UNDERSTANDING THE
NEW EN REGULATIONS
SAFE4 is a fire rated ductwork , the result
of 10 years of research and development,
produced in an ISO9001 quality control
management environment, and installed
by certified installers. The old standard of
BS476 has been superseded as of July 2013
and has been replaced by the new European
Standard EN 12101-7 for smoke extract and
EN 15871 for fire ductwork, kitchen extract
and pressurisation.
PERFORMANCE
CRITERIA
The test specifies the required components
measured under prescribed conditions or
periods of exposure to fire and includes
penetration seals, access doors, fixing
supports, unique insulation and sealant.
Airforce H&V Ltd., 47/48 Broomhill Close, Dublin 24, D24 KH64, Ireland.
Ph: +353 (0)1 4040 909 Email: [email protected] www.fireduct.eu
PENETRATION SEALS
Penetration seals are one of the areas of great
concern. They prevent fire spreading from one
compartment to another. Failure to achieve this
results in test termination.
ACCESS DOORS
(SAFE DOOR)
Access doors tested are not standard access
doors, they are fire rated doors which must
withstand temperatures of up to 1000⁰c.
DW172 states that all interior surfaces of the
ductwork shall be accessible for cleaning and
inspection purposes. It is recommended that
access doors are installed every 3 meters.
These access doors must be the access doors
tested during Type A, Type B and Type C both
horizontally and vertically.
www.airforcehv.com Email: [email protected] www.fireduct.eu
INSULATION
Fire rated insulation ensures that the
temperature measured (outside in Type A,
and inside in Type B) does not exceed 140⁰C
mean average above ambient during the test
and is deemed automatically failed if any
thermocouple rises to 180⁰C.
INTEGRITY
The integrity of the entire system is based
on the performance of all elements from
penetration seals, to smoke leakage to cross
sectional area.
Airforce H&V Ltd., 47/48 Broomhill Close, Dublin 24, D24 KH64, Ireland.
Ph: +353 (0)1 4040 909 Email: [email protected] www.fireduct.eu
TEST TYPE A Compartment Adjacent Compartment
with Fire Outbreak
T1 Temperature Sensor
Type A testing involves fire outside
the duct. The test furnace is raised to
Duct resists penetration
operating temperatures of 1000⁰c of fire from outside
with the specimen suspended Ventilation or Smoke Extract Opening
within. The duct passes through
the dedicated penetration seal
where various measurements and Type A Duct (fire outside) No fire penetration or transfer
observations are used to determine
its suitability and performance.
In this test no fire passes through the duct. up to 80 thermocouples inside the ducting.
The duct is tested for leakage, integrity and This determines the kitchen extract insulation
the rise in temperature where the duct is value.
insulated. The temperature is measured by
TEST TYPE C
Type C is carried out on smoke extract only.
It can only be tested once Type B has been
completed at a pressure of 500pa. The
insulation value achieved in Type B is the one
that is used for this classification.
www.airforcehv.com Email: [email protected] www.fireduct.eu
LEAKAGE
Leakage is set to different parameters for
smoke extract and fire rated duct. Smoke
extract is tested to a maximum of 10m3/hr/m2
and a low of 5m3/hr/m2. Fire duct is tested at a
higher rate to a maximum of 15m3/hr/m2 and a
low of less than 10m3/hr/m2.
CROSS SECTIONAL
AREA
Cross sectional area is the mechanical stability
of the duct being tested. Failure occurs when
the duct has a deflection and the cross sectional
area is reduced by more than 10%. This is
when the duct weakens as a result of full fire
conditions and negative pressure causing the
duct to convex. The duct becomes redundant
when it changes shape sufficiently impairing its
functionality and it loses the ability to perform.
TEST PRESSURE
Test pressure is typically carried out at a
minimum of 300pa for fire duct and 500pa
for smoke extract. During testing there is an
option to increase the pressure to a maximum
of 1500 pascals.
Airforce H&V Ltd., 47/48 Broomhill Close, Dublin 24, D24 KH64, Ireland.
Ph: +353 (0)1 4040 909 Email: [email protected] www.fireduct.eu
HORIZONTAL
& VERTICAL
All of the tests should be carried out both
horizontally and vertically. It is imperative
that the testing has been completed in both
as all real installations involve an element of
horizontal and vertical applications.
CLASSIFICATION
The classification shall indicate if the
performance criteria are satisfied by fire from Classification symbols used:
inside or fire from outside or both and whether
E Integrity
it applies to vertical or horizontal orientations
or both. I Insulation
For example a classification of EI 30 (veho
S Smoke leakage
i<>o) indicates a ventilation duct capable of
satisfying 30 minutes integrity and insulation t class in time
from both inside to outside and vice versa in
both vertical and horizontal applications. Ve Vertical Duct
30, 60, 90 and 120 minutes i>o tested for fire inside duct
Fire rated/Kitchen Extract i<o tested for fire outside the duct
EI 15, 20, 30, 45, 60, 90, 120, and 240
i<>o tested for both respectively
E (uninsulated duct) 30, 60
www.airforcehv.com Email: [email protected] www.fireduct.eu
THIRD PARTY
CERTIFICATION
Airforce H&V Ltd., 47/48 Broomhill Close, Dublin 24, D24 KH64, Ireland.
Ph: +353 (0)1 4040 909 Email: [email protected] www.fireduct.eu
CE MARKING OF THE CE marking ensures that the fire duct
manufacturer has tested all products to the
FIRE RATED DUCT present relevant BS EN tests 1366-1, 1366-8
and 1366-9 at a notified certification body.
CE marking of products with
There is a requirement for the fire duct
harmonised (hEN) standards
manufacturer to have a quality management
became mandatory on the 1st of
system (ISO 9001), and also having passed
July 2013 as stated within the requirements of
a FPC (factory production control) for the
the European directive. Consequently smoke
manufacturing and to have third party
extract duct covered by product standard
certification for the installation of fire duct
BS EN 12101-7 must be CE marked (DW144).
systems.
The old standard BS476 cannot support CE
marking of construction products and has
been withdrawn where a harmonised standard
exists.
www.airforcehv.com Email: [email protected] www.fireduct.eu
SPECIFICATION
SMOKE EXTRACT
All smoke extract ductwork will be to (hEN)
standard 12101-7 and tested to EN 1366-8 for
multi compartment or EN 1366-9 for single
See through the new EN regulations.
compartment.
Where multi compartment ductwork is for testing outside (A), inside (B) and smoke
required it must be insulated to the same extract (C) in both a horizontal and vertical
period of time as the compartment through position.
which it passes as required in DW172.
All ductwork rated “S” for smoke leakage and
All smoke extract will carry CE Marking from have been tested to high pressure 1500 PA. All
July 2013 and is to be installed under a third smoke extract will be tested in a flexible wall
party certifier such as Firas as identified in and be suitable for installation in stud partition,
DW144. All ductwork must have classification block wall and concrete floor.
KITCHEN EXTRACT
All Kitchen Extract will be to the EN standard
15871 and tested to EN 1366-1, and must be
insulated to the same period of time as the
compartment through which it passes as
required in DW172.
Airforce H&V Ltd., 47/48 Broomhill Close, Dublin 24, D24 KH64, Ireland.
Ph: +353 (0)1 4040 909 Email: [email protected] www.fireduct.eu
FIRE RATED
DUCTWORK
All fire rated and pressurisation ductwork will
be to EN standard 15871 and tested to EN 1366‑1
vertically and horizontally for Type A (fire
outside) and Type B (fire inside).
AIRFORCE H&V
Airforce H&V is primarily a sales company. That
means we must be responsive, we must be
versatile, we must be keen to do business, and
most importantly we must be able to offer you
that much more than our rivals.
We believe we are very good at what we do, we Most of all, we would like you to try us out
would like to think the very best, but then, who for yourself, and experience first-hand the
wouldn’t say that! Sure, we could go on to boast difference that we believe we bring, that will
about our quality standards in manufacturing, make you a customer of ours for life.
www.airforcehv.com Email: [email protected] www.fireduct.eu
Must Cal
l
Airforce
H& V!