This document provides guidance on surge protection device (SPD) installation based on location and equipment. It notes that each facility is unique and adjustments may be needed. Key recommendations include:
- Install Type 1 SPDs at service entrances rated for 20kA I-n and bearing the UL mark.
- For areas inside a building, use Type 1 or 2 SPDs. Outdoor areas or equipment may require higher Category B or C SPDs.
- Consider effects of ground potential rises from direct lightning strikes when protecting outdoor equipment.
- Ensure SPDs have appropriate short circuit current ratings for available fault currents.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
119 views1 page
SPD Applications
This document provides guidance on surge protection device (SPD) installation based on location and equipment. It notes that each facility is unique and adjustments may be needed. Key recommendations include:
- Install Type 1 SPDs at service entrances rated for 20kA I-n and bearing the UL mark.
- For areas inside a building, use Type 1 or 2 SPDs. Outdoor areas or equipment may require higher Category B or C SPDs.
- Consider effects of ground potential rises from direct lightning strikes when protecting outdoor equipment.
- Ensure SPDs have appropriate short circuit current ratings for available fault currents.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1
Images depicted herein are for demonstration purposes. Each facility is different, and user needs may vary.
Adjust accordingly, based on equipment value and/or downtime expenses.
IEEE: Category C - Service Entrance Line side requires
Type 1 Exposure Type 1 SPD per SPD NEC 285 & UL 1449 Relevant SPD Standards (1000V and Less):
IEEE C62.41.2-2002 Category C
NEC 285 & NRTL: SPD Type 1, 2, or equivalent Type 4 Line Side ANSI/UL 1449 - Surge Protective Devices Service Entrance UL 1283 – EMI/RFI Filtering N&G Bonded (i.e., L-N and L-G are Gen Set ANSI/IEEE C62.41.1-2002 – Guide on Surge same) Load Side UL 96A Lightning Environment Protection System ANSI/IEEE C62.41.2-2002 – Characterization Higher available fault currents require Type 1 or 2 SPDs at Service of Surges appropriate SCCR ratings SPD Entrances require ANSI/IEEE C62.45-2002 - Testing ATS / STS 20kA I-n and UL Mark IEEE C62.62-2010 - Testing Historical kA ratings: Per Phase: 400kA to 200kA per phase Surge Current kA ratings for IEEE C62.72-2007 – Application Guide Type 1 or 2 Per Mode: 200kA to 100kA per mode all Categories are subjective. SPD Consult SPD mfg for specific (Per Phase generally considered Sum recommendations Load side of the Switch of L-N plus L-G) protects Service and Gen Set
IEEE: Category B - External remnant Distribution Distribution
or Internally Induced IEEE C62.41.2-2002 Category B
NEC 285 & NRTL: SPD Type 1, 2, or Indoor Type 1 or
Type 1 or Type 1 or 2 equivalent Type 4 HVAC 2 SPD 2 SPD SPD (VFD) MCC L-N and L-G are different – need L-N, Indoor L-G, and N-G Equipment installed outside of the building could increase exposure Outdoor Type 1 or Require appropriate SCCR ratings level to Category C. Consider 2 SPD effects of Ground Potential Rises Historical kA Ratings: from direct lightning strikes to earth Busway Per Phase: 300kA to 100kA per phase Per Mode: 150kA to 50kA per mode Outdoor Type 1 or Type 1 or 2 (Per Phase generally considered Sum Wind or PV Type 1 or Outdoor Type 1 or Type 1 or HVAC 2 SPD SPD of L-N plus L-G) Generation 2 SPD Lighting 2 SPD 2 SPD (VFD) Protect both ends of the bus way against reflections
Establishes a new reference to ground, like a
service entrance. L-N only may be sufficient IEEE: Category A, maybe B, maybe C if outdoor loads are connected Branch Branch Type 3 Separately Derived System NEC 285 & NRTL: SPD Type 1, 2, or SPD IEEE C62.41.2-2002 Category A
equivalent Type 4. Could be Type3.
Indoor Type 1 or Type 1 or L-N and L-G are different – need L-N, “Pre” Lighting 2 SPD Small or Office 2 SPD L-G, and N-G SPD Equipment Branch (Type 1) Require appropriate SCCR ratings UPS Type 1 or Historical kA Ratings; Indoor Branch (or PDU, PDM) 2 SPD Per Phase: 160kA to 100kA per phase Per Mode: 80kA to 50kA per mode “Post” Outdoor Type 1 or SPD (Per Phase generally considered Sum 2 SPD of L-N plus L-G) Equipment Type 1 or Type 1 or Outdoor Outdoor Type 1 2 SPD 2 SPD Lighting Equipment or 2 SPD Computers or Servers Series Equipment installed outside of the building could increase Equipment SPD exposure level to Category C. Consider effects of Ground Potential Rises from direct lightning strikes to earth Revision Date: April 14, 2014 Series or two-port SPDs may disconnect downstream loads at end of life