4/22/2019 Document1
4/22/2019 Document1
4/22/2019 Document1
tenants (“Tenants”). Usage notes highlight a few specific editing choices, however the entire section should be evaluated and
edited to fit specific project needs.
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section describes copper and fiber infrastructure for the communication and data network
system.
1.3 REFERENCES
A. Install equipment and materials in accordance with the applicable standards of the following
organizations:
1. ANSI: American National Standards Institute
2. ANSI/TIA: American National Standards Institute and Telecommunications Industry
Association
a. ANSI/TIA-568-C.1: Commercial Building Telecommunications Cabling Standard
b. ANSI/TIA-568-C.2: Balanced Twisted-Pair Telecommunications Cabling and
Components Standard
c. ANSI/TIA-568-C.3: Optical Fiber Cabling Components
d. ANSI/TIA-607-B: Commercial Building Grounding and Bonding Requirements for
Telecommunications
3. BICSI: Building Industry Consulting Service International
4. EIA: Electronic Industries Alliance
a. EIA-310: Cabinets, Racks, Panels, and Associated Equipment
5. IBC: International Building Code
6. IFC: International Fire Code
7. NEC: National Electrical Code
8. NEMA: National Electrical Manufacturers Association
9. UL: Underwriters Laboratories
B. Shop Drawings: Prepare and submit coordination drawings detailing raceways and system
components and materials in relation to other building systems and components. Drawings shall
include, but not be limited to, the following:
1. Floor plans detailing raceway and cabling installations.
2. Enlarged network and equipment room plans showing room layouts including
coordination drawings detailing all equipment to be installed by other trades within the
enlarged area.
3. Wall-mounted facilities on terminal backboards.
4. Equipment rack and cabinet elevations for all termination locations.
5. Detail drawings shall include clearances for servicing equipment, including space for
equipment disassembly required for periodic maintenance.
6. Cable and equipment labeling schemes and sample labels as coordinated with the Port
and in accordance Section 270553.
7. See the drawings for completed telecommunications, backbone cabling, and horizontal
cable matrix schedules. Complete these schedules upon field verification of installation
locations of patch panels, racks, cabinets, etc., and submit to the Port for approval prior to
commencement of work.
D. Submit certified equipment calibration records performed by the equipment manufacturer stating
that the equipment that will be used in the testing of copper and fiber optic cables installed as part
of the work was calibrated within the past 6 months.
F. Review of product data does not relieve the Contractor from responsibility for deviations from
the drawings or specifications, unless the Contractor has, in writing, called attention to such
deviations at the time of submission and obtained written approval from the Port.
H. Test Reports: The Contractor shall be responsible for recording all test data. Submit copies of
all test results to the Port for review and approval no later than one week after completion of the
testing.
1. Prior to commencement of cable testing, submit a sample test report, with the assigned
cable designation clearly indicated, of each test type to the Port for approval.
2. Submit final test report schedules which confirm that the cabling infrastructure has been
tested, labeled, and documented.
3. Submit the test reports and schedules with the testing software program on CD-ROM or
DVD.
I. Submit operation and maintenance manuals. Content of each manual or chapter shall include,
but not be limited to, the following:
1. Description of system.
2. Manufacturers’ brochures. Include manufacturers’ descriptive literature covering devices
and equipment used in the system, together with illustrations, exploded views, and renewal
parts lists. Edit the manufacturers’ standard brochures so that the information applying to
the actual installed equipment is clearly defined.
A. The work shall be performed by Oregon Limited Energy Journeyman licensed technician(s).
B. The structured cabling system shall be installed by a value-added reseller for the manufacturers
specified and their respective products. Each of the Contractor’s installing technicians shall have
completed the manufacturer’s training for the installation of shielded cabling systems (Atlas-X1
Shielded Installation Training) and be a certified member in good standing of the manufacturer
installer program before, during, and through completion of the system installation.
Edit the warranty language as applicable for HQ/P2 and other Port facilities that are not served by a Berk-Tek/Leviton system.
Tenants: Within article, delete “Port” and replace with name of tenant.
1.6 WARRANTY
B. Passive components and products (cables, connectors, patch panels, and/or other associated
components) shall come from the manufacturers listed above to offer an extended warranty on
the structured cabling system being installed. The Contractor or the Contractor’s installer shall
be certified by Berk-Tek/Leviton or Corning to provide the materials warranty and shall meet all
necessary requirements to make the Port eligible for the extended warranties. Upon completion,
submit a certificate from the sponsoring manufacturer stating that the installed system is covered
by the manufacturer’s extended warranty for the minimum period applicable.
C. The Port shall be named the owner of the warranty and guaranteed full and complete rights under
the warranty.
The brand name exemption for Corning Fiber expires September 20, 2021.
PART 2 - PRODUCTS
2.1 MATERIALS
A. Communications products installed as part of this work shall be listed by a recognized testing
laboratory or approved in writing by the inspection authority as required by governing codes and
ordinances.
B. Materials shall be new and of the best quality. The materials shall be manufactured in accordance
with NEMA, ANSI, UL, or other applicable standards.
C. Equipment and materials of the same general type shall be of the same manufacturer throughout
the work to provide uniform appearance, operation, and maintenance.
D. Cable jacket shall be plenum-rated and marked with the CMP designation where appropriate and
as required by code for installation in plenum-rated areas.
E. The structured cabling system components for the horizontal cabling shall consist entirely of
products from CS6700 CAT6A Shielded System by Berk-Tek/Leviton, no substitutions.
A. Fiber optic cables shall be single-mode, loose tube, riser/plenum rated for the environment of the
installation. Corning FREEDM Cable Series, no substitutions.
1. Singlemode fiber shall be 8.3um/125um.
2. Where installed in cable tray, cable shall be armored.
A. Riser cable shall be copper, 24-gauge, paired dual, semi rigid PVC skin over foamed PE. The
core shall be overlaid with a corrugated aluminum sheath bonded to an outer PVC plastic jacket
to form an alvyn sheath. Cable shall be UL verified to TIA/EIA 568-B for Category 3
performance.
B. Acceptable manufactures are General Cable, Berk-Tek, Superior Essex, CommScope Systimax,
or pre-bid approved equal. Cable designation shall be ARMM series.
A. Telephone cable shall be copper, 24-gauge, paired, dual insulated with foam skin and gel filling
compound. Cable shall be plastic core wrapped, and shall have an aluminum steel polyethylene
(ASP) sheath.
B. Acceptable manufacturers are General Cable, Superior Essex, CommScope SYSTIMAX, or pre-
bid approved equal. Cable designation shall be ANMW series.
A. 3M Scotchlok Bonding Connectors, 3M Part No. Series 4460, or pre-bid approved equal, shall be
used to bond multi-pair copper cable jackets to appropriate ground at building entrance terminal
locations.
A. Five pin, three-element gas, 350v module, black in color. Circa Telecom No. 3B1E, or pre-bid
approved equal.
B. Provide protector modules to fully populate each pair listed on the BET’s protector module panel.
A. For Exterior Cat 6A Data Locations: ITW Linx Model CAT6A-LAN, or pre-bid approved equal.
B. For Exterior Cat 6A Cable POE Data and Voice Locations: ITW Linx Model CAT6A-75, or pre-
bid approved equal.
A. Horizontal cables shall be four-pair, shielded, twisted pair (F-UTP), #23 AWG solid copper
conductors, paired, flame-retardant PVC jacket.
A. Horizontal cables shall be four-pair, shielded, twisted pair (F-UTP), #23 AWG solid copper
conductors, paired, and PVC jacket. Cable shall be rated CMR and CMX Outdoor.
B. Manufacturer: Berk-Tek LANmark-MD751 CAT6A FTP Outdoor cable (Part No. 11098512),
no substitutions.
A. Horizontal cables shall be four-pair, unshielded, twisted pair (UTP), #23 AWG solid copper
conductors, paired, polyethylene insulated.
A. Design patch panels for installation on standard NEMA 19-inch equipment racks.
B. Patch panels shall be certified by the manufacturer to ensure optimal channel performance of the
structured cable system. Leviton Atlas-X1 Angled Shielded QuickPort 24 Port Patch Panel+ (Part
No. 4S256-S24), no substitutions.
C. New 2 or 4 RU FODUs:
1. Rack mountable CCH splice cassette loaded with LC connectors, CCH panel and factory-
terminated pigtails. Corning Cabling Systems, Part Nos. CCH-CS12-A9-P00RE and
CCH-CS24-A9-P00RE, no substitutions.
A. Provide Leviton CAT6A high-flex copper patch cords to connect devices connected to outlets,
biscuit jacks, surge protector, and other field termination devices.
B. Provide one set of modular patch cords for 50 percent of horizontal cables installed. One cord
shall be 10 feet in length and the other cord shall be 7 feet in length (Part No. HF6AU-xxS).
Provide an additional 25 percent quantity of patch cords for each size jumper used for connection
of the remaining devices listed above.
C. Modular patch cords shall be certified by the manufacturer to ensure optimum channel
performance for the structured cabling system. Leviton, no substitutions.
2.18 BACKBOARDS
A. AC grade plywood, 3/4" by 48" by 96", or to size, as indicated on the drawings, mounted
vertically with C side against building structure (unless the FR-S rating stamp is on the C side).
1. Fasten plywood to studs at 16"” to 24" using #12 flat head sheet metal screws (nail guns
and explosive discharge devices shall not be used to secure plywood to studs).
2. Backboards shall be free of surface defects such as knots and cracks.
3. Plywood shall have a FR-S flame spread rating.
4. Paint plywood with two coats of light gray low gloss paint. Leave FR-S rating stamp
unpainted.
2.19 FACEPLATES
A. Faceplates shall have a minimum of four communication ports that may be configured for either
copper or fiber installations on a per-port basis and shall be flush-mount unless otherwise
specified.
2.20 JACKS
A. Shielded jacks shall be purple, Leviton Atlas-X1 CAT6A Shielded QuickPort Connector Part No.
6ASJK-RP6, no substitutions.
B. Unshielded jacks shall be purple, Leviton Atlas-X1 CAT6A UTP QuickPort Connector Part No.
6AUJK-RP6, no substitutions.
C. Wall mount jacks (for wall phones) shall be stainless steel Leviton Recessed Wallplate Part No.
4108W-1SP, no substitutions.
2.21 OUTLETS
A. One Port: Leviton, Part No. 41089-1IP, no substitutions, shall be used at Port-approved locations.
C. DIN Rail Mount: Signamax Keystone Industrial DIN Rail module, with side lids on the end units.
Part Nos. KI-DIN-RMM and KI-DIN-RMM-SL, or pre-bid approved equal.
A. Standard two-post 19-inch equipment racks shall have the following minimum requirements:
1. 45 rack mounting spaces.
2. Adjustable equipment mounting rails drilled and tapped to EIA-310 standards.
3. Clear in color.
A. Provide a copper vertical rack busbar kit for each two-post 19” rack, 5/8”(H) x 1/4”(W) x 72”
(D), CPI 40161-072, or pre-bid approved equal.
A. Two Post Racks with 120vac Power Receptacles: Provide a vertical power strip within each rack,
120 VAC, 20 amp, with 20 NEMA 5-20R receptacles, CPI 12851-705, or pre-bid approved equal.
A. Cable runways shall be clear, Telco-style, classified as equipment grounding, and sized according
to the drawings. Chatsworth, or pre-bid approved equal.
C. Cable runway and manufacturers’ hardware shall be UL-listed as a ground bond pathway.
A. Spiral cable wrap, flame retardant polyethylene (UL94V-0), 0.25 OD, wraps cable bundles from
3/16 inch to 2 inch, color shall be black. Panduit Part No. T25FR-C, or pre-bid approved equal.
PART 3 - EXECUTION
3.1 GENERAL
A. Provide services, labor, material, and components necessary for a complete and finished
installation.
B. Install equipment, patch panels, and termination blocks between 1 foot 6 inches AFF and 6 feet 6
inches AFF on equipment racks or backboards as appropriate.
C. Install firestops and seals at penetrations through building floors, walls, or where required by fire
codes.
E. Inspect cable for sheath defects or other irregularities as it is pulled out. Upon detection of defects,
stop pulling and repair or replace the cable section.
H. Provide rack anchor bolts and attachments, installation of cable runway, and anchoring of
equipment in accordance with the manufacturer’s recommendations. Provide
engineered/stamped seismic calculation where required by code.
I. Provide vertical and horizontal cable management troughs as appropriate for the installation and
as indicated on the drawings.
3.2 GROUNDING
A. Each fastening device and support for communications equipment and racks shall be capable of
supporting not less than four times the ultimate weight of the object or objects fastened to or
suspended from the building structure and shall be installed to resist seismic forces as specified
in the IBC for the ground motion accelerations corresponding to the project location.
B. Powder-actuated or similar shot-in fastening devices will not be permitted for any
communications work except when approved by the Port.
3.4 ALIGNMENT
A. Install racks and equipment level and plumb, parallel with structural building lines.
Communications enclosures shall fit neatly without gaps, openings, or distortion. Properly and
neatly close unused openings with approved devices.
B. Fit outlets with neat, appropriate trims, plates, or covers, without overhanging edges, protruding
corners, or raw edges, to leave a finished appearance.
A. Include cutting, patching, and restoration of finishes. Surfaces damaged by this work shall be
neatly patched and finished to match the adjacent construction, including paint or other finishes.
Clean up and remove dirt and debris.
B. Where equipment installations or connections require the installation of an access panel, provide
a properly sized and installed access panel similar to those used for mechanical equipment access.
A. Protect communications work and equipment installed against damage by other trades, weather
conditions, or any other causes. Equipment found damaged or in other than new condition will
be rejected as defective.
B. Communications equipment shall be kept covered or closed to exclude dust, dirt and splashes of
plaster, cement, or paint, and shall be free of all such contamination on exterior and interior before
acceptance. Enclosures and trims shall be in new condition, free of rust, scratches, and other
finish defects. Properly refinish to new condition if damaged.
Tenant: In this article, delete all instances of “Port” and replace with name of tenant.
A. Install fiber optic cable in inner duct, either existing corrugated or new flexible fabric, when using
underground conduits. Use no inner duct in cable trays if armored fiber cable is used. Stop inner
duct before entering a network room or computer room. Leave 10 feet of maintenance loop at
both ends. Coordinate with the Port for location.
B. For installation of fiber optic cabling in the outside plant raceway system, provide a 15
maintenance loop in every third manhole, vault, or pull box in addition to the maintenance loop
indicated above.
C. Fan-Out of Fiber Optic Cable: Prior to termination, fiber optic cable strands shall be furcated
(fanned out) using the specified buffer tube fan-out kits and using the procedure specified by the
manufacturer.
A. Install cables in cable tray or conduit. Install conduit in accordance with Section 260533.
B. Dress cables neatly in cable trays, and tie down at corners and changes in cable tray elevation
using velcro straps. Install cables in center spine cable tray so that the cable tray is balanced.
C. Verify cable lengths prior to installation. Provide notification of cables exceeding 290 feet, do
not install cables that exceed 290 feet without prior Port approval.
A. Terminate horizontal cables on modular jacks inserted in patch panels, faceplates, or surface
mount boxes.
B. Terminate backbone cables on 110 field termination blocks as specified and as shown on the
drawings. Wrap each binder group with the appropriate color to indicate proper binder group
identity. When installing in center hung cable tray, install on the higher side of the tray to keep
the cable tray balanced.
C. All four pairs of each horizontal cable shall be terminated in T568B pinout standard order on the
jack.
D. Lay out cables on the patch panel as indicated on the cable matrix drawings.
Tenant: In this article, in all instances add the following “and the Tenant” after the “Port” unless otherwise noted.
3.11 TESTING
A. Upon completion, test systems to show that equipment installed operates as designed and
specified. Submit testing plans for review prior to testing. Plan system tests for as many at one
time as possible to work into construction phasing. The Port may witness tests at its option and
if so, schedule tests 48 hours in advance.
B. A written record of performance tests shall be compiled, dated, witnessed, and submitted along
with operating and maintenance data, prior to substantial completion.
C. Test reports shall certify that wiring is complete, passes all test criteria, is fully operational, and
that the work has been completed as specified.
D. Provide all forms, instrumentation and test equipment, loads, and other consumables required.
COPPER LOOP dB dB dB
TEST CABLE
BAD CABLE RESISTANCE LOSS LOSS LOSS
LOCATION COUNT/CABLE
PAIRS CUMULATIVE MEASURED @ @ @
NAME NAME
FOOTAGE IN OHMS 1Khz 1Khz 1Khz