This document provides specifications for DEIF's moving coil voltmeters and ammeters, including the DQ and VDQ models. Key details include: - The DQ and VDQ instruments measure low power DC signals or AC voltage and current with accuracy class 1.5. - Variants include different sizes from 48x48mm to 144x144mm and measurement ranges from 60mV to 300V and 1mA to 50A. - Specifications cover scales, burdens, measuring ranges, sizes, bezels, mountings, and IP protection ratings.

Uploaded by

Arturo Benavides
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
179 views7 pages

Deif

This document provides specifications for DEIF's moving coil voltmeters and ammeters, including the DQ and VDQ models. Key details include: - The DQ and VDQ instruments measure low power DC signals or AC voltage and current with accuracy class 1.5. - Variants include different sizes from 48x48mm to 144x144mm and measurement ranges from 60mV to 300V and 1mA to 50A. - Specifications cover scales, burdens, measuring ranges, sizes, bezels, mountings, and IP protection ratings.

Uploaded by

Arturo Benavides
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

DATA SHEET

Voltmeters and Ammeters,


Moving Coil (type DQ)

• Q48, Q72, Q96, Q144


• 90° or 240° pointer
• Accuracy class 1.5
• Exchangeable scale (type –x)

DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com
isenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com
14 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com Document no.: 4921210012S
Data sheet DQ

Application:
Moving-coil instruments are intended for installation in panels of power distribution or wherever AC current or AC
voltages are to be measured.
DQ is applied to measure low power DC signals or AC voltage and current.
Type VDQ is a moving coil meter with rectifier applied for R.M.S. measurement of AC currents or AC voltages where low
meter consumption is required.

DQ96-x (exchangeable scale), 90° DQ96-c (non-exchangeable scale), 240° DQ96-xc (exchangeable scale), 240°

Variants
Q48 Q72 Q96 Q144
Moving Coil
48 x 48 mm 72 x 72 mm 96 x 96 mm 144 x 144 mm
90° DQ48-x DQ72-x DQ96-x DQ144-x
DQ48-c DQ72-c DQ96-c DQ144-c
240°
DQ48-xc DQ72-xc DQ96-xc DQ144-xc
- with rectifier 90° VDQ72-x VDQ96-x VDQ144-x
VDQ72-c VDQ96-c VDQ144-c
- with rectifier 240°
VDQ72-xc VDQ96-xc VDQ144-xc

Custom variants
Anti-glare glass
Options IP54 from front (incl. rubber gasket)
Adjustable red pointer (types Q48-x, Q72-x, Q96-x, Q144-x) (IP52)
Other measuring ranges than those stated in this data sheet: ask for availability
Optional graphics
Scale design - Coloured lines (red, green, yellow)
- Coloured section (red, yellow, green)
- Coloured figures (red, green, yellow)
- Application text (black, red, green, yellow)
- Single scale with double row of figures
- Double scale with 2 rows of figures
- Single scale with fine divisions for standard pointer
New scale design
Suppressed zero (DQ..-x/DQ..-c/-xc: max. 20 %)
Measurement Zero at centre of scale or the like
Integrated adjustment potentiometer (±10 % standard, up to ±50 % on request)
Adjusted to accuracy class 1.0 (not possible for type Q48)

DEIF A/S Page 2 of 7


Data sheet DQ

DQ technical specifications

DQ, moving coil instruments Standards


Type: Q48 Q72 Q96 Q144
Scale Linear
Burden
1 mA, Ri: 1 kΩ/V DC DIN 43700
(voltmeter):
60 mV DC to 0.6 V DC, 4 to 20 mA DC: 1.6 V DC for -x and 1.80 V DC
Burden (ammeter):
for –c at 20 mA DC (electrically suppressed)

Measuring
DQ type Size (mm) Measuring ranges – A DC 1) 2)
range – V DC 1) 2)

DQ48-x 48 x 48 60 mV to 300 V 1 mA to 600 mA, 4 to 20 mA 3)


DQ72-x 72 x 72 60 mV to 300 V 1 mA to 5-7.5 A, 10-22.5 A, 25-37.5 A and 40-50 A 4) 4 to 20 mA 3)
DQ96-x 96 x 96 60 mV to 300 V 1 mA to 5-7.5 A, 10-22.5 A, 25-37.5 A and 40-50 A 4) 4 to 20 mA 3)
DQ144-x 144 x 144 60 mV to 300 V 1 mA to 5-7.5 A, 10-22.5 A, 25-37.5 A and 40-50 A 4) 4 to 20 mA 3)
DQ48-xc/DQ48-c 48 x 48 60 mV to 300 V 1 mA to 600 mA, 4 to 20 mA 3)
DQ72-xc/DQ72-c 72 x 72 60 mV to 300 V 1 mA to 5-7.5 A, 10-22.5 A, 25-37.5 A and 40-50 A 4) 4 to 20 mA 3)
DQ96-xc/DQ96-c 96 x 96 60 mV to 300 V 1 mA to 5-7.5 A, 10-22.5 A, 25-37.5 A and 40-50 A 4) 4 to 20 mA 3)
DQ144-xc/DQ144-c 144 x 144 60 mV to 300 V 1 mA to 5-7.5 A, 10-22.5 A, 25-37.5 A and 40-50 A 4) 4 to 20 mA 3)

1) Standard measuring ranges: 1 - 1.2 - 1.5 - 2 - 2.5 - 3 - 4 - 5 - 6 - 8 and multiples of 10 thereof

2) Safety: Cat. III 300 V max. (515 V ph-ph (300 x √3))

3) 4 to 20 mA: Electrically suppressed, voltage drop at 20 mA = 1.6 V for -x and 1.80 V for -c/-xc

4) Higher measuring ranges: For use with standard shunt: 60 mV DC or 150 mV DC


Supplied with shunt lead, 2 x 1 m – 1 mm2 (0.035 Ω)

VDQ technical specifications

VDQ, moving coil instruments with rectifier Standards


Type: Q72 Q96 Q144
Scale Non-linear
Voltmeter 25 to 300 V AC 1)
Internal resistance Ri: Approx. 1 kΩ/V AC DIN 43700
Ammeter 1 to 600 mA AC
Burden Voltage drop: approx. 1.2 V AC

1) Range <50 V AC: Max. 515 V derived from voltages with max. 300 V to earth (300 V – cat. III/600 V cat. II)

DEIF A/S Page 3 of 7


Data sheet DQ
General technical specifications
Instruments are designed according to below mentioned standards Standards
Class 1.5 (-10 to 15 to 30 to 55°C)

Accuracy ±1.5 % of full scale value (FS) EN 60051

Q48 Q72 Q96 Q144


Sizes:
48 x 48 mm 72 x 72 mm 96 x 96 mm 144 x 144 mm
DIN 43700
Scale length -x: 41 mm 62 mm 92 mm 135 mm
Scale length -xc: 75 mm 113 mm 151 mm 230 mm
Bezels Slim bezels DIN 43718
Scale/pointer Standard pointer DIN 43802
Standard: Vertical (90 ±5°)

Other angles: Specify angle to horizontal

┴ vertical mounting

Mounting angle 60° 60° to horizontal DIN 16257


(e.g.)

Π horizontal mounting

For edgewise instruments only, furthermore specify:


Horizontal or vertical scale
Measuring ranges Others on request. DIN 43701
Protection Standard version IP54 version* *) Marked with label:
From front From rear From front From rear "IP54 from front only
when rubber gasket is
(Housings) IP52 IP52 IP54 IP52
mounted"
Quadratic Edgewise Quadratic Edgewise
(Terminals) IP20 IP00 IP20 IP00 EN 60529
Class HUE, short-term condensing allowed
Climate DIN 40040
Max. 95 % RH: Max. 30 days per year
Max. 85 % RH: Remaining days
Max. 75 % RH: Average per year
-10 to 55°C (nominal)
Temperature -25 to 60°C (operating) EN 60051
-25 to 65°C (storage)
The accuracy is affected neither by the material nor by the
Panel influence EN 60051
thickness of the panel
15 g - 6 times - 3 directions
Shock test 50 g/6 ms IEC 68-2-27, Test: Ea
22 g/20 ms
3 to 13.2 Hz: 3 mm GL + LR: Test 1
Vibrations
13.2 to 100 Hz: 1 g DNV: Class A
Materials All plastic materials are self-extinguishing UL94 (V0)
For detailed information: please see the individual types
Pollution deg. 2
Safety EN 61010-1
Quadratic instruments are supplied with protective cover fitted
over terminals
CE-classified for residential, commercial and light industry plus EN 61000-6-3/4
EMC
industrial environment EN 61000-6-1/2

DEIF A/S Page 4 of 7


Data sheet DQ
Dimensional details

1) For range 15 to 40 A = 59 mm

2) Protective cover

All dimensions in mm
Type A C B Panel cut-out Weight (approx.)
90° instruments
Q48-x 48 x 48 5.0 42.8 x 48.8 45 x 45 +0.3 0.090 kg
Q72-x 72 x 72 5.5 66.5 x 66.5 68 x 68 +0.4 0.200 kg
Q96-x 96 x 96 5.5 90 x 90 92 x 92 +0.4 0.210 kg
Q144-x 144 x 144 8.0 136 x 136 138 x 138 +0.5 0.350 kg
240° instruments
Q48-xc/c 48 x 48 5.0 42.8 x 48.8 45 x 45 +0.3 0.180 kg
Q72-xc/c 72 x 72 5.5 66.5 x 66.5 68 x 68 +0.4 0.220 kg
Q96-xc/c 96 x 96 5.5 90 x 90 92 x 92 +0.4 0.250 kg
Q144-xc/c 144 x 144 8.0 136 x 136 138 x 138 +0.5 0.400 kg

Exchange of scale

1) Press cover at top of instrument as shown.


2) Remove scale by means of a suitable tool (for example a screwdriver).
3) After exchange of scale: refit cover (press till it snaps into place). Calibration is not needed.

Note: Interrupt signal to terminals before exchanging the scale.

DEIF A/S Page 5 of 7


Data sheet DQ
Available variants
Item no. Variant no. Variant description
2961010420 01 DQ48-x all measuring inputs, without scale
2961010420 02 DQ48-x all measuring inputs, with standard scale
2961010420 03 DQ48-x measuring input 4 to 20 mA DC with customised scale and anti-glare glass
2961010420 04 DQ48-x with cos phi scale
2961060420 01 DQ48-c/-xc all measuring inputs, without scale
2961060420 02 DQ48-c/-xc all measuring inputs, with standard scale
2961060420 03 DQ48-c/-xc with cos phi scale
2961010720 01 DQ72-x all measuring inputs, without scale (except direct current >5 A DC)
2961010720 02 DQ72-x all measuring inputs, with standard scale (except direct current >5 A DC)
2961010720 03 DQ72-x direct current measurement with standard scale
2961010720 04 DQ72-x with cos phi scale
2961060720 01 DQ72-c/-xc all measuring inputs, without scale (except direct current >5 A)
2961060720 02 DQ72-c/-xc all measuring inputs, with standard scale (except direct current >5 A DC)
2961060720 03 DQ72-c/-xc direct current measurement with standard scale
2961060720 04 DQ72-c/-xc with cos phi scale
2961010920 01 DQ96-x all measuring inputs, without scale (except direct current >5 A DC)
2961010920 02 DQ96-x all measuring inputs, with standard scale (except direct current >5 A DC)
2961010920 03 DQ96-x direct current measurement with standard scale
2961010920 04 DQ96-x measuring input 4 to 20 mA DC with customised scale incl. anti-glare glass
2961010920 05 DQ96-x measuring input 4 to 20 mA DC with customised scale incl. anti-glare glass
and red pointer in glass
2961010920 06 DQ96-x with cos phi scale
2961060920 01 DQ96-c/-xc all measuring inputs, without scale (except direct current >5 A DC)
2961060920 02 DQ96-c/-xc all measuring inputs, with standard scale (except direct current >5 A DC)
2961060920 04 DQ96-c/-xc direct current measurement with standard scale
2961060920 05 DQ96-c/-xc with cos phi scale
2961011420 01 DQ144-x all measuring inputs, without scale (except direct current >5 A DC)
2961011420 02 DQ144-x all measuring inputs, with standard scale (except direct current >5 A DC)
2961011420 03 DQ144-x direct current measurement with standard scale
2961011420 06 DQ144-x with cos phi scale
2961061420 01 DQ144-c/-xc all measuring inputs, without scale (except direct current >5 A DC)
2961061420 02 DQ144-c/-xc all measuring inputs, with standard scale (except direct current >5 A DC)
2961061420 03 DQ144-c/-xc direct current measurement with standard scale
2961061420 06 DQ144-c/-xc with cos phi scale

DEIF A/S Page 6 of 7


Data sheet DQ

Order specifications
Variants:
Additional options to the standard
Mandatory information variant
Variant
Item no. Type no. Measuring range Scale Option Option

Example:
Additional options to the standard
Mandatory information variant
Variant
Item no. Type no. Measuring range Scale Option Option
Glass w/red
2961060420-02 DQ48-c 02 0 to 10V DC 0 to 100 % adjustable pointer
2961010920-03 DQ96-x 03 0 to 40 A 0 to 40 A IP54

Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
The English version of this document always contains the most recent and up-to-date information about the
product. DEIF does not take responsibility for the accuracy of translations, and translations might not be updated
at the same time as the English document. If there is a discrepancy, the English version prevails.

Due to our continuous development we reserve the right


to supply equipment which may vary from the described.
DEIF A/S, Frisenborgvej 33
DK-7800 Skive, Denmark

Tel.: +45 9614 9614, Fax: +45 9614 9615


E-mail: [email protected], URL: www.deif.com