Inverter R 410a Cooling Only Type 201709142324162961
Inverter R 410a Cooling Only Type 201709142324162961
Inverter R 410a Cooling Only Type 201709142324162961
21/32
[16.67]
ø3-7/16 21/32
[ø87.31] [16.67] 1/2
29/32 [12.70]
2-41/64 [23.02]
[67.07]
57/64
1/2 NPT [22.62]
2-11/64
[55.17]
1/4
[6.00] 2-9/16
[65.09]
7-5/8 [194.06]
1100
1000
900 RL MAX =
Vps - 10.0 Pressure Connections
20mA DC
800 Two integral tubing connectors are provided. They are designed to fit
700 3/16˝ (5 mm) ID tubing. Connect the high pressure to the High side as
600 shown in Fig. 4. Be sure the pressure ratings of the tubing exceed that
500 of the operating ranges.
400
OPERATING
300
REGION
200
100
50 PJ1 PJ2
0 5 10 13 15 20 25 30 35 40 PJ1 PJ2
SW1
POWER SUPPLY AGE
TB1 SW2
Figure 2
The maximum length of connecting wire between the transmitter and the
receiver is a function of wire size and receiver resistance. That portion of
the total current loop resistance represented by the resistance of the
HIGH LOW
connecting wires themselves should not exceed 10% of the receiver
resistance. For extremely long runs (over 1,000 feet), it is desirable to
select receivers with higher resistances in order to keep the size and cost Figure 4
of the connecting leads as low as possible. In installations where the
connecting run is no more than 100 feet, connecting lead wire as small Select Operation Mode and Range:
as No. 22 Ga. can be used. The operating modes and ranges are controlled by two shorting jumpers
on a pair of jumper blocks, PJ3 and PJ5. These two jumper blocks are
3-Wire Operation: shown in Fig. 5.
CAUTION DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS.
PERMANENT DAMAGE NOT COVERED BY WARRANTY
WILL RESULT.
In addition to the obvious change in the scale of the LCD display, the full
scale range and corresponding analog outputs are also affected by the
Figure 5: Mode and Range Programming
measurement units selection. The analog output goes to full scale output
Jumpers and Switches
(5 volts, 10 volts or 20 mA depending on model) of the selected range
and units. See Table 2. For example on Model MS-X2X, when high range
Jumper block PJ3’s primary function is to control when the unit is in the
and English units are selected full scale output occurs at 0.5 in w.c.
High, Medium or Low range. Each unit has three user selectable
(124.5 Pa). When high range and metric units are selected, analog full
operating ranges for what input pressure corresponds to full scale of the
scale output is at 100 Pa (0.4015 in w.c.).
analog output. When the left two pins on PJ3 next to the letter “H” are
shorted together by the supplied shorting jumper, the device’s full scale
FULL SCALE ANALOG OUTPUT
analog output corresponds to the highest pressure range of the unit.
STANDARD MODELS
When the shorting jumper shorts the bottom two jumpers next to the
letter “M” of PJ3, the full scale analog output corresponds to the middle Model Low Medium High
range of the unit. Similarly the low range is selected by placing the MS-X2X English 0.1 in w.c. 0.25 in w.c. 0.5 in w.c.
shorting jumper on the pins of PJ3 next to the letter “L”. The jumper for
PJ3 is factory installed to the high range. If no jumper is installed on PJ3, Metric 25 Pa 50 Pa 100 Pa
the device defaults to the “H” range selection. MS-X1X English 1 in w.c. 2 in w.c. 5 in w.c.
Metric 250 Pa 500 Pa 1250 Pa
Jumper block PJ5’s primary function is to control the operating mode.
Table 2
There are three operating modes, Normal, zero center and Velocity. The
Normal operating mode provides for zero pressure to correspond to 0 V
Zero Center Models
or 4 mA output. This mode is selected by placing the supplied shorting
jumper for PJ5 on the pins next to the letter “N”. The jumper for PJ5 is Model Low Medium High
factory installed to the Normal Mode on standard units. If no jumper is
MS-021 English ±0.1 in w.c. ±0.25 in w.c. ±0.5 in w.c.
installed on PJ5, the device defaults to the “N” selection.
MS-221 Metric ±25 Pa ±50 Pa ±100 Pa
On factory ordered bi-directional units, the PJ5 jumper will come from the
factory in the ZC or Zero-Center position.
Install Optional Display:
The A-435 LCD conversion kit allows any non display model to have the
The Zero Center operating mode provides for zero pressure to
LCD added at a later time. The kit contains an LCD display and
correspond to 2.5 V, 5 V or 12 mA while the selected full scale range
replacement cover with LCD window. The optional display may be set to
corresponds to 5 V, 10 V or 20 mA current. Negative full scale pressure
read pressure either in inches water column or pascal. The optional
is required to go to 0 V or 4.0 mA.
display can be also set to display air velocity in feet per minute or meters
per second when used with a pitot tube or similar flow sensor with a
The Velocity mode provides the ability for the unit in conjunction with a
known K factor.
pitot tube or similar flow sensor with known K factor to give a direct
output in air velocity. This mode is selected by placing the supplied
The optional display for the Magnesense® transmitter is mounted on the
shorting jumper for PJ5 on the pins next to the letter “V”. The Velocity
main board by connectors PJ1 and PJ2. The display is properly mounted
mode overrides the High, Middle, and Low range setting on PJ3 and
when PJ1 and PJ2 on the display are connected to the corresponding
forces the unit to the High range setting. If the optional display is present,
PJ1 and PJ2 on the main board. See Fig. 4. Installing the display upside
this mode prompts the display to read in air velocity. The current or
down causes no harm to the display or the main board. The display just
voltage output is modified such that full scale output is 4004* K* √(∆P)
simply reads upside down.
feet per minute or its metric equivalent in meters per second depending
upon which units are selected. The factory programming for the K factor
When upgrading a Magnesense® transmitter with an A-435 display kit, it
is 1.00 but may be adjusted (see Adjust K Factor). The velocity displayed
is important to note that it is possible for a device to have been user
for the various models can be found in Table 1.
calibrated to appear properly calibrated at the analog output while in fact,
Velocity Displayed it has been improperly calibrated. This can be done by improperly
Model English Metric calibrating the analog output’s zero and span and then using the
MS-X2X K* 2830 fpm K* 14.4 m/s pressure zero and span to compensate for the improperly calibrated
MS-X1X K* 8950 fpm K* 45.5 m/s analog output. This possibility can be eliminated by checking that the
analog output’s zero calibration is either 0 V or 4 mA and the analog
Table 1
output’s full scale calibration is either 10 V or 20 mA output. See the User
Calibration section for details on how to perform these tests.
SETUP
Set Measurement Units:
Label Display (Optional):
Magnesense® transmitters can be easily set to operate in either English
The optional LCD display does not contain engineering unit indication.
or metric units.
So that the display may be appropriately marked, four adhesive labels
have been provided with the units. The unit labels are IN W.C., Pa, fpm,
The programming jumper is PJ7 and is located in the upper half of the
and M/S. Attach the appropriate provided units label above the display
board and under the LCD display if the LCD is present. A representation
window on the cover of the device to indicate to which units the display
of this jumper is shown in Fig. 6. English units are selected by placing the
has been set.
provided shorting jumper on the lower two pins of the block next to the
label “H2O”. Metric units are selected by placing the provided shorting
jumper on the upper two pins of the block next to the label “Pa”. If no
jumper is present English units are selected by default.
Adjust K Factor: Preparation – Depending upon if it is a 2-wire or 3-wire system, connect
If the optional display is present, the K factor used in velocity the voltmeter or milliammeter and power supply, being careful to observe
measurements may be adjusted. This is done by activating the K factor polarities. The transmitter must be calibrated in a vertical position. Make
adjustment function of the unit. To activate the K factor adjustment sure the unit has been returned to its factory default span and zero
function, take the shorting jumper from programming block PJ5 and settings by pressing and holding both the “Zero” and “Span” switches,
place it on the upper two terminals next to the letter “K”. See Fig. 5. The simultaneously, for about 4 to 5 seconds (doing this can be necessary to
display will now show the programmed pitot tube K factor. The K factor erase bad zero and span values that might have been stored by a
can be adjusted up and down by using the zero and span buttons as up previous user of the Magnesense® unit).
and down buttons. Once the desired K factor has been set, replace the
shorting jumper on PJ5 to its velocity position (“V”). The shorting jumper Calibrating Pressure Zero – Leaving the hose barbs vented, press and
must not be left in the “K” position for proper operation of the unit. The hold the “Zero” switch for about 4 to 5 seconds. The zero point should
factory setting for the K factor is 1.0 and it is adjustable from 0.5 to 3. now be set and, if the display is present, the display will read zero.
Calibrating pressure should begin with setting the zero first, then the
Adjust Filter Time Constant: span, since the zero setpoint will affect the span value. Once the “Zero”
If the optional display is present, the dampening filter time constant of the is set, for uni-directional models, your output reading should be close to
output may be adjusted from 0.5 to 15 seconds in 1-second increments. 4.0 mA or 0 V. For bi-directional models, 12 mA for current outputs, 2.5
In turbulent air, the pressure reading may be unstable. The dampening V for 5 V models and 5 volts for 0 to 10 V models.
filter time constant is provided to reduce such noise. The time constant
is the actual filter time constant, not averaging time. For an abrupt Span – PJ3 jumper must be in “H” position to calibrate the span and PJ7
change in pressure it will take three time constants to reach 95% of the jumper must be in the “H2O” position.
final value. Note: If you must calibrate in Pa mode with the PJ7 jumper in the Pa
position, you must calibrate the unit to the full scale inches of water
To activate the filter adjustment function, take the shorting jumper for column equivalent for proper calibration. For example: 5 in w.c. full scale
programming block PJ3 and place it on the upper two terminals next to models the equivalent required is 1250 Pa.
the letter “F”. See Fig. 5. The display will now show the filter time
constant. The time constant can be adjusted up and down by using the Also, the PJ5 jumper should be set to “ZC” on a bidirectional unit and “N”
zero and span buttons as up and down buttons. Once the desired time on a unidirectional unit. Connect the pressure source and apply the high
constant has been set, replace the shorting jumper on PJ3 to its original range rated pressure. When the pressure has stabilized, press and hold
position. The shorting jumper must not be left in the “F” position for the “Span” switch for about 4 to 5 seconds. The display, if present, will
proper operation of the unit. The factory setting for the time constant of now read the calibration pressure. Span may only be calibrated on the
the filter is 0.5 seconds. highest range for the unit.
©Copyright 2015 Dwyer Instruments, Inc. Printed in U.S.A. 2/15 FR# 443337-00 Rev. 9