Pressure Control Trainer
Pressure Control Trainer
DESCRIPTION
The pressure control trainer is designed for teaching the basic pressure control
principles study in chemical and instrumentation engineering. For ease of
understanding, the product is described with its major components.
Pressure loops vary from very tight, fast loops (almost like flow control) to slow
averaging loops (almost like level control). An example of a fast pressure loop is the
case of a valve throttling the flow of a vapour from a vessel
An air stream entering the tank maintains the pressure of the air at a value P i. It is
desired to maintain (or control) the pressure of the air at P R by means of the
controller. If the measured pressure Pm differs from the desired pressure PR, the
controller senses the difference or error e = PR - Pm, and changes the valve position
in such a way that the desired liquid height P R is obtained in the tank.
PT Pressure Transmitter
I/P Current to Pneumatic Converter
CV Pneumatic Control Valve
V Vent Valve
R Air Pressure Regulator
S Supply Pressure Gauge (I/P)
SP Set Point
PIC Pressure Indicator Controller
BLOCK DIAGRAM
Set Point : The set point is synonym for the desired value of the controlled
variable.
Load : The load refers to a change in any variable that may cause the
controlled variable of the process to change.
In the example, the outlet (vent) valve position is a load variable.
The control system shown in Figure 2 is called a closed loop system or a feed back
system because the measured value of the controlled variable is returned to of “fed
back” to a device called the comparator. In the comparator, the controlled variable is
compared with the desired value or set point. If there is any difference between the
measured variable and the set point, an error is generated; this error enters a
controller, which in turn adjusts the final control element in order to return the
controlled variable to the set point.
Load
Vent Valve Controlled
PID Controller Variable, P
Comparator
Final Control Process
Controller Element (Pressure in
(Control Valve) Tank)
Set Point
PR
Measuring Element
(Pressure Sensor &
Transmitter)
Measured
Variable, Pm
Figure 1 & 2 show that a pressure sensor is used to measure the pressure of air in
the tank; the signal from the pressure sensor is sent to the transducer (pressure
transmitter), which produces an output in the range of 4-20 mA, which is a linear
function of the input. The output of the transducer enters the controller where it is
compared to the set point to produce an error signal. The controller converts the
error to an output in the range of 4-20 mA according to the control law (P, PI, PD,
PID or On-Off) stored in the memory of the controller. The output of the controller
enters the I/P converter, which produces an output in the range of 3-15 psig, which is
a linear function of the input. Finally, the output of the converter is sent to the top of
the control valve, which adjusts the flow of air to the tank. The control valve used
here is linear and is pressure-to-open type. The external power of 230 V AC is
required for controller and I/P converter and 24 V DC for pressure transmitter. A
source of 20-psig airs is needed for the converter.
Valve for To see how the components interact with each other, consider the process to be
Pneumatic
Control operating at steady state with the outlet flow rate through the tank is equal to the set
generating
Valve
disturbance point. If the outlet flow rate from the tank increases, the following events occur.
Immediately the pressure sensor & pressure transmitter detects a decrease in the
pressure of the air in the tank and produces a change in the signal to the controller.
As soon as the controller detects decrease in the pressure, relative to the set point,
the controller output increases according to the control action chosen. The increase
in signal to the converter causes the output from the converter to increase and open
the valve in order to increase the flow of air. The increased flow will eventually
increase the pressure of air in the tank and move it towards the set point. From this
quantitative description, we see that the flow of signals from one component to the
next is such that the pressure of air in the tank should return to the set point. In a
well-tuned control system, the response of the pressure will oscillate around the set
point before coming to steady state.
STARTUP PROCEDURE:
Check that the air pressure regulator supplying air to the control valve (fitted
at the back of the equipment) and pressure regulator supplying air to the I/P
converter (fitted on the front panel) are shut off properly.
Check that the drain valve of the air compressor provided beneath the air
supply valve of the pressure tank of the air compressor and the air supply
valve itself is also shut off.
Switch ON the air compressor motor and allow the air pressure to build up in
the compressor’s pressure tank up to about 7-kg/ cm 2 (g).
Now open the air supply valves provided on the compressor’s pressure tank
and allow the air to reach the pressure regulators.
Slowly open the air pressure regulator provided for the pneumatic control
valve (fitted at the back of the equipment) and set the pressure near to 1.5 kg/
cm2 (g) as indicated by the pressure gauge provided on the pressure regulator
and pneumatic control valve also.
Now open the pressure regulator provided for the I/P converter (fitted on the
front panel) and set the pressure to 1.4 kg/ cm 2 (g) as indicated by the
pressure gauge fitted along with it.
In control panel you can have recorder output ( in the range of 0 – 100 % )
( 4 – 20 mA) to which you can attach recorder of same input type. (i.e. 4 – 20
mA.) The current meters at the top panels indicates E/P Converter input and
Transmitter output in the range of 4 –20 Ma respectively.
Check all the air connections for any sort of leakage and in case any leakage
is observed tighten it immediately to prevent the loss of compressed air.
Open the disturbance valve (needle valve) provided on the pressure tank
slightly/ to the desired degree.
Now switch on the PID controller.
Switch ON the computer and start the software for Pressure Control Trainer
by executing the respective executable file (pressure.exe).
SHUTDOWN PROCEDURE:
First of all shutting down the system after experiment, Shutdown the
programme.
Close the air supply to the E/P Converter /control valve by closing the
regulator provided.
Switch off the air compressor and shut off the discharge valve of it. Drain
the filled air from the cylinder of compressor by opening the drain coke at
the bottom of the compressor. Close the air supply valve to the control
trainer.
Adjust the set point of the PID Controller to a lower value. Switch off the
power supply to the trainer.
Fully open the needle valve (vent valve) provided on the top of the
pressure vessel to remove any air quantity of air from the system.
Switch off the power supply to the trainer.
For proper operation read the instruction provided and then follow it step
by step.
Do not apply very high set point to the PID controller (not above range) as
it may damage it may damage the pressure vessel/transmitter after long
time through the vessel is tested to the high pressure.
Do not apply higher pressure to E/P Converter (Greater than 1.4 Kg/cm 2)
as it may damage it. Also the lesser pressure (less than 1.4 Kg/cm 2) may
not give accurate functioning of it.
Do not change link position of the control panel terminals.
Do not alter the wiring of instrument.
Do not alter or modify the components of the trainer.
Use standard parts provided by D. K. Scientific Industries.
Carefully read the manuals of each component fitted in the trainer and
understand the product working. Refer the individual manual of each
proper maintenance and precautions.
If possible put trainer in Air-conditioned room.
Do not put instrument idle for a longer time. Run it once in a week.
Give routine maintenance to it.
Remove dust periodically from the trainer.
Any problem encountered during the use of the set up, first refer
instruction manual. If problem persists, contact us immediately. We provide
support for your specific questions or any up gradation.
ROUTINE MAINTENANCE:
SR.
PART NAME PROBLEM CORRECTIVE MEASURES
NO.
If Indication deviates
above + / - 3 % from
Wrong display of actual Value, calibrate
1 PID Controller
the Control value. the Controller as
mentioned in controller
manual.
Ensure pneumatic air
pressure 1.4 Kg/cm2 is
available from the
pressure regulator to
the I/P Converter as
indicated by the
pressure gauge
provided along with the
regulator on the front
panel.
Check the leakage
from the valve
Diaphragm.
Control valve not Proportional Band (Pb)
2 Control valve
operating. value in the PID
controller is not very
low as it may Cause
oscillation of the control
valve for the fractional
value of error.
Check the transmitter
connection to PID
controller.
Leakage in the airline
running from the E/P
Converter to pneumatic
control valve, change
the pipeline.
Not give the Ensure that the proper
3 Valve positioner proper output to air supply 1.4 Kg/cm2 is
the control valve. come to the positioner.
4 Pressure Does not give Ensure that 24 V DC
Transmitter output. Comes to the
Transmitter.
Ensure that link on the
panel is properly
EXPERIMENTAL PRESSURE CONTROL TRAINER 9
connected.
DESCRIPTION OF APPARATUS :-
PID CONTROLLER :
Procedure for entering the values of P,I and D : To enter the values of
P, I and D into the PID controller press 1st and 3rd key at a time, then
after some time another screen will open, in this screen you can see like
Down arrow key, then select (AT) option, then press 3rd key for next,
now you will find the screen for entering the value of P. Here you can
change the value by Up / Down arrow keys. Then press 3rd key for the
next option. When all the options will complete, then it will show the main
screen of process value(PV) and set point(SP). If you have selected the
auto tuning(AT) option, then you cannot appear the option of P,I and D
by the 3rd (next / enter) key. If you have selected the (-----) option then
and then you will find the another options of P,I and D. This whole
If you want to change the valve position by manually, then press the
fourth key of the PID controller, Now you will get the different screen and
it will appear like M 30. Here 30 indicates that, now the 30% of valve is
open. You can change that value by UP and DOWN arrow keys. Now if
you want to go to the normal screen press this fourth key again.
built with just afew simple building blocks. Typical autopilots are built using a
PID algorithm. PID stands for proportional, integral, and derivative. Typically a
PID controller manipulates one control output to force a process value towards
a reference point. Let me say that again an a bit different way. Imagine a
cruise contro on a car. We know the current speed. We know the target
speed. And we know the accelerator position. The cruise control will
manipulate the accelerator position (control output) to try to make the current
speed (process value) equal to the target speed (reference point.) How the
desired speed (even going up and down hills) is where the magic happens.
Proportional
All three components of the PID algorithm are driven by the difference
between the process value (i.e. the current speed) and the reference point
(i.e. the target speed.) We will call this difference (of error) for one particular
time step . For that same time step, we call the process value and the
reference point .
For simple situations, this all by itself can be a very effect control algorithm.
Typically this works best when you know that when then . For
going to be bank angle, the reference point is going to be zero (zero bank
angle means the wings are level.) Assume a well trimmed aircraft with neutral
stability so that when the ailerons are zero there is no change in bank. A
proportional only control would set the aileron deflection inversely proportional
to the bank angle. As the bank angle gets closer to zero, the aileron deflection
gets closer to zero. Something as simple as this (a formula with one multiply
Integral
Unfortunately life is often more complicated than we'd like, and even in the
case of a simple wing leveler, you encounter situations where the aircraft isn't
perfectly trim and zero aileron deflection does not always equal zero roll
needed to keep the wing level can vary with speed. In these cases, a
proportional only controller will stabilize out quickly, but will stabilize to the
wrong value. We need a way to drive the error in the proportional only
curve. If you have a function, the integral of that function produces a second
function which tells you the area under curve of the first function.
Fortunately we usually don't have a formula for the first function since it
means we can't integrate this function directly and we are spared all the
the error under the process value curve. At each time step we know which
is the difference between the process value and the reference point. If we
multiply this distance times (the time step) we get an area which
approximates the error under the curve just for this time step. If we add these
areas up over time, we get a very reasonable approximation of the area under
the curve. Essentially what this does is that the longer time passes with us not
at our target value, the larger the sum of the (error dt)'s becomes over time.
If we use this sum to push our output value (i.e. our accelerator position) then
the longer we don't quite hit our target speed, the further the system pushes
the accelerator pedal. Over time, the integral component compensates for the
error in the proportional component and the system stabilizes out at the
desired speed.
Derivative
Hopefully someone else can chip in and add more explanation to this section.
But going back again to calculus. The derivative of a function implies the rate
of change of the function output. If you know the function, you can take the
derivative of that function to produce a second function. For any point in time,
function.
are closing on our target value (i.e. the rate of change from each time step to
the next) is an important piece of information that can help us build a more
For a car cruise control, we are measuring velocity at each time step. The rate
physics.)
Combining P + I + D
proportional only controller, it will be very stable but will stabilize to the wrong
build an integral only controller it will quickly hit the target value, but will
overshoot, then overcompensate, and will oscillate wildly around the target
component says the output should be plus what the I component says the
output should be plus what the D component says the output should be. You
As you can see, the actual math involved in a PID controller (while rooted in
EXPERIMENTAL PRESSURE CONTROL TRAINER 14
some deep theory) is actually quite simple to implement. The real trick for
creating a well behaved PID controller and a well behaved autopilot is tuning
Control valve :-
Globe valves are named for their spherical body shape. The two halves
of the valve body are separated by an internal baffle which has an opening
forming a seat onto which a movable plug can be screwed in to close (or shut)
the valve. In globe valves, the plug is connected to a stem which is operated
are of the sliding stem type. These globe valves have a smooth stem rather
Although globe valves in the past had the spherical bodies which gave
them their name, many modern globe valves do not have much of a spherical
shape, but the term globe valve is still often used for valves that have such an
often called stop valves since they don't have the global appearance, but the
term stop valve may refer to valves which are used to stop flow even when
operation. For example, globe valves or valves with a similar mechanism may
be used as sampling valves, which are normally shut except when liquid
samples are being taken. Since the baffle restricts flow, they're not
Globe valves are typically two-port valves, although three port valves
are also produced. Ports are openings in the body for fluid flowing in or out.
The two ports may be oriented straight' across from each other on the body, or
oriented at an angle such as a 90° angle. Globe valves with ports at such an
A body is the main pressure containing structure of the valve and the
most easily identified as it forms the mass of the valve. It contains all of the
valve's internal parts that will come in contact with the substance being
controlled by the valve. The bonnet is connected to the body and provides the
A bonnet provides leakproof closure for the valve body. The threaded
section of stem goes through a hole with matching threads in the bonnet.
Globe valves may have a screw-in, union, or bolted bonnet. Screw-in bonnet
the body added strength. A bonnet attached with bolts is used for larger or
wearable material that maintains the seal between the bonnet and the stem
EXPERIMENTAL PRESSURE CONTROL TRAINER 16
during valve cycling operations
A plug is the closure member of the valve. Plugs are connected to the
stem which is slid or screwed up or down to throttle the flow. Plugs are
typically of the balance or unbalanced type. Unbalanced plugs are solid and
are used with smaller valves or with low pressure drops across the valve. The
advantages are simpler design, with one possible leak path at the seat and
usually lower cost. The disadvantages are the limited size; with a large
unbalanced plug the forces needed to seat and hold the flow off become
impractical. Balanced plugs have holes through the plug. Advantages include
easier shut off as the plug does not have to overcome static forces. However,
a second leak path is created between the plug and the cage, cost is generally
higher.
valve and transmits this actuation force. Stems are either smooth for actuator
controlled valves or threaded for manual valves. The smooth stems are
maintenance. With a smooth stem the ends are threaded to allow connection
to the plug and the actuator. The stem must not only withstand a large amount
of compression force during valve closure, but also have high tensile strength
during valve opening. In addition, the stem must be very straight, or have low
runout, in order to insure good valve closure. This minimum runout also
minimizes wear of the packing contained in the bonnet, which provides the
inside the body of the valve. Typically, the cage is one of the greatest
determiners of flow within the valve. As the plug is moved more of the
openings in the cage are exposed and flow is increased and vise versa. The
design and layout of the openings can have a large effect on flow of material
are in a range). Cages are also used to guide the plug to the seat of the valve
A seat ring provides a stable, uniform and replaceable shut off surface.
Seat rings are usually held in place by pressure from the fastening of the
bonnet to the top of the body. This pushes the cage down on the lip of the
seat ring and holds it firmly to the body of the valve. Seat rings my also be
threaded and screwed into a thread cut in the same area of the body.
However this method makes removal of the seat ring during maintenance
difficult if not impossible. Seat rings are also typically beveled at the seating
surface to allow for some guiding during the final stages of closing the valve.
surface, so that rubber can be compressed against the seat to form a leak-
Valve positioner :-
pressure operating the actuator until the valve stem reaches the position
They are connected mechanically to the valve stem so that stem position can
output and the valve diaphragm. The positioner acts to overcome hysteresis,
packing box friction, and valve plug unbalance due to pressure drop. It
assures exact positioning of the valve stem in accordance with the controller
output.
Allow wide range of flow variation: i.e. operate at less than 10% travel
Principle of Operation :
This stem position is compared with the position called for by the instrument
brought into the positioner for positioning the valve at exactly the point called
PRESSURE VESSEL :-
A pressure vessel is a closed, rigid container designed to hold gases or
liquids at a pressure different from the ambient pressure. The end caps fitted to the
recompression chamber, distillation towers and many other vessels in oil refineries
and petrochemical plants, nuclear reactor vessel, habitat of a space ship, habitat of a
PRESSURE TRANSMITER :-
The fundamental difference between these crystal sensors and static-force devices
such as strain gages is that the electric signal generated by the crystal decays
rapidly. This characteristic makes these sensors unsuitable for the measurement of
results in a flow of electric charge (which lasts for a period of a few seconds). The
resulting electric signal can be measured as an indication of the pressure which was
applied to the crystal. These sensors cannot detect static pressures, but are used to
vibration. Some of these rugged sensors can detect pressure events having "rise
times" on the order of a millionth of a second, and are described in more detail later
in this chapter.
All pages in the Citect/SCADA have a top and a bottom navigation menu that
allow the operator an easy access to all the Citect/SCADA pages.
User can also enter values for SP, OP and Alarm Limits using keyboard. For
that, focus on displayed value, enter new value and press Enter. For OP, slider
control is also available.
EXPERIMENTAL PRESSURE CONTROL TRAINER 22
Top Navigation Menu is having following buttons.
Date &
Page Contact
Alarms &
Login
Figure 3.1.1 – Top Navigation Menu
Parameters such as Set Point (SP), Process Value (PV), Output (OP), and
Proportional (P), Integral (I), Derivative (D) are displayed.
After login, click on tabular of the bottom navigation menu, Tabular page opens
and this Tabular page displays values of all parameters in the tabular format.
PID settings :
Set Point
Process Value
Output
Alarm Lmits
Control Trainer Mimic is Pressure displayed with Panel & Zoom buttons.
Panel page : Through down navigation menu open the panel screen.
PV & SP Trends are displayed in the right half of the Control Trainer
Zoom
Button
OP Trends are displayed in the right half of the Control Trainer page.
In the upper graph window there are four different colours of trends, we
can observe, But After making communication between PC and PID
controller. In this graph green line indicates the PV%(Process Value),
yellow line indicates the SP%(Set Point), red line indicates the Alarm
H(high Alarm) and blue line indicates the Alarm L(Low Alarm).
In the lower graph window the green line indicates the OP%(Output).
PROCEDURE:
CALCULATIONS:
From the above data calculate the output required for maintaining the pressure in the
tank at the desired value with fixed disturbance.
EXPERIMENT: 2
CLOSED LOOP (AUTO MODE) CONTROL
(ON/ OFF CONTROL)
AIM : To Study the Closed Loop (Auto Mode) Control (On/ Off Control).
EXPERIMENTAL PRESSURE CONTROL TRAINER 33
PROCEDURE:
Start the equipment as mentioned in the startup procedure above.
Adjust the opening (approx. 20 %) of the disturbance valve provided on the
pressure tank and do not alter it throughout the course of the experiment.
Select the Auto option by pressing the AUTO/MANUAL button provided on
the main screen. The button should indicate AUTO when the controller is in
Auto Control mode.
Allow the system to attain the steady state at the initial set point (about 2 kg/
cm2 (g)) value of pressure in the pressure tank.
Choose the Save As option in the File menu and save the file by giving
appropriate name.
Choose the On/Off Control action from the Menu Button on the main screen
and also supply the value of difference expressed as % of input span (0.1-
10%, default value 0.5%) in the popped up dialogue box.
Shut down the equipment as mentioned in the shutdown procedure above.
While conducting this experiment the process variable value should not
exceed the value of 5-kg/ cm2 (g) as it may damage the pressure tank/
pressure sensor-transmitter.
OBSERVATIONS:
Observe that if the process variable (pressure) value exceeds the set point
beyond the difference value controller totally shutoff the control valve and if
process variable (pressure) value decreases than the control valve is opened
fully i.e. process is operating as an On-Off switch.
EXPERIMENT: 3
CLOSED LOOP (AUTO MODE) CONTROL
(PROPORTIONAL CONTROL)
PROCEDURE:
Start the equipment as mentioned in the startup procedure above.
Adjust the opening (approx. 20 %) of the disturbance valve provided on the
pressure tank and do not alter it throughout the course of the experiment.
Select the Auto option by pressing the AUTO/MANUAL button provided on
the main screen. The button should indicate AUTO when the controller is in
Auto Control mode.
Allow the system to attain the steady state at the initial set point (about 2 kg/
cm2 (g)) value of pressure in the pressure tank.
Choose the Save As option in the File menu and save the file by giving
appropriate name.
Choose the Proportional (P) Control action from the Menu Button on the
main screen.
Click on to the PID button and enter the desired value of proportional band in
the popped up screen and apply it.
Allow the system to achieve the steady state and observe the offset between
the process variable and set point. Change the value of proportional band
observes the Load change (regulatory problem) may also be applied by
changing the opening position of the disturbance valve provided on the
pressure tank. / Set point change may also be applied by changing the set
point (servo problem) using the up/ down arrow provided besides the indicator
of set point or directly insert the value of desired set point in the set point
value box by inserting the cursor.
Shut down the equipment as mentioned in the shutdown procedure above.
The value of load change / set point change should be approximately 20% of
the range to obtain proper response otherwise the controller may track to its
set point without any overshoot/ undershoot.
While conducting this experiment the process variable value should not
exceed the value of 5-kg/ cm2 (g) as it may damage the pressure tank/
pressure sensor-transmitter.
Observe that the offset decreases with decrease in the proportional band value.
Observe the effect of load & set point change on the behavior of the system.
PROCEDURE:
Start the equipment as mentioned in the startup procedure above.
Adjust the opening (approx. 20 %) of the disturbance valve provided on the
pressure tank and do not alter it throughout the course of the experiment.
Select the Auto option by pressing the AUTO/MANUAL button provided on
the main screen. The button should indicate AUTO when the controller is in
Auto Control mode.
Allow the system to attain the steady state at the initial set point (about 2 kg/
cm2(g) value of pressure in the pressure tank.
Choose the Save As option in the File menu and save the file by giving
appropriate name.
Choose the Proportional + Integral (PI) Control action from the Menu Button
on the main screen.
Click on to the PID button and enter the desired value of proportional band
and reset time in the popped up screen and apply it.
Allow the system to achieve the steady state and observe the path followed
by the process variable to reach the set point. Change the value of
proportional band as well as reset time and observe the same.
Load change (regulatory problem) may also be applied by changing the
opening position of the disturbance valve provided on the pressure tank. / Set
point change may also be applied by changing the set point (servo problem)
using the up/ down arrow provided besides the indicator of set point or directly
insert the value of desired set point in the set point value box by inserting the
cursor.
Shut down the equipment as mentioned in the shutdown procedure above.
The value of load change / set point change should be approximately 20% of
the range to obtain proper response otherwise the controller may track to its
set point without any overshoot/ undershoot.
OBSERVATIONS:
Observe that at any value of proportional band & reset time the value of offset is
zero, however the time required for the same varies as the value changes.
Observe the effect of load & set point change on the behavior of the system.
PROCEDURE:
Start the equipment as mentioned in the startup procedure above.
Adjust the opening (approx. 20 %) of the disturbance valve provided on the
pressure tank and do not alter it throughout the course of the experiment.
Select the Auto option by pressing the AUTO/MANUAL button provided on
the main screen. The button should indicate AUTO when the controller is in
Auto Control mode.
Allow the system to attain the steady state at the initial set point (about 2 kg/
cm2 (g)) value of pressure in the pressure tank.
Choose the Save As option in the File menu and save the file by giving
appropriate name.
Choose the Proportional + Derivative (PD) Control action from the Menu/
Radio Button on the main screen.
Click on to the PID button and enter the desired value of proportional band
and rate time in the popped up screen and apply it.
Allow the system to achieve the steady state and observe the path followed
by the process variable to reach the set point. Change the value of
proportional band as well as rate time and observe the same.
Load change (regulatory problem) may also be applied by changing the
opening position of the disturbance valve provided on the pressure tank. / Set
point change may also be applied by changing the set point (servo problem)
using the up/ down arrow provided besides the indicator of set point or directly
insert the value of desired set point in the set point value box by inserting the
cursor.
Shut down the equipment as mentioned in the shutdown procedure above.
The value of load change / set point change should be approximately 20% of
the range to obtain proper response otherwise the controller may track to its
set point without any overshoot/ undershoot.
EXPERIMENTAL PRESSURE CONTROL TRAINER 39
While conducting this experiment the process variable value should not
exceed the value of 5-kg/ cm2 (g) as it may damage the pressure tank/
pressure sensor-transmitter.
OBSERVATIONS:
Observe that at any value of proportional & rate time the process variable is not able
to reach the set point value.
Observe the effect of load & set point change on the behavior of the system.
PROCEDURE:
Start the equipment as mentioned in the startup procedure above.
Adjust the opening (approx. 20 %) of the disturbance valve provided on the
pressure tank and do not alter it throughout the course of the experiment.
Select the Auto option by pressing the AUTO/MANUAL button provided on
the main screen. The button should indicate AUTO when the controller is in
Auto Control mode.
Allow the system to attain the steady state at the initial set point (about 2 kg/
cm2 (g) value of pressure in the pressure tank.
Choose the Save As option in the File menu and save the file by giving
appropriate name.
Choose the Proportional + Integral + Derivative (PID) Control action from
the Menu/ Radio Button on the main screen.
Click on to the PID button and enter the desired value of proportional band,
reset time and rate time in the popped up screen and apply it.
Allow the system to achieve the steady state and observe the path followed
by the process variable to reach the set point. Change the value of
proportional band, reset time as well as rate time and observe the same.
Load change (regulatory problem) may also be applied by changing the
opening position of the disturbance valve provided on the pressure tank. / Set
point change may also be applied by changing the set point (servo problem)
using the up/ down arrow provided besides the indicator of set point or directly
insert the value of desired set point in the set point value box by inserting the
cursor.
Shut down the equipment as mentioned in the shutdown procedure above.
The value of load change / set point change should be approximately 20% of
the range to obtain proper response otherwise the controller may track to its
set point without any overshoot/ undershoot.
Observations:
Observe that at any value of proportional, reset time & rate time the process variable
reaches the set point value.
Observe the effect of load & set point change on the behavior of the system.
Size ¼ ‘’ BSP
Max. I/P Pressure: 18
Kg/cm2
Regulation of
Air Filter Regulator Inlet pressure: 10 Kg/cm2
pneumatic Supply
Outlet pressure: 7 Kg/cm2
Pressure gauge: 0 – 7
Kg/cm2.
Visual indication of
Pressure Gauge Range: 0 – 30 PSI. Pneumatic
Pressure.
Display of Output
Current of the Level
Range: 4 – 20 mA Transmitter.
Current Indicator
Type: Digital 3 ½ display Display of the Input
Current of the PID
Controller.
EXPERIMENTAL PRESSURE CONTROL TRAINER 43
Display output of
Range: 4 – 20 mA controller.
Current Indicator
Type: Digital 3 ½ display Output 4 – 20 mA to
the E/P Converter.
Make: Toshniwal
Input: 4 – 20 Ma Actuation of Control
E/P Converter
Output: 0.2 to 1 Kg/ cm2 valve.
Supply pressure 1.4 Kg/
cm2
Enclosure for
process Indicator,
Control Panel MOC: MS
controller, output
indicator etc.
Size: 48*48 mm
Make: West, U.K.
WithRS485
PID Controller For process control.
communications.
Input: 4 – 20 Ma
Output: 4 – 20 Ma