Air System Sizing Summary For Zone-3
Air System Sizing Summary For Zone-3
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ..................... Peak zone sensible load
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads
Total coil load .......................................................... 18.5 Tons Load occurs at ................................................... Aug 1500
Total coil load ........................................................ 222.1 MBH OA DB / WB .................................................... 110.0 / 75.0 °F
Sensible coil load ................................................. 193.9 MBH Entering DB / WB ............................................. 79.1 / 62.8 °F
Coil CFM at Aug 1500 ........................................... 6797 CFM Leaving DB / WB .............................................. 52.5 / 51.0 °F
Max block CFM at Oct 1500 ................................. 7908 CFM Coil ADP ..................................................................... 49.5 °F
Sum of peak zone CFM ........................................ 8508 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio ............................................... 0.873 Resulting RH ................................................................. 43 %
ft²/Ton ................................................................... 265.4 Design supply temp. ................................................... 55.0 °F
BTU/(hr-ft²) ............................................................. 45.2 Zone T-stat Check .................................................... 4 of 4 OK
Water flow @ 10.0 °F rise .................................... 44.44 gpm Max zone temperature deviation .................................. 0.0 °F
Actual max CFM at Oct 1500 ................................ 7908 CFM Fan motor BHP ........................................................... 4.33 BHP
Standard CFM ....................................................... 7846 CFM Fan motor kW ............................................................. 3.44 kW
Actual max CFM/ft² ................................................ 1.61 CFM/ft² Fan static .................................................................... 2.00 in wg
1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ..................................................................... 640 CFM
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ..................... Peak zone sensible load
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads
Total coil load .......................................................... 16.7 Tons Load occurs at ................................................... Aug 1500
Total coil load ........................................................ 200.0 MBH OA DB / WB .................................................... 110.0 / 75.0 °F
Sensible coil load ................................................. 182.5 MBH Entering DB / WB ............................................. 79.9 / 62.5 °F
Coil CFM at Aug 1500 ........................................... 6225 CFM Leaving DB / WB .............................................. 52.5 / 50.9 °F
Max block CFM at Aug 1600 ................................. 7216 CFM Coil ADP ..................................................................... 49.5 °F
Sum of peak zone CFM ........................................ 7624 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio ............................................... 0.912 Resulting RH ................................................................. 41 %
ft²/Ton ................................................................... 208.8 Design supply temp. ................................................... 55.0 °F
BTU/(hr-ft²) ............................................................. 57.5 Zone T-stat Check .................................................... 5 of 5 OK
Water flow @ 10.0 °F rise .................................... 40.03 gpm Max zone temperature deviation .................................. 0.0 °F
Actual max CFM at Aug 1600 ............................... 7216 CFM Fan motor BHP ........................................................... 3.95 BHP
Standard CFM ....................................................... 7160 CFM Fan motor kW ............................................................. 3.14 kW
Actual max CFM/ft² ................................................ 2.07 CFM/ft² Fan static .................................................................... 2.00 in wg
1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ..................................................................... 815 CFM