Electricity Meters IEC/MID

Industrial and Commercial

ZMD405AT/CT, ZFD405AT/CT,
ZMD410AT/CT, ZFD410AT/CT

E650 Series 3 (ZMD400AT/CT,


ZFD400AT/CT)
Technical Data

Date: 27.01.2011
Filename: D000030106 E650 ZxD400xT series 3 Technical Data EN e.docx

© Landis+Gyr Investments AG D000030106 EN e


2/8

Revision history
Version Date Comments
e 27.01.2011 Updated document template and Chapter 1.3 table entry “045x 4
outputs, additional power supply 100-240 VAC/VDC”

Copyright © 2010-2011 Landis+Gyr Investments AG. Subject to change without notice.

All Landis+Gyr products and solutions have been designed and developed for the best possible performance. Performance of this product
may vary depending on the system environment. You are strongly advised to only use solutions and products recommended by Landis+Gyr.
It is strictly forbidden to make any changes, alterations or modifications whatsoever to the product without the prior written permission of
Landis+Gyr.
If you use solutions or products not recommended by Landis+Gyr, or if the product is changed, altered or modified in any way, you agree to
assume all responsibility and risk for the use of such system, and all possible warranties from Landis+Gyr are immediately voided.
Landis+Gyr will not be liable for any loss or damage, including without limitation any direct, indirect, consequential, special or incidental
damages arising out of, based on, or resulting from the use of non-recommended solutions or any such changed, altered or modified
products or product solutions.
No part of this document may be reproduced, stored in retrieval system, or transmitted in any form or by any means without the prior written
permission of Landis+Gyr.
Landis+Gyr assumes no responsibility for any errors in this document or for any damages, incidental or consequential, caused by use of this
document.
Landis+Gyr and Gridstream are trademarks of Landis+Gyr Investments AG.
Landis+Gyr system products include software developed by the following trademark owners: Oracle is a registered trademark of Oracle
Corporation. Java and J2EE are registered trademarks of Sun Microsystems, Inc. Microsoft and Windows are registered trademarks of
Microsoft Corporation. Adobe is a registered trademark of Adobe Systems. InstallShield is a registered trademark of InstallShield Software
Corporation. Ant software is developed by the Apache Software Foundation (http://www.apache.org/). Echelon, LON, LonWorks, LonTalk
and Neuron are registered trademarks of Echelon Corporation.
Other brand or product names mentioned in this manual may also be trademarks or registered trademarks of their respective owners and
are used here for identification only.

© Landis+Gyr Investments AG D000030106 EN e — E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) — Technical Data


3/8

The E650 transformer connected I&C meters Modular communication


record active and reactive energy consumption in AT/CT-type meters are equipped with modular
all three-phase four-wire and three-phase three- communication units which provide the right choice
wire networks. for the best data channel at all times. «Plug+Play»
Range modules also offer you full freedom of choice for
E650 meters are the answer to a wide range of deployment of new communication technologies.
specific needs: from the reliable commercial meter Installation support
to the complex measuring device with comprehen-
An indication of phase voltages, phase angles,
sive additional functionality for sophisticated data
rotating field and energy direction supports the
acquisition and flexible tariff control of large indus-
installation.
trial customers.

E650 Series 3 – ZxD400AT/CT Technical specifications


General Measurement Accuracy
ZxD405xT
Voltage active energy, to IEC 62053-22 class 0.5 S
Nominal voltage Un ZMD400xT reactive energy, to IEC 62053-23 accuracy 1%
3 x 58/100 V to 69/120 V
3 x 110/190 V to 133/230 V ZxD410xT
3 x 220/380 V to 240/415 V active energy, to IEC 62053-21 class 1
extended operating voltage range reactive energy, to IEC 62053-23 accuracy 1%
3 x 58/100 to 240/415 V
Measurement Behaviour
Nominal Voltage Un ZFD400xT Starting current ZxD405xT
3 x 100 to 120 V according to IEC 0.1% In
3 x 220 to 240 V typical 0.07% In
extended operating voltage range 3 x 100 to 415 V 5||1 A as 1 A meter

Voltage range 80 to 115% Starting current ZxD410xT


according to IEC 0.2% In
Frequency typical 0.14% In
Nominal frequency fn 50 or 60 Hz 5||1 A as 1 A meter
tolerance ± 2% The startup of the meter is controlled by the starting power
and not by the starting current.
IEC-specific Data Starting power in M-circuit single phase
nominal voltage x starting current
Current
Nominal Current In 1 A, 2 A, 5 A, 5||1 A Starting power in F-circuit all phases
nominal voltage x starting current x √3
Maximal Current Imax
metrological 1 A 2 A, 10 A MID-specific Data
metrological 2 A 4A
metrological 5||1 A 6A Current (for classes B and C)
metrological 5 A 200% In or 400% In Rated current In 1.0 A, 2.0 A, 5.0 A
thermal 1 A, 2 A,5||1 A 12 A
thermal 5 A 12 A or 24 A Minimum current Imin 0.01 A, 0.02 A, 0.05 A
Short Circuit Current 0.5 s with 20 x Imax
Transitional current Itr 0.05, 0.1 A, 0.25 A

Maximum current Imax 2.0 A, 4 A, 10.0 A or 20 A

D000030106 EN e — E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) — Technical Data © Landis+Gyr Investments AG


4/8

Measurement Accuracy to EN 50470-3 Fast transient burst test to IEC 61000-4-4


ZxD400xT classes B and C current and voltage circuits under load
according to IEC 62053-21/23 4 kV
Measurement Behaviour auxiliary circuits > 40 V 2 kV
Starting current Ist
Fast transient surge test to IEC 61000-4-5
class B: Ist 0.002, 0.01 A
current and voltage circuits 4 kV
class C: Ist 0.001, 0.005 A
auxiliary circuits > 40 V 1 kV

General
Insulation Strength
Insulation strength 4 kV at 50 Hz during 1 min.
Operating Behaviour
Voltage failure (Power Down)
Impulse voltage 1.2/50 μs to IEC 62052-11
bridging time 0.5 s
current and voltage circuits 8 kV
data storage after another 0.2 s
auxiliary circuits 6 kV
switch off after approx. 2.5 s

Voltage restoration (Power Up) Protection class ll to IEC 62052-11


function standby 3 phases after 2 s
function standby 1 phase after 5 s Calendar Clock
detection of energy direction and phase voltage Calendar type Gregorian or Persian (Jalaali)
after 2 to 3 s
Power Consumption Accuracy < 5 ppm
Power consumption per phase in voltage circuit
Backup time (power reserve)
phase voltage 58 V 100 V 240 V
with supercap > 20 days
active power (typical) 0.4 W 0.5 W 0.7 W
charging time for max. backup time 300 h
apparent power (typical) 0.8 VA 1.0 VA 1.7 VA
with battery (optional) 10 years
battery type CR-P2
Power consumption per phase in current circuit
phase current 1A 5 A 10 A
Display
active power (typical) 5 mW 0.125 W 0.5 W
apparent power (typical) 5 mVA 0.125 VA 0.5 VA Characteristics
type LCD liquid crystal display
Environmental Influences digit size in value field 8 mm
number of digits in value field up to 8
Temperature range to IEC 62052-11
digit size in index field 6 mm
operation –25 °C to +70 °C
number of digits in index field up to 8
storage –40 °C to +85 °C

Temperature coefficient Inputs and Outputs


range –25 °C to +70 °C Control inputs
average value (typical) ± 0.012% per K control voltage US 100 to 240 VAC
at cosϕ=1 (from 0.05 Ib to Imax) ± 0.02% per K input current < 2 mA ohmic at 230 VAC
at cosϕ=0.5 (from 0.1 Ib to Imax) ± 0.03% per K
Output contacts
Impermeability to IEC 60529 IP51 type solid state relay
voltage 12 to 240 VAC/DC
Electromagnetic Compatibility max. current 100 mA
Electrostatic discharges to IEC 61000-4-2 max. switching frequency (pulse length 20 ms) 25 Hz
contact discharge 15 kV
Optical test outputs active and reactive energy
Electromagnetic RF fields to IEC 61000-4-3 type red LED
80 MHz to 2 GHz 10 and 30 V/m number 2
meter constant selectable
Radio interference suppression
according to IEC/CISPR 22 class B

© Landis+Gyr Investments AG D000030106 EN e – E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) – Technical Data


5/8

Communication Interface Suspension triangle


Optical interface to IEC 62056-21 height (with extended hook) 230 mm
type serial, asynchronous, half-duplex height (suspension eyelet open) 206 mm
max. transmission rate 9600 bps height (suspension eyelet covered) 190 mm
protocols IEC 62056-21 and dlms width 150 mm

Communication Units Terminal cover


Exchangeable communciation units for various short no free space
applications. standard 40 mm free space
long (opaque, transparent) 60 mm free space
Additional Power Supply (optional) GSM 60 mm free space
ZxB-type 80 mm 80 mm free space
On Extension Board 045x
ZxB-type 110 mm 110 mm free space
nominal voltage range 100 to 240 VAC/DC
ADP1 adapter
tolerance 80 to 115% Un
RCR/FTY adapter
frequency 50 or 60 Hz
max. power consumption 6.8 W
Material housing
On Extension Board 046x Polycarbonate, partly glass-fibre reinforced
nominal voltage range 12 to 24 VDC
tolerance 80 to 115% Un Connections
max. power consumption 3.5 W Phase connections
type screw type terminals
Weight and Dimensions diameter 5.2 mm
Weight approx. 1.5 kg recommended conductor cross section 4 to 6 mm2
screw head Pozidrive Combi No. 2
External dimensions screw dimensions M4 x 8
width 177 mm screw head diameter ≤ 5.8 mm
height (with short terminal cover) 244 mm tightening torque < 1.7 Nm
height (with standard terminal cover) 281.5 mm
height (with extended hook) 305.5 mm Other connections
depth 75 mm type screwless spring-type terminal
max. current of voltage outputs 1A
max. voltage of inputs 250 V

D000030106 EN e — E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) — Technical Data © Landis+Gyr Investments AG


6/8

Meter Dimensions (standard terminal cover)


75

extended hook: 230


standard hook: 206
190
26
40

150
177

Terminal Dimensions 12.5

5.2
16 10 10 10 10 10 10 10 10 10
150
168

© Landis+Gyr Investments AG D000030106 EN e – E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) – Technical Data


7/8

Terminal Layout according to DIN

Control inputs and/or Pulse Communication


output contacts of inputs interfaces
extension board Communication unit

Control inputs
and/or
U1 U2 U3 N output contacts
Voltage outputs

U1 U2 U3 N
I1 I1 I2 I2 I3 I3
Voltage connections
Current connections

Symmetrical Terminal Layout (optional, ZMD400 only)

Control inputs and/or Pulse Communication


output contacts of inputs interfaces
extension board Communication unit

Control inputs
and/or
U1 U2 U3 N output contacts
Voltage outputs

U1 U2 U3 N
I1 I2 I3 I3 I2 I1
Voltage connections
Current connections

D000030106 EN e – E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) – Technical Data © Landis+Gyr Investments AG


8/8

Type designation ZMD 4 10 C T 44 4207 S3

Network Type
ZFD 3-phase 3 wire network (F-circuit)
ZMD 3-phase 4 wire network (M-circuit)

Connection Type
4 Transformer operated
Accuracy Class
10 Active energy class 1 (IEC), B (MID)
05 Active energy class 0.5s (IEC), C (MID)
Measured Quantities
C Active and reactive energy
A Active energy
Construction
T With exchangeable communication units
Tariffication
21 Energy rates, external rate control via control inputs
24 Energy rates, internal rate control via time switch
(additionally possible via control inputs)
41 Energy and demand rates, external rate control via control inputs
44 Energy and demand rates, internal rate control via time switch
(additionally possible via control inputs)

All versions with 3 control inputs and 2 output contacts


Additional functions
060x 6 outputs
240x 2 control inputs, 4 outputs
420x 4 control inputs, 2 outputs
045x 4 outputs, auxiliary power supply 100 to 240 VAC/VDC
046x 4 outputs, auxiliary power supply 12 to 24 VDC

xxx0 no additional functions


xxx2 DC-magnet-detection
xxx7 load profile
xxx9 DC-magnet-detection and load profile

Series 3

Contact:
Landis+Gyr (Europe) AG
Theilerstrasse 1
CH-6301 Zug
Switzerland
Phone: +41 41 935 6000
www.landisgyr.com

© Landis+Gyr Investments AG D000030106 EN e – E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) – Technical Data