TECHNICAL DATA LEAFLET LIGHT OIL

RIELLO 40 G Series
One Stage Light Oil Burners

G3 23.8 ÷ 35.5 kW
G3R 23.8 ÷ 35.5 kW
G3RK 15.0 ÷ 35.0 kW
G5 28.0 ÷ 60.0 kW
G5R 28.0 ÷ 60.0 kW
G5RK 12.0 ÷ 60.0 kW
G7 29.0 ÷ 69.0 kW
G10 54.0 ÷ 120.0 kW
G20 95.0 ÷ 213.0 kW
G20S 95.0 ÷ 240.0 kW

www.riello.com
One Stage Light Oil Burners Riello 40 G Series

The Riello 40 G series of one stage light oil burners, is a complete range of products developed to respond
to any request for home heating. The Riello 40 G series is available in ten different models, with an output
ranging from 12 to 240 kW, divided into four different structures.
All the models use the same components designed by Riello for the Riello 40 G series. The high quality level
guarantees safe working.
In developing these burners, special attention was paid to reducing noise, to the ease of installation and
adjustment, obtaining the smallest size possible to fit into any sort of boiler available on the market.
All the models are approved by the EN 267 European Standard and conform to European Directives for EMC, Low
Voltage, Machinery and Boiler Efficiency.
All the Riello 40 G burners are fired before leaving the factory.

2
Technical Data

MODEL R40 G3 R40 G3R R40 G3RK


Burner operation mode One stage
Modulation ratio at max. output ===
type ===
Servomotor
run time s ===
kW 23.8 ÷ 35.5 23.8 ÷ 35.5 15 ÷ 35
Heat output Mcal/h 20.4 ÷ 30.5 20.4 ÷ 30.5 12.9 ÷ 30.1
Kg/h 2-3 2-3 1.3 - 3
Working temperature °C min./max. 0/40
FUEL/AIR DATA
kWh/kg 11.8
net calorific value
Light oil kcal/kg 10200
viscosity at 20°C mm2/s (cSt) 4 - 6 (at 20°C)
type R.B.L
Pump
delivery Kg/h 30 (at 12 bar)
Atomised pressure bar 8 - 15
Fuel temperature max. °C 50
Fuel pre-heater NO YES YES
Fan type Centrifugal with forward curve blades
Air temperature max. °C 40
ELECTRICAL DATA
Electrical supply Ph/Hz/V 1/50/230 ± 10%
Auxiliary electrical supply Ph/Hz/V ===
Control box type RBL 530 SE RBL 531 SE RBL 531 SE
Total electrical power kW 0.115 0.165 0.170
Auxiliary electrical power kW ===
Heaters electrical power kW === 0.055
Protection level IP X0D (IP 40)
electrical power kW 0.09
rated current A 0.7
Fan motor
start up current A 2.8
protection level IP 20
electrical power kW ===
rated current A ===
Pump motor
start up current A ===
protection level IP ===
type Incorporated in the control box
Ignition transformer V1 - V2 (==) - 8 Kv
I1 - I2 (==) - 30 mA
Operation Intermittent (at least one stop every 24h)
EMISSIONS
Sound pressure dB (A) 57 57 56
Noise levels
Sound power dB (A) 68 68 67
CO emission mg/kWh 16 11 40
grade of smoke indicator N° Bacharach <1
Light oil
CxHy emission mg/kWh < 10 (after the first 20s)
NOx emission mg/kWh 170 160 160
APPROVAL
Directive 2006/42/EC - 92/42/EC - 2014/30/UE - 2014/35/UE
Conforming to EN 267
Certification === === CE-00360254/99

Reference conditions:
Temperature: 20°C - Pressure: 1013,5 mbar - Altitude: 0 m a.s.l. - Noise measured at a distance of 1 meter.
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and
at maximum rated output. The sound power is measured with the “Free Field” method, as per EN 15036, and
according to an “Accuracy: Category 3” measuring accuracy, as set out in EN ISO 3746.

3
One Stage Light Oil Burners Riello 40 G Series

MODEL R40 G5 R40 G5R R40 G5RK


Burner operation mode One stage
Modulation ratio at max. output ===
type ===
Servomotor
run time s ===
kW 28 ÷ 60 28 ÷ 60 12 ÷ 60
Heat output Mcal/h 24.1 ÷ 51.6 24.1 ÷ 51.6 10.3 ÷ 51.6
Kg/h 2.3 - 5 2.3 - 5 1-5
Working temperature °C min./max. 0/40
FUEL/AIR DATA
kWh/kg 11.8
net calorific value
Light oil kcal/kg 10200
viscosity at 20°C mm2/s (cSt) 4 - 6 (at 20°C) 2 - 6 (at 20°C)
type R.B.L
Pump
delivery Kg/h 30 (at 12 bar)
Atomised pressure bar 8-15
Fuel temperature max. °C 50
Fuel pre-heater NO YES YES
Fan type Centrifugal with forward curve blades
Air temperature max. °C 40
ELECTRICAL DATA
Electrical supply Ph/Hz/V 1/50/230 ± 10%
Auxiliary electrical supply Ph/Hz/V ===
Control box type RBL 530 SE RBL 531 SE RBL 531 SE
Total electrical power kW 0.130 0.185 0.185
Auxiliary electrical power kW ===
Heaters electrical power kW === 0.055 0.055
Protection level IP XOD (IP 40)
electrical power kW 0.09
rated current A 0.75
Fan motor
start up current A 3
protection level IP 20
electrical power kW ===
rated current A ===
Pump motor
start up current A ===
protection level IP ===
type Incorporated in the control box
Ignition transformer V1 - V2 (==) - 8 Kv
I1 - I2 (==) - 30 mA
Operation Intermittent (at least one stop every 24h)
EMISSIONS
Sound pressure dB (A) 59
Noise levels
Sound power dB (A) 70
CO emission mg/kWh 10 10 20
grade of smoke indicator N° Bacharach <1
Light oil
CxHy emission mg/kWh < 10 (after the first 20s)
NOx emission mg/kWh 180 185 175
APPROVAL
Directive 2006/42/EC - 92/42/EC - 2014/30/UE - 2014/35/UE
Conforming to EN 267
Certification === === CE-00360254/99

Reference conditions:
Temperature: 20°C - Pressure: 1013,5 mbar - Altitude: 0 m a.s.l. - Noise measured at a distance of 1 meter.
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and
at maximum rated output. The sound power is measured with the “Free Field” method, as per EN 15036, and
according to an “Accuracy: Category 3” measuring accuracy, as set out in EN ISO 3746.

4
MODEL R40 G7 R40 G10 R40 G20 R40 G20S
Burner operation mode One stage
Modulation ratio at max. output ===
type ===
Servomotor
run time s ===
kW 29 ÷ 69 54 ÷ 120 95 ÷ 213 95 ÷ 240
Heat output Mcal/h 24.9 - 59.3 46.4 - 103.2 81.7 - 183.2 81.7 - 206.4
Kg/h 2.5 - 5.8 4.5 - 10 8 - 18 8.20
Working temperature °C min./max. 0/40
FUEL/AIR DATA
kWh/kg 11.8
net calorific value
Light oil kcal/kg 10200
viscosity at 20°C mm2/s (cSt) 2 - 6 (at 20°C) 4 - 6 (at 20°C)
type R.B.L
Pump
delivery Kg/h 30 (at 12 bar)
Atomised pressure bar 8 - 15
Fuel temperature max. °C 50
Fuel pre-heater NO NO NO NO
Fan type Centrifugal with forward curve blades
Air temperature max. °C 40
ELECTRICAL DATA
Electrical supply Ph/Hz/V 1/50/230 ± 10%
Auxiliary electrical supply Ph/Hz/V ===
Control box type RBL 530 SE
Total electrical power kW 0.160 0.170 0.320 0.330
Auxiliary electrical power kW ===
Heaters electrical power kW ===
Protection level IP XOD (IP 40)
electrical power kW 0.09 0.15
rated current A 0.85 0.8 1.4 1.5
Fan motor
start up current A 3.4 3.2 5.6 6
protection level IP 20
electrical power kW ===
rated current A ===
Pump motor
start up current A ===
protection level IP ===
type Incorporated in the control box
Ignition transformer V1 - V2 (==) - 8 Kv
I1 - I2 (==) - 30 mA
Operation Intermittent (at least one stop every 24h)
EMISSIONS
Sound pressure dB (A) 64 65 74 72
Noise levels
Sound power dB (A) 75 76 85 83
CO emission mg/kWh 15 15 20 20
grade of smoke indicator N° Bacharach <1
Light oil
CxHy emission mg/kWh < 10 (after the first 20s)
NOx emission mg/kWh 180 190 180 190
APPROVAL
Directive 2006/42/EC - 92/42/EC - 2014/30/UE - 2014/35/UE
Conforming to EN 267
Certification === CE-00360257/99 === ===

Reference conditions:
Temperature: 20°C - Pressure: 1013,5 mbar - Altitude: 0 m a.s.l. - Noise measured at a distance of 1 meter.
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and
at maximum rated output. The sound power is measured with the “Free Field” method, as per EN 15036, and
according to an “Accuracy: Category 3” measuring accuracy, as set out in EN ISO 3746.

5
One Stage Light Oil Burners Riello 40 G Series

Firing Rates

RIELLO 40 G3 - G3R - G3RK

Useful working field


for choosing the
burner

Test conditions
conforming to EN267
Temperature: 20°C
hPa (mbar)

Pressure: 1013,5 mbar


Altitude: 0 m a.s.l.

RIELLO 40 G5 - G5R - G5RK


hPa (mbar)

6
RIELLO 40 G7 - G10

Useful working field


for choosing the
burner

Test conditions
conforming to EN267
hPa (mbar)

Temperature: 20°C
Pressure: 1013,5 mbar
Altitude: 0 m a.s.l.

RIELLO 40 G20 - G20S


hPa (mbar)

7
One Stage Light Oil Burners Riello 40 G Series

Fuel Supply

HYDRAULIC CIRCUIT

All the burners have a R.B.L. geared pump


with safety valve on the return circuit.

G3 - G3R - G3K - G5 - G5R - G5RK - G7 - G10 - G20

U
PH Fuel pump
1

2
S Fuel feed to the burner can be from
VR(NO)
the right or the left side on all models.

S Pump with filter and


pressure regulator on the
delivery pipe
VR (NO) Oil return valve on the
G20S delivery pipe
1 Oil input pipe to the nozzle
2 Oil return pipe from the
regulator
3 Oil delivery pipe to the air
damper hydraulic jack
MT Air damper hydraulic jack
U for high pressure working
1 CR PR1 Low pressure oil regulator
PR2 High pressure oil regulator
PR1 R
PR2 R Delayer
CR Delayer casing
2 PH Oil pre-heater with
S
3 thermostat (where
VR(NO)
provided)
U Nozzle

MT

8
Light Oil Pre-Heater

The models “R” have light oil pre-heater which is located next
ot the nozzle, operated by the control box which delays burner
ignition before each start in order to adequately pre-heat the oil.

SELECTING THE FUEL SUPPLY LINES


The fuel feed must be completed with the safety devices required
by the local regulations in force.

The table shows the choice of piping diameter for the various
burners, depending on the difference in the height between the
burner and the tank and the distance between them.
Pre-heater

Maximum equivalent lenght of the pipework L (m)


Type A system Type B system
Pipe size Ø 8 mm Ø 10 mm Ø 8 mm Ø 10 mm
H (m) Lmax (m) Lmax (m) Lmax (m) Lmax (m)
0 35 100 - -
0.5 30 100 10 20
1.0 25 100 20 40
1.5 20 90 40 80
2.0 15 70 60 100
3.0 8 30 - -
3.5 6 20 - -

A
7 5
H
H
P 1 P 1

2 2
10 cm 10 cm
4 4
1

3 5 3

7 2

H H

6
3

9
One Stage Light Oil Burners Riello 40 G Series

SELECTING THE FUEL SUPPLY LINES

H Pump/Foot valve height difference


Ø Inside pipe diameter
B P Difference in height ≤ 4 m
1
1 Burner
2 Pump
P
3 Filter
H
4 Shut-off solenoid valve
2
5 Suction pipework
6 Bottom valve
4 7 return pipework
3

Ventilation
The ventilation circuits always ensure low noise levels with high performance
of pressure and air delivery, inspite of their compact size.

Combustion Head Air suction

The G3 and G3R models all have fixed heads. Certain models allows you to
choose the length of the combustion head.
This choice depends on the thickness of the front wall and type of the boiler.
Depending on the type of generator, you should check the correct penetration
of the head into the combustion chamber.
Simple adjustment to the combustion head allows adapting internal
geometry of the head to the maximum rated output of the burner.

SUGGESTED COMBUSTION CHAMBER DIMENSIONS Combustion head

2
D
Combustion chamber

Combustion chamber

x
L ma 1 L
length (m)

diameter (m)

1 L min
D max
0,5
D min
Example:
0 0
Burner thermal output = 350 kW;
0 100 200 300 400 500
L Combustion Chamber (m) = 1.2 m (medium value);
Burner output (MW) D Combustion Chamber (m) = 0,8 m (medium value)

10
Operation
BURNER OPERATION MODE

All these models are one stage operation; the G20S model is
one stage operation with reduced output firing.

Air damper

One stage operation with


One stage operation reduced output ignition
Checked Variable

°C
Output Checked Variable

°C
bar bar

time time

ON ON ON ON
Output

OFF OFF OFF OFF


time time

11
One Stage Light Oil Burners Riello 40 G Series

START UP CYCLE

Normal Lock-out due to ignition failure (A)


TR
* Pre-heater

M
Ignition
transformer
V

Lock-out led
0 ÷ 120 s ~12 s 0 ÷ 120 s ~12 s ~5 s

time (s) time (s)


* Only model with pre-heater.

(A) Lock-out is shown by a led on the appliance.

CORRECT OPERATION

0s The burner begins the ignition cycle.


0s-12s Pre-purge with the air damper open.
12s Ignition.
* If the pre-heater is fitted (G…R series), there is a further delay before pre-purge; this delay can reach 120s
depending on room and fuel temperatures.

LOCK-OUT DUE TO IGNITION FAILURE

If the flame does not light within the safety limit (~ 5s) the burner locks-out.

ELECTRICAL CONNECTIONS

Electrical connections must be made by qualified and skilled


personnel in conformity with the local regulations in force.

Control box fitted with


an ignition transformer

12
Emissions

The emission data has been measured in the various models at maximum output, according to EN 267 standard.

NO2 EMISSIONS
300

250

200
mg/kWh

150

100

G5RK
G3RK

G20S
50 G5R
G3R

G20
G10
G5
G3

G7
0
CO EMISSIONS
50

40
mg/kWh

30

20

10
G5RK
G3RK

G20S
G5RG5R
G3RG3R

G20G20
G10G10
G5 G5
G3 G3

G7 G7
G5RK
G3RK

0 G20S
NOISE EMISSIONS
100

80
dB(A)

60

40

20
G5RK
G3RK

G20S
G5R
G3R

G20
G10
G5
G3

G7

Special attention has been paid to noise reduction. All models


are fitted with sound-proofing material inside the cover.

13
One Stage Light Oil Burners Riello 40 G Series

Overall Dimensions (mm)

These models are distinguished by their reduced size, in relation to their outputs, which means they can be fitted to any
boiler on the market.

BURNER

MODEL A D E F F2 H I L
G3 252 215 203 86 - 89 164 19
G3R 252 215 203 86 - 89 164 19
G3RK 252 215 203 97 115 89 164 19
G5 272 233 236 107 - 180 - 89 180 37
G5R 272 233 236 107 - 89 180 37
G5RK 272 233 236 94 112 89 180 37
G7 305 262 261 73 - 89 204 40
G10 305 262 261 108 - 250 - 105 204 40
G20 350 298 295 118 - 260 - 125 230 41
G20S 350 298 295 118 - 125 230 41

BURNER - BOILER MOUNTING FLANGE

G3 - G3R - G3RK - G5 - G5R - G5RK - G7 - G10 G20 - G20S

MODEL C1 C2 F Q R S T
G3 - G3R - G3RK - G5 - G5R - G5RK 130 150 180 45° 11 72 75
G7 - G10 140 170 189 45° 11 83 83
G20 - G20S 160 190 213 90° 11 99 99

14
PACKAGING

MODEL X Y Z kg
G3 363 295 310 10
Z
G3R 363 295 310 10
Y G3RK 363 295 310 10,5
X G5 383 315 325 12
G5R 383 315 325 12
G5RK 383 315 325 12
G7 423 348 340 13
G10 423 348 340 13
G20 483 393 377 16
G20S 483 393 377 17,5

15
One Stage Light Oil Burners Riello 40 G Series

Installation Description

Skilled and qualified personnel must perform installation, start up and maintenance. A nozzle is fitted to the burner and
used for fire tests in the factory. If necessary, change the nozzle on the basis of the maximum output of the boiler.
All operations must be carried in accordance with the technical handbook supplied with the burner.

BURNER SETTING

Air damper and head adjustment area are easily accessible and
the operation is simple thanks to a graduated scale and following
the manual instruction.

The pressure regulator is carried out by setting the adjustment


screw.

ELECTRICAL CONNECTIONS AND MAINTENANCE

Electrical wirings are easily thanks to plug and socket connections.


The 7 pin plug is supplied for connection to the boiler.

16
Burner accessories

REMOTE CONTROL RELEASE


KIT FOR 530-531 CONTROL
BOXES The 530-531 control boxes can be remotely released using an electric command
kit.
This kit must be installed in conformity with current regulations in force.

BURNER CODE
All models 3001030

EXTENDED HEAD KIT


Kits of extended heads are available.

STANDARD HEAD EXTENDED HEAD


BURNER CODE
LENGHT (mm) LENGHT (mm)
G5 - G5R 107 121 3000686
G5 - G5R 107 121 inox 3000687
94 - 112
G5 - G5R 107 3000726
(conic head)
G10 108 168 3000643
G10 108 250 3000770
G20 - G20S 118 178 3000644
G20 - G20S 118 260 3000771

SPACER KIT
Using the special accessories, the burner can be pulled back to reduce head
penetration into the combustion chamber.

SPACER THICKNESS
BURNER CODE
S (mm)
G3 - G3R - G3RK - G5 - G5R - G5RK - G7 25 3000642
G10 25 3000672
G20 - G20S 25 3000673

INLET AIR ASPIRATION KIT This kit allows to channel the external air directly into the burner and is available
as accessory for models:

BURNER CODE
G3 - G3R - G3RK 20027471
G5 - G5R - G5RK 20027574
G7 - G10 20027577
G20 - G20S 20027580

17
One Stage Light Oil Burners Riello 40 G Series

LIGHT OIL FILTER

For cleaning light oil from dirty particles and impurities filters with the following
features are available:
FILTERING DEGREE
BURNER CODE
(µm)
All models 60 3006561

Filter made up of aluminium body and stainless steel filtering cartridge;


available singularly.
FILTERING DEGREE
BURNER CODE
(µm)
All models 60 3075011

Filter made up of aluminium cover, plastic tank and nylon filtering cartridge; available
in packaging of 50 pieces.

LIGHT OIL FILTER/DEGASSING UNIT

To solve problems of air or water in the oil circuit a special filter/degassing unit
is available, made up of aluminium cover, plastic tank, stainless steel filtering
cartridge, air release cap and water purge valve. It is available singularly.

FILTERING DEGREE
BURNER CODE
(µm)
All models 100 3000926

7-PIN PLUG KIT


If necessary a 7-pin plug kit is available (in packaging of n. 5 pieces).

BURNER CODE
All models 300945

HOUR COUNTER KIT FOR 530


SE AND 531 SE CONTROL BOXES

To measure the burner working time a hour counter kit is available.

BURNER CODE
All models 3000904

7-POLE SOCKET KIT FOR 530 SE


AND 531 SE CONTROL BOXES
For burner without pre installed socket a 7-pole socket kit with cable is avail-
able.
BURNER CODE
All models 3001065

18
BALANCED FLUE VERSION

The Riello 40 series balanced flue oil burner has been


specifically designed to meet the increasing trend towards
the use of balanced flue, otherwise known as room sealed
appliances, which avoids the necessity of having a chimney
to discharge the products of combustion.
Balanced flue products are completely sealed from the
environment in which they are installed, drawing air for
combustion directly from the outside, thereby ensuring no
unwelcome smells from combustion of the oil.
As a result of the burner components such as motor, oil pump
etc. being completely enclosed this provides an additional
benefit of low sound levels.
The Riello 40 balanced flue range has been designed and
manufactured to meet the latest European and OFTEC test
requirement and are manufactured under quality assurance
standards.
Riello 40 balanced flue version is available for the following
models: G3, G3R, G3RK, G5, G5R, G5RK. Riello 40 balanced flue version

OVERALL DIMENSIONS (mm) G3 - G3R - G3RK G5 - G5R - G5RK

288 205 234

ø75 ø75

271
249
191 191

24 24

BIO FUELS

Riello Burners is able to offer technical variants which allow burners to be used within environmental heating,
process or special applications. These applications now include solutions for liquid Bio fuels (I.e. biodiesel and
vegetable oil).
Our experience in research and development and field applications with organic origin Bio fuels has resulted in
Riello being able to offer a wide range of solutions for the combustion of Bio fuels.

KEROSENE AND ULSD

Riello 40 G series burners can be supplied, on demand, suitable for applications where combustion of Kerosene,
Low Sulphur Kerosene and Ultra Low Sulphur Diesel Oil (ULSD) is the chosen fuel.
These burner variants can be provided upon request and after a technical-commercial evaluation; for more
information please contact Riello Burners Commercial and Technical Department, our Application Engineers will
be pleased to help you.

19
One Stage Light Oil Burners Riello 40 G Series

Specification

DESIGNATION OF SERIES

A specific index guides your choice of burner from the various models available in the RIELLO 40 G series.
Below is a clear and detailed specification description of the product.

G Standard

Size:

Optional variations: R Light oil pre-heater


K Cone shaped head
S Reduced output ignition
D Two stage output operation

Electrical supply to the system: 1/230/50 1/230V/50Hz


1/220/60 1/220V/60Hz

G 5 RK 1/230/50
BASIC
DESIGNATION
EXTENDED DESIGNATION

STATE OF SUPPLY

Completely automatic monobloc light oil burners, one stage operation, made up of:
- Fan with forward curve blades
- Metallic cover lined with sound-proofing material
- Air damper, completely closed in stand by, with adjustment
- Single phase electric motor 230 V, 50 Hz
- Combustion head fitted with:
- stainless steel head cone, resistant to high temperatures
- ignition electrodes
- flame stability disk
- Geared pump for fuel supply, fitted with:
- filter
- pressure regulator
- attachments for fitting a pressure gauge and vacuum meter
- internal by-pass for preparing for single-pipe installations
- Fuel feed solenoid valve incorporated in the pump
- Photocell for flame detection
- Electronic flame control equipment
- Light oil nozzle
- IP X0D (IP 40) protection level
- Fuel pre-heater (optional)
- Reduced output ignition mechanism (optional).

Standard equipment:
- Two flexible pipes for connection to the light oil supply line
- Two nipples for connection to the pump
- Flange, screws and nuts for fixing
- Thermal gasket
- 7-pin plug (on request)
- Maintenance assembly
- Instruction handbook for installation, use and maintenance
- Spare parts catalogue.

20
AVAILABLE BURNER MODELS

TOTAL
HEAT OUTPUT ELECTRICAL
BURNER MODELS POWER CERTIFICATION NOTE
(KW) (Kg/h) (KW)
G3 1/230/50 23,8 - 35,5 2-3 0,115 CE – 0036 0315/01
G3R 1/230/50 23,8 - 35,5 2-3 0,165 CE – 0036 0315/01
G3RK 1/230/50 15 - 35 1,3 - 3 0,170 CE – 0036 0254/99
G5 1/230/50 28 - 60 2,3 - 5 0,130 -
G5 TL 1/230/50 28 - 60 2,3 - 5 0,130 -
G5R 1/230/50 28 - 60 2,3 - 5 0,185 -
G5RK 1/230/50 12 - 60 1-5 0,185 CE – 0036 0256/99
G7 1/230/50 29 - 69 2,5 - 5,8 0,160 - (1)
G10 1/230/50 54 - 120 4,5 - 10 0,170 CE – 0036 0257/99
G10 1/220/60 54 - 120 4,5 - 10 0,200 -
G10 TL 1/220/50 54 - 120 4,5 - 10 0,200 -
G20 1/230/50 95 - 213 8 - 18 0,320 -
G20 1/220/60 95 - 213 8 - 18 0,400 -
G20 TL 1/220/50 95 - 213 8 - 18 0,400 -
G20S 1/230/50 95 - 240 8 - 20 0,330 -
G20S 1/220/60 95 - 240 8 - 20 0,410 -

MODELS WITH 24V DC ELECTRICAL SUPPLY


G7 24V DC 29 - 69 2,45 - 5,8 0,3
G10 24V DC 54 - 120 4,5 - 10 0,3
G20 24V DC 95 - 201 8 - 17 0,3

(1) UK version
Net calorific value: 11,8 kWh/kg - 10200 kcal/kg - Viscosity at 20°C: 4÷6 mm2/s (cSt)
The burners of G series are in according to EN 267.

Bio fuels
Riello Burners is able to offer technical variants which allow burners to be used within environmental heating,
process or special applications. These applications now include solutions for liquid Bio fuels (I.e. biodiesel and
vegetable oil).
Our experience in research and development and field applications with organic origin Bio fuels has resulted in
Riello being able to offer a wide range of solutions for the combustion of Bio fuels.

Kerosene and ULSD


Riello 40 G series burners can be supplied, on demand, suitable for applications where combustion of Kerosene,
Low Sulphur Kerosene and Ultra Low Sulphur Diesel Oil (ULSD) is the chosen fuel.
These burner variants can be provided upon request and after a technical-commercial evaluation; for more
information please contact Riello Burners Commercial and Technical Department, our Application Engineers will
be pleased to help you.

21
One Stage Light Oil Burners Riello 40 G Series

Conforming to:
- 2014/30/UE directive (electromagnetic compatibility)
- 2014/35/UE directive (low voltage)
- 92/42/EC directive (boiler efficiency)
- 2006/42/EC directive (machine)
- EN 267 (liquid fuel burners)

Available accessories to be ordered separately:


- Remote control release kit for 530-531 control boxes
- Extended head kit
- Spacer kit
- Inlet air aspiration kit
- Light oil filter
- Light oil filter/degassing unit
- 7-pin plug kit
- Hour counter kit for 530 SE and 531 SEcontrol boxes
- 7 pole socket kit for 530 SE and 531 SEcontrol boxes.

22
NOTES

23
Riello Burners a world of experience in every burner we sell.

05/2016
Across the world, Riello sets the standard in reliable and

TS0024UK04
high efficiency burner technology.
With burner capacity from 5 kW to 48 MW, Riello gas,
oil, dual fuel and Low Nox burners deliver unbeatable
performance across the full range of residential and
commercial heating applications, as well as in industrial
processes.
With headquarter in Legnago, Italy, Riello has been
manufacturing premium quality burners for over 90 year.
The manufacturing plant is equipped with the most
innovative systems of assembling lines and modern
manufacturing cells for a quick and flexible response to
the market.
[1]
Besides, the Riello Combustion Research Centre, located in
Angiari, Italy, represents one of the most modern facility
in Europe and one of the most advanced in the world for
the development of the combustion technology.
Today, the company’s presence on worldwide markets is
distinguished by a well-constructed and efficient sales
network, alongside many important Training Centres
located in various countries to meet its customers’ needs.
Riello has 13 operational branches abroad (in Europe,
America and Asia), with customers in over 60 countries.

[2]

BURNERS PRODUCTION PLANT


[1]
S. PIETRO, LEGNAGO (VERONA) - ITALIA

HEADQUARTER BURNERS DIVISION


[2]
S. PIETRO, LEGNAGO (VERONA) - ITALIA

RIELLO S.p.A. - 37045 Legnago (VR) - Italy


tel. +39 0442 630111 - fax: +39 0442 21980
www.riello.com

Since the Company is constantly engaged in the production improvement, the aesthetic
and dimensional features, the technical data, the equipment and the accessories can be
changed. This document contains confidential and proprietary information of RIELLO S.p.A.
Unless authorised, this information shall not be divulged, nor duplicated in whole or in part.