built in;
instead, an Eltek I/O Monitor is required. I/O Monitors feature six alarm inputs
and six output relays.
o The Smartpack S controller has six inputs and six output relays; they are
located on the left side of the controller (when viewed from the front).
28 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
Alarm Terminals Alarm Terminals
Alarm Terminals on
Compack Controller an I/O Monitor2
Input Alarms
There are three categories of input alarms:
o Temperature: Temperature inputs are just one of several possible
designations for the input alarm terminals (three for the Compack
controller; six for the Smartpack S; six for an I/O Monitor2 connected
to the Smartpack2). Enabling the input for Temperature indicates that
a temperature probe is connected to the input terminal selected.
o Virtual Input: Virtual inputs are for use as manual triggers to toggle
an assigned alarm output relay on command. There is no physical
terminal associated with these; they are "virtual".
o Programmable Input (ProgInput): Programmable inputs are the
designations for the input alarm terminals, with the exception of
temperature probes. The programmable input designation can be
used for relay input (normally open or normally closed), diode matrix,
clock input, or voltage.
NOTICE: The input terminals used for Temperature are the same physical
terminals used for the Programmable Inputs ("ProgInput"). If the Temperature
input is enabled, then the corresponding programmable input farther down on
the list turns gray and cannot be configured. Similarly, if the Programmable
Input is enabled, then the corresponding Temperature input turns gray and
cannot be configured.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 29
Setting an Input Alarm through the Web Interface
To setup an input alarm through the web interface:
1. Click on the "Alarm Conf." icon in the top menu bar.
2. In the left menu bar, click on "Inputs" and wait for the list to populate.
3. Find the input to set and click on the edit icon (gears). Wait for the edit
window to populate.
3
2
30 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
4
5 6
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 31
6. Press the [X] key to return to the "Inputs" page.
Input alarm is set.
32 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
Figure 26 - Alarm Outputs Page (Compack Controller)
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 33
Setting Output Relays through the Display Panel
To set output relays through the display panel:
1. From the Main Menu, select
"AlarmConfig".
2. Select "Outputs". Wait for the
page to populate, which can take
about a minute to complete.
NOTICE: All available alarm relays
from all controllers and monitors in
the system are listed on this page.
Alarm Setpoints
Since all alarm parameters are set essentially in the same manner, the
following instructions demonstrate how to set Battery Voltage alarm
parameters as an example. As the diagram in Figure 28 illustrates, this section
explains how to setup alarm inputs (Internal Alarm Parameters in this
example), how to assign the parameters to alarm groups, and how to assign
alarm groups to output relays.
34 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
Alarm Inputs ELTEK CONTROLLER Alarm Output Relays
1
Alarm Group 1
Temperature Probes 2
Alarm Group 2
Programmable Alarm Inputs
Virtual Inputs
3 Output
Alarm Group 3
Internal Alarm Parameters 4
5
Alarm Group X
6
Please note that the screenshots are taken from the Compack controller; the
process is identical for Smartpack2 and Smartpack S controllers.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 35
1
2 4
6
7
7. In the current edit window, click the Save icon and then close the edit
window.
8. Select "Outputs" in the left menu bar. Wait for the window to populate,
which can take about a minute to complete.
NOTICE: At the top of the window is a drop-down box called "Select Unit". Use
this to select the control unit to which the alarms are connected. This is
particularly important for the Smartpack2 Master controller, since the unit
itself only has an audible buzzer to assign to the alarm groups. For the
Smartpack2 controller, I/O Monitors are required for external alarm input and
output; the appropriate I/O Monitor must be selected in the drop-down menu in
order to modify alarm relay assignments.
36 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
8
9. Locate the line of the alarm group assigned to the alarm event ("Alarm
Group 06" in this example; see Figure 31).
10. Click in the field under "Alarm Group" and type in a distinctive name for
this alarm group. In this example, the name is changed to
"BatteryLowMajor" (line 6 in Figure 31).
11. Next, select the output relay that the alarm should trigger. In this
example, "Alarm output1" is selected because it is the default for all
major alarms. Note, too, that there are only three output alarm relays
for the Compack controller.
9, 10, 11
12
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 37
12. Click the "Save" icon (diskette symbol in the lower right corner) to save
changes.
13. Return to the Battery Voltage edit window by clicking on "Battery" in the
left menu bar.
14. Locate "BatteryVoltage" (line #1) and click on the "Edit" icon (gear
symbol).
15. After the window populates, click on the "Alarm Group" box in the "Major
Low" event line.
16. Find and select "BatteryLowMajor".
17. Click the "Save" icon (diskette symbol in the lower right corner) to save
changes.
15, 16
38 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
6. Use either the UP or DOWN arrow key to place a check mark in the box.
7. Press the [ENTER] key to save the change.
8. At the bottom of the page is where alarm thresholds are set. For
Battery Voltage there are four events: Major High, Minor High, Minor
Low, and Major Low. Each event has an "Alarm Level" setting (voltage
setting) and "Alarm Group" setting (for output relay assignment). Use
the [ENTER] key to select an event parameter to change. Use the UP
and DOWN arrow keys to adjust the settings.
9. Note the "Alarm Group" assignments for each event. Use the [ENTER]
key to select an alarm group to change. Use the UP and DOWN arrow
keys to see the alarm groups available.
The output relay assignment of the alarm group and the alarm group
name can be changed on the "Outputs" page. In this example, the
"MajorLowAlarmGroup" parameter is set to "Very Low V-BD2" (very low
voltage, battery discharge).
10. Press the [X] key twice to return to the Alarm Configuration menu.
11. Select "Outputs". Wait for the page to populate, which can take about
a minute to complete.
NOTICE: All available alarm relays from all controllers and monitors in the
system are listed on this page.
12. Locate the line of the alarm group assigned to the alarm event ("Very
Low V-BD2" in this example) and press the [ENTER] key to select the
alarm group.
13. Use the RIGHT and LEFT arrow keys to point to the output relay that
the alarm group should trigger. Use the UP and DOWN arrow keys to
place a check mark in the box. Press [ENTER] to save the change.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 39
More than one relay can be selected. Alarm output relay 2 is selected in
the example. Note that there are six output alarm relays for the
Smartpack2 controller (using the I/O Monitor2 device).
14. Return to the Battery Voltage
page. To do this, press the [X]
key once, then select "Battery",
and then select
"BatteryVoltage".
15. Find "MajorLowAlarmGroup" and
confirm that the alarm group is
still "Very Low V-BD2". If not,
then press the [ENTER] key and
use the UP or DOWN arrow key
to find "Very Low V-BD2". Press
Figure 34 - Setting Battery Voltage
[ENTER] to save the change.
Battery Voltage is now set. Use the same process for other parameters as
needed.
40 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
9. Alarm Relay Test
The alarm relays can be tested manually through both the web interface and
display.
CAUTION: Testing alarm relays causes alarm conditions. Make sure
monitoring equipment and personnel are aware of such testing and will not
be adversely affected. It is not recommended to test alarm relays from an off-site
location!
CAUTION: Some controller units list low-voltage disconnect (LVD)
contactors. Activating these contactors will open them and disconnect
any batteries or loads connected!
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 41
WARNING: These will
open any LVDs!
42 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
10. Setting Site Information (web only)
NOTICE: Site information can be set through the web interface only, not through
the display. However, site information is readable through the display at the
following path:
Main Menu > Logs/Reports > Inventory Report
In the web interface, site information is set on the System Info page, where details
about the site and the power system installation are entered. Entering a field value
is optional, but it is highly recommended for future identification, maintenance and
traceability.
2
Section 1
3
Section 2
Section 3
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 43
The following fields are available (refer to Figure 37):
Section 1:
o Company – Name of the company that owns the power system
o Site – Name and/or ID of the site
o Model – Power system model (refer to documentation provided
with the system)
o Serial Number – System serial number or other identification
number
o Install Date – Installation date (year, month, day)
Section 2:
o Service Date – Date of latest service (year, month, day)
o Responsible – Person or company that serviced the power system
o Message lines (1 and 2) – Free-form fields for any messages related
to services performed on the power system (results, unresolved
issues, etc.)
Section 3:
o Latitude – Latitude of the site (degrees, hours, minutes, hemisphere
[north or south])
o Longitude – Longitude of the site (degrees, hours, minutes,
direction [east or west])
o Elevation – Site elevation (in meters)
44 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
11. Setting SNMP Communication (web only)
NOTICE: This feature is only available through the web interface, not through the
display. Simple Network Management Protocol (SNMP) settings through the web
interface are available from software revision 2.2 and later. Screenshots in this
section are from the Smartpack2 controller.
Eltek controllers use SNMP v3. They also support SNMP v1 and SNMP v2c.
This section describes the setup required to establish the Eltek controller as an
object on an existing network communicating via SNMP. Any other details
regarding the network, Network Management System (NMS), or SNMP configuration
for the installation site must be obtained from local systems administration (IT) and
associated documentation. The SNMP version, network settings, security
protocols, community strings, etc. should be provided by the local IT group.
For details on using various SNMP applications with Eltek controllers, please see
document #2155710 - How to SNMP with Eltek Controllers.
To access the SNMP Settings pages:
1. Click on the "System Conf." icon in the top menu bar.
2. In the left menu bar, click on "Device Settings" to expand the menu.
3. Under Device Settings, click on "SNMP Settings". The "General SNMP
Configuration" page appears.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 45
General SNMP Configuration
o Inhibit Traps – This feature is used in conjunction with the "Block Outputs"
command, which is intended for use during system service to prevent false
alarms from being transmitted. Enabling the "Inhibit Traps" field when
"Block Outputs On" is enabled prevents traps from being sent on the
network.
NOTICE: The "Block Outputs" command times out if there is no user
activity. This command is only available through the display panel menu.
Main Menu > Commands > Block Outputs On
o Send Off Traps – Enabling this field sends a trap when an event or alarm
returns to normal status (in other words, when the alarm or notice turns
"off").
o Trap Repeat Rate (minutes) – Interval in minutes of how frequently a trap
message should be sent when an event or alarm is in active status. Enter
the number zero ("0") to disable.
o Heartbeat Trap Repeat Rate (minutes) – Interval in minutes of how
frequently a heartbeat trap (signal) should be sent. Enter the number zero
("0") to disable.
46 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
Figure 39 - SNMP Settings Configuration Page, Default
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 47
Figure 40 - SNMP Settings Configuration Page, Web-Based Configuration Selected
48 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
The following sections outline the pages for web-based configuration. See
Table 1 for a summary of the configuration order for SNMP v3 and v1/v2c.
Table 1 - Web-Based Configuration Order
The Authentication Protocol and Privacy Protocol fields only apply to SNMP v3.
User accounts set up for SNMP v2c and v1 show "noAuth" for Authentication and
"noPriv" for Privacy, since these protocols are not supported in those versions.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 49
SNMP v3 Authentication Protocols: MD5, SHA1
SNMP v3 Privacy Protocols: DES, AES
A passphrase field is provided for both Authentication and Privacy Protocols.
Security Groups for SNMP v3 are "admin-group", "readwrite-group", and "readonly-
group". Groups "snmpv2c-group", "snmpv12c", and "snmpv1-group" are for legacy
support of the older versions of SNMP.
SNMP v3 user accounts can be edited; only the Authentication and Privacy
protocols and passphrases can be changed.
SNMP v2c and v1 accounts can only be viewed, not edited (Figure 43).
SNMP v3 SNMP v1/v2c
User accounts can be deleted by clicking on the "Delete" button (see Figure 42).
To create a new user account, click the "New" button, located under the "Edit"
column of the first unassigned row (Figure 42). The maximum number of accounts
that can be assigned is 10.
50 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
When creating a new user, select the SNMP Security Model, and then click the
"Continue…" button.
NOTICE: The SNMP Security Model cannot be changed after the "Continue…"
button is clicked.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 51
V1/V2 Community Page
This page is where to enter community strings for SNMP v1 and v2c
"authentication". New and existing community names/strings are modified on this
page. As the page name implies, this configuration page is for SNMP v1 and v2c
only.
The "Community Name" field can be edited by pressing the "Edit" button on the far
right of an existing row.
To create a new community string profile, click the "New" button, located under the
"Edit" column of the first unassigned row. The maximum number of community
strings that can be assigned is 10.
NOTICE: The "User Name" field requires v1 or v2c user accounts set up under the
"USM Users" page.
52 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
Traps Page
The traps page is for setting up the IP addresses of devices that are to receive
traps sent by the Eltek controller. By default several rows are set up as examples
for each SNMP version with IP address 127.0.0.1 (localhost). All rows can be
deleted and/or edited.
Press the "Edit Row" button to customize the IP address of the destination device
that receives the traps.
"Trap Community" comes from the "Community Name" strings set under "V1/V2
Community". Community strings must be configured for SNMP v1 and/or v2c
before traps can be setup.
"USM User name" comes from "USM Users" and only applies to SNMP v3 (since v3
has no "trap community").
This difference (Trap Community vs. USM User Name) is reflected in the
configuration windows.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 53
SNMP v3 SNMP v1/v2c
54 Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013
SNMP Implementation
To configure the controller for the Network Management System (NMS):
1. Compile the Eltek MIB files in the NMS database.
2. Add the Eltek controller object to the management map.
3. Ping the controller to verify connectivity.
4. Define and configure trap handling and SNMP users (especially for SNMP
v3).
The Management Information Base (MIB) files for Eltek controllers are available
only from Eltek. Please contact Eltek Technical Support at 1-800-435-4872 or
[email protected] for the latest MIB files.
Configuration Guide Eltek Smartpack and Compack Controllers ~Doc. No. 370013.063, Issue 1, September 2013 55
Doc. No. 370013.063, Issue 1
Published 6-Sep-13
www.eltek.com
US Office: International:
Eltek, Inc. Eltek AS
2925 E Plano Pkwy, Plano, TX 75074, USA Gråterudv. 8, Pb 2340 Strømsø, 3003 Drammen, Norway
Phone: +1 (469) 330-9100 Fax: +1 (469) 330-9101 Phone: +47 32 20 32 00 Fax: +47 32 20 32 10