M3LCR Manual
M3LCR Manual
M3LCR Manual
WJ21 U(A) □ – □
Input Voltage or Current Signal Interface
U1:0-5V A1:0-1mA 485: output is RS-485 interface
U2:0-10V A2:0-10mA 232: output is RS-232 interface
U3:0-75mV A3:0-20mA
U4:0-2.5V A4:4-20mA
U5:0-±5V A5:0-±1mA
U6:0-±10V A6:0-±10mA
U7:0-±100mV A7:0-±20mA
U8:user-defined A8:user-defined
Sample 1: part No.:WJ21-A4-485 4-20mA input signal,output is RS485 interface
Sample 2: part No.:WJ21-U1-232 0-5V input signal,output is RS232 interface
Sample 3: part No.:WJ21-U8(U8:0-12V)-485 0-12V input signal,output is RS485 interface
General parameters:
(typical @ +25 ℃, Vs to 24VDC)
Input type: Input current / voltage input
Accuracy: 0.1%
Temperature drift:± 30 ppm / ℃ (± 50 ppm / ℃, maximum)
Input Resistance: 50Ω (4-20mA/0-20mA/0- ± 20mA current input)
When enabled checksum (checksum), users need [Checksum]. It accounted for 2 - character. Commands and
responses must be attached checksum feature. Checksum used to check all input commands to help you find the host to
the module command module to the host response to errors and mistakes. Checksum characters placed in command or in
response to the character after the carriage return before.
Calculated as follows: two characters, the hexadecimal number for all issued prior to the ASCII values of and, then
% of FSR
Input Range +F.S. ZERO ‐F.S Displayed Resolution
All input range +100.00 ±000.00 -100.00 0.01%
A1:0-1mA,A2:0-10mA
A3:0-20mA,U1:0-5V
FFF 000 1LSB
U2:0-10V,U3:0-75mV
U4:0-2.5V,U7:0-100mV
A6:0-±10mA
A5:0-±1mA
U5:0-±5V
U6:0-±10V
Example:
1. Input Range is A4:4-20mA, Input is 4mA:
Command #01(cr)
Engineering Units Response >+04.000(cr)
Percent of FSR Response >+020.00(cr)
Twos complement Response >333(cr)
2. Input Range is U1:0-5V, Input is 3V
In order to improve calibration accuracy, it is recommended to calibrate using the following equipment:
1. A stable output, low noise DC voltage / current signal source
2. A five and a half or more high-precision voltage / current measuring instruments to monitor the accuracy of the
input signal
Calibration:
1. According to the module input range, connects to the corresponding input signal.
Which WJ21 module zero calibration is at input 0,full scale calibration is at the input full-scale 100% . For
example, input signal is 4-20mA, when calibrate zero, input 0mA, when full-scale calibration, input 20mA.
input signal is 0-5V, when calibrate zero, input 0V, when the full-scale calibration, input 5V.
2. To WJ21 module input zero signal, usually is 0mA or 0V.
3. Until the signal stabilized, send the offset calibration $ AA1 command to WJ21 module.
4. To WJ21 module input 100% of full scale current or voltage signal.
5. Until the signal is stable, send the gain calibration $ AA0 command to WJ21 module.
6. Finished
Modbus RTU communication protocol:
Module default protocol is character communications protocol. If you need to set the module to Modbus RTU protocol,
please follow these settings:
1. Short connect INIT pin (pin 3) and GND pin (pin 6).
2. Connect the power cord and the communication interface cable.
3. Turn on the power, the module enters the default state automatically, address 00, baud rate 9600.
4. Wait 1 minute, module is initialization.
5. Send the command $00P1(cr), check the response, if is !00 (cr), set successfully.
6. Turn off the power, disconnect the INIT and GND connections.
7. The module has been set to the Modbus RTU protocol mode successfully.
Register Description:
Address 4X(PLC) Address(PC,DCS) Data Property Data Explanation
40001 0001 Input Analog Signal Read Only Measured data(0x0000~0x0FFF)
hexadecimal
Warranty
Two years (but violate operating rules and requirements to create damage, clients need pay maintenance costs)
Copyright
Copyright © 2010 Shenzhen WAYJUN Industrial Automation
Specifications subject to change without notice.
Brand
In this manual, mentioned other trademarks and copyright belongs to their respective owners.