Interruptor Digital Schneider Ihp PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

1

en Discover your IHP


IHP 1C 18 mm: IHP+ 1C 18 mm: 1 A Date
CCT15854 CCT15837 B Seconds ON
C Hours: minutes
OFF
D Day (Day 1 = Monday by default)
E Display of output contact state
2 F "menu": selection of operating mode
A
3 G "-", "+": navigation and parameter setting keys
B H "ok": flashing information validation key
E
C Reset by pressing simultaneously the 4 keys "+", "-",
4 "menu" and "ok", i.e. F , G and H
D
F
H 1 230 V AC power supply, +10%, -15%, 50/60 Hz
G

2 3
2 Programming key connector
5 6 3 LCD screen
4 Transparent cover
5 Output contacts
6 External control input (CCT15837)

Cable Configure
At power up or after performing a Reset (see "Discover" chapter):
bb With the "-" and "+" keys.
bb Choose the language (French, English, etc.).
bb Choose "PROGRAM" to delete or retain the program existing in the product.
bb Set the date, year, month, day and time.
bb Choose the summer/winter time change parameters.

When this phase is completed, the "NO MAINS" message is displayed; you
must programme your IHP.

If you do not agree with the flashing value or word: scroll the display with the
"-" and "+" keys.
To confirm the flashing value or word: confirm with "ok".
100 m max. If you are lost: press "menu" to return to the previous mode without saving the
2 last change.
If you actuate no key during 2 minutes: you are automatically returned to Auto
1 mode without saving.

Zone Summer time Winter time Comments


Note:
The external input operating mode is defined at the EUROPE Last Sunday of Last Sunday of
March at 2 am October at 3 am
level of Chapter 7, "Adapt configuration".
GB/IRL/P Last Sunday of Last Sunday of Great Britain - Portugal
March at 1 am October at 2 am
FIN/GR/TR Last Sunday of Last Sunday of Finland - Greece - Turkey
March at 3 am October at 4 am
CDN First Sunday of April Last Sunday of Canada
at 2 am October at 3 am
FREE RULE According to choice According to choice Choice of month, week, day

4
(Monday, Tuesday, etc.) and time

5
FIX DATE According to choice According to choice Choice of month, date (01, 02, etc.)
and time
NONE - -

Programme your IHP Date / Time


The IHP allows you to programme 3 types of controls: switching (On/Off), Modify the time, date, summer/winter time, day of
pulses (CCT15837) and cycles (CCT15837) the week, time format or date format.
To create an operating period: programme On switching then Off switching.
The "COPY" function allows you to replicate on the other days the switching, pulse Press "menu", and access "TIME/DATE" mode via the
or a cycle currently being created and save memory space (creation of a "block"). "+" key:
Access "PROGRAM" mode by pressing the "menu" key; you then have
5 possibilities: bb Change the time, minutes, and date.
bb "NEW": to build the program and enter it in memory.
bb Choose summer/winter time (see table in the
bb "CHECK": to view the program. "Configure" chapter).

bb "MODIFY": to make changes in the program already in memory. bb Define the first day of the week (e.g. Monday for
If the transition selected to be modified is repeated on other days of the week, the Europe).
product prompts "MODIFY BLOCK"; this function proposes performing modification
of all identical transitions (type and time). bb Modify the date format, "FORM DATE":
vv D / M / Y
bb "DELETE": to delete all or part of the program (the date, time and choice of vv M / D / Y
language are retained). vv Y / M / D.
If the transition selected to be deleted is repeated on other days of the week, the
product prompts "DELETE BLOCK"; this function proposes performing deletion of all bb Modify time format, "FORM TIME":
identical transitions (type and time). vv display on 24h
vv display on 12h.
bb "END": to exit "PROGRAM" mode.
6 7
Manual mode, "MANUAL" Adapt the configuration, "CONFIG"
In this mode you can: Press "menu", and access "CONFIG" mode via the "+" key.
bb Programme periods "PERM ON", "PERM OFF", "OVERRI ON".
bb Program a holiday period, "HOLIDAY" (temporarily cancel On periods by setting the dates and In this "CONFIG" mode you can:
times of start and end of absence). bb View the counter indicating the operating time of the
bb On ref. CCT15837 you can also: "OPERATING HOUR" output and, if you want, perform
vv change, for an adjustable period, the operation (channel On or Off) from the current time, resetting of this counter.
"TIMER"; bb "OPERATING HOUR":
vv use the product in random mode "RANDOM" (to perform presence simulation). vv "SHOW HOUR": counter reading
To perform one of these operations you must: press "menu", and access "MANUAL" mode vv "DELETE": counter resetting.
via the "+" key.
bb "HOLIDAY": possibility of having four different types of operation in this Holiday mode: bb Define the type of external input, "EXT INPUT" (this
vv "ON": output activated choice must correspond to the part cabled on the product)
vv "OFF": output deactivated and its operating mode (CCT15837); there are three possible
vv "RANDOM 1": random operation in a fixed On range choices:
vv "RANDOM 2": On operation in a range for which the start and end are random.

8
vv NOT ACTIVE
After defining the type of operation, enter the start and end of absence dates.
vv BUTTON
bb "TIMER": to define the state and duration of the override.
bb "RANDOM": vv SWITCH
vv "RANDOM 1"
vv "RANDOM 2". When the type has been defined, you must define the
Its operation is identical to the Holiday mode, but with no time limits. operating mode:
vv for the button:
-- OVERRIDE: temporary override control until next switching
-- TIMER: one press initiates a time delay for a given period;
Manual and permanent forced ON/OFF " " this time delay can take place in On mode or Off mode at the
bb Activate temporary ON or temporary OFF (until next switching) by pressing the two " " output level.
keys simultaneously for less than 2 s; the output contact changes state: vv for the switch:
vv the IHP indicates by "MANUAL" the new output contact state. -- Permanent On
vv return to automatic mode by pressing briefly the same two keys for less than 2 s. -- Permanent Off.
For both options, the switch is open in normal operation and
bb Go to permanent ON or permanent OFF by pressing the two " " keys simultaneously its closing results in an On or an Off at output.
for more than 2 s: with each press for more than 2 s, the output contact changes state:
vv the IHP indicates the new output contact state by "PERM". bb Modify the "PIN" code (default code 0000):
vv return to automatic mode by pressing briefly the same two keys for less than 2 s. vv NO PIN
vv WITH PIN.
The IHP also allows external override control by an external switch or push button, cabled If you have forgotten the PIN code, see the 9-digit number

9 10
to the Ext terminal (CCT15837):
permanent On or Off override by external input (switch) takes priority over the product's forced on the side of the product, and enter the 4 digits in ABCD
ON/OFF function. position: xAxBxCxDx
For setting the external input, see "Adapt the configuration". Example: No. 123456789: the PIN code is 2468.

bb Modify the language, "LANGUAGE".

bb Return to the product initialization phase "FACTORY


SETTINGS" ("Configure" chapter 3).
Electronic key (ref. CCT15861) bb Access the product reference "INFO".
bb For easier programming of your IHP you have an electronic key, supplied with the IHP
CCT15837, optional for the IHP CCT15854.

Before inserting your electronic key, place the product in "Auto" mode.
Programme pulses and cycles
Insert your electronic key in its slot 2 , and a specific menu appears:
bb "COPY KEY VTSWI": to copy the program from the key to your IHP. (CCT15837)
bb "COPY TSWI V KEY": to copy the program from the IHP to the key. bb Access "PULSE" mode by pressing the "menu" key,
bb "RUN KEY": to have the IHP operate with the programming stored in the key's memory, "PROGRAM", "ok", "NEW", "ok" access "PULSE" mode with
without program transfer. the "+" key.
bb "CHECK KEY": to read the content of the electronic key, each programming step is then bb Choose "ON" or "OFF" mode.
displayed by pressing the "+" key; a press on "ok" takes you back to the main menu. bb Set the time.

11 12
bb "END": to remove the key. bb Set the pulse length (PULSE LENGTH).
A key programming kit (ref. CCT15860) comprising a PC/Key interface, a cord, a key and a
bb Access "CYCLE" mode by pressing the "menu" key,
programming software allows you to programme your key directly from a PC.
"PROGRAM", "ok", "NEW", "ok" access "CYCLE" mode with
the "+" key.
bb Set the start of cycle time.
bb Set the pulse length (PULSE LENGTH).
Load table bb Set the pause duration (PAUSE).
bb Set the end of cycle time.
S1B8577602-01 (05/2012)

bb Acceptable output contact power:


vv resistive loads:
-- I max. = 16 A - 250 V AC (cos j = 1),
-- I min. = 10 mA - 230 V AC, 100 mA - 12 V AC/DC
vv motors: 1000 W. Characteristics
Type of lighting Max. power per contact bb Power consumption: max. 0.4 W.
bb Memory: 56 switching operations, 84 (CCT15837).
Resistive load 16 A bb Min. time between 2 switching operations: 1 minute.
Cos j = 0.6 4A bb Working temperature: -25°C ... +55°C
230 V incandescent lamp 1000 W (prefer installation in the least hot area of the enclosure).
bb Protection class: II in accordance with EN 60730
230 V halogen lamp 1000 W
(product installed in enclosure).
Fluorescent tube 1000 VA bb Degree of protection: IP20 in accordance with EN 60529.
Parallel compensated fluorescent tube, 3 x 40 W (4,7 µF) - 2 x 58 W (7 µF) - bb Operating precision: y ± 0.5 s/day at 25°C.
Réalisation : SEDOC 04 76 18 04 11

max. 120 W (18 μF) 1 x 100 W (18 µF) bb Power reserve: 10 years (lithium battery).
CFL compact fluorescent lamp, max. 40 W 5 x 7 W - 3 x 11 W - 2 x 15 W - 2 x 20 W - bb Pollution degree: 2.
1 x 23 W bb Device of 1 BSTU type in accordance with
LED up to 2 W 10 W IEC/EN 60730-2-7 or EN 60730-1.
bb Connectors:
LED between 2 W and 8 W 25 W
vv cables, 2 x 0.5 to 2.5 mm²
Compact fluorescent lamp with electronic 22 x 7 W - 18 x 11 W - 16 x 15 W - 16 x 20 W - vv stripping length: 9 mm max.
ballast 14 x 23 W bb Size (9 mm modules): 2 modules.
bb Weight: 90 g.
For other applications, relay with a contactor.

Schneider Electric Industries SAS This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations.
35, rue Joseph Monier As standards, specifications and designs develop from time to time, always ask for confirmation of the information given in this publication.
CS 30323
F-92506 Rueil Malmaison Cedex (France)
tel : +33 (0)1 41 29 70 00

http://www.schneider-electric.com

You might also like