Sizing A Generator
Sizing A Generator
Entered
Item Data Required Calculation Subtotal kW
Value
Power Requirement - Electrical
Critical load- sizing calculator (Calculator total in VA x
value from APC website
Rating of each IT device 187500 0.8)/1000 #1 150.00 kW
For equipment not listed in the Subtotal VA (include fire,
sizing calculator, critical load - security and monitoring 75000 (Subtotal VA x 0.8)/1000 #2 60.00 kW
nameplate systems)
Size of generator needed Total from #12 and #13 above #12 + #13 1,742.05 kW
Data Center or network room heat output calculation worksheet
Entered Heat output Heat Output
Item Data required
Value calculation Subtotal
Same as total IT
Total IT Load
IT Equipment Power in Watts
575000 load power in 575,000.00 Watts
watts
Floor area in
2.0 x floor area (sq
square feet, or
Lighting Floor area in
4844 ft), or 21.53 x floor 9,688.00 Watts
area (sq m)
square meters
Max # of
100 x Max # of
People personnel in data 10
personnel 1,000.00 Watts
center
Subtotals from Sum of heat output
Total above subtotals 698,888.00 Watts
1 TON of cooling = 12,000 BTU/hr 2,384,605.86 BTU/hr
1 kW = 3,412 BTU/hr or 1W = 3.412 BTU/hr 199.68 Tons
1 BTU/hr = 0.293 Watts
1 TON of cooling = 3.5 kW
Orange fields =
Green Fields=entry
calculated