Wood Pole Maintenance: Volume 4 - 6
Wood Pole Maintenance: Volume 4 - 6
Wood Pole Maintenance: Volume 4 - 6
Volume 4 - 6
AUGUST 1992
CONTENTS
Section Page
I. Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
II. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.1. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.2. Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
III. Decay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
5.1. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
VII. Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.1. Forms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
A-1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
A-2. Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
A-4. Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
A-5. Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
i (FIST 4- 6)
CONTENTS - Continued
Section Page
Wood Poles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
LIST OF FIGURES
Figure Page
2. Internal decay In a Douglas fir pole that was in service about 11 years . . . . . . . . . . . . . . . 3
4. Cedar shavings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
LIST OF TABLES
Table Page
1. Pole circumference SF (safety factors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
(FIST 4- 6) ii
I. PURPOSE maintenance are notadequately staffed to
accomplish a full-scale inspection and
The purpose of this volume is to identify destruc treatment program for wood pole lines, the
tive forces that affect wooden transmission struc following two-stage program may be more
tures and to present constructive methods for appropriate for Reclamation use:
eliminating or successfully combating these
forces. This volume also outlines a preventive 2.3.1. Stage 1- Spot check and evalua-
maintenance program based on periodic tests tion.-
and treatment of wood poles to discover and
treat decay and thus prolong the service life of a. Spot check.-Reclamation personnel
structures. should spot check approximately 10
percent of the structures (or one
II. INTRODUCTION structure per mile) in a given line
section in accordance with the
2.1. GENERAL. Asystematic program of inspection procedures outlined in
pole inspection and maintenance is essential section IV and the treatment methods
for the following reasons: discussed in section VI and appendix
A. All poles in each spot-checked
a. Safety to life and property.-Poles structure should be checked and
should be maintained above definite evaluated.
minimum strength requirements.
1 (FIST4-6)
2.4. RECLAMATION WOOD POLE critical groundline zone of poles is most subject
UNES. Many Reclamation wood pole to such deterioration because moisture
lines were constructed in the late 1940's conditions near and below groundline are most
and early 1950's. During this period, favorable to growth of wood-destroying
most pole suppliers changed from the organisms.
use of creosote to pentachlo-rophenol as
a preservative, and adequate quality Most wood-destroying organisms are simple
control measures had not been plants, called fungi. They obtain all their food
established to ensure optimum from the wood they live in. Uke other plants,
preservative treatment. Also, during that fungi develop from spores (seeds) which
period, poles were in short supply, and germinate, establish extensive root-like systems
many species of timber were used for within the wood, and eventually produce
poles. In some instances poles of microscopic size spores by the millions. Sound
western red cedar, Douglas fir, wood may become infected by spores, or by
Iodgepole or southern pine, and western direct contact with infected material, including
larch were used in a given line section. contaminated test equipment.
Throughout this bulletin, two species,
western red cedar and Douglas fir, are During the progress of decay, wood first loses its
discussed. For our purposes, pine and luster (looks "dead"), then, as change in color
larch poles should be considered in the becomes progressively more pronounced, the
same category as Douglas fir unless wood loses its characteristic structure and
otherwise indicated. strength, until only a soft whitish or easily
crumbled brown mass remains. Usually the
2.5 DESTRUCTIVE FORCES. One of decayed wood is wetter than adjacent sound
the most destructive forces affecting wood. In cedar poles, internal decay usually
wooden transmission structures is decay. appears as brown pockets of advanced decay
It will generally progress at a predictable with little surrounding areas of partially decayed
rate and its advance can be readily wood (fig.1). In Douglas fir, on the other hand,
diagnosed in the field at all but the very pockets of advanced decay may be surrounded
early stages. by large areas of wood in various stages of decay
(fig. 2). In some fir poles, most of the cross
Also, the damage caused by termites, section may contain decay in the earlier stages
beetles, ants, and woodpeckers can be but with advanced decay limited to a small area.
significant and should receive attention Most frequently, insects such as termites and
in proportion to the influence of these carpenter ants are also present in the decayed
pests upon the poles in a given area. zone.
Early detection of decay or damage and 3.1.2. External decay.-In any species of timber,
treatment of it is by far the most external decay results from using a poor
important and successful step in preservative or from a Iow absorption of the
extending pole life. preservative by the timer. In older poles, external
decay is a consequence of gradual loss of most
III. DECAY of the preservative in the sapwood through
leaching, evaporation, and chemical change. In
3.1. TYPES OF DECAY.- butt-treated cedar poles, a softening of the
sapwood known as "shell rot' occurs in the upper
3.1.1. Internal decay.-Internal untreated portion of the pole. Such decay starts
deterioration of treated poles is due very in the inner sapwood where air and moisture
largely to development of checks after conditions promote fungus growth, and
treatment that expose the untreated eventually extends to the outer sapwood.
center portion of the pole to fungi and
insects. Although internal decay may 3.1.3. Groundline decay.-In most cases, the first
occur above ground as a result of checks occurrence of decay will be just below the
or holes drilled after treatment, the groundline. This is where the conditions of
(FIST 4- 6) 2
3 (FIST 4- 6)
(FIST4-6) 4
Frequency in years
Fir and
Cedar larch
5 (FIST 4- 6)
(FIST 4 - 6) 6
NOTE: It is suggested that Vapam or a Poles are severely decayed and should
penta solution be injected into the bored be replaced immediately (a) if any
holes even if no sign of decay is quarter has 2 inches or less of good
detected. Decay may also be found wood and the decay as shown in figure 7
between the groundline and the top of a is more than 10 percent of the bored
pole. Spot checks should also be made cross section or (b) if at least three
at the bottom of cracks terminating quarters have 3 inches or less of good
above ground. If decay is found, a wood. Mark poles like the one in figure 7
complete inspection should be pro with a band of red paint or similar
grammed. identification.
NOTE: To determine the decayed area
4.4. SERVICEABlLITY OF POLES. From the in figure 7, multiply the maximum
boring results, determine the amount of sound distance across the decay pocket by the
wood left. Figure 6 shows a typical pocket of minimum distance across it.
decay. Figures 7, 8, and 9 show varying degrees Poles with advanced decay pockets (fig.
of decay. 8) should be programmed for routine
replacement, if all quarters have less
NOTE: When boring at a 45E angle, the thickness than 5 inches but more than 3 inches of
of good wood is approximately two-thirds of the good wood. Mark poles like the one in
bit length (fig. 6). figure 8 with a band of red paint or
similar identification and replace the
poles within 3 years.
7 (FIST4-6)
4.5.POLE-TOPINSPECTIONS.-
(FIST4-6) 8
that would affect structure integrity. Take ence. If the decay is limited to a portion of the
sonic readings in lines with the largest pole not exceeding 6 inches in width and 5
cracks and follow up with a bore test if inches in depth, it shall be classified as an
decay is suspected. "External Pocket," otherwise, external decay
shall be classified as "General External Decay."
4.6. CROSSARM INSPECTION AND
TREATMENT. Inspect crossarms during 5.3. PERMISSIBLE REDUCED
structure inspections or when conditions CIRCUMFERENCE SAFETY FACTORS.
warrant a special inspection. Make periodic Wood pole transmission lines are designed
inspections of spar arms and X-braces. using a pole strength safety factor of 4 (SF
Inspect the crossarm thoroughly from each 4), and the groundline circumference of a
pole in case of a multiple structure. Check pole is used as a measure of pole strength.
crossarms for any damage caused by Table 1 shows the relationship between
lightning, woodpeckers, etc. Inspect for reduced circumferences (caused by general
checks, splits, or decay pockets, particularly external decay) and reduced safety factors.
at holes bored through the arm. Circumference reductions to compensate for
other categories of decay, tables 2, 3, and 4,
Note checks across the top of the crossarm should be applied to the circumferences in
which may hold moisture. Bore the crossarm table 1 to determine the resultant reduced
from below to drain the moisture. Keep bore circumference and the corresponding pole
holes at least I foot apart. Use increment safety factor.
borer or brace and bit to inspect for decay.
If the reduced circumference indicates a pole
NOTE: Because of the scarcity and high cost safety factor less than that specified
of quality wood spar arms, the Mid-Pacific following table 1, the pole should be replaced
region has been replacing deteriorated spar or stubbed immediately. Poles meeting or
arms with I-beams of a high-strength, exceeding the specified safety factors should
corrosive-re-sistant steel (Cor-Ten). be treated as specified in section 6.1.1 or
appendix A, and scheduled for reinspection
V. DETERMINING THE SERVICEABILITY OF as outlined in section 4.3.1.
DECAYED POLES.
The tables should be used in accordance
5.1. GENERAL. The decision to treat or with the following instructions:
replace a decayed pole shall depend upon
the remaining strength or serviceability of the 5.3.1. General external decay. - After
pole. The permissible reduced circumference cutting away all decayed wood,
of a pole is a good measure of serviceability; measure the circumference above or
it may be determined by using the following below the decayed section to determine
discussion and tables. the original (SF 4) circumference. Then
measure around the pole where the
5.2. DECAY CLASSIFICATION. Decay at decay was removed; this
the groundline shall be classified as: measurementis the reduced
circumference. Check the original and
(1) General external decay, reduced circumference. Check the
original and reduced circumferences
(2) External pocket, against table 1.
9 (FIST 4- 6)
Original
circumference Reduced circumference
(inches) (inches)
SF4 SF3.5 SF 3 SF2.65 SF2.5 SF2 SF1.5
30.0 28.7 27.3 26.1 25.6 23.8 21.6
31.0 29.7 28.2 27.0 26.5 24.6 22.3
32.0 30.6 29.1 27.9 27.4 25.4 23.0
33.0 31.6 30.0 28.8 28.2 26.2 23.8
34.0 32.5 30.9 29.6 29.1 27.0 24.5
35.0 33.5 31.8 30.5 29.9 27.8 25.2
36.0 34.4 32.7 31.4 30.8 28.6 25.9
37.0 35.4 33.6 32.3 31.6 29.4 26.6
38.0 36.3 34.5 33.1 32.5 30.2 27.4
39.0 37.3 35.4 34.0 33.3 31.0 28.1
40.0 38.3 36.3 34.9 34.2 31.8 28.8
41.0 39.2 37.3 35.7 35.1 32.5 29.5
42.0 40.2 38.2 36.6 35.9 33.3 30.2
43.0 41.1 39.1 37.5 36.8 34.1 31.0
44.0 42.1 40.0 38.4 37.6 34.9 31.7
45.0 43.0 40.9 39.2 38.5 35.7 32.4
46.0 44.0 41.8 40.1 39.3 36.5 33.1
47.0 45.0 42.7 41.0 40.2 37.3 33.8
48.0 45.9 43.6 41.8 41.0 38.1 34.6
49.0 46.9 44.5 42.7 41.9 38.9 35.3
50.0 47.8 45.4 43.6 42.7 39.7 36.0
51.0 48.8 46.3 44.5 43.6 40.5 38.7
52.0 49.7 47.2 45.3 44.5 41.3 37.4
53.0 50.7 48.2 46.2 45.3 42.1 38.2
54.0 51.6 49.1 47.1 48.2 42.9 38.9
55.0 52.6 50.0 47.9 47.0 43.7 39.6
56.0 53.6 50.9 46.8 47.9 44.4 40.3
57.0 54.5 51.8 49.7 48.7 45.2 41.0
58.0 55.5 52.7 50.6 49.6 46.0 41.8
59.0 56.4 53.6 51.4 50.4 46.8 42.5
60.0 57.4 54.5 52.3 51.3 47.6 43.2
No H-structure shall have SF less than 2.65 and no pole shall have SF less than 2.
For H-structures, add the SF's for each pole and divide by 2 to obtain the structure SE For tension-type
reduction is determined, subtract it from the pocketseparately and add them to get the total
(FIST 4 - 6) 10
11 (FIST 4- 6)
measure the original (SF 4) (2) Whenever a pole over 5 years old
circumference of the pole; then refer to is reset.
table 3 to obtain the circumference.
Check the original end reduced (3) Whenever a used pole is installed
circumferences against table 1. as a replacement.
To determine the shell thickness, bore Various products and methods are now pro
four holes (preferably 5/16- or 3/8-inch moted for the groundline treatment of stand
diameter), 90O apart; measure the shell ing poles. Some solutions are available for
thickness at each hole, add, end divide pouring on the outer surface of the pole for
by 4. No transmission pole shall remain groundline treatment, but the use of a pre
in service with a shell thickness less servative paste or grease is recommended.
then 3 inches. Accepted pastes or greases containing toxic
fungi-killing agents, including a high
5.3.4. Enclosed pocket. - An enclosed concentration of sodium fluoride or
pocket is en off center void as shown in pentachloraphenol are:
table 4, and its diameter should be
measured by boring holes as described a. Pento-creto paste (heavy-duty type),
in section 5.3.3. Using the minimum manufactured by Androc Chemical
thickness of the shell, refer to table 4 for Co., Minneapolis, Minn.
the reduction in circumference. After
calculating the reduced circumference, b. Osmoplastic, menufactured by Os-
check the original end reduced mose Wood Preserving Co. of
circumferences against table 1. American, Inc., Buffalo, N.Y.
(FIST 4 - 6) 12
staples or masking tape to hold the wrapping in should be closely supervised; because to be
place. Backfill and tamp well. effective, the penetration and absorption of
the preservative must be the maximum pos
Groundline treatments should be given during the sible. The recommended preservative is a
summer months. Help is then more readily 10 percent solution of penta in a light petro
available; the preservative need not be heated; leum carrier, or equivalent. The pole
digging is easier, and the pole is drier. surface should be dry, with the pole
moisture content below 30 percent as
This bulletin emphasizes the desirability of determined using a moisture meter.
inspection and groundline treatment before
decay is well advanced into the pole at A Reclamation employee should first spot
groundline. When groundline decay is discovered check the poles from the ground and mark
too late, the pole must be stubbed or replaced. poles that are deemed suitable for the treat
Stubbing can frequently be done at one-third to ment, excluding those defective for any rea
one-half the cost of replacement, particularly son. The contractor should make a second
when replacement would require considerable inspection of the marked poles by climbing
transfer work. Of course, the upper portion of any them and excluding any poles in which top
pole to be stubbed must be sound and in decay is too far advanced.
generally good condition. When stubbing is
decided upon, figure 10 should be used as a In addition to determining that the right
guide. The strength of a stub must equal the poles are treated, a Reclamation employee
strength required for a new pole. should verify the amounts of preservative
used, see that critical points are carefully
6.1.2. Above-ground treatment. - The above- treated, obtain samples of the preservative
ground portion of a pole is not subjected to the for analysis, and generally observe that all
same conditions that promote decay at details of the treatment are carried out as
groundline. Nevertheless, decay above ground agreed. Detailed records should be made
(often referred to as "shell rot") will, in time, and retained in permanent files.
develop in ail poles. In recent years there has
been increased use of spray, flow-on, or brush The treatment is usually applied through a
treatments to the upper portion of poles, flexible hose under 5 to 8 pounds per
especially butt-treated cedar transmission poles. square inch (lbs/in2) of pressure from a tank
truck. Treatment starts at the top of the pole
The treatment should be applied before surface with the preservative flowing thoroughly to
decay starts or while it is in the early stages. It is ail surfaces. Immediately after the first
applied only once in the life of a pole. Such treatment, a second application of
treatments may be considered in the following preservative should be applied to the top 10
cases: feet of the pole to assure maximum
absorption in the upper section and at
(1) In butt-treated cedar transmission attachment points.
poles 15 to 20 years old.
Safety precautions must be carefully ob
(2) In butt-treated or full-length-treated served, especially when applying this treat
poles of other species, but mainly on ment to poles supporting energized electric
transmission lines in which poles are ex lines. Caution should also be used to avoid
pensive to replace and where such poles damage to freshly treated poles by grass
are protected from groundline decay by fires.
repeated groundline treatment.
13 (FIST 4- 6)
(FIST 4-6)
14
6.2. OTHER MAINTENANCE.- able nozzle, can be used to inject the creosote
into two or three holes bored to connect with the
6.2.1. Woodpecker damage. - Wood galleries. Occasionally, ground-dwelling termites
pecker damage is another problem requiring are found in poles otherwise sound, and they
attention in some localities. Many ideas may be destroyed in the same manner.
have been tried to outwit these birds, but
nothing has been entirely successful. Two 6.2.3. Fire damage. - Fire damage can
points are worth keeping in mind: make poles useless. Extreme care should
be used in burning rubbish or brush along
(1) There has been a tendency to exag rights-of-way where treated poles are spot
gerate the damage done by woodpeck ted. After poles are set in the ground, the
ers. The ordinary breaking point is near immediate area should be cleared of weeds.
the ground. Above the midsection, where Freshly treated poles can often be easily
most woodpecker attacks occur, tests ignited; after a few months in service,
have shown that 25 percent of the wood treated poles become more fire resistant.
can be removed without serious loss of Where hot grass fires occur annually, and
strength. With consideration to wind particularly if butt-treated poles are used in
loading, woodpecker holes are less such areas, the grass around poles should
damaging on either face than on the side be eliminated in the spring with commercial
of the pole. weedkillers. Fire-retardant coatings are
available for application to poles. Aluminum
(2) Woodpecker holes often expose un sheets tacked around pole bases have also
treated wood to moisture and the spores proved effective, and are particularly suit
of fungi, with resulting decay that weak able on farmed land. When a chemical
ens the pole far more than the holes weedkiller is to be used, a soil-sterilant,
themselves. water-soluble type that will keep weeds
down for a 3-year period is recommended.
It appears that a woodpecker selects a pole (See FIST Volume 4 - 8, Herbicides
only by chance, and that the first hole Available for Treating Soil for Total Vegeta
invites further attack by other woodpeckers. tion Control.)
Appendix C contains a method of repairing
woodpecker damage to wood poles. VII. REPORTING
6.2.2. Termite and ant damage. 7.1. FORMS. Various forms have been
Termite and ant damage can be a developed for recordkeeping concerning pole
problem in many areas. Ground-dwelling inspection and maintenance. Some utilities
termites can be controlled by the same maintain a record for each pole on a form
measures taken to prevent decay-good that provides spaces for keeping track of
preservative treatment. Black and brown inspections and their results. A sample ADP
carpenter ants can be a serious problem, form developed by BPA (Bonneville Power
especially in cedar or injury and Administration) is displayed in figure 11 with
construct galleries that seriously weaken instructions in figure 12. This particular form
the pole near the groundline. Unlike could be acquired from BPA or a similar form
termites, they do not feed upon the could be developed if a computerized record
wood. They may be effectively destroyed of wood pole inspection and maintenance is
by injecting about I pint of creosote into desired.
the inter-connected galleries. An
ordinary grease gun, fitted with a suit
15 (FIST 4 - 6)
(FIST 4-6)
16
17 (FIST 4-6)
APPENDIX A
inches).
A-4. PROCEDURE.-
19 (FIST4-6)
(6) Carry the bottles of Vapam in sturdy readily manifest its presence so that necessary
cartons in pickup-type vehicles external to corrective actions can be taken readily and
the passenger compartment. safely. To protect workmen who may be
unusually sensitive to Vapam, each crew should
A-5. SAFETY.-Vapam is a rather safe material have a chemical respirator at hand when using
since its external and internal toxicity can be Vapam. As any other active chemical, Vapam
considered low; and it would be nearly impossible should be used consciously and with respect.
to accidentally take in or expose oneself to a
hazardous dosage. However, Vapam's irritating Poles near residences or other locations where
quality, which is similar to that of tear gas, makes children or the public may come in contact with
the use of goggles mandatory and the use of the treated pole shall not be treated with Vapam
rubber gloves highly desirable. On the other or any other toxic material.
hand, however, the foul odor of this material will
(FIST 4 - 6) 20
APPENDIX B
"POL-NU'
Active ingredients: Pentachlorphenol 9.16% *
Other chlorinated phenols 1.07 *
Aromatic petroleum derivative solvents 81.34
inert ingredients: 8.43
100.00%
“TIMPREG"
Active ingredients: Pentachlorophenol 9.21% *
Other chlorinated penols 1.07 *
Creosote 15.00
Sodium Fluoride 15.00
Aromatic petroleum derivative solvents 51.30
Inert ingredients: 8.42
100.00%
"OSMOPLASTIC B"
Active ingredients: Sodium borate 15.0%
Pentachlorophenol 10.0
Creosote 15.0
Inert ingredients: (carrier plus thickener) 60.0
100.0%
21 (FIST 4- 6)
Osmose Wood Preserving Company, Inc. (Cont.)
“OSMOPLASTICF"
Active ingredients: Sodium fluoride 20.0%
Pentachlorophenol 10.0
Creosote 15.0
Inert ingredients: (carrier plus thickener) 55.0
100.0%
Wood Treating Chemicals
Division of Koppers Co., Inc.
5137 S.W. Avenue
St. Louis, MO 63110
(314)772-2200
"POLE-LIFE"
Active ingredients: Sodium fluoride 15.0%
Pentachlorophenol 10.0
Creosote 15.0
Inert ingredients: (carrier plus thickener) 60.0
100.0%
(FIST4-6) 22
APPENDIX C
23 (FIST 4- 6)
C.6.DISTRIBUTORS.-PR-861WoodPatch/Semkits
SEMCO
Glendale CA 91209
Seattle WA 98134
Elmhurst IL 60126
Atlanta GA 30345
Gloucester City NJ
(FIST 4 - 6) 24