0% found this document useful (0 votes)
137 views1 page

Techimp Pdcheck HVPD Longshot Graphic Visualization

The document compares two PD detection systems: Techimp PDCheck and HVPD LongShot. [1] Techimp PDCheck offers more advanced graphic visualization, noise rejection, source separation and identification capabilities compared to HVPD LongShot. [2] It can filter noise, separate different PD sources, and identify defects to determine their harmfulness. [3] PDCheck also enables localization and works with multiple sensor types, offering wider bandwidth and resolution than LongShot.

Uploaded by

Khoiln
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
137 views1 page

Techimp Pdcheck HVPD Longshot Graphic Visualization

The document compares two PD detection systems: Techimp PDCheck and HVPD LongShot. [1] Techimp PDCheck offers more advanced graphic visualization, noise rejection, source separation and identification capabilities compared to HVPD LongShot. [2] It can filter noise, separate different PD sources, and identify defects to determine their harmfulness. [3] PDCheck also enables localization and works with multiple sensor types, offering wider bandwidth and resolution than LongShot.

Uploaded by

Khoiln
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Techimp PDCheck HVPD LongShot

Graphic Complete PRPD time based pattern and T-F map visualization. Bar type PRPD Pattern (repetitive pulse information in unknown, no
visualization polarity information of the pulse)

Noise rejection TF map filtering can filter out certain PD phenomena and this technology is Only based on Pulse shape and Frequency contents of the pulse
most effective for on-line case where there are high level of noise with (multiple noises cannot be eliminated, risk of false alarms)
different PD activities
Separation T-F (Frequency map) is the most reliable source for discriminating pulses Separation based on pulse duration/frequency contents of the pulse,
originated by different PD phenomena inside the EUT, thus it is possible to This is not possible to separate different PD types according to its
separate noise and different PD activities based on their harmfulness harmfulness to the insulation system. Risk of false alarms!
Identification Identification of different PD sources based on fuzzy logic algorithms, thus Cable PD, Local PD, Noise (Identification is only possible for those
enabling the final user to understand the real harmfulness of the defects. three types; it is impossible to find different PD types; internal,
surface, corona PD). Not possible an effective diagnostic.
Localization YES either via frequency/amplitude analysis or (for cables only) and via TDR Yes, less effective because of the lower Signal/Noise Ratio.
reflectometry technique and with any available sensor.
PD Channels 3 PD (extensible to 6 with multiplexer), 1 Sync 4 PD, 1Synch
Resolution 10 bit 12 bit
Bandwidth Ultra Wide Band 0 – 400MHz
15 kHz- 30 MHz (up to 3GHz with UHF sensor using Frequency shifter)
Input impedance 50 Ohm N/A
Sensors HFCT/TEV/COUPLER/ UHF sensors / etc. HFCT/TEV/Coupler/Acoustic
Sync channel 1 1
Galvanic Wifi, Fiber Optic Connection No
Isolation
Notes