Controlling Positive Displacement Pumps
Controlling Positive Displacement Pumps
80
it is closed. Leakage past the piston is neg-
ligible. Diaphragm operated PD pumps have
60 Po no cylinder to leak past. Rotating PD pumps,
such as gear pumps or progressing cavity
40 pumps have internal clearances which permit
E
CURV a small reverse flow, called "slip" or "blowby".
TEM
SYS There is another reason why the curve may
20
rotate to slightly lower flows at higher
Qo discharge pressures: The driver may slow
20 40 60 80 100 120 down as the load increases. None of these
PERCENT RATED FLOW have a significant affect in curving the slope of
the characteristic enough that this slope can
Fig. 2-2. Pump Characteristic and System Curve
be used for control. For most practical
purposes the slope is vertical. The system
curve of the process is also shown on Figure 2-2. Its intersection with the pump characteristic
defines the operating point.
DISCHARGE THROTTLING. Discharge throttling does not work! Looking at the process from the
point of view of the pump, discharge throttling rotates the system curve counter clockwise so that
the modified system curve intersects the pump
curve higher up. The additional pressure is 100
dropped through the valve so that the pressure
EM
PERCENT RATED PRESSURE
and flow to the process is (almost) exactly the
ST
DELTA P
80
SY
VALVE
same as before. The "almost" is due the small
D
MO
increase in internal leakage that results in an
60
equally small reduction in flow. An increased
wear rate and a shortening of the life of the
machine are the only results of this approach. If 40
the pump is seen from the point of view of the
process so that the valve is considered part of 20
MOD PUMP
the pump, the same result is obtained. To obtain
CHANGE
a modified pump characteristic curve, the pump IN FLOW
MOD
80
counter clockwise around its intersection with
PUM
S
SY
40
MO
D exactly what is happening. Note that I have not
used the same operating points in Figure 2-3 as
20 I did in Figure 2-5. It is simply impossible to
show any significant reduction in flow on a curve
RECYCLE FLOW
representing the effects of discharge throttling.
20 40 60 80 100 120
PERCENT RATED FLOW
Recycle control is an efficient method of control
Fig. 2-5. Modified Curves: Recycle Control for PD pumps. Since the flow rate is essentially
constant, the power requirement is roughly
proportional to discharge pressure. Since the effect of recycle is to drop the discharge pressure, it
results in significant reductions in power requirement. Nevertheless there is still wasted power in
proportion to discharge pressure times recycle flow.
Recycle valves experience rather severe service if the pressure drop is high. Cavitation will destroy
them if they are not appropriately selected. Two approaches exist to deal with this problem: The
first solution is to drop the pressure in many small stages through the use of many twists and turns
in the valve trim. The second is to tolerate the resulting cavitation by shooting the liquid as a jet
through a small hole in the middle of a disk. The jet then blasts directly into the discharge piping.
The line diameter is often increased immediately downstream of the valve and the wall thickness is
also increased. In this way the jet cavitates down the middle of the pipe. It makes a terrific racket.
In either case it may be necessary to put a fixed restriction downstream of the valve. It should be
sized so that the ratio of the high to intermediate pressure is the same as the ratio of intermediate to
low pressure. Keep in mind that the restriction will reduce the rangeability of the valve by making it
act like a quick opening valve. This is because the restriction becomes the dominant factor in the
line once the valve is about half way open. From that point on, the valve has little control.
Recycle lines for PD pumps should be run back to the suction vessel. This allows any entrained
bubbles to escape. If they do not, they can build up to the point where pump capacity is impaired.
It may even vapour lock.
SPEED CONTROL. Speed control is an obvious method of controlling the flow rate of PD pumps
since flow is essentially proportional to speed. Pressure can also be controlled by sliding up and
down the system curve. Any point on the system curve can, in theory, be reached. Most drivers,
Variable speed electric motors are somewhat modified versions of normal motors. They require
special provision for cooling and lubrication SPEED ---->
100
at low speed. In addition, they require
100%
20%
40%
60%
80%
specialized electronic power supplies called
OTHER MEANS OF CONTROL. The great variety of types of PD pumps results in a variety of
specialized means of flow control. A pneumatic actuator may be used to vary the geometry of the
crank arrangement of a reciprocating pump so that each cycle displaces a greater or lesser amount
of cylinder volume. Direct acting diaphragm pumps driven by compressed air or some other gas
can be controlled by regulating the gas supply. There is also a technique known as "lost motion"
whereby the crank arrangement first compresses a spring or volume pocket before it begins to work
on the piston or diaphragm. These specialized methods are usually integral parts of the equipment
and the controls engineer simply connects a pneumatic or milliamp signal to the appropriate input
port. None of these methods changes the essentially constant flow nature of the pump curve. (The
flow is still "constant" but at a different value.)
The efficiency of hydraulic or eddy current couplings is about the same as that of recycle control.
This is because the torque on both sides of the coupling is proportional to ∆P. The power lost in the
coupling will be proportional to torque times the reduction in speed. In other words, all unused
power is being dumped. If the pressure does drop with a reduction in net discharge flow, then there
will be a power savings. A valve is a cheaper way of accomplishing the same thing.
"Stroke Counting" is a method used when fixed amounts of liquid must be injected at specific
intervals such as in batch processes. An electronic device is used to count the number of
revolutions of a PD pump. After a sufficient number has been counted, the pump is shut off. When
this method is used for pH control, the correct number of strokes can be calculated from a titration
curve.
MEASUREMENT. The most common application for PD pumps is in high-pressure service. The
flow rates vary from extremely small to moderately large. Pressure control is very common. Since
the control valve tees off the discharge header, it is not significant where the sensing transmitter is
AVERAGE FLOW
may not be possible if the pump
has a recycle loop that returns,
as it should, to the suction
vessel. In that case remember
X X X X X
TIME that the flow sensor will
Fig. 2-7. Aliasing experience not only high
pressure but also a high level of
pulsation. Turbine meters are easily damaged. I am told that Coriolis flow meters do well in this
service.
Certain classes of reciprocating pumps, known as metering pumps, have a very precise volume of
liquid delivered with each stroke. The RPM of the pump can be used as an accurate flow
measurement. However, individual calibration is required if this accuracy is to be realized. Note
that even small amounts of entrained air or other bubbles can cause serious errors. Metering
pumps are commonly applied for chemical injection. There is a simple way to calibrate them if
PD pumps are not generally used for level control in the process industries. The great variety of
types of PD pumps inevitably provides exceptions to every generalization. The direct acting,
pneumatically powered diaphragm pump is one of these exceptions. It is ideal for sumps
containing sludges. The pump can be controlled by an entirely pneumatic control system thus
eliminating all electrical connections. This has the added advantage of being absolutely safe in
hazardous locations.
It is often advisable to install a high discharge pressure shutdown switch or transmitter in addition to
the relief valve. Good engineering practice dictates that operating controls be provided to avoid
shutdowns or relief valve operation for normal operating situations. If it is possible for the pump dis-
charge to be blocked under normal operating conditions, a pressure control loop must be provided
on the discharge. This consists of a pressure transmitter, a controller and a recycle valve. If there
is already a flow control loop on the discharge, a pressure override controller must be added. A
The suction side of the pump may also require protection. A relief valve is required unless all
suction piping is rated for the full discharge pressure. Liquids, especially water, are quite incom-
pressible. Even the smallest reverse leakage through a check valve can raise the pressure of a
blocked suction sufficiently to rupture the line. This can happen even after the pump has been shut
down! The discharge dampener will contain liquid at full pressure unless it has been relieved. The
line rupture may occur minutes or even days after the pump has been shut down and isolated,
depending on the relative sizes of the discharge and suction dampeners and the leakage rate. (
Been there, seen it, don’t want to see it again! )
A low-pressure shutdown switch or transmitter is required on the suction side of larger pumps. The
NPSHR of reciprocating pumps is further complicated by what is termed the "acceleration head".
(See the previous article in this series, Controlling Centrifugal Pumps1, page 7, for a more
detailed discussion of NPSHR and NPSHA. Note that there is one difference between NPSH for
centrifugal and PD pumps: For a PD pump NPSH is specified in pressure units instead of elevation.
This is because the operation of PD pump is not dependent on liquid density. ) When the piston of
a simplex pump begins its intake stroke, the liquid in the suction line is essentially stationary. The
entire line contents must be accelerated rapidly to its maximum velocity, approximately three times
the average velocity. There are two reasons for this three to one ratio: Firstly, the liquid isn't moving
at all for half the cycle. Secondly, even when it is moving the velocity starts at zero and builds up to
a maximum at mid stroke before reducing to zero again at the end of the stroke. The "suction"
required to draw the liquid into the cylinder reduces the pressure sufficiently that air or vapour
bubbles may develop. When these collapse during the discharge stroke, if not sooner, cavitation
occurs. If the bubbles do not collapse, as in the case of air dissolved in water, serious hammering
can occur in the cylinder. The air may accumulate to the point that the pump becomes vapour
locked. Remember that air can compress into the internal clearances of the cylinder and then
expand again on the intake stroke without ever being forced out of the discharge check valve. The
low suction pressure shutdown device should be accompanied by some sort of pre-alarm.
Acceleration head problems are greatly reduced for multi-cylinder pumps. Suction dampeners also
contribute to making the flow rate more even.
Minor mechanical failure in PD pumps can cause significant vibration and subsequent serious
damage to the entire machine. For this reason it is the rule to include a vibration switch on larger
equipment. This switch need not be the extremely sensitive, multichannel system used on high-
speed machinery. We are not monitoring the gradual deterioration of delicate bearings. What we
are looking for is an abrupt event of considerable magnitude. Even the simplest switch will suffice.
The usual type of switch is termed a "seismic" switch. It works by having a small weight held in
Larger PD pumps may have special lubricating requirements for the cylinders. The oil is supplied
by small reciprocating injectors (miniature PD pumps) drawing from a small reservoir. The reservoir
needs a low-level alarm which should also inhibit startup. A shutdown may not be necessary since
damage from low oil level is not immediate. The reservoir is supplied from a larger lube oil tank
through an integral float valve. The tank requires a low and a high level alarm. These can be
provided by a single transmitter.
Variable speed pumps, especially those driven by engines, may require an overspeed trip. This
should come from a separate sensor from the governor since it may be a governor failure that has
caused the overspeed. A simple method is a small bolt mounted in a hole in the rim of the flywheel
and held in place by a spring. Centrifugal force causes the bolt to project from the rim and trip a
limit switch mounted on the frame.
SAFETY. There are no inherent dangers associated with PD pumps other than extremely high
pressure or leakage of toxic or hazardous materials. Actually diaphragm pumps are especially
suitable for toxic service since they have no rotating or sliding seals. The possibility of leakage or
even rupture and a subsequent fire must be considered whenever flammable materials are being
handled. Fire detection methods similar to those discussed in Controlling Centrifugal Pumps4,
may be necessary.
It is possible that a diaphragm may rupture during service. If the liquid is particularly hazardous, a
double diaphragm may be used. In that case a tap will be provided by the manufacturer to install a
pressure sensor for alarm or shutdown.
A fire safe block valve is needed on the suction whenever flammable liquids are being drawn from a
reservoir with significant capacity5. Its interlocking must be handled slightly differently from that
associated with a centrifugal pump. It is not advisable to slam shut the suction valve even if the
pump is stopped simultaneously. Full vacuum may be induced during the rundown. If this causes
air to be drawn into the piping an extremely hazardous situation is created. It is best to use a time
delay circuit so that the suction valve is not closed until several seconds after the pump has been
tripped.
It may also be desirable to have a fire safe block valve on the discharge. Since most PD pumps are
in high-pressure service, there may be the potential of pressurized fluid forcing its way backward
past the discharge check valve into a fire. Automatic closure should also be interlocked to occur at
least several seconds after the pump has been turned off.
ACCESSORY INSTRUMENTS. Any instrument used to control the process or to provide some
safety or machine protection function should, if possible, have a simple local device to verify its
operation. In the case of PD pumps that means pressure gauges at both the suction and the
discharge. Pressurized pulsation dampeners require pressure gauges to ensure that they are
properly charged. Large reciprocating pumps have oil filled crankcases. A gauge glass (by vendor)
and a thermometer should be provided.
If the machine is equipped with cooling water jackets, there should be a thermometer on the outlet
of every jacket. A single thermometer on the supply is a good idea. High outlet temperatures may
not mean the pump is overheating!
The variety of PD pumps implies a variety of special requirements. Be sure to discuss these with
the pump vendor to make certain that nothing "obvious" has been overlooked.
PARALLEL PUMP INSTALLATIONS. PD pumps are quite suitable for parallel operation. Since
the discharge pressure of each pump rises as necessary, all pumps will discharge into the common
header. A common recycle valve is sufficient for flow or pressure control.
Starting up a pump that is discharging into a header that is already pressurized by other pumps
may overload its driver. To prevent this it is necessary to have an individual recycle valve on each
pump. This may be a slow acting ball valve. Starting the pump then becomes a simple timed
sequence in which the valve is first opened, then the pump is started, and finally the valve is slowly
closed again. The pump should also be shut down in the same sequence. Remember that the ball
valve will be opening against the full discharge head and may need a large actuator. In water
service it is extremely important that the appropriate water resistant grease is used.
If variable speed pumps are used, the majority should be placed on fixed speed. One pump is then
selected for process control to take the swings in demand.
SERIES PUMP INSTALLATIONS. PD pumps are not generally installed in series. Since series
pumps must both discharge an identical flow and both are discharging a "constant" flow, it is
extremely unlikely that the two can be matched without complex controls. It is common, however,
to have one or more parallel centrifugal pumps servings as boosters to one or more parallel PD
pumps. The centrifugal pumps serve to provide the NPSH that the PD pumps require. The PD
pumps in turn can provide a very high discharge pressure.
The centrifugal boosters should have sufficient flow capacity to supply the pulsating requirements to
the PD pumps. This means the full peak flow, not the average. If they need controls they should
be on pressure control by way of a recycle valve since there should be no interference in the
suction to the PD pumps.
A warning: It may happen that the PD pump has a very low discharge pressure for some reason --
perhaps the piping has been removed for maintenance. It is then possible for the booster pump to
push liquid through the various check valves and out the discharge without the PD pump being
turned on at all. In fact, the flow may be even greater than if the PD pump were running!
alarm.
- Pressure gauge on the suction. FC FO
the crankcase. PI
A thermal relief valve must be around any isolation valve on the PD pump suction so that internal
leakage does not over-pressure the piping.
REFERENCES