Air System Sizing Summary For Zone-3

This document summarizes the air system sizing for Zone-3 of the 2.Gourmet Palace project in Lahore, Pakistan. The system serves 4 zones totaling 4911 square feet. It is designed to meet the peak sensible loads of each zone from January to December. The central cooling coil is sized at 18.5 tons to handle a total cooling load of 222.1 MBH occurring in August. The outdoor air ventilation requirement for the system is calculated to be 640 CFM.

Uploaded by

harish
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
79 views4 pages

Air System Sizing Summary For Zone-3

This document summarizes the air system sizing for Zone-3 of the 2.Gourmet Palace project in Lahore, Pakistan. The system serves 4 zones totaling 4911 square feet. It is designed to meet the peak sensible loads of each zone from January to December. The central cooling coil is sized at 18.5 tons to handle a total cooling load of 222.1 MBH occurring in August. The outdoor air ventilation requirement for the system is calculated to be 640 CFM.

Uploaded by

harish
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 4

Air System Sizing Summary for Zone-3

Project Name: 2.Gourmet Palace Complete 06.03.2019 03/18/2019


Prepared by: Home 12:13PM

Air System Information


Air System Name .............................................. Zone-3 Number of zones ............................................................. 4
Equipment Class ............................................ CW AHU Floor Area ............................................................... 4911.0 ft²
Air System Type ..................................................... VAV Location ................................................ Lahore, Pakistan

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ..................... Peak zone sensible load
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 18.5 Tons Load occurs at ................................................... Aug 1500
Total coil load ........................................................ 222.1 MBH OA DB / WB .................................................... 110.0 / 75.0 °F
Sensible coil load ................................................. 193.9 MBH Entering DB / WB ............................................. 79.1 / 62.8 °F
Coil CFM at Aug 1500 ........................................... 6797 CFM Leaving DB / WB .............................................. 52.5 / 51.0 °F
Max block CFM at Oct 1500 ................................. 7908 CFM Coil ADP ..................................................................... 49.5 °F
Sum of peak zone CFM ........................................ 8508 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio ............................................... 0.873 Resulting RH ................................................................. 43 %
ft²/Ton ................................................................... 265.4 Design supply temp. ................................................... 55.0 °F
BTU/(hr-ft²) ............................................................. 45.2 Zone T-stat Check .................................................... 4 of 4 OK
Water flow @ 10.0 °F rise .................................... 44.44 gpm Max zone temperature deviation .................................. 0.0 °F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM at Oct 1500 ................................ 7908 CFM Fan motor BHP ........................................................... 4.33 BHP
Standard CFM ....................................................... 7846 CFM Fan motor kW ............................................................. 3.44 kW
Actual max CFM/ft² ................................................ 1.61 CFM/ft² Fan static .................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 640 CFM CFM/person ................................................................ 9.41 CFM/person
CFM/ft² ................................................................... 0.13 CFM/ft²

Hourly Analysis Program v4.90 Page 1 of 4


Ventilation Sizing Summary for Zone-3
Project Name: 2.Gourmet Palace Complete 06.03.2019 03/18/2019
Prepared by: Home 12:13PM

1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ..................................................................... 640 CFM

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft²) Occupants (CFM) (CFM/person) (CFM/ft²) (CFM) (% of supply) (CFM)
Zone 1
GF-12-Z3-Grand Solan 1 1175.0 32.0 3090.1 5.00 0.00 50.0 0.0 210.0
Zone 2
GF-13-Z3-Dinning 1 1135.0 20.0 1641.8 7.50 0.00 0.0 0.0 150.0
Zone 3
GF-09-Z3-Lobby 1 1798.0 12.0 2476.1 5.00 0.00 0.0 0.0 60.0
Zone 4
GF-10-Z3-Main Door 1 803.0 4.0 1129.6 5.00 0.00 200.0 0.0 220.0
Totals (incl. Space Multipliers) 8337.5 640.0

Hourly Analysis Program v4.90 Page 2 of 4


Air System Sizing Summary for Zone-8
Project Name: 2.Gourmet Palace Complete 06.03.2019 03/18/2019
Prepared by: Home 12:13PM

Air System Information


Air System Name .............................................. Zone-8 Number of zones ............................................................. 5
Equipment Class ............................................ CW AHU Floor Area ............................................................... 3481.0 ft²
Air System Type ..................................................... VAV Location ................................................ Lahore, Pakistan

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ..................... Peak zone sensible load
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 16.7 Tons Load occurs at ................................................... Aug 1500
Total coil load ........................................................ 200.0 MBH OA DB / WB .................................................... 110.0 / 75.0 °F
Sensible coil load ................................................. 182.5 MBH Entering DB / WB ............................................. 79.9 / 62.5 °F
Coil CFM at Aug 1500 ........................................... 6225 CFM Leaving DB / WB .............................................. 52.5 / 50.9 °F
Max block CFM at Aug 1600 ................................. 7216 CFM Coil ADP ..................................................................... 49.5 °F
Sum of peak zone CFM ........................................ 7624 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio ............................................... 0.912 Resulting RH ................................................................. 41 %
ft²/Ton ................................................................... 208.8 Design supply temp. ................................................... 55.0 °F
BTU/(hr-ft²) ............................................................. 57.5 Zone T-stat Check .................................................... 5 of 5 OK
Water flow @ 10.0 °F rise .................................... 40.03 gpm Max zone temperature deviation .................................. 0.0 °F

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM at Aug 1600 ............................... 7216 CFM Fan motor BHP ........................................................... 3.95 BHP
Standard CFM ....................................................... 7160 CFM Fan motor kW ............................................................. 3.14 kW
Actual max CFM/ft² ................................................ 2.07 CFM/ft² Fan static .................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 815 CFM CFM/person .............................................................. 35.43 CFM/person
CFM/ft² ................................................................... 0.23 CFM/ft²

Hourly Analysis Program v4.90 Page 3 of 4


Ventilation Sizing Summary for Zone-8
Project Name: 2.Gourmet Palace Complete 06.03.2019 03/18/2019
Prepared by: Home 12:13PM

1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ..................................................................... 815 CFM

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft²) Occupants (CFM) (CFM/person) (CFM/ft²) (CFM) (% of supply) (CFM)
Zone 1
1F-47-Z8-lounge 1 585.0 6.0 1069.1 5.00 0.00 0.0 0.0 30.0
Zone 2
1F-48-Z8-lobby 1 317.0 2.0 599.2 5.00 0.00 0.0 0.0 10.0
Zone 3
1F-49-Z8-kitchen 1 301.0 4.0 1056.0 5.00 0.00 500.0 0.0 520.0
Zone 4
1F-51-Z8-Main Entrance 1 803.0 4.0 2429.1 5.00 0.00 200.0 0.0 220.0
Zone 5
1F-46-Z8-Lobbe 1 1475.0 7.0 2318.5 5.00 0.00 0.0 0.0 35.0
Totals (incl. Space Multipliers) 7471.8 815.0