Digsilent Print

The document reports the results of a load flow calculation for an electrical grid model called RED_BASE using PowerFactory software. It shows voltage profiles and power interchange values for the grid at different voltage levels. Key parameters of the load flow calculation are also summarized such as solution method, tolerance settings, and total power losses.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
99 views3 pages

Digsilent Print

The document reports the results of a load flow calculation for an electrical grid model called RED_BASE using PowerFactory software. It shows voltage profiles and power interchange values for the grid at different voltage levels. Key parameters of the load flow calculation are also summarized such as solution method, tolerance settings, and total power losses.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

DIgSILENT Project:

PowerFactory
15.1.7 Date: 4/17/2019

Load Flow Calculation Complete System Report: Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1.00 kVA
Model Equations 0.10 %

Grid: RED_BASE System Stage: RED_BASE Study Case: 2036_Max Annex: / 1


rtd.V Bus - voltage Voltage - Deviation [%]
[kV] [p.u.] [kV] [deg] -10 -5 0 +5 +10
BARRA 10kV
10.00 1.000 10.00 0.00
DIgSILENT Project:
PowerFactory
15.1.7 Date: 4/17/2019

Load Flow Calculation Complete System Report: Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1.00 kVA
Model Equations 0.10 %

Grid: RED_BASE System Stage: RED_BASE Study Case: 2036_Max Annex: / 2


Volt. Generation Motor Load Compen- External Power Total Load Noload
Level Load sation Infeed Interchange Interchange Losses Losses Losses
[kW]/ [kW]/ [kW]/ [kW]/ [kW]/ to [kW]/ [kW]/ [kW]/ [kW]/
[kV] [kvar] [kvar] [kvar] [kvar] [kvar] [kvar] [kvar] [kvar] [kvar]
10.00 0.00 0.00 2606.87 0.00 2641.08 34.22 34.22 0.00
0.00 0.00 1385.72 0.00 1423.05 37.34 40.42 -3.08
Total: 0.00 0.00 2606.87 0.00 2641.08 0.00 34.22 34.22 0.00
0.00 0.00 1385.72 0.00 1423.05 0.00 37.34 40.42 -3.08
DIgSILENT Project:
PowerFactory
15.1.7 Date: 4/17/2019

Load Flow Calculation Complete System Report: Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1.00 kVA
Model Equations 0.10 %

Total System Summary Study Case: 2036_Max Annex: / 3


Generation Motor Load Compen- External Inter Area Total Load Noload
Load sation Infeed Flow Losses Losses Losses
[kW]/ [kW]/ [kW]/ [kW]/ [kW]/ [kW]/ [kW]/ [kW]/ [kW]/
[kvar] [kvar] [kvar] [kvar] [kvar] [kvar] [kvar] [kvar] [kvar]
\FC_Danny\Iquitos 2019\ALIMENTADOR R-02 y R-03\Network Model\Network Data\RED_BASE
0.00 0.00 2606.87 0.00 2641.08 0.00 34.22 34.22 0.00
0.00 0.00 1385.72 0.00 1423.05 0.00 37.34 40.42 -3.08
Total:
0.00 0.00 2606.87 0.00 2641.08 34.22 34.22 0.00
0.00 0.00 1385.72 0.00 1423.05 37.34 40.42 -3.08