Lumen Method Worksheet SI v2

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 8
At a glance
Powered by AI
The lumen method calculation worksheet is used to calculate the lighting design for a space based on illuminance levels, fixture types, and room dimensions and properties. It helps determine the number of fixtures needed to achieve the target illumination value.

The lumen method calculation worksheet is used to calculate lighting designs. It helps determine parameters like room cavity ratio (RCR), coefficient of utilization (CU), light loss factors (LLF), and the number of fixtures required to achieve the target illumination level for a space.

To calculate the CU, you first determine the low and high RCR values and their corresponding CU values (CU1 and CU2). Then based on the actual RCR, you calculate the difference (X) between it and the low RCR. Using CU1 and the difference X, you calculate the actual CU.

Lumen Method Calculation Worksheet

Project Information

Project Name: Type of Activity:


1 Target Illumination Value: lux
Fixture Type: # Lamps/Fixture:
Lamp Type: Initial Lamp Lumens:

Room Data

Ceiling Reflectance (Ρcc): Length * Width = Area


2 Wall Reflectance(Ρwc):
Floor Reflectance(Ρfc): * = 0 m2

Room Cavity Ratio (RCR)

Ceiling Height - Work surface = Cavity Height 5 * Cavity Height


3 - = 0.0
Area

5 * 0.0
0

With RCR, Calculate the Coefficient of Utilization (CU)

Low RCR: CU1: CU1 -


Actual RCR: Actual CU: 2
4 High RCR: CU2: 0.0000 -

Actual RCR - Low RCR CU1 -(


=X= =X=
1 High RCR - Low RCR 3
0.0000 -(

Light Loss Factors (LLF)

Luminaire Ambient Temp: Luminaire Dirt Depreciation:


Voltage Variation: Room Surface Depreciation:
5 Luminaire Surface
Depreciation:
Ballast Factor:
Lamp Lumen Depreciation:
Lamp Burn Out:

0.00 * 0.00 * 0.00 * 0.00 * 0.00 * 0.00 *


Calculations

Target Average Illuminance Level * Area


# of Fixtures Required =
# of Lamps / Fixture * Lamp Lumens * CU *
6
# of lamps per Lamp
Illumination due to # of fixtures * * * CU *
= fixture Lumens
specific # of fixtures
Area
Type of Activity:

# Lamps/Fixture:
Initial Lamp Lumens:

m2

* ( Length + Width )
= RCR
Area

*( 0 + 0 )
=
0

CU2 = Y

0.0000 = 0.0000

X * Y )= Actual CU

* 0.0000 )=

Total LLF

0.00 * 0.00 = 0.00


Area
= =
LLF

LLF
= lux
Lumen Method Calculation Worksheet
Project Information

Project Name: ABC Inc Type of Activity:


1 Target Illumination Value: 500 lux
Fixture Type: 20cm recessed downlight # Lamps/Fixture:
Lamp Type: 42w compact fluorescent Initial Lamp Lumens:

Room Data

Ceiling Reflectance (Ρcc): 80 Length * Width = Area


2 Wall Reflectance(Ρwc): 50
Floor Reflectance(Ρfc): 20 12 * 6 = 72 m2

Room Cavity Ratio (RCR)

Ceiling Height - Work surface = Cavity Height 5 * Cavity Height


3 3.0 - 0.8 = 2.2
Area

5 * 2.2
72

With RCR, Calculate the Coefficient of Utilization (CU)

Low RCR: 2.00 CU1: 0.6100 CU1 -


Actual RCR: 2.75 Actual CU: 0.5800 2
4 High RCR: 3.00 CU2: 0.5700 0.6100 -

Actual RCR - Low RCR CU1 -(


=X= 0.75
1 High RCR - Low RCR 3
0.6100 -(

Light Loss Factors (LLF)

Luminaire Ambient Temp: 1.00 Luminaire Dirt Depreciation:


Voltage Variation: 1.00 Room Surface Depreciation:
5 Luminaire Surface
Depreciation:
Ballast Factor:
1.00
0.98
Lamp Lumen Depreciation:
Lamp Burn Out:

1.00 * 1.00 * 1.00 * 0.98 * 0.78 * 0.97 *


Calculations

Target Average Illuminance Level * Area


# of Fixtures Required =
# of Lamps / Fixture * Lamp Lumens * CU *
6
# of lamps per Lamp
Illumination due to # of fixtures * * * CU *
= fixture Lumens
specific # of fixtures
Area
Type of Activity: Computer / Paper

# Lamps/Fixture: 1
Initial Lamp Lumens: 3200

m2

* ( Length + Width )
= RCR
Area

*( 12 + 6 )
= 2.75
72

CU2 = Y

0.5700 = 0.0400

X * Y )= Actual CU

0.7500 * 0.0400 )= 0.5800

0.78
0.97
0.85
0.98 Total LLF

0.85 * 0.98 = 0.62


Area
LLF
= 31.28 = 32
LLF
= 511.43 lux