Multiple Feeder Protection System: Grid Solutions
Multiple Feeder Protection System: Grid Solutions
Multiple Feeder Protection System: Grid Solutions
Grid Solutions
F35
Multiple Feeder Protection
System
Instruction Manual
Product version: 7.7x
GE publication code: 1601-0106-AG2 (GEK-131037A)
E83849
S T ER
GI
ED
RE
ISO 9001
LISTED
G
E
IN
M U LT I L
IND.CONT. EQ.
52TL
1601-0106-AG2
Copyright © 2018 GE Multilin Inc. All rights reserved.
F35 Multiple Feeder Protection System Instruction Manual for version 7.7x.
F35, FlexLogic, FlexElement, FlexCurve, FlexAnalog, FlexInteger, FlexState, EnerVista,
CyberSentry, HardFiber, Multilin, and GE Multilin are trademarks or registered trademarks
of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-0106-AG2 (May 2018)
F35 Multiple Feeder Protection System
Table of contents
ABBREVIATIONS
INDEX
Chapter 1: Introduction
Introduction
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Ensure that all connections to the product are correct so as to avoid accidental risk of shock
and/or fire, for example such as can arise from high voltage connected to low voltage terminals.
Follow the requirements of this manual, including adequate wiring size and type, terminal torque settings, voltage,
current magnitudes applied, and adequate isolation/clearance in external wiring from high to low voltage circuits.
Use the device only for its intended purpose and application.
Ensure that all ground paths are uncompromised for safety purposes during device operation and service.
Ensure that the control power applied to the device, the alternating current (AC), and voltage input match the ratings
specified on the relay nameplate. Do not apply current or voltage in excess of the specified limits.
Only qualified personnel are to operate the device. Such personnel must be thoroughly familiar with all safety
cautions and warnings in this manual and with applicable country, regional, utility, and plant safety regulations.
1 Hazardous voltages can exist in the power supply and at the device connection to current transformers, voltage
transformers, control, and test circuit terminals. Make sure all sources of such voltages are isolated prior to
attempting work on the device.
Hazardous voltages can exist when opening the secondary circuits of live current transformers. Make sure that
current transformer secondary circuits are shorted out before making or removing any connection to the current
transformer (CT) input terminals of the device.
For tests with secondary test equipment, ensure that no other sources of voltages or currents are connected to such
equipment and that trip and close commands to the circuit breakers or other switching apparatus are isolated,
unless this is required by the test procedure and is specified by appropriate utility/plant procedure.
When the device is used to control primary equipment, such as circuit breakers, isolators, and other switching
apparatus, all control circuits from the device to the primary equipment must be isolated while personnel are working
on or around this primary equipment to prevent any inadvertent command from this device.
Use an external disconnect to isolate the mains voltage supply.
Personal safety can be affected if the product is physically modified by the end user. Modifications to the product
outside of recommended wiring configuration, hardware, or programming boundaries is not recommended end-use
practice. Product disassembly and repairs are not permitted. All service needs to be conducted by the factory.
LED transmitters are classified as IEC 60825-1 Accessible Emission Limit (AEL) Class 1M. Class 1M
devices are considered safe to the unaided eye. Do not view directly with optical instruments.
This product is rated to Class A emissions levels and is to be used in Utility, Substation Industrial
environments. Not to be used near electronic devices rated for Class B levels.
Product description
The F35 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are
upgradable.
The following single-line diagram illustrates the relay functionality using American National Standards Institute (ANSI)
device numbers.
Table 2-1: ANSI device numbers and functions supported
Device number Function Device number Function
2 27P
27X
Phase undervoltage
Auxiliary undervoltage
51N
51P
Neutral time overcurrent
Phase time overcurrent
32N Wattmetric zero-sequence directional 51_2 Negative-sequence time overcurrent
49 Thermal overload protection 52 AC circuit breaker
50DD Disturbance detector 59N Neutral overvoltage
50G Ground instantaneous overcurrent 59P Phase overvoltage
50N Neutral instantaneous overcurrent 59X Auxiliary overvoltage
50P Phase instantaneous overcurrent 79 Autoreclose
50_2 Negative-sequence instantaneous overcurrent 81U Underfrequency
51G Ground time overcurrent
52 2 3 4 5
79
Same functions as breaker 1
CLOSE TRIP
Monitoring
Transducer
FlexElementsTM inputs
2
2.2 Security
The following security features are available:
• Password security — Basic security present by default
• EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The
feature is present by default in the EnerVista software.
• CyberSentry security — Advanced security available using a software option. When purchased, the option is enabled
automatically, and the default Password security and EnerVista security are disabled.
Administrator
Engineer
Operator
Observer Supervisor 2
842838A2.CDR
Table Notes:
RW = read and write access
R = read access
Supervisor = RW (default), Administrator = R (default), Administrator = RW (only if Supervisor role is disabled)
NA = the permission is not enforced by CyberSentry security
The R-GOOSE protocol described in IEC 61850-8-1 is available through the IEC 61850 software option. R-GOOSE
security requires the CyberSentry software option.
For Japanese, the settings display in Japanese on the graphical front panel, while the keys printed on the panel are
in English.
2
BW | | | | | | | | | IEEE 1588 and IEC 61850 and PID controller
D0 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1
C0 | | | | | | | | | Parallel Redundancy Protocol (PRP)
C1 | | | | | | | | | PRP and Ethernet Global Data
C3 | | | | | | | | | PRP and IEC 61850
C4 | | | | | | | | | PRP, Ethernet Global Data, and IEC 61850
CW | | | | | | | | | PRP, PID controller, and IEC 61850
D1 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and Ethernet Global Data (EGD)
D3 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D4 | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
DW | | | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and PID controller
E0 | | | | | | | | | IEEE 1588 and PRP
E1 | | | | | | | | | IEEE 1588, PRP, and Ethernet Global Data
E3 | | | | | | | | | IEEE 1588, PRP, and IEC 61850
E4 | | | | | | | | | IEEE 1588, PRP, Ethernet Global Data, and IEC 61850
EW | | | | | | | | | IEEE 1588, PRP, PID controller, and IEC 61850
F0 | | | | | | | | | PRP and CyberSentry Lvl 1
F1 | | | | | | | | | PRP, CyberSentry Lvl 1, and Ethernet Global Data
F3 | | | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
F4 | | | | | | | | | PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
FW | | | | | | | | | PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
G0 | | | | | | | | | IEEE 1588 and PRP
G1 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and Ethernet Global Data
G3 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G4 | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
GW | | | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
J0 | | | | | | | | | IEC 60870-5-103
J1 | | | | | | | | | IEC 60870-5-103 + EGD
J3 | | | | | | | | | IEC 60870-5-103 + IEC 61850
J4 | | | | | | | | | IEC 60870-5-103 + EGD + IEC 61850
JW | | | | | | | | | IEC 60870-5-103 + PID controller + IEC 61850
K0 | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103
K1 | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD
K3 | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + IEC 61850
K4 | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD + IEC 61850
KW | | | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + PID controller + IEC 61850
L0 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1
L1 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD
L3 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850
L4 | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD + IEC 61850
LW | | | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + PID controller + IEC 61850
MOUNT/COATING H | | | | | | | | Horizontal (19” rack)
A | | | | | | | | Horizontal (19” rack) with harsh environmental coating
FRONT PANEL + INTERFACE C | | | | | | | English display
D | | | | | | | French display
R | | | | | | | Russian display
A | | | | | | | Chinese display
P | | | | | | | English display with 4 small and 12 large programmable pushbuttons
G | | | | | | | French display with 4 small and 12 large programmable pushbuttons
S | | | | | | | Russian display with 4 small and 12 large programmable pushbuttons
B | | | | | | | Chinese display with 4 small and 12 large programmable pushbuttons
K | | | | | | | Enhanced front panel with English display
M | | | | | | | Enhanced front panel with French display
Q | | | | | | | Enhanced front panel with Russian display
U | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | | | Enhanced front panel with Turkish display
Y | | | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | | | Enhanced front panel with German display
J | | | | | | | Enhanced front panel with German display and user-programmable pushbuttons
H | | | | | | | Enhanced front panel with Polish display
O | | | | | | | Enhanced front panel with Polish display and user-programmable pushbuttons
E | | | | | | | 7" Graphical front panel display in multiple languages with USB front port and user-
programmable pushbuttons (English, French, Chinese, Russian, Turkish, German,
Polish, Japanese)
POWER SUPPLY H | | | | | | 125 / 250 V AC/DC power supply
(redundant supply must H | | | | | RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
be same type as main supply) L | | | | | | 24 to 48 V (DC only) power supply
L | | | | | RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
ENHANCED DIAGNOSTICS CT/VT | | XX | XX | No DSP module (rear slots M and U only)
DSP 8L | 8L | 8L | Standard 4CT/4VT with enhanced diagnostics
(requires all DSP to be enhanced 8M | 8M | 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
diagnostic) 8N | 8N | 8N | Standard 8CT with enhanced diagnostics
8R | 8R | 8R | Sensitive Ground 8CT with enhanced diagnostics
8V | | | | | Standard 8VT with enhanced diagnostics (only one module supported)
2
6G 6G 6G 6G 6G 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H 6H 6H 6H 6H 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K 6K 6K 6K 6K 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L 6L 6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 6M 6M 6M 6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 6N 6N 6N 6N 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6P 6P 6P 6P 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 6R 6R 6R 6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 6S 6S 6S 6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 6T 6T 6T 6T 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6U 6U 6U 6U 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 6V 6V 6V 6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8
contact inputs
6W 6W 6W 6W 6W 30 Contact inputs - pin terminals (max 4 modules)
6X 6X 6X 6X 6X 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
TRANSDUCER INPUTS/OUTPUTS 5A 5A 5A 5A 5A 4 DCmA inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
(select a maximum of 3 per unit) 5C 5C 5C 5C 5C 8 RTD inputs
5D 5D 5D 5D 5D 4 RTD inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
5E 5E 5E 5E 5E 4 RTD inputs, 4 DCmA inputs
5F 5F 5F 5F 5F 8 DCmA inputs
INTER-RELAY 2A C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E Bi-phase, single channel
2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
2I Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode,
Laser
2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode,
Laser
72 1550 nm, single-mode, Laser, 1 Channel
73 1550 nm, single-mode, Laser, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, Laser
75 Channel 1 - G.703; Channel 2 - 1550 nm, single-mode Laser
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, Laser, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multimode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multimode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, Laser, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
F35 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
D0 | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D1 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and Ethernet Global Data (EGD)
D3 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D4 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
DW | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and PID controller
E0 | | | | | | | IEEE 1588 and PRP
E1 | | | | | | | IEEE 1588, PRP, and Ethernet Global Data
E3 | | | | | | | IEEE 1588, PRP, and IEC 61850
E4 | | | | | | | IEEE 1588, PRP, Ethernet Global Data, and IEC 61850
EW | | | | | | | IEEE 1588, PRP, PID controller, and IEC 61850
F0 | | | | | | | PRP and CyberSentry Lvl 1
F1 | | | | | | | PRP, CyberSentry Lvl 1, and Ethernet Global Data
F3 | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
2
F4 | | | | | | | PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
FW | | | | | | | PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
G0 | | | | | | | IEEE 1588 and PRP
G1 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and Ethernet Global Data
G3 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G4 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
GW | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
J0 | | | | | | | IEC 60870-5-103
J1 | | | | | | | IEC 60870-5-103 + EGD
J3 | | | | | | | IEC 60870-5-103 + IEC 61850
J4 | | | | | | | IEC 60870-5-103 + EGD + IEC 61850
JW | | | | | | | IEC 60870-5-103 + PID controller + IEC 61850
K0 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103
K1 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD
K3 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + IEC 61850
K4 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD + IEC 61850
KW | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + PID controller + IEC 61850
L0 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1
L1 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD
L3 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850
L4 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD + IEC 61850
LW | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + PID controller + IEC 61850
MOUNT/COATING V | | | | | | Vertical (3/4 rack)
B | | | | | | Vertical (3/4 rack) with harsh environmental coating
FRONT PANEL + INTERFACE F | | | | | English display
D | | | | | French display
R | | | | | Russian display
A | | | | | Chinese display
K | | | | | Enhanced front panel with English display
M | | | | | Enhanced front panel with French display
Q | | | | | Enhanced front panel with Russian display
U | | | | | Enhanced front panel with Chinese display
L | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | Enhanced front panel with Turkish display
Y | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | Enhanced front panel with German display
J | | | | | Enhanced front panel with German display and user-programmable pushbuttons
POWER SUPPLY H | | | | 125 / 250 V AC/DC power supply
L | | | | 24 to 48 V (DC only) power supply
ENHANCED DIAGNOSTICS CT/VT DSP XX | XX | No DSP module (rear slots M and U only)
(requires all DSP to be enhanced 8L | 8L | Standard 4CT/4VT with enhanced diagnostics
diagnostic) 8M | 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
8N | 8N | Standard 8CT with enhanced diagnostics
8R | 8R | Sensitive Ground 8CT with enhanced diagnostics
8V | | | Standard 8VT with enhanced diagnostics (only one module supported)
CONTACT INPUTS/OUTPUTS XX XX XX No Module
4A 4A 4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4B 4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C 4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D 4D 16 Contact inputs with Auto-Burnishing (maximum of three modules within a case)
4L 4L 4L 14 Form-A (no monitoring) Latching outputs
67 67 67 8 Form-A (no monitoring) outputs
6A 6A 6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B 6B 6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C 6C 6C 8 Form-C outputs
6D 6D 6D 16 Contact inputs
6E 6E 6E 4 Form-C outputs, 8 contact inputs
6F 6F 6F 8 Fast Form-C outputs
6G 6G 6G 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H 6H 6H 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K 6K 6K 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 6M 6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 6N 6N 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6P 6P 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 6R 6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 6S 6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 6T 6T 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6U 6U 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 6V 6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact inputs
6W 6W 6W 30 Contact inputs - pin terminals (max 4 modules)
6X 6X 6X 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
TRANSDUCER INPUTS/OUTPUTS 5A 5A 5A 4 DCmA inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
(select a maximum of 3 per unit) 5C 5C 5C 8 RTD inputs
5D 5D 5D 4 RTD inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
5E 5E 5E 4 RTD inputs, 4 DCmA inputs
5F 5F 5F 8 DCmA inputs
INTER-RELAY 2A C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E Bi-phase, single channel
For the last module, rear slot P is used for digital and transducer 2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
input/output modules; rear slot R is used for inter-relay 2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
communications modules. 2I Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser
72 1550 nm, single-mode, Laser, 1 Channel
73 1550 nm, single-mode, Laser, 2 Channel
F35 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, Laser
75 Channel 1 - G.703; Channel 2 - 1550 nm, single-mode Laser
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, Laser, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multimode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multimode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
2
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, Laser, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
2
U | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | | | Enhanced front panel with Turkish display
Y | | | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | | | Enhanced front panel with German display
J | | | | | | | Enhanced front panel with German display and user-programmable pushbuttons
H | | | | | | | Enhanced front panel with Polish display
O | | | | | | | Enhanced front panel with Polish display and user-programmable pushbuttons
E | | | | | | | 7" Graphical front panel display in multiple languages with USB front port and
user-programmable pushbuttons (English, French, Chinese, Russian, Turkish,
German, Polish, Japanese)
POWER SUPPLY H | | | | | | 125 / 250 V AC/DC power supply
(redundant supply must H | | | | | RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
be same type as main supply) L | | | | | | 24 to 48 V (DC only) power supply
L | | | | | RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
PROCESS BUS MODULE | 81 | | | | Eight-port digital process bus module
CONTACT INPUTS/OUTPUTS XX XX XX XX XX No Module
4A 4A | 4 Solid-State (no monitoring) MOSFET outputs
4B 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D | 16 Contact inputs with Auto-Burnishing (maximum of three modules within a case)
4L 4L | 14 Form-A (no monitoring) Latching outputs
67 67 | 8 Form-A (no monitoring) outputs
6A 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C 6C | 8 Form-C outputs
6D 6D | 16 Contact inputs
6E 6E | 4 Form-C outputs, 8 contact inputs
6F 6F | 8 Fast Form-C outputs
6G 6G | 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H 6H | 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K 6K | 4 Form-C and 4 Fast Form-C outputs
6L 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 6N | 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6P | 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 6T | 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6U | 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8
contact inputs
6W 6W | 30 Contact inputs - pin terminals (max 4 modules)
6X 6X | 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
INTER-RELAY 2A C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E Bi-phase, single channel
2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
2I Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode,
Laser
2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode,
Laser
72 1550 nm, single-mode, Laser, 1 Channel
73 1550 nm, single-mode, Laser, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, Laser
75 Channel 1 - G.703; Channel 2 - 1550 nm, single-mode Laser
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, Laser, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multimode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multimode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, Laser, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
Table 2-7: F35 order codes for reduced-size vertical units with process bus
F35 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
BASE UNIT F35 | | | | | | | | | Base Unit
CPU T | | | | | | | | RS485 and Three Multi-mode fiber 100Base-FX (SFP with LC)
U | | | | | | | | RS485 and Two Multi-mode fiber 100Base-FX (SFP with LC), One 10/100Base-TX (SFP with RJ45)
V | | | | | | | | RS485 and Three 10/100Base-TX (SFP with RJ45)
W | | | | | | | | RS485 with Two 100Base-FX Ethernet, multimode ST + 10/100Base-TX Ethernet, RJ-45
SOFTWARE OPTIONS 00 | | | | | | | No Software Options
01 | | | | | | | Ethernet Global Data (EGD)
03 | | | | | | | IEC 61850
04 | | | | | | | Ethernet Global Data (EGD) and IEC 61850
A0 | | | | | | | CyberSentry Lvl 1
A1 | | | | | | | CyberSentry Lvl 1 and Ethernet Global Data (EGD)
2
A3 | | | | | | | CyberSentry Lvl 1 and IEC 61850
A4 | | | | | | | CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
AW | | | | | | | CyberSentry Lvl 1 and IEC 61850 and PID controller
B0 | | | | | | | IEEE 1588
B1 | | | | | | | IEEE 1588 and Ethernet Global Data (EGD)
B3 | | | | | | | IEEE 1588 and IEC 61850
B4 | | | | | | | IEEE 1588 and IEC 61850 and Ethernet Global Data (EGD)
BW | | | | | | | IEEE 1588 and IEC 61850 and PID controller
C0 | | | | | | | Parallel Redundancy Protocol (PRP)
C1 | | | | | | | PRP and Ethernet Global Data
C3 | | | | | | | PRP and IEC 61850
C4 | | | | | | | PRP, Ethernet Global Data, and IEC 61850
CW | | | | | | | PRP, PID controller, and IEC 61850
D0 | | | | | | | IEEE 1588 and CyberSentry Lvl 1
D1 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and Ethernet Global Data (EGD)
D3 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850
D4 | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and Ethernet Global Data (EGD)
DW | | | | | | | IEEE 1588 and CyberSentry Lvl 1 and IEC 61850 and PID controller
E0 | | | | | | | IEEE 1588 and PRP
E1 | | | | | | | IEEE 1588, PRP, and Ethernet Global Data
E3 | | | | | | | IEEE 1588, PRP, and IEC 61850
E4 | | | | | | | IEEE 1588, PRP, Ethernet Global Data, and IEC 61850
EW | | | | | | | IEEE 1588, PRP, PID controller, and IEC 61850
F0 | | | | | | | PRP and CyberSentry Lvl 1
F1 | | | | | | | PRP, CyberSentry Lvl 1, and Ethernet Global Data
F3 | | | | | | | PRP, CyberSentry Lvl 1, and IEC 61850
F4 | | | | | | | PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
FW | | | | | | | PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
G0 | | | | | | | IEEE 1588 and PRP
G1 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and Ethernet Global Data
G3 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G4 | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
GW | | | | | | | IEEE 1588, PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
J0 | | | | | | | IEC 60870-5-103
J1 | | | | | | | IEC 60870-5-103 + EGD
J3 | | | | | | | IEC 60870-5-103 + IEC 61850
J4 | | | | | | | IEC 60870-5-103 + EGD + IEC 61850
JW | | | | | | | IEC 60870-5-103 + PID controller + IEC 61850
K0 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103
K1 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD
K3 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + IEC 61850
K4 | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + EGD + IEC 61850
KW | | | | | | | IEEE1588 + PRP + IEC 60870-5-103 + PID controller + IEC 61850
L0 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1
L1 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD
L3 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850
L4 | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD + IEC 61850
LW | | | | | | | IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + PID controller + IEC 61850
MOUNT/COATING V | | | | | | Vertical (3/4 rack)
B | | | | | | Vertical (3/4 rack) with harsh environmental coating
FRONT PANEL + INTERFACE F | | | | | English display
D | | | | | French display
R | | | | | Russian display
A | | | | | Chinese display
K | | | | | Enhanced front panel with English display
M | | | | | Enhanced front panel with French display
Q | | | | | Enhanced front panel with Russian display
U | | | | | Enhanced front panel with Chinese display
L | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
W | | | | | Enhanced front panel with Turkish display
Y | | | | | Enhanced front panel with Turkish display and user-programmable pushbuttons
I | | | | | Enhanced front panel with German display
J | | | | | Enhanced front panel with German display and user-programmable pushbuttons
F35 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
POWER SUPPLY H | | | | 125 / 250 V AC/DC power supply
L | | | | 24 to 48 V (DC only) power supply
CT/VT MODULES | 81 | | Eight-port digital process bus module
CONTACT INPUTS/OUTPUTS XX XX XX No Module
4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 16 Contact inputs with Auto-Burnishing (maximum of three modules within a case)
4L 14 Form-A (no monitoring) Latching outputs
67 8 Form-A (no monitoring) outputs
6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C 8 Form-C outputs
2
6D 16 Contact inputs
6E 4 Form-C outputs, 8 contact inputs
6F 8 Fast Form-C outputs
6G 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K 4 Form-C and 4 Fast Form-C outputs
6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T 4 Form-A (no monitoring) outputs, 8 contact inputs
6U 6 Form-A (no monitoring) outputs, 4 contact inputs
6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact inputs
6W 30 Contact inputs - pin terminals (max 4 modules)
6X 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
INTER-RELAY 2A C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E Bi-phase, single channel
For the last module, rear slot P is used for digital and transducer 2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
input/output modules; rear slot R is used for inter-relay 2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
communications modules. 2I Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
2J Channel 1 - IEEE C37.94, MM, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser
72 1550 nm, single-mode, Laser, 1 Channel
73 1550 nm, single-mode, Laser, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, Laser
75 Channel 1 - G.703; Channel 2 - 1550 nm, single-mode Laser
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, Laser, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multimode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multimode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, Laser, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
UR - ** - *
FRONT PANEL + INTERFACE | 3C | Horizontal front panel with keypad and English display
| 3D | Horizontal front panel with keypad and French display
| 3R | Horizontal front panel with keypad and Russian display
| 3A | Horizontal front panel with keypad and Chinese display
| 3P | Horizontal front panel with keypad, user-programmable pushbuttons, and English display
| 3G | Horizontal front panel with keypad, user-programmable pushbuttons, and French display
| 3S | Horizontal front panel with keypad, user-programmable pushbuttons, and Russian display
| 3B | Horizontal front panel with keypad, user-programmable pushbuttons, and Chinese display
| 3K | Enhanced front panel with English display
| 3M | Enhanced front panel with French display
| 3Q | Enhanced front panel with Russian display
| 3U | Enhanced front panel with Chinese display
| 3L | Enhanced front panel with English display and user-programmable pushbuttons
2
| 3N | Enhanced front panel with French display and user-programmable pushbuttons
| 3T | Enhanced front panel with Russian display and user-programmable pushbuttons
| 3V | Enhanced front panel with Chinese display and user-programmable pushbuttons
| 3I | Enhanced front panel with German display
| 3J | Enhanced front panel with German display and user-programmable pushbuttons
| 3H | Enhanced front panel with Polish display
| 3O | Enhanced front panel with Polish display and user-programmable pushbuttons
| 3Z | Enhanced front panel with Japanese display
| 3X | Enhanced front panel with Japanese display and user-programmable pushbuttons
| 3E | 7" Graphical front panel display in multiple languages with USB front port and user-programmable pushbuttons
CONTACT INPUTS AND OUTPUTS | 4A | 4 Solid-State (no monitoring) MOSFET outputs
| 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
| 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
| 4D | 16 Contact inputs with Auto-Burnishing
| 4L | 14 Form-A (no monitoring) Latching outputs
| 67 | 8 Form-A (no monitoring) outputs
| 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
| 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
| 6C | 8 Form-C outputs
| 6D | 16 Contact inputs
| 6E | 4 Form-C outputs, 8 contact inputs
| 6F | 8 Fast Form-C outputs
| 6G | 4 Form-A (voltage with optional current) outputs, 8 contact inputs
| 6H | 6 Form-A (voltage with optional current) outputs, 4 contact inputs
| 6K | 4 Form-C and 4 Fast Form-C outputs
| 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
| 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
| 6N | 4 Form-A (current with optional voltage) outputs, 8 contact inputs
| 6P | 6 Form-A (current with optional voltage) outputs, 4 contact inputs
| 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
| 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
| 6T | 4 Form-A (no monitoring) outputs, 8 contact inputs
| 6U | 6 Form-A (no monitoring) outputs, 4 contact inputs
| 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact inputs
| 6W | 30 Contact inputs - pin terminals (max 4 modules)
| 6X | 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
CT/VT MODULES | 8L | Standard 4CT/4VT with enhanced diagnostics
(not available for the C30) | 8N | Standard 8CT with enhanced diagnostics
| 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
| 8R | Sensitive Ground 8CT with enhanced diagnostics
| 8V | Standard 8VT with enhanced diagnostics (only one module supported)
INTER-RELAY COMMUNICATIONS | 2A | C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
| 2B | C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
| 2E | Bi-phase, single channel
| 2F | Bi-phase, dual channel
| 2G | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
| 2H | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 2I | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
| 2J | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser
| 72 | 1550 nm, single-mode, Laser, 1 Channel
| 73 | 1550 nm, single-mode, Laser, 2 Channel
| 74 | Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, Laser
| 75 | Channel 1 - G.703; Channel 2 - 1550 nm, single-mode Laser
| 76 | IEEE C37.94, 820 nm, multimode, LED, 1 Channel
| 77 | IEEE C37.94, 820 nm, multimode, LED, 2 Channels
| 7A | 820 nm, multimode, LED, 1 Channel
| 7B | 1300 nm, multimode, LED, 1 Channel
| 7C | 1300 nm, single-mode, ELED, 1 Channel
| 7D | 1300 nm, single-mode, Laser, 1 Channel
| 7E | Channel 1 - G.703; Channel 2 - 820 nm, multimode
| 7F | Channel 1 - G.703; Channel 2 - 1300 nm, multimode
| 7G | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
| 7H | 820 nm, multimode, LED, 2 Channels
| 7I | 1300 nm, multimode, LED, 2 Channels
| 7J | 1300 nm, single-mode, ELED, 2 Channels
| 7K | 1300 nm, single-mode, Laser, 2 Channels
| 7L | Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
| 7M | Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
| 7N | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
| 7P | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
| 7Q | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
| 7R | G.703, 1 Channel
| 7S | G.703, 2 Channels
| 7T | RS422, 1 Channel
| 7W | RS422, 2 Channels
TRANSDUCER INPUTS/OUTPUTS | 5A | 4 DCmA inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
| 5C | 8 RTD inputs
| 5D | 4 RTD inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
| 5E | 4 DCmA inputs, 4 RTD inputs
| 5F | 8 DCmA inputs
2
| 3M | Enhanced front panel with French display
| 3Q | Enhanced front panel with Russian display
| 3U | Enhanced front panel with Chinese display
| 3L | Enhanced front panel with English display and user-programmable pushbuttons
| 3N | Enhanced front panel with French display and user-programmable pushbuttons
| 3T | Enhanced front panel with Russian display and user-programmable pushbuttons
| 3V | Enhanced front panel with Chinese display and user-programmable pushbuttons
| 3I | Enhanced front panel with German display
| 3J | Enhanced front panel with German display and user-programmable pushbuttons
CONTACT INPUTS/OUTPUTS | 4A | 4 Solid-State (no monitoring) MOSFET outputs
| 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
| 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
| 4D | 16 Contact inputs with Auto-Burnishing
| 4L | 14 Form-A (no monitoring) Latching outputs
| 67 | 8 Form-A (no monitoring) outputs
| 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
| 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
| 6C | 8 Form-C outputs
| 6D | 16 Contact inputs
| 6E | 4 Form-C outputs, 8 contact inputs
| 6F | 8 Fast Form-C outputs
| 6G | 4 Form-A (voltage with optional current) outputs, 8 contact inputs
| 6H | 6 Form-A (voltage with optional current) outputs, 4 contact inputs
| 6K | 4 Form-C and 4 Fast Form-C outputs
| 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
| 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
| 6N | 4 Form-A (current with optional voltage) outputs, 8 contact inputs
| 6P | 6 Form-A (current with optional voltage) outputs, 4 contact inputs
| 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
| 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
| 6T | 4 Form-A (no monitoring) outputs, 8 contact inputs
| 6U | 6 Form-A (no monitoring) outputs, 4 contact inputs
| 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact inputs
| 6W | 30 Contact inputs - pin terminals (max 4 modules)
| 6X | 18 Form-A (no monitoring) outputs - pin terminals (max 4 modules)
CT/VT MODULES | 8L | Standard 4CT/4VT with enhanced diagnostics
(not available for the C30) | 8N | Standard 8CT with enhanced diagnostics
| 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
| 8R | Sensitive Ground 8CT with enhanced diagnostics
| 8V | Standard 8VT with enhanced diagnostics
INTER-RELAY COMMUNICATIONS | 2A | C37.94SM, 1300 nm single-mode, ELED, 1 channel single-mode
| 2B | C37.94SM, 1300 nm single-mode, ELED, 2 channel single-mode
| 2E | Bi-phase, single channel
| 2F | Bi-phase, dual channel
| 2G | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
| 2H | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 2I | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1300 nm, single-mode, Laser
| 2J | Channel 1 - IEEE C37.94, multimode, 64/128 kbps; Channel 2 - 1550 nm, single-mode, Laser
| 72 | 1550 nm, single-mode, Laser, 1 Channel
| 73 | 1550 nm, single-mode, Laser, 2 Channel
| 74 | Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, Laser
| 75 | Channel 1 - G.703; Channel 2 - 1550 nm, single-mode Laser
| 76 | IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
| 77 | IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
| 7A | 820 nm, multimode, LED, 1 Channel
| 7B | 1300 nm, multimode, LED, 1 Channel
| 7C | 1300 nm, single-mode, ELED, 1 Channel
| 7D | 1300 nm, single-mode, Laser, 1 Channel
| 7E | Channel 1 - G.703; Channel 2 - 820 nm, multimode
| 7F | Channel 1 - G.703; Channel 2 - 1300 nm, multimode
| 7G | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
| 7H | 820 nm, multimode, LED, 2 Channels
| 7I | 1300 nm, multimode, LED, 2 Channels
| 7J | 1300 nm, single-mode, ELED, 2 Channels
| 7K | 1300 nm, single-mode, Laser, 2 Channels
| 7L | Channel 1 - RS422; Channel 2 - 820 nm, multimode, LED
| 7M | Channel 1 - RS422; Channel 2 - 1300 nm, multimode, LED
| 7N | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
| 7P | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser
| 7Q | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser
| 7R | G.703, 1 Channel
| 7S | G.703, 2 Channels
| 7T | RS422, 1 Channel
| 7W | RS422, 2 Channels
TRANSDUCER INPUTS/OUTPUTS | 5A | 4 DCmA inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
| 5C | 8 RTD inputs
| 5D | 4 RTD inputs, 4 DCmA outputs (only one 5A or 5D module is allowed)
| 5E | 4 DCmA inputs, 4 RTD inputs
| 5F | 8 DCmA inputs
Tracking
HMI frequency Events
Protection
Ethernet selection,
algorithms Control
ports estimation Comtrade, data
I> elements,
Communi-
monitoring logger
Serial cation Z<
Serial
ports protocols U< elements,
FlexLogic, DNP, Modbus,
IEC60870
IRIG-B
Accurate
IEEE Real-Time Time stamping PMU (IEEE C37.118,
Ethernet
1588 clock Synchrophasors Aggregation, IEC 61850-90-5)
SNTP calculations post-filtering IEC 61850 (GOOSE,
CPU module MMS Server)
Contact Inputs
Analog Inputs
Inter-relay
Inter-relay
comms
module
module
module
comms
module
Ddebounce Channel A
filtering monitoring
CRC check D Contact Outputs
module
G.703, RS-422,
Optoisolated C37.94, direct fiber DCmA, RTD
859740A1.vsd
The UR samples its AC signals at 64 samples per cycle, that is, at 3840 Hz in 60 Hz systems, and 3200 Hz in 50 Hz systems.
The sampling rate is adjusted dynamically to the actual system frequency by an accurate and fast frequency tracking
system.
The analog/digital converter has the following ranges of AC signals:
Voltages:
Eq. 2-1
Currents:
Eq. 2-2
2 Current harmonics are estimated based on raw samples with the use of the full-cycle Fourier filter. Harmonics 2nd through
25th are estimated.
True RMS value for the current is calculated on a per-phase basis. The true RMS can be used for demand recording or as an
input signal to Time Overcurrent function, if the latter is intended for thermal protection. The true RMS is calculated as per
the widely accepted definition:
Eq. 2-3
RMS values include harmonics, inter-harmonics, DC components, and so on, along with fundamental frequency values.
The true RMS value reflects thermal effects of the current and is used for the thermal related monitoring and protection
functions.
Protection and control functions respond to phasors of the fundamental and/or harmonic frequency components
(magnitudes and angles), with an exception for some functions that have an option for RMS or fundamental
measurements, or some function responding to RMS only. This type of response is explained typically in each element's
section in this instruction manual.
Currents are pre-filtered using a Finite Impulse Response (FIR) digital filter. The filter is designed to reject DC components
and low-frequency distortions, without amplifying high-frequency noise. This filter is referred to as a modified MIMIC filter,
which provides excellent filtering and overall balance between speed and accuracy of filtering. The filter is cascaded with
the full-cycle Fourier filter for the current phasor estimation.
Voltages are pre-filtered using a patented FIR digital filter. The filter has been optimized to reject voltage-transformer-
specific distortions, such as Capacitive Voltage Transformer (CVT) noise and high-frequency oscillatory components. The
filter is cascaded with the half-cycle Fourier filter for the voltage phasor estimation.
The URs measure power system frequency using the Clarke transformation by estimating the period of the waveform from
two consecutive zero-crossings in the same direction (negative-to-positive). Voltage or current samples are pre-filtered
using a Finite Impulse Response (FIR) digital filter to remove high frequency noise contained in the signal. The period is
used after several security conditions are met, such as true RMS signal must be above 6% nominal for a certain time. If
these security conditions are not met, the last valid measurement is used for a specific time after which the UR reverts to
nominal system frequency.
Synchrophasors are calculated using a patented convolution integral algorithm. This algorithm allows use of the same
time-stamped samples, which are used for protection and taken at the same sampling frequency. This allows URs to use
one sampling clock for both protection algorithms and synchrophasors.
Synchrophasors on firmware versions 7.23 and up have been tested and certified to meet IEEE C37.118-2011 and
C37.118.1a-2014 standards for both metering and protection classes with outputs available up to 60 synchrophasors per
second for the metering class and 120 synchrophasors per second for the protection class. Synchrophasors measurement
is also available via IEC 61850-90-5 protocol.
The contact inputs threshold is settable in the firmware with 17, 33, 84, and 166 V DC settings available. Inputs are scanned
every 0.5 ms and can be conditioned for the critical applications, using debounce time timer, settable from 0.0 to 16.0 ms.
Contact inputs with auto-burnishing are available as well, when external contacts are exposed to the contamination in a
harsh industrial environment.
All measured values are available in the UR metering section on the front panel and via communications protocols.
Measured analog values and binary signals can be captured in COMTRADE format with sampling rates from 8 to 64
samples per power cycle. Analog values can be captured with the Data Logger, allowing much slower rates extended over
a long period of time.
Other advanced UR order code options are available to support IEC 61850 (including fast GOOSE, ICD/CID/IID files, and so
on), IEEE 1588 (IEEE C37.238 power profile) based time synchronization, CyberSentry (advanced cyber security), the Parallel
Redundancy Protocol (PRP), IEC 60870-5-103, and so on.
2.5 Specifications
Specifications are subject to change without notice.
2
2.5.1 Protection elements
The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated. FlexLogic
operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect with other
protection or control elements of the relay, building FlexLogic equations, or interfacing with other intelligent electronic
devices (IEDs) or power system devices via communications or different output contacts. If not specified, the operate times
given here are for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
PHASE/NEUTRAL/GROUND TOC
Current: Phasor or RMS
Pickup level: 0.020 to 30.000 pu in steps of 0.001
Dropout level: 97% to 98% of pickup
Level accuracy:
0.1 to 2.0 CT: ±0.5% of reading or ±0.4% of rated (whichever is greater)
> 2.0 CT: ±1.5% of reading > 2.0 CT rating
Curve shapes: IEEE Moderately/Very/Extremely Inverse; IEC (and BS) A/B/C and Short Inverse; GE IAC Inverse,
Short/Very/ Extremely Inverse; I2t; FlexCurves™ (programmable); Definite Time (0.01 s base
curve)
Curve multiplier: Time Dial = 0.00 to 600.00 in steps of 0.01
Reset type: Instantaneous/Timed (per IEEE)
Curve timing accuracy at 1.03 to 20 x pickup:
±3.5% of operate time or ±½ cycle (whichever is greater) from pickup to operate
Voltage restraint: Modifies pickup current for voltage in the range of 0.1 < V < 0.9 VT Nominal in a fixed linear rela-
tionship
PHASE/NEUTRAL/GROUND IOC
Pickup level: 0.020 to 30.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup
Level accuracy:
0.1 to 2.0 CT rating: ±0.5% of reading or ±0.4% of rated (whichever is greater)
> 2.0 CT rating: ±1.5% of reading
Overreach: <2%
Pickup delay: 0.00 to 600.00 s in steps of 0.01
Reset delay: 0.00 to 600.00 s in steps of 0.01
Operate time: <16 ms at 3 pickup at 60 Hz (Phase/Ground IOC)
<20 ms at 3 pickup at 60 Hz (Neutral IOC)
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)
Curve shapes: IEEE Moderately/Very/Extremely Inverse; IEC (and BS) A/B/C and Short Inverse; GE IAC Inverse,
Short/Very/ Extremely Inverse; I2t; FlexCurves™ (programmable); Definite Time (0.01 s base
curve)
Curve multiplier (Time dial): 0.00 to 600.00 in steps of 0.01
Reset type: Instantaneous/Timed (per IEEE) and Linear
Curve timing accuracy
at 1.03 to 20 x pickup: ±3.5% of operate time or ±½ cycle (whichever is greater) from pickup to operate
PHASE UNDERVOLTAGE
Pickup level: 0.004 to 3.000 pu in steps of 0.001
Dropout level: 102 to 103% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Curve shapes: GE IAV Inverse;
Definite Time (0.1 s base curve)
Curve multiplier: Time dial = 0.00 to 600.00 in steps of 0.01
Curve timing accuracy at <0.90 x pickup:
±3.5% of operate time or ±1/2 cycle (whichever is greater) from pickup to operate
Operate time: <30 ms at 0.9 pickup at 60 Hz for Definite Time mode
AUXILIARY UNDERVOLTAGE
Pickup level: 0.004 to 3.000 pu in steps of 0.001
Dropout level: 102 to 103% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Curve shapes: GE IAV Inverse, Definite Time
Curve multiplier: Time Dial = 0 to 600.00 in steps of 0.01
Curve timing accuracy at <0.90 x pickup:
±3.5% of operate time or ±1/2 cycle (whichever is greater) from pickup to operate
Operate time: <30 ms at 0.9 pickup at 60 Hz for Definite Time mode
PHASE OVERVOLTAGE
Voltage: Phasor only
Pickup level: 0.004 to 3.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Pickup delay: 0.00 to 600.00 in steps of 0.01 s
NEUTRAL OVERVOLTAGE
Pickup level: 0.004 to 3.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Pickup delay: 0.00 to 600.00 s in steps of 0.01 (definite time) or user-defined curve
Reset delay: 0.00 to 600.00 s in steps of 0.01
Curve timing accuracy at >1.1 pickup: ±3.5% of operate time or ±1 cycle (whichever is greater) from pickup to operate 2
Operate time: <30 ms at 1.10 pickup at 60 Hz
AUXILIARY OVERVOLTAGE
Pickup level: 0.004 to 3.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Pickup delay: 0 to 600.00 s in steps of 0.01
Reset delay: 0 to 600.00 s in steps of 0.01
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)
Operate time: <30 ms at 1.10 pickup at 60 Hz
UNDERFREQUENCY
Minimum signal: 0.10 to 1.25 pu in steps of 0.01
Pickup level: 20.00 to 65.00 Hz in steps of 0.01
Dropout level: pickup + 0.03 Hz
Level accuracy: ±0.001 Hz
Time delay: 0 to 65.535 s in steps of 0.001
Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater)
Operate time: typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables, such as frequency change instance, and test method, and can vary by ±0.5
cycles.
BREAKER FLASHOVER
Operating quantity: phase current, voltage, and voltage difference
Pickup level voltage: 0.004 to 1.500 pu in steps of 0.001
Dropout level voltage: 97 to 98% of pickup
Pickup level current: 0.020 to 1.500 pu in steps of 0.001
Dropout level current: 97 to 98% of pickup
Level accuracy: ±0.5% or ±0.1% of rated, whichever is greater
Pickup delay: 0 to 65.535 s in steps of 0.001
Timer accuracy: ±3% of operate time or ±42 ms, whichever is greater
Operate time: <42 ms at 1.10 pickup at 60 Hz
BREAKER RESTRIKE
Principle: detection of high-frequency overcurrent condition ¼ cycle after breaker opens
Availability: one per digital signal processor (DSP)
Pickup level: 0.1 to 2.00 pu in steps of 0.01
2 AUTORECLOSURE
Single breaker applications, 3-pole tripping schemes
Up to four reclose attempts before lockout
Independent dead time setting before each shot
Possibility of changing protection settings after each shot with FlexLogic
FLEXCURVES™
Number: 4 (A through D)
Reset points: 40 (0 through 1 of pickup)
Operate points: 80 (1 through 20 of pickup)
Time delay: 0 to 65535 ms in steps of 1
FLEX STATES
Number: up to 256 logical variables grouped under 16 Modbus addresses
Programmability: any logical variable, contact, or virtual input
FLEXELEMENTS™
Number of elements: 16
Operating signal: any analog actual value, or two values in differential mode
NON-VOLATILE LATCHES
Type: set-dominant or reset-dominant 2
Number: 16 (individually programmed)
Output: stored in non-volatile memory
Execution sequence: as input prior to protection, control, and FlexLogic
LED TEST
Initiation: from any contact input or user-programmable condition
Number of tests: 3, interruptible at any time
Duration of full test: approximately 3 minutes
Test sequence 1: all LEDs on
Test sequence 2: all LEDs off, one LED at a time on for 1 s
Test sequence 3: all LEDs on, one LED at a time off for 1 s
SELECTOR SWITCH
Number of elements: 2
Upper position limit: 1 to 7 in steps of 1
Selecting mode: time-out or acknowledge
Time-out timer: 3.0 to 60.0 s in steps of 0.1
Control inputs: step-up and 3-bit
Power-up mode: restore from non-volatile memory or synchronize to a 3-bit control input or synch/restore mode
8-BIT SWITCH
Number of elements: 6
DIGITAL ELEMENTS
Number of elements: 48
Operating signal: any FlexLogic operand
Pickup delay: 0.000 to 999999.999 s in steps of 0.001
2 Dropout delay:
Timing accuracy:
0.000 to 999999.999 s in steps of 0.001
±3% or ±4 ms, whichever is greater
2.5.3 Monitoring
OSCILLOGRAPHY
Maximum records: 64
Sampling rate: 64 samples per power cycle
Triggers: any element pickup, dropout, or operate; contact input change of state; contact output change
of state; FlexLogic equation
Data: AC input channels; element state; contact input state; contact output state
Data storage: in non-volatile memory
EVENT RECORDER
Capacity: 1024 events
Time-tag: to 1 microsecond
Triggers: any element pickup, dropout, or operate; contact input change of state; contact output change
of state; self-test events
Data storage: in non-volatile memory
DATA LOGGER
Number of channels: 1 to 16
Parameters: any available analog actual value
Sampling rate: 15 to 3600000 ms in steps of 1
Trigger: any FlexLogic operand
Mode: continuous or triggered
Storage capacity: (NN is dependent on memory)
1-second rate:
01 channel for NN days
16 channels for NN days
60-minute rate:
01 channel for NN days
16 channels for NN days
FAULT LOCATOR
Number of independent fault locators: 1 per CT bank (to a maximum of 5)
Method: single-ended
Voltage source: wye-connected VTs, delta-connected VTs and neutral voltage, delta-connected VTs and zero-
sequence current (approximation)
Maximum accuracy if: fault resistance is zero or fault currents from all line terminals are in phase
Relay accuracy: ±1.5% (V > 10 V, I > 0.1 pu)
Worst-case accuracy:
VT%error + user data
CT%error + user data
ZLine%error + user data
RELAY ACCURACY%error + 1.5%
2.5.4 Metering
RMS CURRENT: PHASE, NEUTRAL, AND GROUND
Accuracy at
0.1 to 2.0 CT rating: ±0.25% of reading or ±0.1% of rated (whichever is greater)
2.0 CT rating: ±1.0% of reading
RMS VOLTAGE
Accuracy: ±0.5% of reading from 10 to 208 V 2
REAL POWER (WATTS)
Accuracy at 0.1 to 1.5 x CT rating and 0.8 to 1.2 x VT rating:
±1.0% of reading at –1.0 PF < –0.8 and 0.8 < PF 10
CURRENT HARMONICS
Harmonics: 2nd to 25th harmonic: per phase, displayed as a % of f1 (fundamental frequency phasor)
THD: per phase, displayed as a % of f1
Accuracy:
HARMONICS: 1. f1 > 0.4pu: (0.20% + 0.035% / harmonic) of reading or 0.15% of 100%, whichever is greater
2. f1 < 0.4pu: as above plus %error of f1
THD: 1. f1 > 0.4pu: (0.25% + 0.035% / harmonic) of reading or 0.20% of 100%, whichever is greater
2. f1 < 0.4pu: as above plus %error of f1
VOLTAGE HARMONICS
Harmonics: 2nd to 25th harmonic: per phase, displayed as a % of f1 (fundamental frequency phasor)
THD: per phase, displayed as a % of f1
Accuracy:
HARMONICS: 1. f1 > 0.4pu: (0.20% + 0.035% / harmonic) of reading or 0.15% of 100%, whichever is greater
2. f1 < 0.4pu: as above plus %error of f1
THD: 1. f1 > 0.4pu: (0.25% + 0.035% / harmonic) of reading or 0.20% of 100%, whichever is greater
2. f1 < 0.4pu: as above plus %error of f1
FREQUENCY
Accuracy at
V = 0.8 to 1.2 pu: ±0.001 Hz (when voltage signal is used for frequency measurement)
I = 0.1 to 0.25 pu: ±0.005 Hz
I > 0.25 pu: ±0.02 Hz (when current signal is used for frequency measurement)
DEMAND
Measurements: Phases A, B, and C present and maximum measured currents
3-Phase Power (P, Q, and S) present and maximum measured currents
Accuracy: ±2.0%
2.5.5 Inputs
2 AC CURRENT
CT rated primary: 1 to 50000 A
CT rated secondary: 1 or 5 A by connection
Relay burden: < 0.2 VA at rated secondary
Conversion range:
Standard CT: 0.02 to 46 CT rating RMS symmetrical
Sensitive Ground CT module: 0.002 to 4.6 CT rating RMS symmetrical
Current withstand: 20 ms at 250 times rated
1 sec at 100 times rated
continuous 4xInom
Short circuit rating: 150000 RMS symmetrical amperes, 250 V maximum (primary current to external CT)
AC VOLTAGE
VT rated secondary: 50.0 to 240.0 V
VT ratio: 1.00 to 24000.00
Relay burden: < 0.25 VA at 120 V
Conversion range: 1 to 275 V
Voltage withstand: continuous at 260 V to neutral
1 min/hr at 420 V to neutral
FREQUENCY
Nominal frequency setting: 25 to 60 Hz
Sampling frequency: 64 samples per power cycle
Tracking frequency range: 20 to 70 Hz
CONTACT INPUTS
Dry contacts: 1000 maximum
Wet contacts: 300 V DC maximum
Selectable thresholds: 17 V, 33 V, 84 V, 166 V
Tolerance: ±10%
Contacts per common return: 4
Recognition time: < 1 ms
Debounce time: 0.0 to 16.0 ms in steps of 0.5
Continuous current draw: 4 mA (when energized)
DCMA INPUTS
Current input (mA DC): 0 to –1, 0 to +1, –1 to +1, 0 to 5, 0 to 10, 0 to 20, 4 to 20 (programmable)
Input impedance: 379 ±10%
Conversion range: –1 to + 20 mA DC
Accuracy: ±0.2% of full scale
Type: Passive
RTD INPUTS
Types (3-wire): 100 Platinum, 100 and 120 Nickel, 10 Copper
Sensing current: 5 mA
Range: –50 to +250°C
Accuracy:
Isolation:
±2°C
36 V pk-pk 2
IRIG-B INPUT
IRIG formats accepted: B000…B007, B120…B127
IRIG control bits: IEEE Std C37.118.1-2011
Amplitude modulation: 1 to 10 V pk-pk
DC shift: TTL–Compatible
Input impedance: 50 k
Isolation: 2 kV
DIRECT INPUTS
Input points: 32
Remote devices: 16
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration: Yes, No
Data rate: 64 or 128 kbps
CRC: 32-bit
CRC alarm:
Responding to: Rate of messages failing the CRC
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold: 1 to 1000 in steps of 1
Unreturned message alarm:
Responding to: Rate of unreturned messages in the ring configuration
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold: 1 to 1000 in steps of 1
TELEPROTECTION
Input points: 16
Remote devices: 3
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration: No
Data rate: 64 or 128 kbps
CRC: 32-bit
HIGH RANGE
Nominal DC voltage: 125 to 250 V
Minimum DC voltage: 88 V
Maximum DC voltage: 300 V
Nominal AC voltage: 100 to 240 V at 50/60 Hz
ALL RANGES
Volt withstand: 2 Highest Nominal Voltage for 10 ms
Power consumption: typical = 15 to 20 W/VA
maximum = 45 W/VA
INTERNAL FUSE
Ratings:
Low range power supply: 8 A / 250 V
High range power supply: 4 A / 250 V
Interrupting capacity:
AC: 100 000 A RMS symmetrical
DC: 10 000 A
2.5.7 Outputs
FORM-A RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous: 6A
Break (DC inductive, L/R = 40 ms):
Voltage Current
24 V 1A
48 V 0.5 A
125 V 0.3 A
250 V 0.2 A
LATCHING RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous: 6 A as per IEEE C37.90
Break (DC resistive as per IEC61810-1):
Voltage Current
24 V 6A
48 V 1.6 A
125 V 0.4 A
250 V 0.2 A
Voltage Current
24 V 1A
48 V 0.5 A
125 V
250 V
0.3 A
0.2 A
2
Operate time: < 8 ms
Contact material: silver alloy
DIRECT OUTPUTS
Output points: 32
DCMA OUTPUTS
Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
Max. load resistance: 12 k for –1 to 1 mA range
12 k for 0 to 1 mA range
600 for 4 to 20 mA range
2.5.8 Communications
IEC 61850
IEC 61850: Supports IEC 61850 Editions 1.0 and 2.0. See the UR Family Communications Guide and its con-
formance statements.
RS485
1 rear port: up to 115 kbps, Modbus RTU, DNP 3, IEC 60870-5-103
Typical distance: 1200 m
Isolation: 2 kV, isolated together at 36 Vpk
OTHER 2
TFTP, SFTP, HTTP, IEC 60870-5-104, Ethernet Global Data (EGD), IEEE C37.118
RS422 distance is based on transmitter power and does not take into consideration the clock source provided by
the user.
Emitter, fiber type Cable type Transmit power Received Power budget Maximum
sensitivity optical input
power
820 nm, Multimode 62.5/125 μm -16 dBm -32 dBm 16 dBm -8 dBm
50/125 μm -20 dBm 12 dBm
1300 nm, Multimode 62.5/125 μm -16 dBm -32 dBm 16 dBm -8 dBm
50/125 μm -20 dBm 12 dBm
1300 nm, Single 9/125 μm -15 dBm -32 dBm 17 dBm -8 dBm
mode
1300 nm Laser, 9/125 μm 0 dBm -34 dBm 34 dBm -8 dBm
Single mode
1550 nm Laser, 9/125 μm 5 dBm -34 dBm 39 dBm -10 dBm
Single mode
The following specifications apply to filter interface modules implemented before January 2012.
The power budgets are calculated from the manufacturer’s worst-case transmitter power and worst case receiver
sensitivity.
The power budgets for the 1300 nm ELED are calculated from the manufacturer's transmitter power and receiver
sensitivity at ambient temperature. At extreme temperatures these values deviate based on component tolerance.
On average, the output power decreases as the temperature is increased by a factor of 1 dB / 5 °C.
Typical distances listed are based on the following assumptions for system loss. As actual losses vary from one
installation to another, the distance covered by your system can vary.
FIBER LOSSES
820 nm multimode: 3 dB/km
1300 nm multimode: 1 dB/km
1300 nm single mode: 0.35 dB/km
1550 nm single mode: 0.25 dB/km
Splice losses: one splice every 2 km at 0.05 dB loss per splice
SYSTEM MARGIN
3 dB additional loss added to calculations to compensate for all other losses.
Compensated difference in transmitting and receiving (channel asymmetry) channel delays using GPS satellite clock: 10 ms
Pages: 5 single-line diagram pages with controls, status, and metering values
up to 8 annunciator pages with total of 96 annunciator windows
1 phasor metering page for each AC Source
5 tabular metering pages with dynamic metering and status
event records page with dynamic update
product information page
settings, actual values, error messages (targets)
LED INDICATORS
Functions: 5 device status indicators
9 event cause indicators
2
8 user-programmable pushbutton indicators
PUSHBUTTONS
Type: membrane
Functions: 5 bottom Tab pushbuttons and 1 Home pushbutton for page recall
4 directional, 1 ENTER, and 1 ESCAPE pushbutton element selection
10 side pushbuttons for power system element control
RESET pushbutton
8 physical user-programmable pushbuttons, 8 graphical interface pushbuttons
INGRESS PROTECTION
IP code: IP54 front, IP10 back (IP20 back with IP20 cover accessory)
2.5.12 Environmental
AMBIENT TEMPERATURES
Storage temperature: –40 to 85°C
Operating temperature: –40 to 60°C; the LCD contrast can be impaired at temperatures less than –20°C
HUMIDITY
Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6 days)
OTHER
Altitude: 2000 m (maximum)
Pollution degree: II
Overvoltage category: II
Ingress protection: IP20 front, IP10 back (basic front panel and Rev. 1 enhanced front panel)
IP40 front, IP10 back (Rev. 2 enhanced front panel)
IP54 front with IP54 mounting collar accessory (Rev. 2 enhanced front panel)
Ingress protection with IP20 cover accessory:
IP20 back
Noise: 0 dB
2 Damped oscillatory
Electrostatic discharge
IEC 61000-4-18 / IEC 60255-22-1
EN 61000-4-2 / IEC 60255-22-2
2.5 kV CM, 1 kV DM
Level 3
RF immunity EN 61000-4-3 / IEC 60255-22-3 Level 3
Fast transient disturbance EN 61000-4-4 / IEC 60255-22-4 Class A and B
Surge immunity EN 61000-4-5 / IEC 60255-22-5 Level 3 and 4
Conducted RF immunity EN 61000-4-6 / IEC 60255-22-6 Level 3
1
Power frequency immunity EN 61000-4-7 / IEC 60255-22-7 Class A and B
Voltage interruption and ripple DC IEC 60255-11 12% ripple, 200 ms interrupts
Radiated and conducted emissions CISPR11 / CISPR22 / IEC 60255-25 Class A
Sinusoidal vibration IEC 60255-21-1 Class 1
Shock and bump IEC 60255-21-2 Class 1
Seismic IEC 60255-21-3 Class 1
Power magnetic immunity IEC 61000-4-8 Level 5
Pulse magnetic immunity IEC 61000-4-9 Level 4
Damped magnetic immunity IEC 61000-4-10 Level 4
Voltage dip and interruption IEC 61000-4-11 0, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatory IEC 61000-4-121 2.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz IEC 61000-4-16 Level 4
Voltage ripple IEC 61000-4-17 15% ripple
1
Ingress protection IEC 60529 IP20 front, IP10 back
Cold IEC 60068-2-1 –40°C for 16 hours
Hot IEC 60068-2-2 85°C for 16 hours
Humidity IEC 60068-2-30 6 days, variant 1
Damped oscillatory IEEE/ANSI C37.90.1 2.5 kV, 1 MHz
RF immunity IEEE/ANSI C37.90.2 20 V/m, 80 MHz to 1 GHz
Safety UL 508 e83849 NKCR
Section 43 - Temperature test
Energization of Contact Inputs and/or Contact
Outputs for continuous duty is not to exceed a
total of 31 W of power
Safety UL C22.2-14 e83849 NKCR7
Safety UL 1053 e83849 NKCR
Safety IEC 60255-27 Insulation: class 1, Pollution degree: 2, Over
voltage cat II
2.5.15 Approvals
APPROVALS
Compliance Applicable council directive According to
CE Low voltage directive EN 60255-5
EMC directive EN 60255-26 / EN 50263
EN 61000-6-5
C-UL-US --- UL 508
UL 1053
2
C22.2 No. 14
2.5.16 Maintenance
MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds) of torque.
CLEANING
Normally, cleaning is not required. When dust has accumulated on the front panel display, wipe with a dry cloth.
To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized
state once per year, for one hour continuously.
Chapter 3: Installation
Installation
This chapter outlines installation of hardware and software. You unpack, mount, wire the unit, turn on power, then install
the software and configure settings.
Model: F35D00HCHF8AH6AM6BP8BX7A
RATINGS:
F35
Mods: NONE
Wiring Diagram: See manual
Multiple Feeder Management Relay Control Power: 125-250 V — 0.7A/100-240, 50/60Hz, 0.7A
Contact Inputs: 300 V ---- Max 10mA Inst. Manual: 1601-0106
Serial Number: AAIC07000515
Contact Outputs: Refer to Instruction Manual Firmware: A09MA521.000
GE Multilin E83849 Mfg. Date: NOV 12, 2012
PO Num: 600001234.56
Item Num:
® LISTED
® IND.CONT. EQ.
52TL
832772A3.CDR
4. Any protective plastic film on the front panel is normally peeled off, but also can be left on.
5. For any issues, contact GE as outlined in the For Further Assistance section in chapter 1.
6. Check that you have the latest copy of the F35 Instruction Manual and the UR Family Communications Guide, for the
applicable firmware version, at http://www.gegridsolutions.com/multilin/manuals/index.htm
The Instruction Manual outlines how to install, configure, and use the unit. The Communications Guide is for advanced use
with communication protocols. The warranty is included at the end of this instruction manual and on the GE Grid Solutions
website.
11.016”
[279,81 mm]
9.687”
[246,05 mm]
17.56”
[446,02 mm]
3
7.460”
[189,48 mm]
6.995” 6.960”
[177,67 mm] [176,78 mm]
19.040”
[483,62 mm] 842807A1.CDR
9.687”
[24.605 cm] 10.97”
[27.86 cm]
6.995” 6.96”
[17.767 cm] [17.68 cm]
7.13” 4.000”
[181.1 mm] [101,60 mm]
17.750”
[450,85 mm] 842808A2.CDR
BEZEL OUTLINE
8x0.156”
(9.5 mm)
0.375”
(3.962 mm)
(47.6 mm)
10.90”
1.875”
8.97”
(227.8 mm) (276.8 mm)
9.80”
(248.9 mm) 6.960”
(9.5 mm)
0.375”
(176.8 mm)
(121.5 mm)
4.785”
0.375”
17.52” Brackets repositioned (9.5 mm)
(445.0 mm) for switchgear mounting 5.000” 0.375”
(127.0 mm)
9.520” (9.5 mm)
14.520” (241.8 mm)
CUTOUT
7.13” 4.00”
(181.1 mm) (101.6 mm) 7.00”
(177.8 mm)
17.75” 19.00”
(450.8 mm) (482.6 mm)
827704B5.cdr
11.093”
[281,76 mm]
9.687 “
[246,05 mm]
6.995” 6.960”
[177,67 mm] [176,78 mm]
18.974”
[481,94 mm]
862700A1.cdr
MOUNTING PANEL
8.34”
[21.18 cm]
7.65”
[19.43 cm]
IP54 COLLAR
NOTES
1. INSPECT THE COLLAR BEFORE INSTALLATION, VERIFY GASKET IS ADHERED TO THE METAL ON ALL SIDES
2. MAKE SURE THE RELAY IS POSITIONED CENTER TO THE CUT OUT
3. INSTALL IP-54 COLLAR, CONFIRM THE GASKET PROPERLY MATES WITH THE PANEL ON ALL SIDES
SECURE USING #8-32 HEX NUT AT 6 PLACES. 842497A1.cdr
Front
Bezel
13.56”
15.00” (344.4 mm)
(381.0 mm)
3
14.03”
9.58” (356.2 mm) CUTOUT
(243.4 mm)
Front of Panel
Reference only 13.66”
(347.0 mm)
1.38”
(35.2 mm)
Mounting Bracket
Vertical Enhanced Top View
Front
bezel
13.72" 13.50"
(348.5 mm) (342.9 mm)
7.13”
(181.1 mm)
1.85" 4.00
(47.0 mm) (101.6)
1.57” 0.46”
(39.9 mm) (11.7 mm)
9.00"
(228.6 mm) Mounting bracket
(365.8 mm)
(346.7 mm)
14.40”
13.65”
Terminal blocks
7.00"
(177.8 mm)
For side-mounting F35 devices with the enhanced front panel, see the following documents available on the UR DVD and
the GE Grid Solutions website:
• GEK-113180 — UR-Series UR-V Side-Mounting Front Panel Assembly Instructions
• GEK-113181 — Connecting a Remote UR-V Enhanced Front Panel to a Vertical UR Device Instruction Sheet
• GEK-113182 — Connecting a Remote UR-V Enhanced Front Panel to a Vertically-Mounted Horizontal UR Device
Instruction Sheet
DISPLAY CABLE
GROUND CABLE
ATTACH CABLE TO
FRONT BEZEL
BEFORE MOUNTING
#10-32 NYLOCK
NUT
For side-mounting F35 devices with the basic front panel, use the following figures.
P/N: 1422-1032
4 PLACES SIDE MOUNT COVER
#10-3/8" PAN PHILIPS HEAD P/N: 1004-0018
ZINC
P/N: 1410-0006 UR-V FRONT BEZEL
4 PLACES TO MOUNT THE ASSEMBLY UR-V UNIT
BRACKETS PANEL
Figure 3-9: Vertical side-mounting installation (basic front panel)
3-9
PANEL CUTOUTS
3
PANEL CUTOUTS CHAPTER 3: INSTALLATION
6.66"
(169.2)
5.33"
(135.4)
INCHES
(MILLIMETERS) 2.83"
1.00"
(71.9)
(25.4)
PANEL SHOWN FOR
0.68" 0.04" 1.33" REFERENCE ONLY
(17.3) (1.0) (33.9) (VIEWED FROM FRONT)
3 'X' 'X'
1.00"
(25.4)
OUT
T-
CU
5.27"
(133.8)
12.20"
(309.9)
'X' 'X'
Ground
Model: F35D00HCHF8AH6AM6BP8BX7A
RATINGS:
F35
Mods: NONE
Wiring Diagram: See manual
Multiple Feeder Management Relay Control Power: 125-250 V — 0.7A/100-240, 50/60Hz, 0.7A
Contact Inputs: 300 V ---- Max 10mA Inst. Manual: 1601-0106
Serial Number: AAIC07000515
Contact Outputs: Refer to Instruction Manual Firmware: A09MA521.000
GE Multilin E83849 Mfg. Date: NOV 12, 2012
PO Num: 600001234.56
Item Num:
® LISTED
® IND.CONT. EQ.
52TL
X W V U T S R P N M L K J H G F D B
c b a c b a c b a c b a
b a
LK1
Tx1 1
1
2
Rx1 2
ACT1
3
LK2
3
Tx1
4
4
5
Tx2 b a
ACT2 5
1 6
3
1
2 LK3
2 6
3
Rx2 3 7
4
4 7
8
Tx2 8
ACT3
IN
Do not touch any rear terminals while the relay is energized, else death or serious injury can
result from electrical shock.
Small form-factor pluggable ports (SFPs) are pluggable transceivers. They transmit, receive, and
convert electrical signals to optical signals and vice-versa. Supplied with the device, they are inserted
into the Ethernet ports on the CPU module. A photo in the Maintenance chapter shows this plug-in
device. Do not use non-validated transceivers or install validated transceivers in the wrong Ethernet
slot, else damage can occur.
Terminal number assignments are three characters long and assigned by module slot position, row number, and column
letter. Two-slot wide modules take their slot designation from the first slot position (nearest to CPU module), indicated by
an arrow on the terminal block. The figure shows an example of rear terminal assignments.
J H G F Slot position
c b a c b a Column letter
Torque 9 inch-pounds
842761A2.CDR
The torque used to connect the screws that connect the terminal blocks (top screws a, b, c) and the metal plates over
empty slots to the chassis is 9 inch-pounds. For the screws used to wire the terminal blocks (rows 1 to 8), use 19±1 inch-
pounds.
The CPU module type depends on order code. During manufacturing, the power supply and CPU modules are installed in
slots B and D of the chassis with 13 inch-pounds of torque on the screws at the top and bottom of the modules. Wire
connections to these two modules at 13 inch-pounds.
Figure 3-12: CPU modules and power supply
RS485 Ethernet (3) RS485 Ethernet (3) RS485 Ethernet (3) RS485 Ethernet (3) Power
b a
LK1 LK1 LK1
RJ-45 1
LC copper 1
fiber 2
2
ACT1 ACT1 ACT1 Link, 3
LK2 LK2 LK2 Activity 3
4
4
5
b a
ACT2
b a
ACT2
b a
ACT2
b a 5
1
1
1
1
1
1
1
1 6
2 LK3 2 LK3 2 LK3 2
2 2 2 2 6
3 3 3 3
3 3 3 3 7
4 4 4 4
7
BNC
4 4 4 4
ST 8
for ACT3 ACT3 ACT3 fiber 8
IRIG-B
IN IN IN IN
T CPU module U CPU module V CPU module W CPU module Power supply
module
859758A1.CDR
The following figure shows the optical connectors for CPU modules.
3.3 Wiring
3.3.1 Typical wiring
Figure 3-14: Typical wiring diagram (T module shown for CPU)
Typical configuration.
The AC signal path is configurable. Positive watts
6H
I
Voltage and A B C
H1b H1 IA F1b
current supervision V
TC1 H1c
IA1 F1c
H2a I
H2b H2 IB5 F2a
V
Voltage supervision H2c F35 IB F2b
TC2 H3a I Multiple Feeder IB1 F2c
Protection System 1
H3b H3
V IC5 F3a
H3c
3
H4a I IC F3b
H4b H4 IC1 F3c
Current inputs
IG
I
F4b
H5b H5
V IG1 F4c
I
P1b P1 IG5 F8a
V
P1c IG F8b
P2a I IG1 F8c
P2b P2 IA5 M1a
V
P2c
IA M1b
P3a
P3b P3 IA1 M1c
( DC only )
IG M4b
P7a Contact input P7a
IG1 M4c
P7c Contact input P7c
P8a Contact input P8a IA5 M5a
P8c Contact input P8c IA M5b
P7b Common P7b IA1 M5c
P8b Surge IB5 M6a
IB M6b
B1b IB1 M6c
B1a Critical failure 4
B2b IC5 M7a
DC B3a IC M7b
48 V DC output
B3b IC1 M7c
B5b HI
Power supply
IG5 M8a
AC or DC B6b LO Control power
IG M8b
B6a
B8a Surge IG1 M8c
B8b Filter IA5 U1a
Fibre IA U1b
Tx1100BaseFX
optic Port 1 IA1 U1c
T
Rx1
IB U2b
Shielded Tx3100BaseFX
Ground at Port 3 IB1 U2c 5
twisted pairs Rx3
remote IC5 U3a
D1a
Type 8F/8G CT/VT module
device
D2a RS485 COM 2 IC U3b
D3a COM IC1 U3c
D4b
IG5 U4a
D4a
IRIG-B input IG U4b
CPU
VB U6a
VB U6c
VC U7a
Contacts shown
No. 10AWG with no VC U7c
Modules must be
minimum control power VX U8a Connection
grounded if terminal
is provided VX U8c as required
Ground bus
832778A2.CDR
Filter networks and transient protection clamps are used in the hardware to prevent damage caused
by high peak voltage transients, radio frequency interference (RFI), and electromagnetic interference
(EMI). These protective components can be damaged by application of the ANSI/IEEE C37.90
specified test voltage for longer than the specified minute.
Power supplied to the relay must be connected to the matching power supply range of the relay. If
incorrect voltage is applied or voltage is applied to the wrong terminals, damage can occur.
The F35, like almost all electronic relays, contains electrolytic capacitors. These capacitors are well-
known to deteriorate over time if voltage is not applied periodically. Deterioration can be avoided by
powering up the relay at least once a year.
The power supply module is ordered with one of two possible voltage ranges, and the F35 can be ordered with or without a
redundant power supply module option. Each range has a dedicated input connection for proper operation. The ranges
are as follows (see the Specifications section of chapter 2 for details):
• Low (LO) range — 24 to 48 V (DC only) nominal
• High (HI) range — 125 to 250 V nominal
The power supply module provides power to the relay and supplies power for dry contact input connections.
The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay (see the
Typical Wiring Diagram earlier). The critical failure relay is a form-C device that is energized once control power is applied
and the relay has successfully booted up with no critical self-test failures. If ongoing self-test diagnostic checks detect a
critical failure (see the Self-Test Errors section in chapter 7) or control power is lost, the relay de-energizes.
Connect all wires at be back of a UR before connecting to power, else death or serious injury can
result from electrical shock.
3 Continuous on
On/off cycling
OK
Failure
Off Failure or no power
NOTE:
AC or DC 14 gauge stranded
wire with suitable
disconnect devices
is recommended.
Heavy copper conductor
or braided wire
827247A1.CDR
Channels 4 and 8 are intended for connection to a single-phase source. For voltage inputs, these channels are labelled as
auxiliary voltage (VX). For current inputs, these channels are intended for connection to a CT between system neutral and
ground, and are labelled as ground current (IG).
Verify that the connection made to the relay terminals for nominal current of 1 A or 5 A matches the
secondary rating of the connected CTs. Unmatched CTs can result in equipment damage or
inadequate protection.
To connect to the module, size 12 American Wire Gauge (AWG) is used commonly; the maximum size is 10 AWG.
CT/VT modules can be ordered with a standard ground current input that is the same as the phase current input. Each AC
current input has an isolating transformer and an automatic shorting mechanism that shorts the input when the module is
withdrawn from the chassis. There are no internal ground connections on the current inputs. Current transformers with 1
to 50000 A primaries and 1 A or 5 A secondaries can be used.
CT/VT modules with a sensitive ground input are also available. The ground CT input of the sensitive ground modules is 10
times more sensitive than the ground CT input of standard CT/VT modules. However, the phase CT inputs and phase VT 3
inputs are the same as those of regular CT/VT modules.
These modules have enhanced diagnostics that can detect automatically CT/VT hardware failure and take the relay out of
service.
CT connections for both ABC and ACB phase rotations are identical, as shown in the Typical Wiring Diagram.
The exact placement of a zero-sequence core balance CT to detect ground fault current is shown as follows. Twisted-pair
cabling on the zero-sequence CT is recommended.
Figure 3-16: Zero-sequence core balance CT installation
UNSHIELDED CABLE SHIELDED CABLE
Ground connection to neutral
Stress cone
Source must be on the source side Source shields
A B C N G A B C
Ground
outside CT
To ground;
LOAD must be on
load side
LOAD 996630A6.CDR
The phase voltage channels are used for most metering and protection purposes. The auxiliary voltage channel is used as
input for the synchrocheck and volts-per-hertz features, which are optional features for some UR models.
Substitute the tilde “~” symbol with the slot position of the module in the following figure.
IA5 ~ 1a
IA ~ 1b
IA1 ~ 1c
IB5 ~ 2a
IA5 ~1a IB ~ 2b
IA ~1b IB1 ~ 2c
IB5 ~2a IC ~ 3b
IB1 ~2c 8H, 8J, 8N, and 8R modules (8 CTs) IG5 ~ 4a VA ~1c
8F, 8G, 8L, and 8M modules (4 CTs and 4 VTs)
8V modules (8 VTs)
IG ~4b IA1 ~ 5c VX ~4a
Voltage inputs
IG1 ~4c IB5 ~ 6a VX ~4c
VA ~5a IB ~ 6b VA ~5a
VB ~6c IC ~ 7b VB ~6c
~
VC ~7a IC1 ~ 7c VC ~7a
VX ~8a IG ~ 8b VX ~8a
842809A2.CDR
Figure 3-18: Form-A and solid-state contact outputs with voltage and current monitoring
~#a ~#a
I I
~#b ~#b Load
V Load V
~#c + ~#c +
a) Voltage with optional
Voltage monitoring only Both voltage and current monitoring
current monitoring
~#a ~#a
V V
3 I ~#b
Load
I ~#b Load
~#c + ~#c +
b) Current with optional
Current monitoring only Both voltage and current monitoring
voltage monitoring
(external jumper a-b is required)
~#a
~#b
Load
~#c +
c) No monitoring
827862A5.CDR
The operation of voltage and current monitors is reflected with the corresponding FlexLogic operands (CONT OP # VON, CONT
OP # VOFF, and CONT OP # ION) that can be used in protection, control, and alarm logic. The typical application of the voltage
monitor is breaker trip circuit integrity monitoring; a typical application of the current monitor is seal-in of the control
command.
See the Digital Elements section of chapter 5 for an example of how form-A and solid-state relay contacts can be applied
for breaker trip circuit integrity monitoring.
Consider relay contacts unsafe to touch when the unit is energized. Death or serious injury can
result from touching live relay contacts.
Where a tilde “~” symbol appears, substitute the slot position of the module. Where a number sign “#” appears,
substitute the contact number.
When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, give the
FlexLogic operand driving the contact output a reset delay of 10 ms to prevent damage of the output
contact (in situations when the element initiating the contact output is bouncing, at values in the
region of the pickup value).
For high-density input/output modules 6W and 6X, use the following guidelines to connect. The new I/O modules use pin
type terminal blocks instead of the current ring type. The new terminals are required to achieve higher I/O count per
module.
• 12 to 24 AWG (3.3 mm2 to 0.2 mm2), single wire termination
• 16 to 24 AWG (1.31 mm2 to 0.2 mm2), multiple wire termination with matching wire sizes and stranding. Two wires
maximum per circuit.
• Suggested wiring screw tightening torque is a minimum 4.43 in-lb (0.5 Nm) and maximum 5.31 in-lb (0.6 Nm)
•
•
Minimum suggested temperature rating for the conductors is 75°C
Wire type: copper
3
Table 3-3: Contact input and output module assignments
~6A module ~6B module ~6C module ~6D module
Terminal Output or Terminal Output or Terminal Output Terminal Output
assignment input assignment input assignment assignment
~1 Form-A ~1 Form-A ~1 Form-C ~1a, ~1c 2 Inputs
~2 Form-A ~2 Form-A ~2 Form-C ~2a, ~2c 2 Inputs
~3 Form-C ~3 Form-C ~3 Form-C ~3a, ~3c 2 Inputs
~4 Form-C ~4 Form-C ~4 Form-C ~4a, ~4c 2 Inputs
~5a, ~5c 2 Inputs ~5 Form-C ~5 Form-C ~5a, ~5c 2 Inputs
~6a, ~6c 2 Inputs ~6 Form-C ~6 Form-C ~6a, ~6c 2 Inputs
~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7 Form-C ~7a, ~7c 2 Inputs
~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8 Form-C ~8a, ~8c 2 Inputs
3 ~2
~3
Form-A
Form-A
~2
~3
Form-A
Form-C
~2
~3
Form-A
Form-C
~2
~3
Form-A
Form-A
~4 Form-A ~4 Form-C ~4 Form-C ~4 Form-A
~5 Form-A ~5a, ~5c 2 Inputs ~5 Form-C ~5a, ~5c 2 Inputs
~6 Form-A ~6a, ~6c 2 Inputs ~6 Form-C ~6a, ~6c 2 Inputs
~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs
~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs
842762A4.CDR
6K
I I
~ 1b ~1 ~ 5c CONTACT IN ~ 5c ~1 ~ 1b ~ 7c CONTACT IN ~ 7c ~1 ~ 1b
~ 1c ~ 6a CONTACT IN ~ 6a ~ 1c ~ 8a CONTACT IN ~ 8a ~ 1c
~ 2a ~ 6c CONTACT IN ~ 6c V ~ 2a ~ 8c CONTACT IN ~ 8c V ~ 2a
I I
~ 2b ~2 ~ 5b COMMON ~ 5b ~2 ~ 2b ~ 7b COMMON ~ 7b ~2 ~ 2b
~ 2c ~ 2c ~ 2c
~ 7a CONTACT IN ~ 7a ~ 8b SURGE
~ 3a ~ 3a ~ 3a
~ 7c CONTACT IN ~ 7c
~ 3b ~3 ~3 ~ 3b ~3 ~ 3b
~ 8a CONTACT IN ~ 8a
~ 3c ~ 3c ~ 3c
~ 8c CONTACT IN ~ 8c
~ 4a ~ 4a ~ 4a
~ 7b COMMON ~ 7b
~ 4b ~4 ~4 ~ 4b ~4 ~ 4b
~ 4c ~ 8b SURGE ~ 4c ~ 4c
~ 5a ~ 5a
~ 5b ~5 ~5 ~ 5b
~ 5c ~ 5c
~ 6a ~ 6a
~ 6b ~6 ~6 ~ 6b
~ 6c ~ 6c
~ 7a
DIGITAL I/O
~ 7b ~7
~ 7c
~ 8a
~ 8b ~8
3
~ 8c
842763A2.CDR
3 For proper functionality, observe the polarity shown in the figures for all contact input and output
connections.
B1b
B1a Critical failure
B2b
Power supply module
B3a
48 V DC output
B3b
B5b HI+
B6b LO+ Control power
B6a
B8a Surge
B8b Filter
827741A5.CDR
Where a tilde “~” symbol appears, substitute the slot position of the module.
There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend
using an external DC supply.
Contact Input
859755A1.cdr
The presence of the impedance path (R1) across the contact output allows the stray (distributed) capacitance C1 to charge
as shown, thus developing a voltage across the contact input enough to momentarily operate the input while the
capacitance discharges in the presence of DC ground on the positive terminal of the battery.
The duration of the discharge depends on the value of the distributed capacitance, the initial voltage of the distributed
capacitance, and the input impedance of the contact input. If the duration is greater than the debounce time setting, then
the contact input operates.
The application example that follows describes how to mitigate this issue by connecting a resistor across the contact
input, as shown in the next figure, or by adjusting the debounce time setting to a value greater than the discharge time to
prevent spurious operation of the contact input only if the voltage (with output open) across the contact input due to trickle
current is less than the threshold voltage. This operation of contact inputs also can be prevented by using the Auto-Burnish
contact inputs or contact inputs with active impedance.
Figure 3-24: Contact input connected to a contact output with resistor (R2) across the input
3
Contact Input
859756A1.cdr
Application example
This example is for illustrative purposes only and the calculations present the worst-case scenario. In practice, the value of
debounce time can be lower.
Contact input ON state impedance used in the calculation of the discharge period is based on the following table.
Table 3-4: Discharge period
Battery voltage (V) Input impedance (kΩ)
130 50
250 97
50 to 70 mA
3 mA
Time
25 to 50 ms
842749A1.CDR
Regular contact inputs limit current to less than 3 mA to reduce station battery burden. In contrast, contact inputs with
auto-burnishing allow currents up to 50 to 70 mA at the first instance when the change of state is sensed. Then, within 25
to 50 ms, this current is slowly reduced to 3 mA as indicated. The 50 to 70 mA peak current burns any film on the contacts,
allowing for proper sensing of state changes. If the external device contact is bouncing, the auto-burnishing starts when
external device contact bouncing is over.
Another important difference between the auto-burnishing input module and the regular input modules is that only two
contact inputs have common ground, as opposed to four contact inputs sharing one common ground (see the Contact
Input and Output Module Wiring diagrams). This is beneficial when connecting contact inputs to separate voltage sources.
Consequently, the threshold voltage setting is also defined per group of two contact inputs.
The auto-burnish feature can be disabled or enabled using the DIP switches found on each daughter card. There is a DIP
switch for each contact, for a total of 16 inputs.
Figure 3-26: Auto-burnish DIP switches
842751A1.CDR
The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, check the auto-burnish
functionality using an oscilloscope.
30
84 V threshold
166 V threshold
17 V threshold
33 V threshold
e
at
st
e
25
nc
da
pe
im
w
Lo
20
3
Current (millamperes)
15
s
m
oh
K
10
10
166 V threshold
84 V threshold
33 V threshold
5
17 V threshold
dance state
100 K ohms HIgh impe
0
0 50 100 150 200 250 300
Voltage (Volts) 859757A2.vsd
Where a tilde “~” symbol appears, substitute the slot position of the module.
842764A1.CDR
Hot ~1a
RTD ~1
Comp ~1c
For RTD ~1 & ~2 Return ~1b RTD terminals
RTD ~2
Hot ~2a 3
Comp ~2c
RTD
1: N/A
2: (TXD)
3: (RXD)
RELAY
PERSONAL 4: N/A
COMPUTER 5: (SGND) Signal Ground
FRONT PANEL
6: N/A
PROGRAM PORT 7: N/A
8: N/A
9: N/A
9 PIN
RS232 RS232
D CONNECTOR D CONNECTOR
9 PIN 25 PIN
CONNECTOR CONNECTOR
3.3.9.1 Overview
There is a rear RS485 communication port on the CPU module. The CPU module does not require a surge ground
connection.
Figure 3-31: CPU module communications wiring
MM fiber-
Port 1
T
optic cable Tx1 Rx1 100Base-FX
Tx2 Rx2 100Base-FX Port 2
Shielded
twisted-pairs
Tx3 Rx3 100Base-FX Port 3
D1a +
RS485
D2a —
COM2
3 Ground at
remote
device
D3a
D4b
D4a
COMMON
+
— IRIG-B
input
CPU
BNC
Co-axial cable
U
100Base-TX Port 1
MM fiber-
optic cable Tx1 Rx1 100Base-FX Port 2
Shielded Tx2 Rx2 100Base-FX Port 3
twisted-pairs
D1a +
RS485
D2a —
COM2
Ground at D3a COMMON
remote D4b +
device
D4a — IRIG-B
input
CPU
BNC
Co-axial cable
Port 1
V
100Base-TX
100Base-TX Port 2
Shielded 100Base-TX Port 3
twisted-pairs
D1a +
RS485
D2a —
COM2
Ground at D3a COMMON
remote D4b +
device
D4a — IRIG-B
input
CPU
BNC
Co-axial cable
W
10/100Base-TX Port 1
MM fiber-
optic cable
Tx1 Rx1 100Base-FX Port 2
Shielded Tx2 Rx2 100Base-FX Port 3
twisted-pairs
D1a +
RS485
D2a —
COM2
Ground at D3a COMMON
remote D4b +
device
D4a — IRIG-B
input
CPU
BNC
Co-axial cable
859774A1.CDR
COM
COMP 485COM
COMP 485COM
Up to 32 devices,
maximum 4000 feet
(1200 m)
Relay
ZT (*)
RS485 +
RS485 –
Ensure that the dust covers are installed when the fiber is not in use. Dirty or scratched connectors can lead to high losses
on a fiber link.
3.3.10 IRIG-B
There is a round IRIG-B connector at the back of the CPU module, marked "IN". Use is optional.
IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The
IRIG-B code allows time accuracies of up to 100 ns. The GE MultiSync 100 1588 GPS Clock as well as third-party equipment
are available for generating the IRIG-B signal. This equipment can use a global positioning system (GPS) satellite system to
obtain the time reference so that devices at different geographic locations can be synchronized. The IRIG time code
formats are serial, pulse width-modulated codes that can be either DC level shifted or amplitude modulated (AM). Using
IRIG-B input, the F35 operates an internal oscillator with 1 µs resolution and accuracy.
Figure 3-33: Options for IRIG-B connection
3
UR-series device
4B IRIG-B (+)
IRIG-B
4A IRIG-B (–)
time code generator
RG58/59 coaxial cable Receiver
(DC-shift or + BNC (in)
amplitude modulated
signal can be used)
IRIG-B
time code generator
UR-series device
Twisted-pair cable
(DC-shift or +
4B IRIG-B (+)
amplitude modulated
4A IRIG-B (–)
signal can be used)
Receiver
BNC (in)
827756A8.CDR
Tx
UR 2
Rx
Tx
UR 3
Rx
Tx
UR 4
Rx
842006A2.CDR
Inter-relay communication (IRC) modules with protocol C37.94 and G.703 are designed for back-to-back communication
connections, so the ring configuration shown in the previous figure does not apply. To establish inter-relay communication
in more than two URs, you need to have a two-channel IRC module and enable the DIRECT I/O CHANNEL CROSSOVER setting
in all relays, as shown in the next figure. This configuration can be expanded to 16 URs, and this configuration does not
provide a redundancy ring since both channels are made into a single ring by the channel crossover function. As per the
figure entitled Typical Pin Interconnection between Two G.703 Interfaces later in this chapter, the clock is supplied typically
by multiplexer (MUX) and all URs are in Loop Timing Mode. If there is no MUX, then UR1 and UR3 can be in Internal Timing
Mode and UR2 and UR4 can be in Loop Timing Mode. That is, connected channels must have opposite timing modes.
Figure 3-35: Ring configuration for C37.94 module (concept also applies to G.703)
842236A1.CDR
The interconnection for dual-channel type 7 communications modules is shown as follows. Two-channel modules allow for
a redundant ring configuration. That is, two rings can be created to provide an additional independent data path. The
required connections are: UR1-Tx1 to UR2-Rx1, UR2-Tx1 to UR3-Rx1, UR3-Tx1 to UR4-Rx1, and UR4-Tx1 to UR1-Rx1 for the
first ring; and UR1-Tx2 to UR4-Rx2, UR4-Tx2 to UR3-Rx2, UR3-Tx2 to UR2-Rx2, and UR2-Tx2 to UR1-Rx2 for the second ring.
Tx1
Rx1
UR 1
Tx2
Rx2
Tx1
Rx1
UR 2
Tx2
Rx2
3 Tx1
Rx1
UR 3
Tx2
Rx2
Tx1
Rx1
UR 4
Tx2
Rx2
842007A3.CDR
The following figure shows the connection for three UR-series relays using two independent communication channels. UR1
and UR3 have single type 7 communication modules; UR2 has a dual-channel module. The two communication channels
can be of different types, depending on the type 7 modules used. To allow the direct input and output data to cross-over
from channel 1 to channel 2 on UR2, set the DIRECT I/O CHANNEL CROSSOVER setting to “Enabled” on UR2. This forces UR2 to
forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1.
Figure 3-37: Direct input and output single/dual channel combination connection
Tx
UR 1
Rx
Channel 1
Tx1
Rx1
UR 2
Tx2
Rx2
Channel 2
Tx
UR 3
Rx
842013A2.CDR
The inter-relay communications modules are available with several interfaces and some are outlined here in more detail.
Those that apply depend on options purchased. The options are outlined in the Inter-Relay Communications section of the
Order Code tables in Chapter 2. All of the fiber modules use ST type connectors.
Rx1 Rx1
Tx1 Tx1
3
Rx2
Tx2
1 channel 2 channels
831719A3.CDR
Tx1 Tx1
Rx1 Rx1
Tx2
Rx2
1 channel 2 channels
831720A5.CDR
The following figure shows configuration for the 2I and 2J fiber-laser modules.
Rx1
Tx1
Rx2
3 Tx2
2 channels
831827A1.CDR
When using a laser Interface, attenuators can be necessary to ensure that you do not exceed the
maximum optical input power to the receiver.
3.4.4.1 Description
G.703 is an International Telecommunications Union (ITU) standard for the transmission of data and voice signals. Modules
7R (one channel) and 7S (two channels) apply.
The following figure shows the 64K ITU G.703 co-directional interface configuration. This is module 7S.
The G.703 module is fixed at 64 kbps. The SETTINGS PRODUCT SETUP DIRECT I/O DIRECT I/O DATA RATE setting is not
applicable to this module.
AWG 24 twisted shielded pair wiring is recommended for external connections, with the shield grounded only at one end.
Connecting the shield to pin X1a or X6a grounds the shield since these pins are connected internally to ground. Thus, if
pin X1a or X6a is used to ground the shield at one end, do not ground the shield at the other end. This interface module is
protected by surge suppression devices.
Figure 3-41: G.703 interface configuration
Shield ~1a
7S
Tx – ~1b
G.703 Rx – ~2a
channel 1
Tx + ~2b
Rx + ~3a
G.703 communications
Surge ~3b
Shield ~6a
Tx – ~6b
G.703 Rx – ~7a
channel 2
Tx + ~7b
Rx + ~8a
Surge ~8b
842773A3.CDR
The following figure shows the typical pin interconnection between two G.703 interfaces. For the actual physical
arrangement of these pins, see the Rear Terminal Layout section earlier in this chapter. All pin interconnections are to be
maintained for a connection to a multiplexer.
Figure 3-42: Typical pin interconnection between two G.703 interfaces
7S
7S
Tx – X1b X1b Tx –
G.703 Rx – X2a X2a Rx – G.703
channel 1 channel 1
Tx + X2b X2b Tx +
Rx + X3a X3a Rx +
G.703 communications
G.703 communications
Surge X3b X3b Surge
Shield X6a X6a Shield
Tx – X6b X6b Tx –
G.703 Rx – X7a X7a Rx – G.703
channel 2 channel 2
3
Tx + X7b X7b Tx +
Rx + X8a X8a Rx +
Surge X8b X8b Surge
831727A5.CDR
Pin nomenclature differs from one manufacturer to another. It is not uncommon to see pinouts numbered TxA, TxB,
RxA, and RxB. In such cases, assume that “A” is equivalent to “+” and “B” is equivalent to “–.”
Ejector/inserter clip
FRONT
Channel 1
Timing selection
switches
Top cover
3
Channel 2
Cover screw
Ejector/inserter clip
REAR
831774A3.CDR
842752A2.CDR
DMX G7R
842774A1.CDR
In dual loopback mode, the multiplexers are active and the functions of the circuit are divided into two with each receiver/
transmitter pair linked together to deconstruct and then reconstruct their respective signals. Differential Manchester data
enters the Differential Manchester receiver module and then is returned to the differential Manchester transmitter module.
Likewise, G.703 data enters the G.703 receiver module and is passed through to the G.703 transmitter module to be
returned as G.703 data. Because of the complete split in the communications path and because, in each case, the clocks
are extracted and reconstructed with the outgoing data, in this mode there must be two independent sources of timing.
One source lies on the G.703 line side of the interface while the other lies on the differential Manchester side of the
interface.
Figure 3-46: G.703 dual loopback mode
DMX G7R
842775A1.CDR
3.4.5.1 Description
There are two RS422 inter-relay communications modules available: single-channel (module 7T) and dual-channel (module
7W). The modules can be configured to run at 64 kbps or 128 kbps. AWG 20 to 24 twisted shielded pair cable is
recommended for external connections. These modules are protected by optically-isolated surge suppression devices.
The shield pins (6a and 7b) are connected internally to the ground pin (8a). Proper shield termination is as follows:
• Site 1 — Terminate shield to pins 6a or 7b or both
• Site 2 — Terminate shield to COM pin 2b
Match the clock terminating impedance with the impedance of the line.
Figure 3-47: RS422 interface connections
3 Single-channel RS422 module Dual-channel RS422 module
7W
Tx – ~3b Tx – ~3b
7T
Rx – ~3a Rx – ~3a
RS422 communications
The following figure shows the typical pin interconnection between two single-channel RS422 interfaces installed in slot W.
All pin interconnections are to be maintained for a connection to a multiplexer.
Figure 3-48: Typical pin interconnect between two RS422 interfaces
Tx – W3b W3b Tx –
7T
7T
Rx – W3a W3a Rx –
RS422 communications
RS422 communications
outputs from the multiplexer (data module 1) connects to the clock inputs of the UR RS422 interface in the usual way. In
addition, the send timing outputs of data module 1 are also paralleled to the terminal timing inputs of data module 2. By
using this configuration, the timing for both data modules and both UR RS422 channels is derived from a single clock
source. As a result, data sampling for both of the UR RS422 channels is synchronized via the send timing leads on data
module 1, shown as follows. If the terminal timing feature is not available or this type of connection is not wanted, the
G.703 interface is a viable option that does not impose timing restrictions.
Figure 3-49: Timing configuration for RS422 two-channel, three-terminal application
Data module 1
Signal name
Tx1(+) W2a SD(A) - Send data
7W
Data module 2
Signal name
TT(A) - Terminal timing
TT(B) - Terminal timing
SD(A) - Send data
SD(B) - Send data
RD(A) - Received data
RD(B) - Received data
RS(A) - Request to send (RTS)
RS(B) - Request to send (RTS)
CS(A) - Clear To send
CS(B) - Clear To send
Local loopback
Remote loopback
Signal ground
ST(A) - Send timing
ST(B) - Send timing
831022A3.CDR
Data module 1 provides timing to the F35 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides
timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been
omitted in the figure because they vary by manufacturer.
Tx Clock
Tx Data
831733A1.CDR
When using a laser interface, attenuators can be necessary to ensure that you do not exceed
maximum optical input power to the receiver.
Figure 3-51: RS422 and fiber interface connection
+ ~1a
7L, 7M, 7N,
7P, and 74
Clock
channel 1 – ~1b
Common COM ~2b
Tx – ~3b
Rx – ~3a
RS422 Tx + ~2a
channel 1
communications
Rx + ~4b
Shield ~6a
Fiber Tx2 Rx2
RS422
channel 2
Surge ~8a
842777A3.CDR
The connections shown in the figure are for multiplexers configured as data communications equipment (DCE) units.
When using a laser interface, attenuators can be necessary to ensure that you do not exceed the
maximum optical input power to the receiver.
Figure 3-52: G.703 and fiber interface connection
Shield ~1a
communications
Rx + ~3a
Surge ~3b
Fiber Tx2
G.703
channel 2 Rx2
842778A2.CDR
Digital
UR-series multiplexer,
device IEEE C37.94
compliant
up to 2 km
842755A2.CDR
The UR-series C37.94 communication module can be connected to the electrical interface (G.703, RS422, or X.21) of a non-
compliant digital multiplexer via an optical-to-electrical interface converter that supports the IEEE C37.94 standard. The
following figure shows the concept.
842756A2.CDR
In 2008, GE Grid Solutions released revised modules 76 and 77 for C37.94 communication to enable multi-ended fault
location functionality with firmware 5.60 release and higher. All modules 76 and 77 shipped since the change support this
feature and are fully backward compatible with firmware releases below 5.60. For customers using firmware release 5.60
and higher, the module can be identified with "Rev D" printed on it and is to be used on all ends of F35 communication for
two and three terminal applications. Failure to use it at all ends results in intermittent communication alarms. For
customers using firmware revisions below 5.60, it is not required to match the revision of the modules installed.
The UR-series C37.94 communication module has six switches to set the clock configuration. The following figure shows
the functions of these control switches.
Figure 3-55: Switches
Loop timing mode
Internal timing mode (factory default)
842753A2.CDR
For the internal timing mode, the system clock is generated internally. Therefore, set the timing switch selection to internal
timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, set the timing selection to
loop timing mode for connections to higher order systems.
The IEEE C37.94 communications module cover removal procedure is as follows:
1. With power to the relay off, remove the IEEE C37.94 module (type 2G, 2H, 2I, 2J, 76, or 77 module) as follows. Record
the original location of the module to help ensure that the same or replacement module is inserted into the correct
slot.
2. Simultaneously pull the ejector/inserter clips located at the top and bottom of each module in order to release the
module for removal.
3. Remove the module cover screw.
4. Remove the top cover by sliding it towards the rear and then lift it upwards.
5. Set the timing selection switches (channels 1 and 2) to the required timing modes (see description earlier).
6. Replace the top cover and the cover screw.
7. Re-insert the IEEE C37.94 module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged
position as the module is inserted smoothly into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module is inserted fully.
Figure 3-56: IEEE C37.94 timing selection switch setting
Bottom cover
Ejector/inserter clip
FRONT 3
Channel 1
Timing selection
switches
Top cover
Channel 2
Cover screw
Ejector/inserter clip
REAR
831774A3.CDR
Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the
following figure.
Tx1
CH1 Link/Activity LED
COMMS
Rx1
2B
C37.94SM
1300nm single-mode
ELED
2 channel
Tx1
Tx2
REV. D CH2 Link/Activity LED
Technical support:
3
Tel: (905)294-6222
Fax: (905)201-2098
Rx2
(NORTH AMERICA)
1 800 547-8629
GE Multilin
The UR-series C37.94SM communication module can be connected directly to any compliant digital multiplexer that
supports C37.94SM, as shown.
C37.94SM
fiber interface
Digital
UR-series
multiplexer
device
C97.94SM
up to 10 km
842757A2.CDR
It also can be connected directly to any other UR-series relay with a C37.94SM module, as shown.
C37.94SM
fiber interface 3
UR-series UR-series
device with device with
C37.94SM C37.94SM
module module
up to 10 km
842758A2.CDR
In 2008, GE Grid Solutions released revised modules 2A and 2B for C37.94SM communication to enable multi-ended fault
location functionality with firmware 5.60 release and higher. All modules 2A and 2B shipped since the change support this
feature and are fully backward compatible with firmware releases below 5.60. For customers using firmware release 5.60
and higher, the module can be identified with "Rev D" printed on it and is to be used on all ends of F35 communication for
two and three terminal applications. Failure to use it at all ends results in intermittent communication alarms. For
customers using firmware revisions below 5.60, it is not required to match the revision of the modules installed.
The UR-series C37.94SM module has six switches that are used to set the clock configuration. The following figure shows
the functions of these control switches.
Figure 3-58: Switches
842753A2.CDR
For the internal timing mode, the system clock is generated internally. Therefore, set the timing switch selection to internal
timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, set the timing selection to
loop timing mode for connections to higher-order systems.
The C37.94SM communications module cover removal procedure is as follows:
1. With power to the relay off, remove the C37.94SM module (module 2A or 2B) as follows. Record the original location of
the module to help ensure that the same or replacement module is inserted into the correct slot.
2. Simultaneously pull the ejector/inserter clips located at the top and at the bottom of each module in order to release
the module for removal.
3. Remove the module cover screw.
4. Remove the top cover by sliding it towards the rear and then lift it upwards.
5. Set the timing selection switches (channels 1 and 2) to the required timing modes (see description earlier).
Ejector/inserter clip
FRONT
3 Channel 1
Timing selection
switches
Top cover
Channel 2
Cover screw
Ejector/inserter clip
REAR
831774A3.CDR
Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the
following figure.
Tx1
CH1 Link/Activity LED
COMMS
Rx1
2B
C37.94SM
1300nm single-mode
ELED
2 channel
Tx1
Tx2
REV. D CH2 Link/Activity LED
Technical support:
Tel: (905)294-6222
Fax: (905)201-2098
(NORTH AMERICA)
1 800 547-8629
Rx2
3
GE Multilin
RELAY SETTINGS: When the relay is powered up, the "Trouble LED" is on, the "In Service" LED is off, and this message
Not Programmed displays, indicating that the relay is in the "Not Programmed" state and is safeguarding (output
relays blocked) against the installation of a relay whose settings have not been entered. This
message remains until the relay is explicitly put into "Programmed" state.
The relay can be activated on the front panel or in the EnerVista software.
To activate the relay using the front panel:
1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message displays.
2. Press the MESSAGE right arrow until the SECURITY message displays.
3. Press the MESSAGE down arrow until the INSTALLATION message displays.
4. Press the MESSAGE right arrow until the RELAY SETTINGS: Not Programmed message displays.
SETTINGS
SETTINGS SECURITY
PRODUCT SETUP
DISPLAY
PROPERTIES
INSTALLATION RELAY SETTINGS:
Not Programmed
3 5. After the RELAY SETTINGS: Not Programmed message displays, press a VALUE key to change the selection to
"Programmed."
6. Press the ENTER key to save the change.
7. When the "NEW SETTING HAS BEEN STORED" message appears, the relay is in "Programmed" state and the "In Service"
LED turns on.
To activate the relay using EnerVista software:
1. Navigate to Settings > Product Setup > Installation and change the Relay Settings field to "Programmed."
2. Save the change.
Regional
control
center
Ethernet Remote
10/100 Mbps communications link
Local
control
UR-series IED
EnerVista Engineer
GE Multilin F485
communications converter
Modem
3
RS485 115 kbps
RS232
EnerVista
Reports
EnerVista
Troubleshooting
Commissioning
Setting changes
842759A2.CDR
To communicate through the F35 rear RS485 port from a computer RS232 port, the GE Grid Solutions RS232/RS485
converter box is required. This device (catalog number F485) connects to the computer using a straight-through serial
cable. A shielded twisted-pair wire (20, 22, or 24 AWG) connects the F485 converter to the F35 rear communications port.
The converter terminals (+, –, GND) are connected to the F35 communication module (+, –, COM) terminals. See the CPU
Communication Ports section in chapter 3 for details. The line is terminated with an R-C network (that is, 120 , 1 nF) as
described in this chapter.
The front panel can be switched in the EnerVista software between enhanced and basic panels under
Maintenance > Change Front Panel.
3 To install the software from the DVD and using EnerVista Launchpad:
1. Insert the DVD into the DVD drive of your computer.
2. Click the Install Now button and follow the instructions.
3. When installation is complete, start the EnerVista Launchpad application.
4. Click the IED Setup section of the Launch Pad window.
Figure 3-62: Adding a UR device in Launchpad window
5. In the EnerVista Launch Pad window, click the Add Product button and select the appropriate product as follows.
Select the Web option to ensure the most recent software release, or select CD if you do not have an Internet
connection, then click the Add Now button to list software items for the product. EnerVista Launchpad obtains the
software from the Internet or DVD and automatically starts the installation program after prompting about updates.
From the web, the software is downloaded. A wizard opens.
6. In the wizard, click the Next button and complete the process. The files are installed in the directory indicated, and the
installation program automatically creates icons and adds an entry to the Windows start menu.
The UR device is added to the EnerVista Launchpad window, as shown.
Figure 3-64: UR device added to Launchpad window
7. For other than English, configure the language for the front panel in the EnerVista software under Settings > Product
Setup > Display Properties. User-entered strings are not translated, for example relay names, so setting the language
now ensures that the names are entered/displayed in the required language. For the EnerVista software language,
access the View > Language menu item.
• Connect locally with a computer through either the front RS232 or USB port or rear Ethernet port; see the Connect to
the F35 section
• Discover automatically UR devices within a network; see the Automatic Discovery of UR Devices section
Devices in the Device Setup window are listed in the order entered.
Devices in the main software window are listed alphabetically. Use the Device Name to order them as required, for
example B30 Odessa, B30 Truro, B90, T35.
You cannot import a file to add a device to the software. You can import settings as outlined at the end of the chapter.
The Quick Connect button also can be used to add devices. The device is added to a Quick Connect menu item in the
Online Window area, cannot be moved from it to another grouping, and needs to be renamed in the Device Setup window.
GE instead recommends using the Device Setup window to add devices, as outlined here.
Both network and subnet addresses are contained within a range. The number of hosts determines the class and
addresses as follows:
• Class A 255.0.0.0 — The first octet (255) specifies the network, the second to fourth octets (0) specify the subnet and
host. Use this class when you have more than 65,535 hosts (UR devices).
• Class B 255.255.0.0 — The first two octets (255) specify the network, the third octet (0) specifies the subnet, and the
fourth octet (0) specifies the host. Use this class when you have 255 to 65,534 hosts (UR devices).
• Class C 255.255.255.0 — The first three octets (255) specify the network and the last octet (0) specifies the subnet and
host. Use this class when you have up to 254 hosts (UR devices).
An example of implementation is one computer and one UR device. Because there is one UR device, class C addressing is
required. So we use UR 192.167.2.x with subnet mask 255.255.255.0 and computer 192.167.3.x with subnet mask
255.255.255.0.
For older, non-CIDR routing protocols, such as RIP version 1, follow these restrictions:
• Identical subnet masks — Use a single mask for all subnets within a network
• Contiguous subnets — The subnets must be contiguous and not split among networks. The subnets cannot pass
traffic through other networks.
The IP and subnet addresses need to be added to the UR for Ethernet communication.
For serial communication, for example using any front RS232 port and the Quick Connect feature, the addresses are not
required, but typically they are entered to add/configure devices for regular use.
To add the IP addresses:
1. On the front of the UR, press the MENU key until the SETTINGS menu displays.
2. Navigate to SETTINGS PRODUCT SETUP COMMUNICATIONS NETWORK PRT IP ADDRESS SETTING.
3. Enter an IP address, for example 10.11.33.1, and press the ENTER key to save the value. For example, press the period
key to clear any existing address, then press the number keys to add anew address.
4. In the same menu, select the PRT SUBNET IP MASK setting. Enter a subnet IP address, for example 255.0.0.0.
5. Press the ENTER key to save the value.
The gateway address also needs to be configured when connecting through an Ethernet network. Access SETTINGS
PRODUCT SETUP COMMUNICATIONS IPv4 ROUTE TABLE DEFAULT IPv4 ROUTE GATEWAY ADDRESS.
If using a blue or grey Ethernet cable, skip the rest of the this section. If using an orange cross-over Ethernet cable, the
computer needs to be set up as follows.
1. Use an orange Ethernet cross-over cable to connect the computer to the rear Ethernet port. In case you need it, the
following figure shows the pinout for an Ethernet cross-over cable.
Figure 3-65: Ethernet cross-over cable PIN layout
3 4 5 6
END 1 END 2
2 7 Pin Wire color Diagram Pin Wire color Diagram
1 8
3
1 White/orange 1 White/green
2 Orange 2 Green
3 White/green 3 White/orange
4 Blue 4 Blue
5 White/blue 5 White/blue
6 Green 6 Orange
7 White/brown 7 White/brown
8 Brown 8 Brown
842799A1.CDR
Next, assign the computer an IP address compatible with the relay’s IP address.
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network
connections window. Or in Windows 7, access the Network and Sharing Center in the Control Panel.
3. Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button.
Before using the Quick Connect feature through the Ethernet port, disable any configured proxy settings in Internet
Explorer.
4. Ensure that the “Use a proxy server for your LAN” box is not checked.
If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been
disconnected from the F35 relay.
1. Start the Internet Explorer software.
2. Select the UR device from the EnerVista Launchpad to start EnerVista UR Setup.
4. Select the Ethernet interface and enter the IP address assigned to the F35, then click the Connect button. The 3
EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick
Connect” and displays them on the left side of the screen.
5. Expand the sections to view data directly from the F35 device.
Each time that the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct
communications to the F35. This ensures that configuration of the EnerVista UR Setup software matches the F35 model
number.
When direct communications with the F35 via Ethernet is complete, make the following changes:
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network
connections window.
2. Right-click the Local Area Connection icon and select the Properties item.
3. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.
4. Set the computer to “Obtain a relay address automatically” as shown.
If the computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been
disconnected from the F35 relay.
3 3.
4.
Click the Device Setup button. The window opens.
Click the Add Site button. A new category is added. Enter a site name in the Site Name field. Optionally add a short
Description of the site. This example uses “Location 1” as the site name.
5. Click the Add Device button. A new device is added.
6. Enter a name in the Device Name field, up to 15 characters, and optionally add a Description of the site. The Color is
for the text in the device list in the Online Window.
7. Select “Serial” from the Interface drop-down list. Interface parameters display that must be entered for serial
communications. Try to load automatically the fields by clicking the Read Order Code button.
Figure 3-66: Configuring serial communication
8. Enter the COM port used by the computer, the baud rate, and parity settings from the front panel SETTINGS PRODUCT
SETUP COMMUNICATIONS SERIAL PORTS menu, and the relay slave address setting from the front panel SETTINGS
PRODUCT SETUP COMMUNICATIONS MODBUS PROTOCOL MODBUS SLAVE ADDRESS menu in their respective
fields.
Baud Rate — Typically 19200 bits per second (bps) for RS232, and higher for RS485. Both modems need to use the
same rate, meaning at the computer and the F35 ends.
Parity — Set to None if unsure
Bits — Set to 8 if unsure
Stop Bits — Set to 1 if unsure
Post Terminal Window — Enable this option if you have a Schweitzer Engineering (SEL) SEL-203x Communications
Processor, such as an SEL-2030 or SEL-2032. This option enables display of a terminal window to allow interaction
with the other device.
9. Click the Read Order Code button to connect to the F35 and upload the order code to the EnerVista software. If a
communications error occurs, ensure that the EnerVista software serial communications values entered in the
previous step correspond to the relay setting values, and also ensure that the same IP address is not assigned to
multiple F35 ports.
10. Click the OK button when the relay order code has been received. The new site and device are added to the Online
3
Window.
The device has been configured for serial communications. Proceed to the Connect to the F35 section to begin
communication.
8. Enter the relay IP Address, which can be viewed on the device front panel under SETTINGS PRODUCT SETUP
COMMUNICATIONS NETWORK IP ADDRESS. Once the IP address is entered, try to load automatically the fields by
clicking the Read Order Code button.
9. Enter the relay Slave address and Modbus Port address values from the settings in the front panel SETTINGS
PRODUCT SETUP COMMUNICATIONS MODBUS PROTOCOL menu.
10. If using a gateway to connect to the device, select Yes from the drop-down list.
11. Click the Read Order Code button to connect to the F35 device and upload the order code. If the device was entered
already, a message displays "Device ’x’ is also using IP address...." If a communications error occurs, ensure that the
values entered in the previous steps correspond to the relay setting values, and also ensure that the same IP address
is not assigned to multiple F35 ports.
12. Click the OK button when the relay order code has been received. The new site and device are added to the Online
Window.
The device has been configured for Ethernet communications. Proceed to the Connect to the F35 section to begin
communications.
2. Start the EnerVista UR Setup software, or in EnerVista Launchpad select the UR device to start the software.
3. Click the Device Setup button. The window opens.
4. Click the Add Site button. A new category is added. Enter a site name in the Site Name field, such as London East.
Optionally add a short Description of the site, such as the address or intersection.
5. Click the Add Device button. A new device is added.
6. Enter a name in the Device Name field, up to 15 characters, and optionally add a Description of the site. The Color is
for the text in the device list in the Online Window.
7. Select “Modem” from the Interface drop-down list. This displays a number of interface parameters that must be
entered.
8. Select "Generic Modem" from the Modem Name drop-down list, then enter the Phone Number to dial to establish
communication with the remote modem.
Post Terminal Window — Enable this option if you have a SEL-203x Communications Processor, such as an SEL-2030
or SEL-2032. It enables display of a terminal window to allow interaction with the other device. 3
9. Once the phone number is entered, try to load automatically the device information by clicking the Read Order Code
button.
10. Click the OK button when the relay order code has been received. The new device is added to the Online window.
The UR device has been added to the software.
When multiple computers are connected to a F35 device, EnerVista settings windows are not updated
automatically. They are refreshed when re-opened. If a user changes a setting on one computer, the other users
need to refresh the display by closing and opening the settings window to see the change. To ensure that current
settings are always viewed, close settings windows when not in use so that they are up-to-date when next
accessed.
3
Expand the site list by double-clicking
or selecting the +/– box.
842743A3.CDR
2. If the status indicator is red, verify that the Ethernet network cable is properly connected to the Ethernet port on the
back of the relay and that the relay has been properly set up for communication.
3. If a relay icon appears in place of the status indicator, then a report (such as an oscillography or event record) is open.
Close the report to re-display the green status indicator.
4. The Display Properties settings can now be viewed, edited, or printed.
3 4. Select the serial Interface and the communications port (COM Port) from the drop-down lists, then click Connect. The
COM Port is that of the computer.
5. The EnerVista software creates a site named “Quick Connect” with a corresponding device also named “Quick
Connect” and displays them in the Online Window. Expand the sections to view data directly from the UR device. Use
the Device Setup button to change the site name.
Each time that the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct
communications to the F35. This ensures that configuration of the EnerVista UR Setup software matches the F35 model
number.
2. Select the Ethernet interface and enter the IP address assigned to the F35, then click the Connect button. The 3
EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named "Quick
Connect" and displays them in the Online Window.
3. Expand the sections to view data directly from the F35 device. Use the Device Setup button to change the site name.
Each time that the EnerVista software is initialized, click the Quick Connect button to establish direct communications to
the F35. This ensures that configuration of the EnerVista UR Setup software matches the F35 model number.
3
During the commissioning phase, you have the option to bypass the use of passwords. Do so by enabling the Bypass
Access setting under Settings > Product Setup > Security > Supervisory. Be sure to disable this bypass setting after
commissioning the device.
You can change the password for any role either from the front panel or through EnerVista. If using EnerVista, navigate to
Settings > Product Setup > Security. Change the Local Administrator Password, for example. It is strongly recommended
that the password for the Administrator be changed from the default. Changing the passwords for the other three roles is
optional.
When EIC 61850 and version is 7.30 or later, the file is added and time stamp is unchanged. When clicking in the
software on the tree element, a device folder is created, the original file moves into it, SCL files are generated there,
and the "Last modified" time stamp on the URS file changes.
Chapter 4: Interfaces
Interfaces
This chapter explains the EnerVista software interface, the front panel interface, logic diagrams, and Engineer interface for
logic design and monitoring.
• Remote resources
• Testing
Factory default values are supplied and can be restored after any changes.
The following communications settings are not transferred to the F35 with settings files:
Modbus Slave Address
Modbus TCP Port Number
RS485 COM2 Baud Rate
RS485 COM2 Parity
COM2 Minimum Response Time
COM2 Selection
RRTD Slave Address
RRTD Baud Rate
IP Address (see end of previous chapter for information)
IP Subnet Mask
IP Routing
When a settings file is loaded to a F35 that is in-service, the following sequence occurs:
4 1. The F35 takes itself out of service.
2. The F35 issues a UNIT NOT PROGRAMMED major self-test error.
3. The F35 closes the critical fail contact.
The Maintenance chapter outlines how to use a settings file in the .urs format for backup and restore.
2 1 6 7
10
4
4 5
9 8 842786A2.CDR
When templates are created for online settings, the password is added during the initial template creation step. It
does not need to be added after the template is created.
4
Phase time overcurrent window with template applied via
the Template Mode > View In Template Mode command.
The template specifies that only the Pickup and Curve
Phase time overcurrent settings window without template applied.
settings be available.
842858A1.CDR
Viewing the settings in template mode also modifies the settings menu, showing only the settings categories that contain
editable settings. The effect of applying the template to a typical settings menu is shown as follows.
Figure 4-7: Applying templates using the View in Template Mode settings command
Use the following procedure to display settings available for editing and settings locked by the template.
1. Right-click the device in the Online or Offline Window area and apply the template by selecting the Template Mode >
View All Settings option.
2. Enter the template password then click OK to apply the template.
Once the template has been applied, users are limited to edit the settings specified by the template, but all settings are
shown. The effect of applying the template to the phase time overcurrent settings is shown as follows.
Figure 4-8: Applying templates using the View All Settings command
Phase time overcurrent settings window without template applied. Phase time overcurrent window with template applied via
the Template Mode > View All Settings command.
The template specifies that only the Pickup and Curve
settings be available.
4
842859A1.CDR
4 5. Click the Save button to save and apply changes to the settings template.
6. Select the Template Mode > View In Template Mode option to view the template.
7. Optionally apply a password to the template by right-clicking the device and selecting the Template Mode >
Password Protect Template option.
Once the template has been applied, users are limited to view and edit the FlexLogic entries not locked by the template.
The effect of applying the template to the FlexLogic entries is shown here.
Figure 4-10: Locking FlexLogic entries through settings templates
Typical FlexLogic™ entries without template applied. Typical FlexLogic™ entries locked with template via
the Template Mode > View In Template Mode command.
842861A1.CDR
The FlexLogic entries are also shown as locked in the graphical view and on the front panel display.
2. Enter the serial number of the F35 device to lock to the settings file in the Serial # Lock field.
3. Click the OK button to apply the change. The serial number is not validated.
The settings file and corresponding secure FlexLogic equations are now locked to the F35 device specified by the serial
number.
The serial number of the UR-series device and the file transfer
date are added to the setting file when setting files
are transferred to the device.
842863A1.CDR
This information is also available in printed settings file reports as shown in the example. A report is generated by right-
clicking and selecting the Print Settings option.
Traceability data
in settings report
4
842862A1.CDR
This information is also available from the front panel display through the following actual values:
ACTUAL VALUES PRODUCT INFO MODEL INFORMATION SERIAL NUMBER
ACTUAL VALUES PRODUCT INFO MODEL INFORMATION LAST SETTING CHANGE
Display
4
Keypad
Control
pushbuttons (3)
Front panel
RS232 port
Display
Front panel
RS232 port
Small user-programmable
User-programmable Keypad
(control) pushbuttons 1 to 7
pushbuttons 1 to 12
827801A9.CDR
The following figure shows the vertical front panel for relays ordered with the vertical option.
4 Figure 4-19: Basic vertical front panel
GE Multilin
Display
MENU 7 8 9
HELP MESSAGE 4 5 6
ESCAPE 1 2 3
Keypad
ENTER VALUE 0 . +/-
1 3 5
USER LABEL USER LABEL USER LABEL
User-programmable
2 4 6
pushbuttons 1 to 6
USER LABEL USER LABEL USER LABEL
LED panel 2
RS232 port
827830A3.CDR
1 5
IN SERVICE
TROUBLE
TEST MODE
TRIP
ALARM 2 6
4
PICKUP
VOLTAGE
CURRENT 3 7
USB port FREQUENCY
OTHER
PHASE A 4 8
PHASE B
Not used
PHASE C
NEUTRAL / GND
RESET ESC
ENTER
The front panel can be viewed and used in the EnerVista software, for example to view an error message displayed on the
front panel or the LEDs.
To view the front panel in EnerVista software:
1. Click Actual Values > Front Panel, then any option.
Figure 4-23: Home page example with default content (product information)
Setting Group
Alarm Target Relay Date and Time
4
859850A1.cdr
There are multiple ways to navigate pages, by using the pushbuttons and the menu hierarchy. The menu hierarchy is
similar to the other front panels whereby you select a submenu using Up and Down arrow pushbuttons, and press the
ENTER or Right pushbutton. On setting pages, opening a setting for editing is done by highlighting the setting using Up and
Down pushbuttons, and pressing the ENTER or Right pushbutton.
Home page
Press the Home pushbutton to display the root page no matter the state. Any edit, control, or password entry sessions are
cancelled. The header shows several relay/system status icons. The default content of the home page is the product
information page and can be user-configured to show the content of any single-line diagram page, annunciator page,
metering page, or event records page for example. The Tab pushbuttons on the bottom row each navigate to their page.
The home page displays for a user-configured time period, then scrolls through user-configured pages, a feature referred
to as rolling.
Holding the Home pushbutton for one second displays the product information page. The Home page also can display
when settings are saved.
Security indicator, showing how many people are logged in, including local and remote users. The lock is red when
one or more users are logged in and other otherwise green.
When no users are logged in because login is not required, an icon does not display.
Identifies the active setting group number (not shown)
Displays when an abnormal annunciator alarm is present. Navigate to the Annunciator for details. When there
are no such alarms, the icon does not display.
Even when you acknowledge/reset an alarm, the icon displays as long as the condition remains. For example, a
breaker trouble alarm displays, you acknowledge it, but the icon remains because the breaker trouble remains.
Active targets symbol, where targets are error messages.
View error messages by pressing the Menu Tab pushbutton, then accessing the TARGETS menu. Pressing the
RESET button clears those messages that can be.
Configure the home page in the software under Settings > Product Setup > Graphical Panel > Home Page. The menu
does not display when there is no graphical front panel.
Rolling mode
After a user-defined period of inactivity, the graphical front display rolls among up to 10 user-selected pages. The roll-to-
pages are selected in the EnerVista software, with the defaults being the product information page. Each page displays for
less than five seconds. Also, the display backlight intensity is lowered after a configurable period to a user-defined level (0,
10, 20, or 30%); lower intensity extends the life of the display.
Configure rolling mode in the software under Settings > Product Setup > Graphical Panel > Rolling Mode.
Operation works as follows:
• Press the Home pushbutton or ESCAPE pushbutton twice to cancel rolling, restore full backlight intensity, and return
to the Home page
• Press the ENTER, ESCAPE, or a pushbutton to pause rolling once and restore full backlight intensity
Rolling is disabled by setting the delay to 0.
The following buttons display at the top of the window:
• Save — Updates the connected device if online or the open setting file if offline with changes made
• Restore — Undoes changes that have not been saved
• Default — Changes all rolling mode settings to their factory default values
• Reset — Displays factory default values. Previous changes are not lost unless you save the reset window.
4 Single-line diagrams
A single-line diagram, or mimic diagram, is a line drawing of elements in an electrical system. The graphical front panel
displays up to five single-line diagrams. Each can be configured to show the arrangement of a portion of the power
system, the status of circuit breakers and of ground and disconnect switches, user-programmable pushbuttons, and
metering and status values. Each also enables control of the displayed power system devices.
One diagram is provided by default, single_bus_line_dsc.mif, which can be modified.
Configure the diagrams under Settings > Product Setup > Graphical Panel > Single Line Diagram Editor.
Each single-line diagram page has a user-configurable name that appears in the header and in the footer Tab pushbutton
label. Factory default names are SLD 1 to SLD 5. Pages that have no configured content have a blank Tab pushbutton
label, and the Tab pushbutton does nothing. The label for the current page has a blue background.
Figure 4-24: Toolbar options for single-line diagram
The letters T, S, B, R, and X next to a controllable element have the following meaning. An example (TSB) is shown in the
next figure.
• T — The element is "tagged." Local and remote control of the device are inhibited, both open and close. Tripping is
unaffected unless additional logic has been configured.
• S — The position indication of the device is substituted with a manually entered value
• B — Blocking open/close command is bypassed
• R — Autoreclose is enabled and not blocked
• X — The device is out-of-service and control is not available
Under Settings > System Setup > Switches and Breakers, enable and name the six switches and two breakers. Switch 6,
M568G, has the A/3 Pole Opened setting on.
4
In the EnerVista software, open the single-line diagram editor under Settings > Product Setup > Graphical Panel > Single
Line Diagram Editor.
Add the four switches for the top line by clicking the GE switch symbol in the toolbar, then clicking in the window. (If the UR
device is not online, the software attempts to connect.) Right-click to edit properties. Rotate switches SW569 and SW5682
to 270 degrees. Rotate switches 5681 and SW523 to 90 degrees. Ignore the TSB text.
Add the two lower switches. Leave rotation at 0 degrees.
Add the two breakers by clicking the GE breaker symbol in the toolbar, then click in the window. Right-click to edit
properties, rotating 90 degrees and setting the color to red (open).
Draw lines to fill in the gaps between the switches and breakers by clicking the line symbol in the toolbar, then clicking and
dragging on the canvas to draw a line. Do not draw a single line for the top line, but instead draw several small lines.
Add the feeder arrow head by clicking the symbol in the toolbar, then clicking the end of the line.
Add the ground symbol by clicking the symbol in the toolbar, then clicking the end of the line.
Add three metered values by clicking the M symbol in the toolbar, then clicking near the feeder arrow. Double-click to edit.
The three metered values are SRC1 Vag Mag, SRC 1 P, and SRC 1 Q.
Name the page by right-clicking the bottom tab. Here, page 1 is renamed "Milton line M568M."
Note that active symbols in the toolbar display and those that are inactive are greyed-out.
The diagram has been created. Save it by clicking the Save button.
Next is to close circuit breaker CB523. This circuit breaker is shown at the top right of the figure. A vertical line means that
it is open, and the color can be set as red or green.
On the graphical front panel, press the Home pushbutton, then press the SLDs pushbutton to activate the first single-line
diagram page.
Press the Enable Control pushbutton. The side pushbutton labels display.
Figure 4-28: Side pushbutton display on graphical front panel 4
Press the pushbutton to close the breaker, confirming the action at the prompt.
4 In this diagram, the two circuit breakers have hard-coded actions available to them. No action is possible on the switches.
Note the USER PB 9 and 10 entries in the earlier figure. As outlined later, these are activated by clicking the PB icon on the
software toolbar. These two pushbuttons can be configured under Settings > Product Setup > User-Programmable
Pushbuttons.
Lines
Line components represent power system buses or electrical connections between power system elements. They can also
be used as visual dividers and underline.
To add a line component, click it in the toolbox, then click in the window. Double-click a line to open its properties window
to set orientation.
Static symbols
Static symbols depicting power system elements are available. For information, see the ANSI/IEEE 315A and IEC 60617
standards.
Up to 32 static symbols can be used per single-line diagram.
To add a symbol, click it in the toolbox, then click in the window. Double-click the symbol to open its properties window to
set orientation.
Figure 4-31: IEEE and IEC static symbols
To add a breaker or disconnect component, click it in the toolbox, then click in the window. Up to 10 dynamic components
can be added to each single-line diagram.
Breaker and disconnect components have three different parts: label, symbol, and flags. Drag each of its parts to their final
locations. Double or right-click any of these parts to open the properties window. Properties that can be edited are label
text, breaker control element or disconnect switch element number, symbol orientation (horizontal or vertical), color
scheme (red - closed, or red - open), and assigned side button (if any). If the selected breaker or disconnect element does
not exist in the target relay or has not been enabled, then the component is displayed in the graphical front panel and in
the drawing edit window in grey. The color scheme selection has no effect when an IEC style symbol is used because IEC
style symbols do not use color.
Symbol orientation
The figure shows the orientation available for the breaker and disconnect switch (taking Open status as examples). The
default position is 0 degrees.
Figure 4-33: Single-line diagram symbol orientation
A question mark displays in a symbol on the graphical front panel when status is bad. The question mark does not rotate
with orientation.
Figure 4-34: Symbols when status is bad
The following figures show the orientation available for the static components. The default position is 0 degrees.
User-programmable pushbuttons
User-programmable pushbuttons 1 to 8 are physical pushbuttons on the right side of the graphical front panel, numbering
down the two columns.
User-programmable pushbuttons 9 to 16 can be programmed among the 10 pushbuttons on the left and right sides of the
screen display. They show dynamically and provide a means to perform the same control as the other pushbuttons.
4 As an example, if you set up a single-line diagram with two breakers and six switches, then eight of the side pushbuttons
are used automatically for control of the breakers and switches. Side pushbuttons 9 and 10 are available. In the single-line
diagram, let us set side pushbutton 9 to clear event records as follows:
• Show side pushbutton 9 on the graphical front panel — Click the PB symbol in the toolbar, then set Side button 9 to
pushbutton 9 in the drop-down list. This pushbutton then displays when appropriate on the right side of the screen
display.
• Program event record clearing — Set Settings > Product Setup > Clear Relay Records > Clear Event Records to
FlexLogic operand PUSHBUTTON 9 ON
• Program pushbutton 9 — Set Settings > Product Setup > User-Programmable Pushbuttons > Pushbutton 9
Function to "Self-reset." When pressed, pushbutton 9 clears the event records.
To instead set the second user pushbutton (not a side pushbutton) to clear events, follow the second and third bullet
points, selecting settings of PUSHBUTTON 2 ON and Pushbutton 2.
Metering components
Metering components show dynamically the value of a FlexAnalog operand or actual value. Up to 16 metering
components can be added to each single-line diagram.
To add a metering component, click the M symbol in the toolbox, then click in the window. Drag it to its final location.
Double-click it to open the properties window. The figure shows the properties that can be edited.
Status components
Status components show dynamically the value of a FlexLogic operand. Up to 16 can be used in a diagram and 30 in all
single-line diagrams.
An example is to show the Off or On state of the ANY MAJOR ERROR FlexLogic operand. The name of the operand displays in
the single-line diagram editor, then as Off or On on the graphical front panel.
To add a status component, click the S symbol in the toolbox, then click in the window. Drag it to its final location. Double-
click it to open the properties window. Properties that can be edited include parameter (any FlexLogic operand), text color
background color, and on and off text.
Optionally add a text label to display beside the status.
Text
Text components show a single line of user-configured text.
Up to 16 text components can be used per single-line diagram.
To add a text component, click the T symbol in the toolbox, then click in the window. Drag it to its final location. Double-
click it to open the properties window. Properties that can be edited are text, color, and size.
Annunciator
An annunciator is a grid of small windows for alarms, actual values, self-test messages, and product information.
The graphical front panel emulates a conventional annunciator panel. The annunciator has 96 windows, each with a
description of the alarm condition that lights the window. The windows are arranged in rows and columns of 3 x 4, 4 x 6, or
6 x 8 over several pages. Each window can have up to three lines of configurable text, and one line can instead be a
metered value. Normally the window background is dark, and when the configured FlexLogic operand becomes On, the
window lights up.
The figure shows that two alarms are active. One alarm is configured red and the other alarm is configured blue. The red
alarm type is Self Reset, so the alarm displays in a solid color. The blue alarm type is Acknowledgeable, so the alarm flashes
until it is acknowledged, for example by navigating with the arrow keys and pressing the ENTER button. The alarm then
remains blue until the trigger condition is eliminated.
To display the annunciator, press the Home pushbutton, then the Annunciator Tab pushbutton. If there is one or more
4 window in alarm or requiring reset, the annunciator page showing the first of these opens. Otherwise the first annunciator
page opens.
Alarms do not display automatically. Set the Home page and/or rolling pages to display annunciator pages.
The Tab pushbutton labels populate with the annunciator pages. The label text for each annunciator page is configurable
and displays in the header and Tab label. The current page has a blue Tab label. Tab labels for annunciator pages that
have an active window (that is, on, latched, or unacknowledged) are red. Pages where alarms are not triggered have a grey
Tab label. Pages that have no configured windows do not have Tab pushbuttons and do not display.
The Up, Down, Left, and Right pushbuttons cause the selection to move one window in the indicated direction. Pressing the
Right pushbutton past the last window in a row scrolls the display to any next annunciator page, not the next row. The
behavior is similar for the other pushbuttons, for example pressing the Up pushbutton while in the top row goes to any
previous page. If no previous page exists, no action occurs.
Annunciator windows are positioned statically, so that all windows are visible no matter their state.
Alarm types of each window can be configured as Self Reset, Latched, or Acknowledgeable. In Self Reset mode, the
window lighting follows the state of the configured FlexLogic operand. The self-reset mode alarm sequence conforms to
ISA-18.1-1979 (R2004) standard type A 4 5 6.
Figure 4-40: Annunciator alarm sequence in Self Reset mode
Process: Normal
Sequence: Normal
Visual: Off
Return to Normal
To Abnormal
Process: Abnormal
Sequence: Acknowledged
Visual: On
859856A1.vsd
Latched mode is intended for transient signals such as trip, and it conforms to ISA-18.1-1979 (R2004) standard type M 6.
Figure 4-41: Annunciator alarm sequence in Latched mode
Process: Normal
Sequence: Normal To Abnormal
Visual: Off
Process: Abnormal
Reset while
Sequence: Acknowledged
Abnormal
Visual: On
859857A1.vsd
4
In Acknowledgeable mode, both Off to On and On to Off state changes in the configured operand cause the background to
flash; the window must be acknowledged/reset to cancel flashing. This mode conforms to ISA-18.1-1979 (R2004) standard
type R-6.
Figure 4-42: Annunciator alarm sequence in Acknowledgeable mode
Process: Normal
Reset Sequence: Normal To Abnormal
Visual: Off
Process: Abnormal
Reset while
Return to Normal Sequence: Acknowledged
Abnormal
Visual: On
859858A1.vsd
An alarm remains in an alarm state (for example, displays red) when the condition remains. That is, if you acknowledged a
flashing alarm but the alarm condition remains, the background color remains red.
The SETTINGS > INPUTS/OUTPUTS > RESETTING > RESET ANNUNCIATOR setting can be used to select a FlexLogic
operand that when activated acknowledges/resets all annunciator windows.
Annunciator editor
The annunciator editor is used to configure alarms and actual value displays for the graphical front panel.
The path in the EnerVista software is Settings > Product Setup > Graphical Panel > Annunciator Editor.
The figure shows the annunciator editor and its preview window. The page name is entered as General at the top right.
Acknowledgeable and self-resetting alarms are set for basic functions, such as online/offline, Ethernet ports, unauthorized
access/failed logins, and battery failure. The text to display in the annunciator window is entered. The IN SERVICE LED is set
to be green because when the device is on, this LED is green. The preview shows what the annunciator looks like with all
alarms triggered. The last window is not configured and displays blank/grey. In order for the Ethernet and battery alarms
to work, the corresponding self-test alarms have been enabled under Settings > Product Setup > User-Programmable
Self Tests (not shown). The LEDs can be viewed on the front panel, so adding them to the annunciator is for illustrative
purposes only.
The three page layouts (3 × 4, 4 × 6, and 6 × 8) select the number of rows x columns of windows that appear in a page.
Annunciator window size and text size shrink as the number of annunciator windows in a page increases.
Properties that can be edited include alarm type (acknowledgeable, latched, self-reset), alarm input (any FlexLogic
operand), text color, and alarm background color.
The following buttons display at the top of the window:
• Save — Updates the connected device if online or the open setting file if offline with changes made
• Restore — Undoes changes that have not been saved
• Default — Changes all annunciator settings to their factory default values
• Reset — Displays factory default values. Previous settings are not lost unless you save the reset window.
Metering editor
The metering editor is an actual values display tool. It creates pages of actual values for the graphical front panel. There
are two types: tables and phasor diagrams. Tabular actual values pages have settings to configure, while phasor actual
values pages have no settings. Five tabular metering pages can be configured, while there can be a phasor page for each
configured AC source. They display on the graphical front panel using the Metering Tab pushbutton.
The path to the editor is Settings > Product Setup > Graphical Panel > Metering Editor.
Figure 4-44: Metering editor with preview window
4
The inputs are selected at the top. Select from the drop-down list or start typing in the field.
The page, page name, and grid layout are set below the inputs.
Content to display is configured with the cell lines. The content can be actual values, a status indicator, or text.
• Actual value — Select from the FlexAnalogs applicable to the F35, where a FlexAnalog is an analog parameter
• Status — Select from the FlexLogic operands identified in the Status Inputs at the top of the window. An example is to
display text to indicate whether the BATTERY FAIL operand is on or off.
• Text — Enter text to display in the table, for example name of table or column heading
If the metering input is other than OFF, the value of the selected metering input displays, formatted according to the size,
text color, units, multiplier, and decimal configuration. Otherwise either the Text or the Off Text displays depending on the
value of the operand selected by setting Status Input/Index.
A maximum of eight Status Inputs/Indexes can be used per metering page and 16 in all metering pages.
The following buttons display at the top of the window:
• Save — Updates the connected device if online or the open setting file if offline with changes made
• Restore — Undoes changes that have not been saved
• Default — Changes all actual value settings to their factory default values
• Reset — Displays factory default values. Previous settings are not lost unless you save the reset window.
The path is Settings > Product Setup > Graphical Panel > Configurable Navigation.
The settings consist of 64 field pairs, each with a condition and an activation page. The condition selects any FlexLogic
operand. The activation page selection is the standard set, such as product information, event records, annunciator pages,
and single-line diagrams.
To use the feature, select a CONDITION, select its ACTIVATE PAGE option, then save. When selecting the condition
operand, open the drop-down list and start typing in the field to auto-fill. For example, typing F displays FIRST ETHERNET
FAIL.
The following buttons display at the top of the window:
• Save — Updates the connected device if online or the open setting file if offline with changes made
• Restore — Undoes changes that have not been saved
SETTINGS
PRODUCT SETUP
HELP 4 5 6
3. Press to scroll third level fields MESSAGE
2. Press to scroll second level:
ESCAPE 1 2 3 PRODUCT SETUP.
4. Press to scroll through values
ENTER VALUE 0 . +/-
5. Press to save change
842231A1.cdr
Up/Down/Left/Right — These pushbuttons move the selector among the options on a page. The selection is
indicated by a yellow background or a yellow border. On menu pages, the Right pushbutton activates the selected
submenu drilling down the menu hierarchy, and the Left pushbutton backs up the menu hierarchy. These
pushbuttons have a typematic feature on some pages: after a short pause, the pushbutton repeats as long as it is
pressed.
ENTER — Activates the selection on the display, for example a submenu, a control, a keypad key, or a setting. Also
stores updated settings.
ESCAPE — If a setting is open for edit, this pushbutton closes the setting without saving. If a popup menu is open,
this pushbutton closes it. If an item is selected, this pushbutton deselects it. Otherwise this pushbutton activates
the previous page in the page hierarchy.
RESET — Clears all latched LED indications and target messages. When a page with acknowledgeable/resettable
items is displayed, it instead resets/acknowledges all items on that page, or if an item on that page is selected, it
resets/acknowledges that item.
If you reset/acknowledge alarms, they stop flashing but remain in the alarm state as long as that state remains. In
other words, a red alarm does not switch off just because you acknowledged the alarm.
Home — Activates the home page, which is the root page. The page displays product information by default and
is configurable.
Side pushbutton — Five pushbuttons on the left side of the display and five pushbuttons on the right side of the
display. They perform various functions depending on the displayed page, such as switchgear controls. The
display dynamically shows its label next to each side pushbutton when the pushbutton has an assigned function.
These pushbuttons can also be programmed to function as user-programmable pushbuttons 9 to 16.
Tab pushbutton — Five pushbuttons under the display. They navigate through the page hierarchy, and on some
pages activate other actions. The display footer dynamically labels the page or action that is activated by the Tab
pushbutton.
User-programmable pushbutton — Eight physical pushbuttons are associated with the first eight user-
programmable pushbutton elements. Numbering is down, that is, 1 to 4 down the left column and 5 to 8 down the
right column.
These elements control a set of FlexLogic operands that can be used to initiate outputs or select modes. Each
physical pushbutton has an integrated LED indicator that can be user-configured to display the appropriate
status.
4 These pushbuttons have clear covers behind which custom labels can be mounted. A utility is available to print
the labels, under File > Front Panel Report in the software.
842811A1.CDR
• TROUBLE — Indicates that the relay has detected an internal problem. Check the self-test messages outlined at the
end of the Commands and Targets chapter, and view the event records under Actual Values > Records. For a beta /
pre-release, this LED is always on.
• TEST MODE — Indicates that the relay is in test mode. For information, see the Test Mode section in the Settings
chapter.
• TRIP — Indicates that the selected FlexLogic operand serving as a trip input has operated. Set the operand under
Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs. This indicator latches; initiate the reset
command to reset the latch.
• ALARM — Indicates that the FlexLogic operand serving as an alarm switch has operated. Set the operand under
Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs. This indicator never latches.
• PICKUP — Indicates that an element is picked up. This indicator never latches.
The event-cause indicators in the first column are as follows.
Event-cause LEDs are below the status LEDs. They are turned on or off by protection elements that have their respective
target setting selected as either “Enabled” or “Latched.” If a protection element target setting is “Enabled,” then the
corresponding event-cause LEDs remain on as long as the operand associated with the element remains asserted. If a
protection element target setting is “Latched,” then the corresponding event-cause LEDs turn on when the operate
operand associated with the element is asserted and remains on until the RESET button on the front panel is pressed after
the operand is reset.
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B, or C LEDs. This 4
includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
• VOLTAGE — This LED indicates voltage was involved
• CURRENT — This LED indicates current was involved
• FREQUENCY — This LED indicates frequency was involved
• OTHER — This LED indicates a composite function was involvedThis LED indicates a composite function was involved
• PHASE A — This LED indicates phase A was involved
• PHASE B — This LED indicates phase B was involved
• PHASE C — This LED indicates phase C was involved
• NEUTRAL/GROUND — This LED indicates that neutral or ground was involved
The user-programmable LEDs consist of 48 amber LED indicators in four columns. The operation of these LEDs is user-
defined. Support for applying a customized label beside every LED is provided. Default labels are shipped in the label
package of every F35, together with custom templates. The default labels can be replaced by user-printed labels.
User customization of LED operation is of maximum benefit in installations where languages other than English are used
to communicate with operators. See the User-Programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
Status indicators
• IN SERVICE — Indicates that control power is applied, all monitored inputs/outputs and internal systems are fine, and
the relay is in (online) Programmed mode (under Settings > Product Setup > Installation)
4 • TROUBLE — Indicates that the relay has detected an internal problem. Check the self-test messages outlined at the
end of the Commands and Targets chapter, and view the event records under Actual Values > Records. For a beta /
pre-release, this LED is always on.
• TEST MODE — Indicates that the relay is in test mode. For information, see the Test Mode section in the Settings
chapter.
• TRIP — Indicates that the selected FlexLogic operand serving as a trip switch has operated. This indicator always
latches; initiate the reset command to reset the latch.
• ALARM — Indicates that the selected FlexLogic operand serving as an alarm switch has operated. This indicator never
latches.
• PICKUP — Indicates that an element is picked up. This indicator never latches.
Event-cause indicators
Event-cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched.” If a protection element target setting is “Enabled,” then the corresponding event cause LEDs
remain on as long as the operand associated with the element remains asserted. If a protection element target setting is
“Latched,” then the corresponding event cause LEDs turn on when the operate operand associated with the element is
asserted and remains on until the RESET button on the front panel is pressed after the operand is reset.
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B, or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
• VOLTAGE — Indicates voltage was involved
• CURRENT — Indicates current was involved
• FREQUENCY — Indicates frequency was involved
• OTHER — Indicates a composite function was involved
• PHASE A — Indicates phase A was involved
• PHASE B — Indicates phase B was involved
• PHASE C — Indicates phase C was involved
• NEUTRAL/GROUND — Indicates that neutral or ground was involved
User-programmable indicators
The second and third panels provide 48 amber LED indicators whose operation is controlled by the user. Custom labelling
can be done.
User customization of LED operation is of maximum benefit in installations where languages other than English are used
to communicate with operators. See the User-programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
Figure 4-49: LED panels 2 and 3 (index template)
Firmware revisions 2.9x and earlier support eight user setting groups; revisions 3.0x and higher support six setting
groups. For convenience of users using earlier firmware revisions, the relay panel shows eight setting groups. Even
though the LEDs have default labels, they are fully user-programmable.
The relay is shipped with the default label for the LED panel 2. The LEDs, however, are not pre-programmed. To match the
pre-printed label, the LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. The
LEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explained in
the next section.
Figure 4-50: LED panel 2 (default labels)
Status indicators
• IN SERVICE — Indicates that control power is applied, all monitored inputs/outputs and internal systems are fine, the
relay’s test mode is disabled, and the relay is in (online) Programmed mode (under Settings > Product Setup >
Installation)
• TROUBLE — Indicates that the relay has detected an internal problem. Check the self-test messages outlined at the
end of the Commands and Targets chapter, and view the event records under Actual Values > Records. For a beta /
pre-release, this LED is always on.
• TEST MODE — Indicates that the relay is in Isolated (solid) or Forcible (flashing) test mode. For information, see the Test
Mode section in the Settings chapter.
• TRIP — Indicates that the selected FlexLogic operand serving as a trip input has operated. Set the operand under
Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs. This indicator latches; initiate the reset
command to reset the latch.
• ALARM — Indicates that the selected FlexLogic operand serving as an alarm input has operated. Set the operand
under Settings > Product Setup > User-Programmable LEDs > Trip & Alarm LEDs.
Figure 4-51: Example of LEDs on graphical front panel
4. Enter the text to appear next to each LED and above each user-programmable pushbutton in the fields provided. The
LED Offsets and Button Offsets buttons move all labels left/right and up/down on the page (they both do the same
action, so use either button). The Button Offsets button does not display when there are no pushbuttons to customize.
5. Feed the UR front panel label cutout sheet into a printer and press the Print button in the front panel report window.
6. When printing is complete, fold the sheet along the perforated lines and punch out the labels.
7. Remove the UR label insert tool from the package and bend the tabs as described in the following procedures. These
tabs are used for removal of the default and custom LED labels.
Use the tool with the printed side containing the GE part number facing the user.
The label package shipped with every F35 contains the three default labels, the custom label template sheet, and the label
removal tool.
If the default labels are suitable for your application, insert them in the appropriate slots and program the LEDs to match
them. If you require custom labels, use the following procedures to remove the original labels and insert the new ones.
To set up and use the label removal tool:
1. Bend the tabs at the left end of the tool upwards as shown.
To remove the LED labels from the F35 front panel and insert the custom labels:
1. Use the knife to lift the LED label and slide the label tool underneath. Ensure that the bent tabs are pointing away from
the relay.
2. Slide the label tool under the LED label until the tabs snap out as shown. This attaches the label tool to the LED label.
4. Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown.
To remove the user-programmable pushbutton labels from the F35 front panel and insert the custom labels:
1. Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown. Ensure that the bent
4 tab points away from the relay.
2. Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown. This attaches the
label tool to the user-programmable pushbutton label.
4. Slide the new user-programmable pushbutton label inside the pocket until the text is properly aligned with the
buttons.
4
4
4. Optionally save the changes by clicking the Save icon on the toolbar.
5. Click the Print icon on the toolbar. Consider printing to PDF format and adjusting the zoom for appropriate label size,
then print on a physical printer.
6. Cut labels as a block or individually, for example with scissors or an Exacto knife.
7. If there is a plastic cover over the front panel, remove it by gently pushing in on the right side and lifting off the cover.
8. Remove the plastic cover over the LEDs or pushbutton(s) using a screw driver.
9. Insert the labels.
10. Re-attach the plastic covers.
Figure 4-54: Front panel label designer for graphical front panel
5. Click the Print button in the window and select the printer.
6. Once printed, peel the labels off the template and stick them on the front panel. For the enhanced and graphical front
panels, they go over the clear plastic inserts, not under. For the basic front panel, they go under or over the plastic
covers.
Any changes are not saved. Each time that the label designer window opens, the original template displays. Any labels
deleted are not lost.
values. Continually pressing the MESSAGE right arrow from a header display displays specific information for the category.
Conversely, continually pressing the MESSAGE left arrow from a setting value or actual value display returns to the header
display.
Default values are indicated in this instruction manual in mixed case. In the example shown here, the default access level is
Restricted.
Highest level Lowest level (setting value)
Example
ACTUAL VALUES Press the MENU key until the Actual Values header page appears. This page contains system
STATUS and relay status information.
4 SETTINGS
Press the MENU key until the Settings header page appears. This category contains settings to
PRODUCT SETUP configure the relay.
SECURITY Press the MESSAGE right arrow once to display the first sub-header (Security).
ACCESS LEVEL: Press the MESSAGE right arrow once to display the first setting for Security.
Restricted
SECURITY Press the MESSAGE left arrow to return to the Security heading.
DISPLAY Press the MESSAGE down arrow to display the second setting sub-header associated with the
PROPERTIES Product Setup header.
LANGUAGE: Press the MESSAGE right arrow once to display the first setting for Display Properties.
English
SETTINGS Press the MESSAGE left arrow to return to the Display Properties page, then again to return to
SYSTEM SETUP the Product Setup Page. Press the MESSAGE down arrow to move to the next Settings page. This
page contains settings for System Setup.
Numerical data
Each numerical setting has its own minimum, maximum, and increment value associated with it. These parameters define
what values are acceptable for a setting.
FLASH MESSAGE For example, select the SETTINGS PRODUCT SETUP DISPLAY PROPERTIES FLASH
TIME: 10.0 s MESSAGE TIME setting.
MINIMUM: 0.5 Press the HELP key to view the minimum and maximum values. Press the key again to view the
MAXIMUM: 10.0 next context sensitive help message.
Two methods of editing and storing a numerical setting value are available.
• 0 to 9 and decimal point — The relay numeric keypad works the same as a calculator. A number is entered one digit at
a time. The leftmost digit is entered first and the rightmost digit is entered last. Pressing the MESSAGE left arrow or
pressing the ESCAPE key, returns the original value to the display.
• VALUE keys — The VALUE up arrow increments the displayed value by the step value, up to the maximum value
allowed. While at the maximum value, pressing the VALUE up arrow again allows the setting selection to continue
upward from the minimum value. The VALUE down arrow decrements the displayed value by the step value, down to
the minimum value. While at the minimum value, pressing the VALUE down arrow again allows the setting selection to
continue downward from the maximum value.
FLASH MESSAGE As an example, set the flash message time setting to 2.5 seconds. Press the appropriate numeric
TIME: 2.5 s keys in the sequence “2 . 5". The display message changes as the digits are being entered.
NEW SETTING Until ENTER is pressed, editing changes are not registered by the relay. Press ENTER to store the
HAS BEEN STORED new value in memory. This flash message momentarily appears as confirmation of the storing
process. Numerical values that contain decimal places are rounded-off if more decimal place digits
are entered than specified by the step value.
Enumeration data
Enumeration settings have data values that are part of a set, whose members are explicitly defined by a name. A set has
two or more members.
ACCESS LEVEL: For example, the selections available for ACCESS LEVEL are "Restricted," "Command," "Setting," and
Restricted "Factory Service."
Enumeration type values are changed using the VALUE keys. The VALUE up arrow displays the next selection while the
VALUE down arrow displays the previous selection.
ACCESS LEVEL: If the ACCESS LEVEL needs to be "Setting," press the VALUE keys until the proper selection displays.
Setting Press HELP at any time for the context sensitive help messages.
NEW SETTING Changes are not registered by the relay until the ENTER key is pressed. Pressing ENTER stores the
HAS BEEN STORED new value in memory. This flash message momentarily appears as confirmation.
4 Alphanumeric text
Text settings have data values that are fixed in length, but user-defined in characters. They can be upper-case letters,
lower-case letters, numerals, and a selection of special characters.
There are several places where text messages can be programmed to allow the relay to be customized for specific
applications. One example is the Message Scratchpad. Use the following procedure to enter alphanumeric text messages.
For example, enter the text “Breaker #1”.
1. Press the decimal point to enter text edit mode.
2. Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position.
3. Repeat step 2 for the remaining characters: r,e,a,k,e,r, ,#,1.
4. Press ENTER to store the text.
5. If you have any problem, press HELP to view context sensitive help. Flash messages appear sequentially for several
seconds each. For the case of a text setting message, pressing HELP displays how to edit and store new values.
Numerical data
This example outlines how to change the FLASH MESSAGE TIME setting. Flash messages are status, warning, error, and
information messages displayed in response to certain key presses during settings programming. An example is a
confirmation message upon saving settings. This setting specifies how long to display the message.
Press the Menu pushbutton to display the main menu.
Use the Up or Down pushbutton to select SETTINGS, then press the Right or ENTER pushbutton.
Figure 4-57: Settings menu 4
Use the Up or Down pushbutton to select DISPLAY PROPERTIES, then press the Right or ENTER pushbutton.
4 Figure 4-59: Display Properties menu
Use the Up or Down pushbutton to select FLASH MESSAGE TIME, then press the Right or ENTER pushbutton. If the relay is
configured to require login to edit settings, and the user is not already logged in, the login page displays. When the user
has successfully logged in, the setting is opened for edit. As the FLASH MESSAGE TIME setting accepts a numerical value, a
keypad displays. The time is to be changed to 4.0 seconds.
The current setting displays. A flashing cursor line marks the insertion point, initially positioned after the last character of
the setting. The setting range displays under the text.
Press the <-- Move Cursor and Move Cursor --> Tab pushbuttons to move the insertion point. Place it after the 2.
Press the Backspace Tab pushbutton to remove the character to the left of the cursor, in this case the 2.
Using the arrow keys, enter another time, for example 4 for four seconds. These Up, Down, Left, and Right pushbuttons
move the keypad key selector. Pressing the ENTER pushbutton with the - key selected inverts the sign. Pressing the ENTER
pushbutton with the decimal point selected enters that character at the insertion point. Push ENTER now to accept the 4.
Press the Save Tab pushbutton, which does a range check on the value, saves the setting when valid, closes the page, and
displays the previous page. 4
When a setting is not saved due to an invalid value, a message flashes, for example being out of range. In cases where the
relay needs to be restarted for settings to take effect, the flash message advises.
Setting entry can be cancelled without impact on the original value by pressing the ESCAPE or Home pushbutton.
Alphanumeric text
Settings that accept alphanumeric values display a keyboard. An example is a pushbutton name.
The &123 key toggles between text and numbers.
The shift key (up arrow on keyboard) is green upon activation, while the keyboard letters switch to upper case. Double-click
the shift key to lock capital lettering, or full capitals.
The globe key (shown greyed-out) toggles the keyboard language between English and another display language selected,
for example between English and French. (The second language needs to be activated under Settings > Product Setup >
Display Properties.)
For Japanese and Chinese, up to 10 characters can be input in a field, not 20.
To add accents, highlight a key and hold the ENTER pushbutton on the graphical front panel. Any special characters
associated with the key display.
Figure 4-61: Settings page with keyboard and accents
The configurable name displays in the header and Tab pushbutton label. Factory default names are Page 1, Page 2, and so
on.
The phasor sources are configured under Settings > System Setup > Signal Sources. The tables to display the actual
values are configured in the software under Settings > Product Setup > Graphical Panel > Metering Editor.
4
ENTER COMMAND This message appears when the USER 1, USER 2, or USER 3 key is pressed and a COMMAND
PASSWORD PASSWORD is required, that is, if COMMAND PASSWORD is enabled and no commands have been
issued within the last 30 minutes.
Press USER 1 This message appears if the correct password is entered or if none is required. This message
To Select Breaker displays for 30 seconds or until the USER 1 key is pressed again.
BKR1-(Name) SELECTED This message displays after the USER 1 key is pressed for the second time. Three possible actions
USER 2=CLS/USER 3=OP can be performed from this state within 30 seconds as per the following items (1), (2) and (3).
(1)
USER 2 OFF/ON If the USER 2 key is pressed, this message appears for 20 seconds. If the USER 2 key is pressed
To Close BKR1-(Name) again within that time, a signal is created that can be programmed to operate an output relay to
close breaker 1.
(2)
USER 3 OFF/ON If the USER 3 key is pressed, this message appears for 20 seconds. If the USER 3 key is pressed
To Open BKR1-(Name) again within that time, a signal is created that can be programmed to operate an output relay to
4 open breaker 1.
(3)
BKR2-(Name) SELECTED If the USER 1 key is pressed at this step, this message appears showing that a different breaker is
USER 2=CLS/USER 3=OP selected. Three possible actions can be performed from this state as per (1), (2) and (3). Repeatedly
pressing the USER 1 key alternates between available breakers. Pressing keys other than USER 1, 2,
or 3 at any time cancels the breaker control function.
5. After the CHANGE...PASSWORD message appears on the display, press the VALUE up or down arrow to change the
selection to “Yes.”
6. Press the ENTER key and the display prompts you to ENTER NEW PASSWORD.
7. Type in a password and press the ENTER key.
8. When VERIFY NEW PASSWORD displays, re-type the password and press ENTER.
CHANGE SETTING
PASSWORD: No
NEW PASSWORD
HAS BEEN STORED
9. When the NEW PASSWORD HAS BEEN STORED message appears, your new Setting (or Command) password is active.
4 •
from the TRIP BUS 1 RESET FlexLogic operand must be 1, or output from the RESET OP FlexLogic operand must be 1.
For the settings, one of 16 input conditions at the top left must be met for the OR, the TRIP BUS 1 FUNCTION must be
Enabled, and the TRIP BUS 1 BLOCK output must output as 0, which is then negated/reversed by NOT to become 1.
Table 4-2: Logic diagram symbols
Symbol Description
= Off Output from FlexLogic operand, so user-defined
= Enabled 1 = Enabled and 0 = Disabled
OR Any function input on the left side satisfies the condition
AND All functions input on the left side are required to satisfy the condition
Not. Negates/reverses the output, for example 0 becomes 1.
Connection
S, R Set, Reset
TPKP Timer pickup. Triggered by the settings latch in the diagram.
TRST Timer reset. Triggered by the reset latch in the diagram.
SETTINGS
TRIP BUS 1 FLEXLOGIC OPERAND
FUNCTION
TRIP BUS 1 PKP
= Enabled
TRIP BUS 1 BLOCK AND
= Off
SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
= Off
OR
4
FLEXLOGIC OPERAND
RESET OP 842023A1.CDR
• Toolbars
4.4.1.1 Examples 4
The symbols are displayed in the UR format.
Preparation — Under Settings > Inputs/Outputs > Virtual Outputs, the first and second virtual outputs are named
OscTrigger
Top logic — Three-minute timer trigger
Bottom logic — Turn on LED 1 for 10 seconds when the trigger starts
Preparation — Under Settings > Inputs/Outputs > Virtual Outputs, virtual outputs 3 and 4 are named DLTrigger
Top logic — Seven-minute timer trigger
Bottom logic — Turn on LED 9 for 10 seconds when the trigger starts
4 Preparation — Under Settings > Inputs/Outputs > Virtual Outputs, virtual output 5 is named EVStart, 6 is named
EVTriggered, and 7 is named EVMakeEvent
Top logic — One-minute timer trigger
Middle logic — Turn on LED 17 for 10 seconds when trigger starts
Bottom logic — Create events at 100 ms intervals for the same 10 second period
The FlexLogic Equation Editor window is in view-only mode when the Logic Designer is open. To instead work in the
FlexLogic Equation Editor, close the Logic Designer window, then re-open the FlexLogic Equation Editor.
the device in the Online Window area and select the Add Device to Offline Window option.
Figure 4-69: Access Engineer in the Offline Window area
4
A default block diagram opens that shows 48 inputs (boxes) and 48 user-programmable LEDs (circles).
For the graphical front panel, no LEDs can be added to the window and the LEDs are removed when opening any
existing files. For these existing files with the LEDs removed, save the file without them.
Figure 4-70: Default view of FlexLogic designer
2. Optionally delete the default logic diagram by right-clicking its tab at the bottom of the window and selecting Delete.
3. To add a blank sheet, click Edit > Add Sheet. A new tab displays. Or use the last tab displayed, which is a blank sheet.
4. Optionally right-click the new tab and Rename it.
5. Add the input blocks to the logic diagram. For example, click the I/O Tokens tab on the right, click the Input element,
then click in the logic sheet to add it. Or drag-and-drop it.
6. Double-click the block on the sheet to configure it, selecting from the two drop-down lists. The figure shows that
virtual input 61 is being added. The View Associated Screen button opens its settings window.
Figure 4-71: Configuring an input block
4
7. Add the output blocks to the logic diagram. For example, click the I/O Tokens tab, click the Virtual Output element,
then click in the logic sheet to add it. Double-click the block on the sheet to configure it. For the name, make it unique.
The figure shows virtual output 61 is being added, with a suffix of "io" added to the name to make it unique. Note that
the outline color of a block is red until it is configured, and that this properties window varies by block and the
selectable options by order code.
Figure 4-72: Configuring an output block
8. Connect the input blocks to the output blocks by drawing a line as follows. Click at the end of one block and drag the
line to the next block. Or click the Drawing Tools tab, then select the Line option. The cursor needs to be at the
connection point to end the line, not elsewhere on the block. Note that the outline color is no longer red on the blocks.
9. Add any remaining blocks or information. Right-click a block to copy and paste it. Notes are as follows.
Add a text box — Drawing Tools > Text
Add a FlexElement — Elements > FlexElement. An analog input is expected where a small arrow head shows in the
box.
Figure 4-74: FlexElement accepts analog inputs on left side where arrow heads display
Add an Element — Elements tab. Available elements reflect the product, for example the Control Elements category.
Figure 4-75: Elements reflect Control Elements
10. Check for any blocks that have a red outline. These are invalid. Fix them before continuing, for example by configuring
them.
11. Compile the logic diagram to check for errors by clicking the Compile button at the bottom left or by pressing the F7
key.
If prompted about a message about sorting, click Yes to apply the default (for this example), which can be automatic
sorting based on an algorithm that applies fastest execution time.
With successful compiling, the file is saved and the FlexLogic equations populate automatically. Scroll up through the
compile messages, with the red errors being the only messages that require fixing before proceeding.
The figure shows that we forgot to add the "Io" suffix to the names of virtual outputs 62 and 63, as indicated by
"Warning: Virtual output xx using default name." This warning is a minor warning.
The warning "input using disabled feature" means that input needs to be enabled. Double-click the block, click the
View Associated Screen button, enable the setting, save, and recompile.
The output and messages are explained in the next section.
Some information displayed in the compile messages updates automatically, for example messages after a device is
unplugged.
Figure 4-76: Compile and check the logic
12. View the FlexLogic equations by navigating in the Offline Window area to FlexLogic > FlexLogic Equation Editor. The
window opens with the entries displayed in the next tab.
Figure 4-77: Logic displayed in FlexLogic Equation Editor
4
When the Update SCL files option is selected, the CID and IID files in the device folder are updated by the user
configuration in the IEC 61850 panel and thereby become synchronized. The CID file and the IID file (depending on the
preference 'Do not update IID file when updating SCL files') are updated. If the CID file is not already there, it is generated.
The location of these files is C:\ProgramData\GE Power Management\urpc, for example, in the Offline and Online folders.
Any FlexLogic equations entered in the Offline Window area are erased. The logic drawn in the Logic Designer window in
Engineer in the Offline Window area remain. The warning icon disappears after updating.
The following information is contained in the compile window.
Figure 4-79: Compiled results
Number of Lines Saved — The number of compiled logic lines eliminated by using the optimization algorithm, as set in the
Optimize Compiled Output option of the Preferences. In the example shown, no lines were saved because the optimizer is
disabled.
FlexLogic Lines — The number of lines that the compiled logic uses, for example seven of 512 available.
Virtual Output equations — The number of FlexLogic equations used in the Logic Designer window.
Timers used — The number of timers used in the Logic Designer window.
Memory Used — The percent of memory used in the Logic Designer window.
Errors
Table 4-3: Errors from compiling
Category Block or gate Message Description
affected
Error All Number of lines (nnn) exceeds The compiled result exceeds the limit of 512. Reduce the number of
maximum limit of 512 equations to 512 or less.
Error Tag-In Tag-in not configured (TAG_ID, A Tag-In is connected to a circuit but the Tag-In is not referencing an
SheetReference) existing Tag-Out
Error 1 Shots One Shot is over limit The number of One-Shots contained within all of the VO blocks has
(SYMBOL_ID, SheetReference) exceeded the maximum allowed for the firmware revision. This value can
either be 0 or 32.
Error =VO VO has no inputs (VO_ID, A Virtual Output block is located within the FlexLogic diagram and there
SheetReference) is no block connected as input to it. Connect and identify the inputs.
Warnings
When using the 'Reset OP' operand, a warning can appear indicating that this is a disabled feature. This means that the
Reset Settting's FlexLogic operand is set to OFF. Resetting of the relay can be done by pressing the reset button on the front
panel of the relay or by sending a Reset command through communications.
Table 4-4: Warning messages from compiling
Category Block or Message Description
gate
affected
Minor warning Input Input set to unused VO An Input symbol is using an unassigned Virtual Output
4 Major warning Tag-Out
(SYMBOL_ID,Name,Sheet)
Tag-out not connected A Tag-Out symbol has no input
(TAG_ID,Sheet)
Major warning All Symbol not connected A symbol’s input and/or output is not connected and is not part of a
(SYMBOL_ID,Name,Sheet) VO block. Draw the input and/or output to the block.
Minor warning =VO Virtual Output n using default The Assigned Virtual Output is using the default name. Change the
name (VO_ID,Sheet) name.
Minor warning Input Input using default name An Input symbol is using a Contact Input, Contact Output, Digital
(SYMBOL_ID,Name,Sheet) Element, FlexElement, or Digital Counter set to the default name.
Change the name so that it is unique.
Setting warning Input Input using disabled feature An Input symbol is using a disabled Virtual Input, Contact Input, Digital
(SYMBOL_ID,Name,Sheet) Element, FlexElement, Digital Counter, Control Pushbutton,
Programmable Pushbutton, Contact Output, or Protection/Monitoring
Element. Enable it and try again.
Major warning Input Input set to OFF An Input symbol is set to OFF
(SYMBOL_ID,Sheet)
Major warning Input Input set to ON An Input symbol is set to ON
(SYMBOL_ID,Sheet)
Setting warning Input Contact Output Operate is OFF The symbol block is using the default setting of OFF
(SYMBOL_ID, Contacts)
Setting warning Input Contact Output Seal-In is OFF The symbol block is using the default setting of OFF
(SYMBOL_ID, Contacts)
4. In the second sheet, click and drag the Tag In element to the sheet where the first sheet is to connect.
5. Double-click the element and in the window that opens, select the first sheet from the drop-down list to connect the
two sheets.
6. Save the work.
You can also select an element from the drop-down list on the toolbar. It is then highlighted in the logic diagram.
Figure 4-86: Monitoring a device, with minor error caused by weak battery
To print labels:
1. In the Front Panel Report window, double-click an LED or pushbutton and enter text.
2. To print the labels, click the Print icon on the toolbar.
3. To save the report and labels, click File > Save As, enter a file name, and select the FPR, JPG, or PDF format.
4. Use the instructions in the second tab of the window to add the labels to the physical device.
4.4.6 Preferences
Preferences determine functionality. As such, you are encouraged to review them. This section outlines some options
available in the menus and preference panels.
Access them in the Logic Designer panel under the View menu and under File > Preferences. The Logic Designer and
Logic Monitor preferences are outlined here, not all preferences for a device.
Workbook Setup
WorkBook 4
Print Scale — The scale for logic diagram when printing. Scaling a large diagram to 200 percent, for example, results in the
diagram being cut off.
Orphan Protection — When enabled, the printing output prevents Virtual Output circuits from spanning more than a single
page. The largest Virtual Output circuit is scaled to fit on a single page and all remaining Virtual Output circuits are scaled
so that all circuits are printed using the same scale.
Show Title Block — When enabled, places an information box at the bottom right of the diagram when printing. Enter the
information in the File Information panel.
Show Sheet Name — When enabled, shows Sheet 1, Sheet 2, or any other name at the top of the logic diagram when
printing.
Start Sheet On New Page — Places the sheet on the next page when printing.
Show Notes Selection — When other than None, prints the text from any information notes added to the document (under
Drawing Tools tab > Note). The text is printed after the logic diagram.
File Information
The text entered here displays at the bottom right of a diagram when printing, provided that the Show Title Block option is
enabled. Note the option to change the logo from the GE logo to your company logo.
Display
The panel sets how the element boxes display. The figure shows how an AND gate displays when the UR default, IEC, or
ISO symbol type is selected.
Figure 4-90: AND gate varies by standard selected
Symbol Style — IEC, ISO, UR Setup — Sets how the gates display in the logic diagram.
Symbol Color — When set to Black & White, only logic blocks with issues continue to display red.
Zoom Operation — Determines what happens when the View > Zoom functions are used. When set to Sheet Only and the
zoom is changed, the single tab changes. When set to Workbook, all tabs change.
Editor
Repeat Symbol — Enable this feature to add element blocks rapidly in sequence, for example when you have inputs 1 to
10, without having to select the element each time. Select the element block from the toolbox, click the diagram, then
continue to click to add additional blocks.
Use first available VO / Timer — When enabled and you copy and paste a virtual output or timer element, the numbering
continues in sequence. For example, you copy timer 5 and paste it as timer 6. When disabled and you copy and paste a
virtual output or timer element, the same number is used. For example, you copy timer 5 and paste it as timer 5.
Auto-Save Logic Designer every x minutes — Logic diagrams with changes are saved automatically according to this
interval. The range is 5 minutes (default) to 30 minutes. With auto-save, the file extension of the saved file is .auto. This file
remains until you save the file manually.
Auto Populate
These options work in the Edit > Auto Populate Workbook function.
VOs per Worksheet — When an existing settings file is opened in the Logic Designer, the Logic Designer populates the
canvas and attempts to evenly distribute the Virtual Output circuits across multiple sheets. A value of 100 in this setting
places all FlexLogic equations on a single sheet until there are 100, then the next ones are placed on another sheet. A value
of 1 places each Virtual Output circuit on a separate sheet.
4 Show / FlexLogic Merge / Show Unused — If Show Contact Outputs and Show LEDs are selected, for example, the function
places Contact Output and User-programmable LED symbols for settings that are configured. If you disable the LED check
boxes, then the LED tab/sheet does not display when you next open the Logic Designer window. The settings apply to all
products, not just the active window when it is next opened. Close then reopen the Logic Designer window for the setting
to take effect.
Compiler
Show Warnings — Options to filter the messages that display when logic compiles.
Minor — Enable to display minor errors. An example is using the default values of an element added to the diagram, such
as the name of the element. An example is "Warning: Virtual output xx using default name," for which you simply click into
the element to rename it.
Major — Enable to display major errors. Examples are an input that does not have a corresponding output, using disabled
features, and failing to connect a symbol. Fix these errors.
Setting — Enable to display error message related to settings, such as an improperly configured setting, such as using ON
or OFF.
Automatically Sort VOs — When enabled, the logic is compiled with an algorithm to give best results and quickest
performance, for example the fastest logic first. The fastest logic displays in the FlexLogic Equation Editor output as the
first entries in the table. Use sorting when virtual outputs have dependencies on other virtual outputs. This setting takes
precedence over order set manually in the VO Order tab in the compiler.
When disabled, the sequence in which the blocks were drawn is followed.
Optimize Compiled Output — With this option enabled, the software automatically optimizes a logic diagram to reduce
space and free up FlexLogic entries. Run the compiler again, for example by clicking the Compile button at the bottom left
of the software. The number of saved lines displays in the Optimization Summary. Changes also display when the FlexLogic
Equation Editor is accessed. The logic diagram does not change.
Display
The software displays the color specified when an element is on. There is no color when the element is off.
The software displays another color when the status cannot be determined and is unknown.
Timing
Timing Information can be displayed in the monitoring window. This timing information is only an approximate
representation of how Engineer sees transitions. Use the device's Event Record to view accurate timing information.
The timing information can also be streamed to a comma-separated values (CSV) spreadsheet.
The timing information displayed and recorded can be filtered based on six categories. If a category is not selected, any
timing information related to that category does not display and is not recorded to the CSV file.
Show Timing Information in Output Window — Enable to display times in the monitoring window.
Because of the update rate of the Logic Monitoring, the timing information cannot be used as an accurate representation
of the events that occur within the relay. Use instead the device's event record. Timing information can be delayed by 30
seconds.
Save Timing Information to CSV File — Enable to write timing information in a spreadsheet. The timing information is
recorded in a text file that uses commas to separate each of the fields. This file uses the extension CSV that is supported by
any spreadsheet application.
Every change written to the CSV file requires a timestamp.
The format for the timing information in the output window is as follows:
yyyy/mm/dd hh:dd:ss
devicename offline 4
yyyy/mm/dd hh:dd:ss
devicename ONLINE
yyyy/mm/dd hh:dd:ss
VO1: Virt Out 1- 0
VI4: Virt In 4- 1
DI3: Direct In 3- 0
RI2: Remote In 2- 1
H5a: Contact In 1- 1
H1: Contact Output 1- 0
Data is only appended to the CSV file. The format for the data is as follows:
yyyy/mm/dd hh:dd:ss, devicename, offline
yyyy/mm/dd hh:dd:ss, devicename, ONLINE
yyyy/mm/dd hh:dd:ss, VO1: Virt Out 1, 0
yyyy/mm/dd hh:dd:ss, VI4: Virt In 4, 1
yyyy/mm/dd hh:dd:ss, DI3: Direct In 3, 0
yyyy/mm/dd hh:dd:ss, RI2: Remote In 2, 1
yyyy/mm/dd hh:dd:ss, H5a: Contact In 1, 1
yyyy/mm/dd hh:dd:ss, H1: Contact Output 1, 0
Options display for filtering, such as recording timing for Virtual Inputs and Outputs, but not Communications Status.
4.4.7 Toolbars
These are toggled in the View > Toolbar menu.
The UR symbols are displayed for the toolbox icons. They change when the default setting is changed to IEC or ISO
symbols. The symbols displayed in the toolbox also vary by firmware version, reflecting what is supported for each release.
Open File Open an existing settings file in the URS, CID, or IID format
PDF Report Create a PDF document from Logic Designer diagram(s). Settings can be
changed under File > Preferences > Workbook Setup.
Sort Order Select to change the sort order of the Virtual Output list to the right of the
icon. Virtual Outputs can be sorted numerically in ascending and
descending order based on numbers and names.
Select VO to View (x - x) Select a Virtual Output to locate and select it in the workbook. Each Virtual
Output listed also contains the name of the sheet where the Virtual Output
is located.
Edit Mode Switch to Logic Designer mode
Logic Designer
Monitor Mode Switch to Logic Monitor mode
Logic Monitor
Turn On ALL Communications Turn on all communications to all Logic Designer diagrams that are in the
monitoring mode. Default upon each launch of Engineer.
Turn Off All Communications Turn off all communications to all Logic Designer diagrams that are in the
monitoring mode. This is a legacy function for serial communication to turn
off communication to devices. Turning off communication applies to the
current session only. When you re-launch the EnerVista software,
communication is on by default.
Drawing Tools
Draw multiple joined lines. Click and drag for each line. Double-click to finish.
Draw multiple, closed curves. Click for each line. Double-click to finish.
Add text box with rectangle around it. Click to add. Double-click it to change text.
4
Add figure. Select file in the window that opens, then click on diagram canvas to add figure.
Add note icon and text. Click to add. Double-click to edit the title and text.
I/O Tokens
These are parts used in FlexLogic equations. They are the inputs and outputs of the Virtual Output equations. The display
can vary from that shown here.
Input from another UR device. Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive and
cannot be used simultaneously.
Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive and cannot be used simultaneously.
FlexAnalog symbol that can be used as the input to a FlexElement or use the FlexAnalog symbol to monitor an actual
value when in logic Monitoring mode
Contact Input Gate is similar to the Input symbol but is restricted to the operands associated with a Contact Input
Contact Output Gate is similar to the Input symbol but is restricted to the operands associated with a Contact Output.
The Operate and Seal-In settings can be configured graphically.
The Non-Volatile Latch is similar to the Input symbol but is restricted to the operands associated with a Non-Volatile
Latch. The Set and Reset settings can be configured graphically.
The final output of an equation is a numbered register called a virtual output. Virtual outputs can be used as an input
operand in any equation, including the equation that generates the output, as a seal-in or other type of feedback.
4
Place and configure a Remote Output. The UR's order code and firmware version then determine the availability of the
Remote Output.
Place and configure a Direct Output. The UR's order code and firmware version then determine the availability of the
Direct Output to another UR device.
Place and configure a Teleprotection Output. The UR's order code and firmware version then determine the availability
of the Teleprotection Output.
Place a User Programmable LED in the Logic Designer diagram. Not applicable when using a graphical front panel.
A Tag Out can be used in 1 of 2 ways. The first use of the Tag Out is to break up logic that needs to span several sheets.
The second use of the Tag Out is to associate a frequently used block of code with the Tag Out and then repeatedly use
the same block of code using a Tag In. When a Tag Out is referenced more than once, the Tag Out is replaced with a
Virtual Output during the compile phase.
Tag-In can is used to reference an existing Tag-Out. It joins another diagram to a previous diagram.
Boolean Tokens
These symbols are used to create FlexLogic Equations. Use them as intermediate logic for the Virtual Output equations.
The display can vary from that shown here.
Place an OR gate in the Logic Designer diagram. Only one action needs to occur. Any function input on the left side
satisfies the condition.
The number of inputs is configurable from two to 16.
Place an AND gate in the Logic Designer diagram. Multiple actions need to occur. All functions input on the left side are
required to satisfy the condition.
The number of inputs is configurable from two to 16.
Place a NOR gate in the Logic Designer diagram. Gives the value of one when all input operands have a value of zero
and otherwise gives a value of zero. It gives an output signal when there are no input signals. An inverter that reverses
the logic state.
The number of inputs is configurable from two to 16.
Place a NAND gate in the Logic Designer diagram. Gives the value of zero when all input operands have a value of one
and otherwise gives a value of one. It gives an output signal until all signals are present on its inputs. An inverter that
reverses the logic state.
The number of inputs is configurable from two to 16.
Place a XOR gate in the Logic Designer diagram, which is two exclusive OR gates. Only one action needs to occur. If
there are two inputs or there is no input, there is no output.
Place a NOT gate in the Logic Designer diagram. Gives the value of one when the input operand has a value of zero and
otherwise gives a value of zero. It gives an output signal when there is no input signal. An inverter that reverses the
logic state.
4
Place a latch in the Logic Designer diagram. A latch has two inputs and one output. One input is the Set input, and
other input is the Reset input.
Place a positive one shot symbol that responds to a positive going edge in the Logic Designer diagram. A "one shot" is a
single input gate that generates a pulse ins response to an edge on the input.
Place a negative one shot symbol that responds to a negative going edge in the Logic Designer diagram
Place a positive one shot and a negative one shot symbol in the Logic Designer diagram
Elements
These blocks configure properties of the element or use element operands as input to FlexLogic equations.
Place and configure a FlexElement. A FlexElement is a universal comparator used to monitor any analog actual value
calculated by the relay or a net difference of any two analog actual values of the same type.
Place and configure a Selector Switch element. Firmware version determines feature availability. The Selector Switch
element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic. The element provides for two control inputs.
Place and configure a Digital Element. A Digital Element can monitor any FlexLogic operand
and present a target message and/or enable events recording depending on the output operand state.
Place and configure a Digital Counter element. A Digital Counter counts the number of state transitions
4 from Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element.
Select Select components. Click one component and hold down the CTRL key to select others.
Or click and drag an area that contains multiple components to select.
Edit Vertices Shows vertices points for the component selected (if the component support vertices
manipulation)
Properties Shows the properties of the selected component
Zoom Normal Zoom in and center the screen to the spot selected
Zoom to Fit Zoom in to a magnitude that fits your entire schema layout on your entire screen
Pan Move the viewable area of your screen around the schema. To activate, select this tool
and then place the hand icon over and part of your schema. Click and drag the hand in
a direction to move around the schema.
Align Top, Middle, Bottom Align the selected components to the top, middle, or bottom of the reference
component
Align Left, Center, Right Align the selected components to the left, middle, or right of the reference component
Space Across Evenly space the selected components across a horizontal axis, starting from the far
left component and ending at the far right component
Space Down Evenly space the selected components across a vertical axis, starting from the top
component and ending at the bottom component
Same Width Set the width of the selected components to the same width as the reference
component
Same Height Set the height of the selected components to the same height as the reference
component
Same Size Set the width and height of the selected components to the same width and height of
the reference component
Only basic objects (lines, rectangles, ellipses) can be rotated and flipped.
Only objects from the Drawing Toolbar can be structured (grouped, ungrouped, forward, backward).
Nudge Up, Down, Left, Right Moves selected component one pixel upward, downward, left, right
Rotate Rotates selected component freely. Once selected, put your mouse cursor over the
component and move the component clockwise or counter-clockwise depending on
what you need.
Rotate Left, Right Rotates selected component 90 degrees counter-clockwise or clockwise
Forward, Backward Moves current components on layer higher or lower than its original layer hierarchy
Chapter 5: Settings
Settings
This chapter outlines front panel and/or software settings. The relay is not taken out of service when saving settings; the
relay is taken out of service when a settings file is written to it.
Settings can be viewed remotely in a web browser by entering the IP address of the relay, accessing the Device
Information Menu option, then the Front-Panel Display Report option.
When indicated that a restart is required for a setting change to take effect, use the Maintenance > Reboot Relay
Command in the software.
Settings file conversion from previous firmware versions is supported. See the Maintenance chapter.
5 REMOTE RESOURCES
Access in EnerVista
See page 5-183
SETTING GROUP 2
SETTING GROUP 3
SETTING GROUP 4
SETTING GROUP 5
SETTING GROUP 6
8-BIT SWITCHES
See page 5-282 5
MONITORING See page 5-284
ELEMENTS
5.2 Overview
5.2.1 Introduction to elements
For URs, the term element is used to describe a feature that is based around a comparator. The comparator is provided
with an input (or set of inputs) that is tested against a programmed setting (or group of settings) to determine if the input is
5 within the defined range that sets the output to logic 1, also referred to as setting the flag. A single comparator can make
multiple tests and provide multiple outputs. For example, the time overcurrent comparator sets a pickup flag when the
current input is above the setting and sets an operate flag when the input current has been at a level above the pickup
setting for the time specified by the time-current curve settings. All comparators use analog actual values as the input.
An exception to this rule is digital elements, which use logic states as inputs.
Elements are arranged into two classes, grouped and control. Each element classed as a grouped element is provided with
six alternate sets of settings, in setting groups numbered 1 through 6. The performance of a grouped element is defined by
the setting group that is active at a given time. The performance of a control element is independent of the selected active
setting group.
The main characteristics of an element are shown on a logic diagram. This includes the inputs, settings, fixed logic, and the
output operands generated. The previous chapter explains how to read a logic diagram, and the abbreviations used in a
diagram are defined in the Abbreviations chapter.
Some settings are specified in per-unit (pu) calculated quantities:
pu quantity = (actual quantity) / (base quantity)
Where the current source is from a single current transformer (CT), the base quantity is the nominal secondary or primary
current of the CT. Use the secondary current base to convert per-unit settings to/from a secondary current value, and use
the primary current base to convert to/from a primary current value.
Where the current source is the sum of two or more CTs with different nominal primary current, the primary base quantity
is the largest nominal primary current. For example, if CT1 = 300 / 5 A and CT2 = 100 / 1 A, then in order to sum these, CT2
is scaled to the CT1 ratio. In this case, the base quantity is 300 A primary, 5 A secondary for CT1, and 300/(100/1) = 3 A
secondary for CT2.
For voltage elements, the primary base quantity is the nominal phase-to-phase primary voltage of the protected system
provided that the VT ratio setting is set to the nominal ratio of the VTs and the secondary voltage setting is set to the
phase-to-phase voltage seen by the relay when the voltage of the protected system in nominal. The UR uses the
convention that nominal voltages in a three-phase system are phase-to-phase voltages.
For example, on a system with a 13.8 kV nominal primary voltage, the base quantity is 13800 V. With 14400:120 V delta-
connected VTs, the secondary base quantity and secondary voltage setting is:
Eq. 5-1
For wye-connected VTs, the primary and secondary base quantities are as before, but the secondary voltage setting (here
a phase-to-ground value) is:
Eq. 5-2
5.2.2.1 Background
A mechanism called a source configures the routing of CT and VT input channels to measurement sub-systems. Sources, in
the context of UR series relays, refer to the logical grouping of current and voltage signals such that one source contains all
the signals required to measure the load or fault in a particular power apparatus. A given source can contain all or some of
the following signals: three-phase currents, single-phase ground current, three-phase voltages, and an auxiliary voltage
from a single VT for checking for synchronism.
The basic idea of an AC source is to select a point on the power system where the voltages and currents are of interest. To
illustrate the concept of sources, as applied to current inputs only, consider the breaker-and-a-half scheme that follows.
(The breaker-and-a-half scheme is used for illustrative purposes and is available on select UR products.) In this application,
the current flows as shown by the arrows. Some current flows through the upper bus bar to some other location or power
equipment, and some current flows into transformer winding 1. The current into winding 1 is the phasor sum (or difference)
of the currents in CT1 and CT2 (whether the sum or difference is used depends on the relative polarity of the CT
connections). The same considerations apply to transformer winding 2. The protection elements require access to the net
current for transformer protection, but some elements can need access to the individual currents from CT1 and CT2.
Figure 5-1: Breaker-and-a-half scheme
CT1 through current CT2
Winding 1
5
current
Winding 1
UR-series
relay Power
transformer
Winding 2
CT3 CT4
827791A3.CDR
In conventional analog or electronic relays, the sum of the currents is obtained from an appropriate external connection of
all CTs through which any portion of the current for the element being protected can flow. Auxiliary CTs are required to
perform ratio matching if the ratios of the primary CTs to be summed are not identical. In the UR series of relays, provisions
have been included for all the current signals to be brought to the UR device where grouping, ratio correction, and
summation are applied internally via configuration settings.
A major advantage of using internal summation is that the individual currents are available to the protection device, for
example as additional information to calculate a restraint current, or to allow the provision of additional protection
features that operate on the individual currents, such as breaker failure.
Given the flexibility of this approach, it becomes necessary to add configuration settings to the platform to allow the user
to select which sets of CT inputs are to be added to form the net current into the protected device.
The internal grouping of current and voltage signals forms an AC source. This source can be given a specific name through
the settings and becomes available to protection and metering elements in the UR platform. Individual names can be
given to each source to help identify them for later use. For example, in the scheme shown in the preceding figure, the user
configures one source to be the sum of CT1 and CT2 and can name this source as “Wdg1 I.”
Once the sources have been configured, the user has them available as selections for the choice of input signal for the
protection elements and as metered quantities.
The UR platform allows for a maximum of six sets of three-phase voltages and six sets of three-phase currents. The result
of these restrictions leads to the maximum number of CT/VT modules in a chassis to three. The maximum number of
sources is six. A summary of CT/VT module configurations is as follows.
Item
CT/VT Module
Maximum number
3
5
CT Bank (3 phase channels, 1 ground channel) 6
VT Bank (3 phase channels, 1 auxiliary channel) 3
• EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The
feature is present by default in the EnerVista software.
• CyberSentry security — Advanced security available using a software option. When purchased, the option is enabled
automatically, and the default Password security and EnerVista security are disabled.
Lost password
If all passwords are lost, recovery is possible by resetting the unit to default values. Note that the relay is reset to default
values, not just the passwords.
To reset the unit after a lost password:
1. Email GE customer service at [email protected] with the serial number and using a recognizable corporate email
account. Customer service provides a code to reset the relay to the factory defaults.
2. Enter the reset code on the front panel, under COMMANDS RELAY MAINTENANCE SERVICE COMMAND.
3. Change the default password of ChangeMe1# as outlined in the Set Up CyberSentry and Change Default Password
section at the end of the Installation chapter.
Password requirements
A user account requires an alpha-numeric password that meets the following requirements:
• Password is case-sensitive
• Password cannot contain the user account name or parts of the user account that exceed two consecutive
characters
• Password must be 8 to 20 characters in length
ACCESS LEVEL — The "Restricted" option means that settings and commands can be accessed, but there is no access to
factory configuration. Access automatically reverts to the Restricted level according to the access level timeout setting
values. The access level is set to Restricted when control power is cycled.
The "Factory Service" level is not available and intended for factory use only.
There are two user security access levels, setting and command, for which you can set a password for each. Use of a
password for each level controls whether users can enter commands or change settings. Another option is to specify
setting and/or command access for individual user accounts.
• Setting — Allows the user to make any changes to any of the setting values:
– Changing any setting
– Test mode operation
• Command — Restricts the user from making any settings changes, but allows the user to perform the following
operations:
– Changing the state of virtual inputs
– Clearing the event records
– Clearing the oscillography records
– Changing the date and time
– Clearing energy records
– Clearing the data logger
– Clearing the user-programmable pushbutton states
When entering a settings or command password via EnerVista or any serial interface, the user must enter the
corresponding connection password. If the connection is to the back of the F35, the remote password must be used. If the
connection is to the RS232 port of the front panel, the local password must be used.
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
5
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command
sessions are initiated by the user through the EnerVista software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic operands:
• ACCESS LOC SETG OFF — Asserted when local setting access is disabled
• ACCESS LOC SETG ON — Asserted when local setting access is enabled
• ACCESS LOC CMND OFF — Asserted when local command access is disabled
• ACCESS LOC CMND ON — Asserted when local command access is enabled
• ACCESS REM SETG OFF — Asserted when remote setting access is disabled
• ACCESS REM SETG ON — Asserted when remote setting access is enabled
• ACCESS REM CMND OFF — Asserted when remote command access is disabled
• ACCESS REM CMND ON — Asserted when remote command access is enabled
A command or setting write operation is required to update the state of the remote and local security operands
listed.
When a setting password or command password is set or updated, user access with a graphical front panel is
removed. Simply log in again on the graphical front panel.
When the setting password is set or updated, the graphical front panel Access Level displays as Command. This is
because the graphical front panel is a Modbus client and it does not have automatic access to the password
change.
PASSWORD ACCESS EVENTS — This setting allows recording of password access events in the event recorder.
As outlined in the previous section, there are two user security access levels, setting and command. Use of a password for
each level controls whether users can enter commands or change settings.
Proper password codes are required to enable each access level. When a CHANGE COMMAND PASSWORD or CHANGE
SETTING PASSWORD setting is programmed to “Yes” via the front panel interface, the following message sequence is
invoked:
1. ENTER NEW PASSWORD: ____________.
2. VERIFY NEW PASSWORD: ____________.
3. NEW PASSWORD HAS BEEN STORED.
To gain write access to a “Restricted” setting, program the ACCESS LEVEL setting in the main security menu to “Setting” and
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access is allowed. Access automatically reverts to the “Restricted” level according to the
access level timeout setting values and when power is cycled.
If the setting and command passwords are identical, then this one password allows access to both commands and
settings.
5. Click the OK button. The password is checked to ensure that it meets requirements.
If you establish a local (serial) connection to the relay, you cannot view remote passcodes.
Access supervision
SETTINGS PRODUCT SETUP SECURITY ACCESS SUPERVISION
ACCESS ACCESS LEVEL See below
SUPERVISION TIMEOUTS
These settings allow the user to specify the length of inactivity required before returning to the Restricted access level.
Note that the access level is set to Restricted when control power is cycled.
COMMAND LEVEL ACCESS TIMEOUT — This setting specifies the length of inactivity (no local or remote access) required to
return to Restricted access from the Command password level.
SETTING LEVEL ACCESS TIMEOUT — This setting specifies the length of inactivity (no local or remote access) required to return
to Restricted access from the Command password level.
This feature provides a mechanism to prevent unauthorized or unintended upload of settings to a relay through the local
or remote interface.
The following settings are available through the local (front panel) interface only.
• LOCAL SETTING AUTH — This setting is used for local (front panel or RS232 interface) setting access supervision. Valid
values for the FlexLogic operands are either “On” (default) or any physical “Contact Input ~~ On” value.
If this setting is “On,“ then local setting access functions as normal; that is, a local setting password is required. If this
setting is any contact input on FlexLogic operand, then the operand must be asserted (on) prior to providing the local
setting password to gain setting access.
5 If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the UNAUTHORIZED ACCESS message displays on the front panel.
If this setting is "Off," firmware upgrades are blocked. If this setting is "On," firmware upgrades are allowed.
• REMOTE SETTING AUTH — This setting is used for remote (Ethernet or RS485 interface) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required. If this setting is “Off,” then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic operand, then the operand must be asserted (set as on) prior to
providing the remote setting password to gain setting access.
If this setting is "Off," firmware upgrades are blocked. If this setting is "On," firmware upgrades are allowed.
• ACCESS AUTH TIMEOUT — This setting represents the timeout delay for local setting access. This setting is applicable
when the LOCAL SETTING AUTH setting is programmed to any operand except “On.” The state of the FlexLogic operand
is monitored continuously for an off-to-on transition. When this occurs, local access is permitted and the timer
programmed with the ACCESS AUTH TIMEOUT setting value is started. When this timer expires, local setting access is
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the
timeout is restarted. The status of this timer updates every five seconds.
The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product
Setup > Security menu item to display the security settings window.
The Remote Settings Authorized setting is used for remote (Ethernet or RS485 interface) setting access supervision. If this
setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is required.
If this setting is “Off,” then remote setting access is blocked even if the correct remote setting password is provided. If this
setting is any other FlexLogic operand, then the operand must be asserted (on) prior to providing the remote setting
password to gain setting access.
The Access Authorized Timeout setting represents the timeout delay remote setting access. It applies when the Remote 5
Settings Authorized setting is programmed to any operand except “On” or “Off.” The state of the FlexLogic operand is
continuously monitored for an off-to-on transition. When this occurs, remote setting access is permitted, and the timer
programmed with the Access Authorized Timeout setting value is started. When this timer expires, remote setting access
is denied immediately. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout
is restarted. The status of this timer updates every five seconds.
2. Enable the Enable Security check box in the lower-left corner to enable the security management system.
3. Click the Ok button.
5 If you force password entry by using this feature, ensure that you know the Administrator password. If you do not
know the password and are locked out of the software, contact GE Grid Solutions for the default password of a UR
device. When using CyberSentry, the default password is "ChangeMe1#".
Security is now enabled for the EnerVista UR Setup software. Upon starting the software, users are now required to enter a
username and password.
3. Select the user access rights by enabling the check box of one or more fields.
3. Modify the user access rights by enabling or disabling one or more of the check boxes.
This feature requires a CyberSentry software option. See the Order Codes section in chapter 2 for details.
The EnerVista software provides the means to configure and authenticate the F35 access using either a server or the
device. Access to functions depends on user role.
The login screen of EnerVista has two options for access to the F35, these being Server and Device authentication.
When the "Server" Authentication Type is selected, the F35 uses the RADIUS server and not its local authentication
database to authenticate the user.
When the "Device" button is selected, the F35 uses its local authentication database and not the RADIUS server to
authenticate the user. In this case, it uses built-in roles (Administrator, Engineer, Supervisor, Operator, Observer, or
Administrator and Supervisor when Device Authentication is disabled), as login accounts and the associated passwords
are stored on the F35 device. In this case, access is not user-attributable. In cases where user-attributable access is
required, especially for auditable processes for compliance reasons, use server authentication (RADIUS) only.
No password or security information is displayed in plain text by the EnerVista software or the UR device, nor are they ever
transmitted without cryptographic protection.
Only (TCP/UDP) ports and services that are needed for device configuration and for customer enabled features are
open. All the other ports are closed. For example, Modbus is on by default, so its TCP port 502, is open. But if
Modbus is disabled, port 502 is closed. This function has been tested and no unused ports have been found open. 5
When CyberSentry is enabled, Modbus communications over Ethernet is encrypted, which is not always tolerated by
SCADA systems. The UR has a bypass access feature for such situations, which allows unencrypted Modbus over Ethernet.
The Bypass Access setting is available on the SETTINGS PRODUCT SETUP SECURITY SUPERVISORY screen. Note that
other protocols (DNP, 101, 103, 104, EGD) are not encrypted, and they are good communications options for SCADA
systems when CyberSentry is enabled.
When using the rear RS485 port and CyberSentry, registers can be read with a maximum buffer of 64 bytes. Settings may
not be written, so use another port or configure the SERIAL INACTIVITY TIMEOUT setting to a high value, such as eight
minutes, to give the relay enough time to finish the task.
For the Device > Settings > Product Setup > Supervisory option, the panel looks like the following.
Figure 5-4: Supervisory panel
5
LOGIN — This setting is applicable for Device authentication only. This setting allows a user to log in with a specific role, as
outlined here. For the Supervisor role, enable the “Supervisor Role” setting. Log out by right-clicking the device in EnerVista
and selecting the Disconnect option.
Whenever a new role is logged in, the user is prompted to enter a password. Passwords must obey the requirements
specified earlier in the chapter in the Password Requirements section.The UR device supports five roles. Roles have their
corresponding passwords, except the Observer role, which does not require a password. There are no time-outs for the
Administrator, Engineer, Operator, and Supervisor when logged in using the front panel; log out manually or use the
Command > Security commands in the software.
The roles are defined as follows:
• Administrator — Complete read/write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
• Engineer — Complete read/write access to all settings and commands except configuring Security settings and
firmware upgrades. This role does not allow concurrent access.
• Operator — The Operator has read/write access to all settings under the Commands menu/section. This role does not
•
exist offline.
Supervisor — This is only an approving role. This role’s authentication commits setting changes submitted by
5
Administrator or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not
approve changes after the fact. Only a Supervisor can set the Settings Lock and Firmware Lock in the Security
settings. This role also has the ability to forcefully log off any other role and clear the security event log. This role can
also be disabled, but only through a Supervisor authentication. When this role is disabled its permissions are assigned
to the Administrator role.
• Observer — This role has read-only access to all F35 settings. This role allows unlimited concurrent access but it has
no download access to any files on the device. Observer is the default role if no authentication has been done to the
device. This role displays as "None" on the front panel. When local authentication is used, no password is required for
this role. When RADIUS server authentication is used, a password is required.
The Factory service role is not available. It is for factory use only.
The Local Access Denied message on the front panel can mean that you need to log in to the UR in order to
complete the action.
The menu is shown on the front panel upon successful login of the Administrator role.
The LOGIN setting in this menu is similar to that described in SETTINGS > PRODUCT SETUP > SECURITY except for the factory
role.
In Device authentication mode, the Observer role does not have a password associated with it. In Server
authentication mode the Observer role requires a password.
If you are locked out of the software, contact GE Grid Solutions for the default password. When using CyberSentry,
the default password is "ChangeMe1#".
Once the passwords are set, the Administrator with Supervisor approval can change the role-associated password.
In CyberSentry, password encryption is not supported.
Session settings
SETTINGS PRODUCT SETUP SECURITY SESSION SETTINGS
SESSION SESSION LOCKOUT: Range: 0 to 99
SETTINGS 3
SESSION LOCKOUT — This setting specifies the number of failed authentications before the device blocks subsequent
authentication attempts for the lockout period. A value of zero means lockout is disabled.
SESSION LOCKOUT PERIOD — This setting specifies the period of time in minutes of a lockout period. A value of 0 means that
there is no lockout period.
Restore defaults
LOAD FACTORY DEFAULTS — This setting is used to reset all the settings, communication, and security passwords. An
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.
Supervisory
SETTINGS PRODUCT SETUP SECURITY SUPERVISORY
SUPERVISORY DEVICE Range: Yes, No
AUTHENTICATION: Yes
The Supervisory menu settings are available for Supervisor role only, or if the Supervisor role is disabled then for the
Administrator role only.
DEVICE AUTHENTICATION — This setting is enabled by default, meaning "Yes" is selected. When enabled, Device
authentication with roles is enabled. When this setting is disabled, the UR only authenticates to the AAA server (RADIUS).
However, the Administrator and Supervisor (when enabled) remain active even after device authentication is disabled and
their only permission is to re-enable Device authentication. To re-enable Device authentication, the Supervisor unlocks the
device for settings changes, then the Administrator re-enables device authentication.
BYPASS ACCESS — The bypass security feature provides an easier access, with no authentication and encryption for those
special situations when this is considered safe. Only the Supervisor, or the Administrator when the Supervisor role is
disabled, can enable this feature.
Mode Front panel or serial (RS232, RS485) Ethernet
Normal mode Authentication — Role Based Access Control (RBAC) Authentication — RBAC and passwords encrypted
and passwords in clear SSH tunneling
Bypass access mode No passwords for allowed RBAC levels No passwords for allowed RBAC levels
No SSH tunneling
Self-tests
SETTINGS PRODUCT SETUP SECURITY SUPERVISORY SELF TESTS
SELF TESTS FAILED See below
AUTHENTICATE
FAILED AUTHENTICATE — If this setting is Enabled then the number of failed authentications is compared with the Session
Lockout threshold. When the Session Lockout threshold is exceeded, this minor alarm indication comes up.
FIRMWARE LOCK — If this setting is Enabled, then any firmware upgrade operation attempt when the Lock Relay setting is
enabled brings up this self test alarm.
SETTINGS LOCK — If this setting is Enabled then an unauthorized write attempt to a setting for a given role activates this self
test.
SETTINGS PRODUCT SETUP SECURITY SUPERVISORY SELF TESTS FAILED AUTHENTICATE
FAILED FAILED AUTHENTICATE: Range: Enabled, Disabled
AUTHENTICATE Enabled
CyberSentry setup
When first using CyberSentry security, use the following procedure for setup.
1. Log in to the relay as Administrator by using the VALUE keys on the front panel to enter the default password
"ChangeMe1#". Note that the Lock Relay setting needs to be disabled in the Security > Supervisory menu. When this
setting is disabled, configuration and firmware upgrade are possible. By default, this setting is disabled.
2. Enable the Supervisor role if you have a need for it.
3. Make any required changes in configuration, such as setting a valid IP address for communication over Ethernet.
5 4. Log out of the Administrator account by choosing None.
5. Next, Device or Server authentication can be chosen on the login screen, but the choice is available only in EnerVista.
Use Device authentication to log in using the five pre-configured roles (Administrator, Supervisor, Engineer, Operator,
Observer). When using a serial connection, only Device authentication is supported. When Server authentication is
required, characteristics for communication with a RADIUS server must be configured. This is possible only in the
EnerVista software. The RADIUS server itself also must be configured. The appendix called RADIUS Server at the end of
this instruction manual gives an example of how to set up a simple RADIUS server. Once both the RADIUS server and
the parameters for connecting the UR to the server have been configured, you can choose Server authentication on
the login screen of EnerVista.
The use of CyberSentry for devices communicating through an Ethernet-to-RS485 gateway is not
supported. Because these gateways do not support the secure protocols necessary to communicate
with such devices, the connection cannot be established. Use the device as a non-CyberSentry
device.
Users logged in through the front panel are not timed out and cannot be forcefully logged out by a
supervisor. Roles logged in through the front panel that do no allow multiple instances (Administrator,
Supervisor, Engineer, Operator) must switch to None (equivalent to a logout) when they are done in
order to log out.
For all user roles except Observer, only one instance can be logged in at a time, for both login by front
panel and software.
To configure Server authentication:
1. In the EnerVista software, choose Device authentication and log in as Administrator.
2. Configure the following RADIUS server parameters: IP address, authentication port, shared secret, and vendor ID.
3. On the RADIUS server, configure the user accounts. Do not use the five pre-defined roles as user names (Administrator,
Supervisor, Engineer, Operator, Observer) in the RADIUS server. If you do, the UR relay automatically provides the
authentication from the device.
4. In the EnerVista software, choose Server authentication and log in using the user name and password configured on
the RADIUS server for Server authentication login.
When changing settings offline, ensure that only settings permitted by the role that performs the
settings download are changed because only those changes are applied.
Pushbuttons (both user-control buttons and user-programmable buttons) located on the front panel can be pressed by an
Administrator or Engineer role. This also applies to the RESET button, which resets targets, where targets are errors
displayed on the front panel or the Targets panel of the EnerVista software. The RESET button has special behavior in that it
allows these two roles to press it even when they are logged in through the RS232 port and not through the front panel.
To reset the security event log and self-test operands:
1. Log in as Supervisor (if the role is enabled) or Administrator (if the Supervisor role is disabled) and execute a clear
security command under Commands > Security > Clear Security.
Security events
The security events produced when the CyberSentry option is purchased are sent as sytem log (syslog) messages to a
syslog server, if one is configured. The format is as follows.
Security log Event Number Date & Username IP address Role Activity Value
Timestamp
Enumeration Description
1 Authentication Failed
2 User Lockout
3 FW Upgrade
4 FW Lock
5 Settings Lock
6 Settings Change. Because this can fill the entire event log, it is supported by the
already existing Settings_Change.log file. This event is not required.
7 Clear Oscillography command
8 Clear Data Logger command (not applicable to all UR products)
9 Clear Demand Records command (not applicable to all UR products)
10 Clear Energy command (not applicable to all UR products)
11 Clear Unauthorized Access command
12 Clear Teleprotection Counters command (not applicable to all UR products)
13 Clear All Relay Records command
14 Role Log in
Enumeration Description
15 Role Log off
In addition to supporting syslog, a F35 with CyberSentry also saves the security events in two local security files, these
being SECURITY_EVENTS.CSV and SETTING_CHANGES.LOG. Details on these files and how to retrieve them are available in
the EnerVista software under Maintenance > Retrieve File. Depending on the level of criticality/severity, a syslog server or
a reporting tool gathering information from a syslog server can produce reports, charts, and so on. All severity levels are
per RFC 5424.
Table 5-6: CyberSentry system events recorded
Event Severity Description
FAILED_AUTH, ORIGIN, TIMESTAMP Notice (5) A failed authentication with origin information (username and IP:MAC
address), a time stamp in UTC time when it occurred
AUTH_LOCKOUT, ORIGIN, TIMESTAMP Warning (4) An authentication lockout has occurred because of too many failed
authentication attempts
FIRMWARE_UPGD, ORIGIN, Information (6) Indicates that a change of firmware has occurred
TIMESTAMP
FIRMWARE_LOCK, ORIGIN, Warning (4) An attempt was made to change firmware while the firmware lock was
TIMESTAMP enabled
SETTING_CHG, ORIGIN, TIMESTAMP Notice (5) Indicates setting change(s)
SETTING_LOCK, ORIGIN, TIMESTAMP Warning (4) An attempt was made to change settings while the settings lock was enabled
LOGIN, ORIGIN, TIMESTAMP Information (6) Indicates when a certain role logged in
LOGOUT, ORIGIN, TIMESTAMP Information (6) Indicates when a certain role logged out or timed out
CLEAR_OSCILLOGRAPHY Notice (5) Clear oscillography command was issued
5 CLEAR_DATA_LOGGER
CLEAR_DEMAND_RECS
Notice (5)
Notice (5)
Clear data logger command was issued
Clear demand records command was issued
CLEAR_ENERGY Notice (5) Clear energy command was issued
RESET_UNAUTH_ACCESS Notice (5) Reset Unauthorized access command was issued
CLEAR_TELEPROTECTION_CNT Notice (5) Clear teleprotection counters command was issued
CLEAR_ALL_RECS Notice (5) Clear all records command was issued
WRITE_SETTING_FILE Notice (5) Write settings file to the relay
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
LANGUAGE — This setting selects the language used to display settings, actual values, and targets. This setting displays
when a language other than English was purchased, and the range depends on the order code of the relay.
For Japanese, the settings display in Japanese on the graphical front panel, while the keys printed on the panel are in
English.
For Japanese and Chinese, up to 10 characters can be input in a field on the graphical front panel, not 20.
With the graphical front panel, the language can be changed regardless of the language purchased. That is, all languages
can be used. If you select a language with which you are unfamiliar and want to switch back to English for example, the
menu order remains the same. That is, Settings is always second, Product Setup is always first, Display Properties is always
second, and Language is always first.
If the language is changed after entering user-configured names, such as relay names, the strings are not translated. For
example, a relay name is entered in English, the language is changed to Japanese, and the relay name remains in English.
Set the language before changing settings.
The language can be selected also for the front panel in EnerVista under Maintenance > Change Front Panel.
The language of the EnerVista software can be changed under View > Language. Languages supported by the operating
system display; that is for Polish or Japanese to display, the software needs to be installed on a Polish or Japanese
operating system.
FLASH MESSAGE TIME — Flash messages are status, warning, error, and information messages displayed in response to
certain key presses during settings programming. These messages override any normal messages. Use this setting to
change the duration of flash messages on the display.
DEFAULT MESSAGE TIMEOUT — If the keypad is inactive for a period of time, the relay automatically reverts to a default
message. The inactivity time is modified using this setting to ensure that messages remain on the screen long enough
during programming or reading of actual values. This setting is not supported on the graphical front panel.
DEFAULT MESSAGE INTENSITY — To extend phosphor life in the vacuum fluorescent display, the brightness can be
5
attenuated during default message display. During keypad interrogation, the display always operates at full brightness.
This setting is not supported on the graphical front panel.
SCREEN SAVER FEATURE and SCREEN SAVER WAIT TIME — These settings are only visible if the F35 has a liquid crystal display
(LCD) and control its backlighting. When the SCREEN SAVER FEATURE is “Enabled,” the LCD backlighting turns off after the
DEFAULT MESSAGE TIMEOUT followed by the SCREEN SAVER WAIT TIME, provided that no keys have been pressed and no
target messages are active. When a keypress occurs or a target becomes active, the LCD backlighting turns on. These
settings are not supported on the graphical front panel.
CURRENT CUT-OFF LEVEL — This setting modifies the current cut-off threshold. Very low currents (1 to 2% of the rated value)
are very susceptible to noise. Some customers prefer very low currents to display as zero, while others prefer the current to
display even when the value reflects noise rather than the actual signal. The F35 applies a cut-off value to the magnitudes
and angles of the measured currents. If the magnitude is below the cut-off level, it is substituted with zero. This applies to
phase and ground current phasors as well as true RMS values and symmetrical components. The cut-off operation applies
to quantities used for metering, protection, and control, as well as those used by communications protocols. Note that the
cut-off level for the sensitive ground input is 10 times lower that the CURRENT CUT-OFF LEVEL setting value. Raw current
samples available via oscillography are not subject to cut-off.
VOLTAGE CUT-OFF LEVEL — This setting modifies the voltage cut-off threshold. Very low secondary voltage measurements
(at the fractional volt level) can be affected by noise. Some customers prefer these low voltages to be displayed as zero,
while others prefer the voltage to be displayed even when the value reflects noise rather than the actual signal. The F35
applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below the cut-off level,
it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical components. The cut-off
operation applies to quantities used for metering, protection, and control, as well as those used by communications
protocols. Raw samples of the voltages available via oscillography are not subject to cut-off.
The CURRENT CUT-OFF LEVEL and the VOLTAGE CUT-OFF LEVEL are used to determine the metered power cut-off levels. The
power cut-off level is calculated using the following equations. For Delta connections:
Eq. 5-3
Eq. 5-4
Eq. 5-5
Lower the VOLTAGE CUT-OFF LEVEL and CURRENT CUT-OFF LEVEL with care as the relay accepts lower signals as valid
measurements. Unless dictated otherwise by a specific application, the default settings of “0.02 pu” for CURRENT
CUT-OFF LEVEL and “1.0 V” for VOLTAGE CUT-OFF LEVEL are recommended.
The graphical front panel is a hardware option. See the Order Codes section in chapter 2 for details.
Use the EnerVista software to configure the graphical front panel. The settings are not accessible from the graphical front
panel.
The following screens are available:
• Home page
• Rolling mode
• Metering editor
• Single-line diagram editor
• Annunciator editor
• Configurable navigation
The settings menu itself and the event record pages are not configurable.
Multiple screens can be opened in the EnerVista software, but the first remains active and the others can be read-only. For
example, the Annunciator Editor and Single Line Diagram Editor can be open and active, then subsequently opened Rolling
Mode and Home Page screens are read-only. Close the windows, then re-open the one required.
859850A1.cdr
– The first annunciator page that contains an annunciator window that is in ringback. Ringback is a "return alert."
Visual and audible signals are given when conditions return to normal, then the sequence returns to normal by
pushing the RESET button.
– The first annunciator page that contains an annunciator window that is in abnormal state
– Annunciator page 1
Whenever an annunciator window changes state this list is re-evaluated, which can result in the home page displaying
a different annunciator page.
The Tabular option displays a configured actual values/metering page.
The Targets option displays error messages, such as wrong transceiver, similar to event record entries.
Date Format
Range: yyyy-mm-dd, dd-mmm-yy, yyyy/mm/dd, m/d/yyyy, m/d/yy, mm/dd/yy, mm/dd/yyyy, yy/mm/dd
Default: yyyy-mm-dd
This setting specifies the format for dates on the graphical front panel. It applies to the page header, the events records,
the annunciator, and everywhere else a date displays on the panel. If the relay is synchronized to an external time
source via PTP, IRIG-B, SNTP, and so on, the date/time is shown in white, and otherwise in yellow.
yyyy — four-digit year, for example 2017
yy — two-digit year, for example 17 for 2017
mmm — abbreviation of month name, for example Jan for January
mm — two-digit month, for example 01 for January
m — one or two-digit month, for example 1 for January and 10 for October
dd — two-digit day, for example 08
5 Set the Current Page, Page Name, Layout, configure the top inputs, then the cells. The 16 inputs at the top of the page are
used as inputs for the Status Index fields. Click the Preview button to view the page.
For a phasor diagram, configure the source under Settings > System Setup > Signal Sources. The diagram is then
viewable by pushing the Metering Tab pushbutton on the graphical front panel. The Metering Editor is not used for these
phasor diagrams.
The figures show setup and table preview.
The Cells configured are not retained when using the Convert Device Settings function, for example when converting a
file in the Offline Window from version 7.6 to 7.7.
5
Figure 5-9: Preview for graphical front panel
STATUS INPUTS 1 to 16
Range: OFF, ON, any FlexLogic operand
Default: OFF
This setting identifies the potential inputs for use in the STATUS INDEX fields, for display of the status of FlexLogic
operands.
A maximum of eight Status Inputs can be used per metering page, and 16 in all metering pages.
Select the metering input from the drop-down list. The options reflect the FlexLogic operands applicable to the F35. They
are inputs for all five metering pages, not just the current page.
CURRENT PAGE
Range: Page 1...Page 5
Default: Page 1
Select the metering page to configure from the drop-down list. There are five pages possible, viewable with the Tab
pushbuttons on the graphical front panel.
PAGE NAME
Range: Page 1...Page 5
Default: Page 1
Up to 20 characters can be input here as the name of each metering page. The name displays for the Tab pushbutton on
the graphical front panel.
LAYOUT
Range: 3x4, 4x6, 6x8, 6x4, 8x6, 12x8, 12x4, 16x6, 18x8
Default: 6x4
This setting determines how many rows and columns display on the graphical front panel with the metering information.
The configurable rows in the settings window change dynamically based on this setting.
CONTENT
Range: Actual, Status, Text
Default: Text
Select the type of content to display.
– Actual — an actual value/data. The Configure button becomes active for the actual value to be selected.
– Status — one of the operands selected from the STATUS INPUTS fields. Select it in the STATUS INDEX field.
BACK COLOR
Range: 24-bit color selector
Default: Grey
Set the background color to display in the specified cell.
ACTUAL (Configure)
Range: Configure
Default: Configure
The Configure button becomes active when the CONTENT field is set to "Actual." The window specifies the metering
data to display.
Figure 5-10: Metering value properties window
5
Parameter
Range: any FlexAnalog parameter
Default:
This setting selects a FlexAnalog parameter that specifies the metered value to display in the metering window. A
FlexAnalog is an analog parameter.
Units
Range: up to eight alphanumeric characters
Default:
This setting specifies the units of measurement for the metered value and is populated based on the Parameter
selected. The field can be left blank when units of measure do not apply.
Scale Factor
Range: G Giga, M Mega, k Kilo, None
Default: None
This setting allows the user to specify the scaling factor for the metering units value. Options depend on the Parameter.
Multiplier
Range: -1000000 to 1000000
Default: 1.0
This setting allows the user to specify a multiplier for the metering parameter value. The multiplier must be in
compliance with the 32-bit floating-point format per IEEE 754, otherwise, the input value is represented as per the IEEE
standard. For example, 1234.56789 is represented as 1234.567871094, and 9876.54321 as 9876.54296875.
Number of Integers
Range: 1 to 12 in steps of 1
Default: 1
This setting specifies the number of integers in the displayed metered value. It can be used to provide for leading
character spacing of the display value.
For example, setting the number to 2 displays 00.000[V] and setting it to 3 displays 000.000[V].
Number of Decimals
Range: 0 to 10 in steps of 1
Default: 3
This setting specifies the number of decimal places in the displayed metered value. For example, setting the number to 1
displays 0.0 and setting it to 2 displays 0.00.
Reset
Range: ON, OFF, any FlexLogic operand
Default: OFF
This setting selects a FlexLogic operand that when activated acknowledges/resets all annunciator windows in the
graphical front panel. For example, to have the first user pushbutton resets all alarms, set this to PUSHBUTTON 1 ON and
turn on the pushbutton under Settings > Product Setup > User-Programmable Pushbuttons. This setting is the same
as the one defined in Settings > Inputs/Outputs > Resetting > Reset Annunciator. See the Resetting section later in this
chapter.
LAYOUT
Range: 3x4, 4x6, 6x8
Default: 3x4
Selects the number of rows and columns to display on the annunciator pages. For example, 3x4 means 12 windows
display per page over eight pages. Up to 96 entries are possible.
To view the layout, click the Preview button.
PAGE NAMES
Range: up to 20 alphanumeric characters
Default: Page 1...Page 8
Up to 20 characters can be input as the name of each annunciator page. The number of pages depends on the Layout.
The name displays for the Tab pushbutton on the graphical front panel.
PARAMETER
Range: Indicator 1...Indicator 96
Default: Indicator 1...Indicator 96
Read-only field. Up to 96 windows are possible.
CONTENT
Range: Actual, Alarm, Mixed
Default: Alarm
Select if the cell is to be an alarm, an actual value, or a combination thereof, for example consists of a single metered
value (set to “Actual”), contains a single alarm indication (set to “Alarm”), or contains both a metered value and an alarm
indication (set to “Mixed”).
ALARM INPUT
Range: OFF, ON, any FlexLogic operand
Default: OFF
Select a trigger for the alarm, or the input signal connected to the alarm. For example, when set to "FIRST ETHERNET
FAIL" and the Ethernet cable connected to port 1 is removed, the alarm is triggered. (Note that when the Ethernet cable
is inserted into an SFP connector and the SFP connector is removed, the alarm is not triggered.) The field is read-only for
an actual value.
The selectable options are the FlexLogic operands specific to the product.
ALARM TYPE
Range: Acknowledgeable, Self Reset, Latched
Default: Acknowledgeable
Set the alarm type. The field is read-only for an actual value.
5 Acknowledgeable — Follow the state transitions, as outlined in the Annunciator section of the Interfaces chapter. The
alarm blinks until acknowledged, then remains on until the condition clears.
Self Reset — Track the state of the input operand. The alarm turns on when the trigger activates and off when the trigger
clears.
Latched — Alarm is on until acknowledged/reset individually or until the RESET button is pressed.
To acknowledge/reset/unlatch an alarm, use the arrow buttons on the graphical front panel and press the ENTER
button.
TEXT (LINE 1 to 3)
Range: up to 10 alphanumeric characters
Default:
The text that displays in the annunciator cell. Three lines can be displayed. Note that a specified metering value replaces
the text for the selected line. This means that a line can display text or be set to show an actual metered value. If the text
does not display it is because an actual metered value is over-riding it; change the line for the text or for the actual value.
TEXT COLOR
Range: 24-bit color selector
Default: White
The color to display for the three text or actual value lines specified.
BACK COLOR
Range: 24-bit color selector
Default: Red
The background color to display for any triggered cell, for example when an alarm is triggered.
ACTUAL (Configure)
Range: Configure
Default: Configure
The Configure button becomes active when the CONTENT field is set to "Actual" or "Mixed." The window specifies the
metering data to display.
Parameter
Range: any FlexAnalog parameter
Default:
This setting selects a FlexAnalog parameter that specifies the metered value to display in the annunciator alarm.
Units
Range: up to eight alphanumeric characters
Default:
This setting specifies the units of measurement for the metered value and is populated based on the Parameter
selected. The field can be left blank when units of measure do not apply.
Scale Factor
Range: G Giga, M Mega, k Kilo, None
Default: None
This setting allows the user to specify the scaling factor for the metering units value. Options depend on the Parameter.
Multiplier
Range: -1000000 to 1000000
Default: 1.0
This setting allows the user to specify a multiplier for the metering parameter value. The multiplier must be in
compliance with the 32-bit floating-point format per IEEE 754, otherwise, the input value is represented as per the IEEE
standard. For example, 1234.56789 is represented as 1234.567871094, and 9876.54321 as 9876.54296875.
Number of Integers
Range: 1 to 12 in steps of 1
Default: 1
This setting specifies the number of integers in the displayed analog value. It can be used to provide for leading 5
character spacing of the display value.
For example, setting the number to 2 displays 00.000[V] and setting it to 3 displays 000.000[V].
Number of Decimals
Range: 0 to 10 in steps of 1
Default: 3
This setting specifies the number of decimal places in the displayed analog value. For example, setting the number to 1
displays 0.0 and setting it to 2 displays 0.00.
Display in Line
Range: 1, 2, 3
Default: 1
This setting specifies the line in the annunciator alarm window to display the metered value. The actual value replaces
the text for the selected line. For example, 2 means the value displays in line 2 of the text; any text configured to display
in that line does not display.
In the example shown, failure of any of the three Ethernet ports triggers the Product Information page to display. With
unauthorized access (such as wrong password), IRIG-B clock failure, or breaker trouble, the Event Records display. When a
breaker opens, a single-line diagram displays. For the Ethernet and IRIG-B failure operation to work, these functions also
have been enabled under Settings > Product Setup > User-Programmable Self Tests.
Figure 5-12: Configurable navigation editor
To use the feature, select a CONDITION, select an ACTIVATE PAGE, then save.
CONDITION
5.3.5 Communications
5.3.5.1 Menu
SETTINGS PRODUCT SETUP COMMUNICATIONS
COMMUNICATIONS SERIAL PORTS See below
RS485 COM2 BAUD Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
RATE: 19200 28800, 33600, 38400, 57600, 115200 bit/s
The front RS232 port applies to enhanced and basic front panels.
RS232 BAUD RATE, RS485 COM2 BAUD RATE, and PARITY — The F35 is equipped with two independent serial communication
ports. The front panel RS232 port (USB port with graphical front panel) is intended for local use. The rear COM2 port is
RS485 and has settings for baud rate and parity. It is important that these parameters agree with the settings used on the
computer or other equipment that is connected to these ports. Any of these ports can be connected to a computer
running the EnerVista software, for example to download and upload setting files, view measured parameters, and
upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and connected to a DCS, PLC, or computer
using the RS485 ports. If IEC 60870-103 is chosen as the protocol, valid baud rates are 9600 and 19200 bit/s, and valid
parity is Even.
RS485 COM2 RESPONSE MIN TIME — This setting specifies the minimum time before the rear RS485 port transmits after
receiving data from a host. This feature allows operation with hosts that hold the RS485 transmitter active for some time
after each transmission.
Example 1
IP1/Mask1: 10.1.1.2/255.255.255.0 (where LAN 1 is 10.1.1.x/255.255.255.0)
IP2/Mask2: 10.2.1.2/255.255.255.0 (where LAN2 is 10.2.1.x/255.255.255.0)
IP3/Mask3: 10.3.1.2/255.255.255.0 (where LAN3 is 10.3.1.x/255.255.255.0)
Example 2
IP1/Mask1: 10.1.1.2/255.0.0.0 (where LAN1 is 10.x.x.x/255.0.0.0)
IP2/Mask2: 11.1.1.2/255.0.0.0 (where LAN2 is 11.x.x.x/255.0.0.0)
IP3/Mask3: 12.1.1.2/255.0.0.0 (where LAN3 is 12.x.x.x/255.0.0.0)
Example 3 — Incorrect
IP1/Mask1: 10.1.1.2/255.0.0.0
IP2/Mask2: 10.2.1.2/255.0.0.0
IP3/Mask3: 10.3.1.2/255.0.0.0
This example is incorrect because the mask of 255.0.0.0 used for the three IP addresses makes them belong to the same
network of 10.x.x.x.
SCADA
EnerVista Software
LAN1
ML3000
P1
IP1/ P2 P3
MAC1
UR
859708A2.vsd
Public Network
SCADA
EnerVista Software
LAN1 LAN2
LAN2
ML3000
ML3000 ML3000
P1 P2 P3
IP1/ IP2/ IP2/
MAC1 MAC2 MAC2
Redundancy mode
UR
859709A4.vsd
Public Network
SCADA
EnerVista Software
LAN1 LAN2
LAN3
ML3000
ML3000 ML3000
P1 P2 P3
IP1/ IP2/ IP3/
MAC1 MAC2 MAC3
UR
859710A2.vsd
5.3.5.4 Network
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different
network or subnet using the IP addresses and mask. Configure the network IP and subnet settings before configuring the
routing settings.
Follow the IP and subnet mask rules outlined in the Set IP Address in UR section of the Installation chapter.
To obtain a list of all port numbers used, for example for audit purposes, contact GE technical support with substantiating
information, such as the serial number and order code of your device.
SETTINGS PRODUCT SETUP COMMUNICATIONS NETWORK 1(3)
NETWORK PORT 1 PRT1 IP ADDRESS: Range: standard IPV4 address format
127.0.0.1
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, HTTP, and PRP protocols. PRP is
explained in its own section later.
Use the front panel to change these settings. When online, the EnerVista software can be used to enable/disable each port
only. In the Offline Window area, all settings can be changed except port 2 redundancy (depending on firmware version).
When using GOOSE, in failover or PRP mode, port 3 configuration in the CID file is ignored. The Port 3 ConnectedAP
elements has no meaning, as ports 2 and 3 use the port 2 MAC address, IP address, and mask.
PRT1 (2 or 3) IP ADDRESS — This setting sets the port’s IPv4 address in standard IPV4 format. This setting is valid on port 3 if
port 2 REDUNDANCY is set to None.
PRT1 (2 or 3) SUBNET MASK — This setting sets the port’s IPv4 subnet mask in standard IPV4 format. This setting is valid on
port 3 if port 2 REDUNDANCY is set to None.
PRT1 (2 or 3) FUNCTION — This setting enable/disables network communication on the respective port. When the port
function is Disabled, the network traffic on this port is disabled. The PRT2 redundancy setting has no effect on this
functionality. The change takes effect upon relay restart.
If you disable a port here that is used to communicate between the relay and the software, this can take down all
communication between the two. For example, an Ethernet connection set to the IP address of the relay can be disabled
and cannot be reached, even when pinging. The port needs to be re-enabled, IP and any gateway addresses need to be
checked, and the relay needs to be set to Programmed.
PRT2 REDUNDANCY — Determines if ports 2 and 3 operate in redundant or independent mode. If a license for PRP was
purchased, the options are None, Failover, and PRP. If a license for PRP was not purchased, the options are None and
Failover. In non-redundant mode (REDUNDANCY set to None), ports 2 and 3 operate independently with their own MAC, IP,
and mask addresses. If REDUNDANCY is set to Failover, the operation of ports 2 and 3 is as follows:
• Ports 2 and 3 use the port 2 MAC address, IP address, and mask
• The configuration fields for IP address and mask on port 3 are hidden
• Port 3 is in standby mode and does not actively communicate on the Ethernet network but monitors its link to the
Multilink switch. If port 2 detects a problem with the link, communications is switched to Port 3. Port 3 is, in effect,
acting as a redundant or backup link to the network for port 2. Once port 2 detects that the link between itself and the
switch is good and that communication is healthy for five minutes, then switching back to port 2 is performed. The
delay in switching back ensures that rebooted switching devices connected to the F35, which signal their ports as
active prior to being completely functional, have time to completely initialize themselves and become active. Once
port 2 is active again, port 3 returns to standby mode.
If REDUNDANCY is set to PRP, the operation of ports 2 and 3 is as follows:
• Ports 2 and 3 use the port 2 MAC address, IP address, and mask
• The configuration fields for IP address and mask on port 3 are overwritten with those from port 2. This is visible on the
front panel but not displayed in the EnerVista software.
• Port 2 MCST ADDRESS field is visible
• The port 2 PTP function still uses only port 2 and the port 3 PTP function still uses only port 3. The relay still
5 synchronizes to whichever port has the best master. When ports 2 and 3 see the same master, as is typically the case
for PRP networks, the port with the better connectivity is used.
Behavior for GOOSE messages is as follows:
• If REDUNDANCY is set to Failover or PRP, In order to transmit a GOOSE message on port 2, the CID file must be
configured to have the corresponding GSE element in both ConnectedAPs S2 and S3. In the EnerVista software, the
TxGOOSE PORT ASSIGNMENT needs to be "Ports-1,2,3" to transmit GOOSE on both ports 1 and 2, or "Ports-2,3" to have
GOOSE only on port 2, with failover/ PRP.
• If REDUNDANCY is set to PRP, the port 2 configured GOOSE message is simultaneously transmitted on ports 2 and 3
• If REDUNDANCY is set to failover and the port 2 link fails, then only the port 2 configured GOOSE message is transmitted
on port 3
The two ports must be connected to completely independent LANs with no single point of failure, such as common
power supplies that feed switches on both LANs.
For any changes to this setting to take effect, restart the unit.
PRT2 PRP MCST ADDR — This setting allows the user to change the multicast address used by the PRP supervision frames.
This setting is available if REDUNDANCY is set to PRP. All devices in the same PRP network need to have the same multicast
address. Choose an address that does not conflict with another multicast protocol.
When the local receiver again detects a signal, the local transmitter automatically returns to normal operation.
If a Far-End Fault pattern is received by a fiber interface that supports the Far-End Fault feature and it is enabled, it reacts
by dropping the link as if there were no signal at all.
If the receiving interface does not support the Far-End Fault feature or has it disabled, an incoming Far-End Fault pattern is
ignored.
It is strongly recommended to have switches used for substation automation that support the Far-End Fault feature,
especially when UR 7 redundancy Failover is selected for redundancy.
The F35 is provided with optional PRP capability. This feature is specified as a software option at the time of
ordering. See the Order Codes section in chapter 2 for details.
The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation
networks. It applies to networks based on Ethernet technology (ISO/IEC 8802-3) and is based on the second edition (July
2012) of IEC 62439-3, clause 4.
PRP is designed to provide seamless recovery in case of a single failure in the network, by using a combination of LAN
duplication and frame duplication. Identical frames are sent on two completely independent networks that connect source
and destination. Under normal circumstances both frames reach the destination and one of them is sent up the OSI stack
to the destination application, while the second one is discarded. If an error occurs in one of the networks and traffic is
prevented from flowing on that path, connectivity is provided through the other network to ensure continuous
communication. Take care when designing the two LANs, so that no single point of failure (such as a common power
supply) is encountered, as such scenarios can bring down both LANs simultaneously.
Figure 5-16: Example of parallel redundant network 5
PRP uses specialized nodes called doubly attached nodes (DANPs) for handling the duplicated frames. DANP devices have
an additional module, called a Link Redundancy Entity (LRE). LRE is responsible for duplicating frames and adding the
specific PRP trailer when sending the frames out on the LAN, as well as making decisions on received frames as to which
one is sent up the OSI stack to the application layer and which one is discarded. LRE is responsible for making PRP
transparent to the higher layers of the stack.
In addition, there is a second type of specialized device used in PRP networks, called RedBox, with the role of connecting
Single Attached Nodes (SANs) to a redundant network.
UR relays implement the DANP functionality. The RedBox functionality is not implemented.
The original standard IEC 62439-3 (2010) was amended to align PRP with the High-availability Seamless Redundancy (HSR)
protocol. To achieve this, the original PRP was modified at the cost of losing compatibility with the PRP 2010 version. The
revised standard IEC 62439-3 (2012) is commonly referred to as PRP-1, while the original standard is PRP-0. The UR relays
support PRP-1.
The relay implements PRP on two of its Ethernet ports, specifically Ports 2 and 3 of the CPU module. Use the previous
section (network port configuration) to configure PRP.
PRP is purchased as a separate option. If purchased (valid order code), PRP can be enabled in configuration through a
setting available on the network configuration menu, REDUNDANCY, which already has the capability of enabling failover
redundancy. The options on this setting must be changed to accommodate two types of redundancy: failover and PRP.
When REDUNDANCY is set to either failover or PRP, the ports dedicated for PRP (Ports 2 and 3) operate in redundant mode.
In this mode, Port 3 uses the MAC, IP address, and mask of Port 2.
IPv4 NETWORK
ROUTE 1
IPv4 NETWORK
ROUTE 6
5 IPv4 NETWORK
ROUTE 1 RT1 DESTINATION:
127.0.0.1
Range: standard IPV4 address format
Configure the network IP and subnet settings before configuring the routing settings.
2. Delete the default route by replacing the default gateway with the default value of 127.0.0.1.
Router1
Public network
.1
Router2
10.1.2.0/24 10.1.3.0/24
10.1.1.0/24
ML3000 ML3000 .1
EnerVista Software
P1 P2 P3
IP1/ IP2/ IP3/
.2 .2 MAC2 MAC3
MAC1
UR
859714A1.vsd
In the figure, the UR connects through the following two Ethernet ports:
• Port 1 (IP address 10.1.1.2) connects the UR to LAN 10.1.1.0/24 and to the Internet through Router1. Router1 has an
interface on 10.1.1.0/24 and the IP address of this interface is 10.1.1.1.
• Port 2 (IP address 10.1.2.2) connects the UR to LAN 10.1.2.0/24 and to the EnerVista software through Router2. Router2
has an interface on 10.1.2.0/24 and the IP address of this interface is 10.1.2.1.
The configuration before release 7.10 was as follows:
• PRT1 IP ADDRESS = 10.1.1.2
PRT1 SUBNET IP MASK = 255.255.255.0
PRT1 GWY IP ADDRESS = 10.1.1.1
PRT2 IP ADDRESS = 10.1.2.2
PRT2 SUBNET IP MASK = 255.255.255.0
The behavior before release 7.10 was as follows. When sending packets to EnerVista, the UR noticed that the destination
was not on a connected network and it tried to find a route to destination. Since the default route was the only route it
knew, it used it. Yet EnerVista was on a private network, which was not reachable through Router1. Hence a destination
unreachable message was received from the router.
The configuration starting with release 7.10 is as follows:
• PRT1 IP ADDRESS = 10.1.1.2
PRT1 SUBNET IP MASK = 255.255.255.0
PRT2 IP ADDRESS = 10.1.2.2
PRT2 SUBNET IP MASK = 255.255.255.0
IPV4 DEFAULT ROUTE: GATEWAY ADDRESS = 10.1.1.1
STATIC NETWORK ROUTE 1: RT1 DESTINATION = 10.1.3.0/24; RT1 NET MASK = 255.255.255.0; and RT1 GATEWAY =
10.1.2.1
The behavior since release 7.10 is as follows. There is one added static network route to the destination 10.1.3.0/24, where
a computer running EnerVista is located. This static route uses a different gateway (10.1.2.1) than the default route. This
gateway is the address of Router2, which has knowledge about 10.1.3.0 and is able to route packets coming from the UR
The serial communication ports utilize the Modbus protocol, unless the port is configured for DNP or IEC 60870-5-103
operation. This allows the EnerVista UR Setup software to be used on the port. UR devices operate as Modbus slave
devices only.
For more information on the protocol, including the memory map table, see the UR Family Communications Guide.
MODBUS SLAVE ADDRESS — When using the Modbus protocol on the RS232 port, the F35 responds regardless of the
MODBUS SLAVE ADDRESS programmed. For the RS485 port, each device on the serial bus must have a unique slave address
from 1 to 254. Address 0 and addresses from 248 and up are reserved by the Modbus protocol specification, and so their
use here is not recommended. Address 0 is the broadcast address to which all Modbus slave devices listen. Addresses do
not have to be sequential, but no two devices can have the same address or conflicts resulting in errors occur. Generally,
starting at 1, set each device added to the link to use the next higher address. When using Modbus TCP/IP, the client must
use the programmed MODBUS SLAVE ADDRESS value in the Unit Identifier field.
MODBUS TCP PORT NUMBER — Modbus over TCP/IP can also be used on any of the Ethernet ports. The listening TCP port 502
is reserved for Modbus communications, and only in exceptional cases when MODBUS TCP PORT NUMBER is set to any other
port. The MODBUS TCP PORT NUMBER setting sets the TCP port used by Modbus on Ethernet. A MODBUS TCP PORT NUMBER of
0 disables Modbus over TCP/IP, meaning closes the Modbus TCP port. When the port number is changed to 0, the change
takes effect when the F35 is restarted. When it is set to 0, use the front panel or serial port to communicate with the relay.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
5
those protocols.
The PROTOCOL menu allows selection of one of the following protocols: DNP 3.0, IEC60870-104, or IEC60870-103.
SCADA PROTOCOL — This setting selects the SCADA protocol on which the unit communicates, among DNP3.0, IEC 60870-
104, and IEC 60870-103, with DNP being the default. Options depend on order code. For any change to take effect, restart
the unit.
MMS CONNECTION TIMEOUT — This setting specifies a time delay for the detection of network TCP connection lost. If there is
no data traffic on the TCP connection for greater than the time specified by this setting, the connection is terminated. This
frees up the connection to be re-used by a client. A setting of 10 seconds disables this timer. The TCP connection then is
managed by a standard TCP KeepAlive message sequence. These messages are transmitted every 20 seconds when there
is no MMS communication between the relay and the client. If there are no responses to the TCP KeepAlive messages, the
connection is closed. For any change to this setting to take effect, restart the unit. The change takes effect for a new
connection. For any existing open connection when the change is made, close and re-open the connection. Cycling power
to the relay also applies the new setting.
The table shows which of DNP 3.0, IEC 60870-5-104, IEC 60870-5-103, and IEC 61850 protocols are operational on the
RS232, RS485, and Ethernet ports. It shows all possible combinations of the PROTOCOL and DNP CHANNEL 1(2) PORT settings.
5 Channel 1: RS232
Channel 2: RS485
DNP DNP Modbus, IEC 61850
IEC61850 EDITION — Switches between Editions 1 and 2 of the IEC 61850 protocol. Settings default with the change, except
GGIO1, GGIO2, GGIO4, and those for the graphical front panel. A message displays that a reboot is required, which can be
done using Maintenance > Reboot Relay Command.
DNP CURRENT SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000, 1000000, 10000000, 100000000
DNP VOLTAGE SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000, 1000000, 10000000, 100000000
DNP POWER SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000, 1000000, 10000000, 100000000
DNP ENERGY SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000, 1000000, 10000000, 100000000
DNP PF SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000, 1000000, 10000000, 100000000
DNP OTHER SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
FACTOR: 1 100000, 1000000, 10000000, 100000000
DNP PF DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1 5
DNP OTHER DEFAULT Range: 0 to 100000000 in steps of 1
DEADBAND: 30000
The Distributed Network Protocol (DNP) allows for the optimization of control and data acquisition between the equipment
in the substation and the central control center. The protocol is scalable; that is, it is designed to be compatible with the
latest high speed LAN technology yet still be implemented over slower speed serial links.
The DNP improves upon many master-slave protocols by improving overall communication performance requirements
and provides time-stamping with millisecond accuracy.
The F35 supports DNP version 3.0.
DNP is enabled when the SETTINGS PRODUCT SETUP COMMUNICATIONS PROTOCOL setting is set to DNP 3.0. The F35
can be used as a DNP slave device connected to multiple DNP masters (usually an RTU or a SCADA master station). Since
the F35 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively
communicate with the F35 at one time.
DNP is not available using the USB port on the graphical front panel.
See the UR Family Communications Guide for more information on DNP.
The DNP Channels sub-menu is shown.
SETTINGS PRODUCT SETUP COMMUNICATIONS DNP PROTOCOL DNP CHANNELS
DNP CHANNELS DNP CHANNEL 1 PORT: Range: NONE, COM1 - RS485, COM2 - RS485, FRONT
NONE PANEL - RS232, NETWORK - TCP, NETWORK - UDP
DNP CHANNEL 2 PORT: Range: NONE, COM1 - RS485, COM2 - RS485, FRONT
5 NONE PANEL - RS232, NETWORK - TCP
The DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings select the communications port assigned to the DNP protocol
for each channel. Once DNP is assigned to a serial port, DNP is the only protocol running on that port; Modbus or IEC
60870-5-103 are disabled. If DNP is assigned to RS485, the protocol must be set to DNP on the serial port configuration as
well, for the change to take effect. When the DNP CHANNEL 1(2) PORT setting is set to “Network - TCP,” the channel 1(2) DNP
protocol can be used over TCP/IP on the Ethernet ports. When this value is set to “Network - UDP,” the DNP protocol can be
used over UDP/IP on channel 1 only. The "Front Panel - RS232" setting does not apply to the graphical front panel; when
selected the DNP client cannot establish a connection on a USB port.
For any change to take effect, restart the relay.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
The DNP ADDRESS setting is the DNP slave address. This number identifies the F35 on a DNP communications link. Assign a
unique address to each DNP slave.
The F35 can specify a maximum of five clients for its DNP connections. These are IP addresses for the controllers to which
the F35 can connect. The settings follow.
SETTINGS PRODUCT SETUP COMMUNICATIONS DNP PROTOCOL DNP NETWORK CLIENT ADDRESSES
DNP NETWORK CLIENT ADDRESS 1: Range: standard IP address
CLIENT ADDRESSES 0.0.0.0
CLIENT ADDRESS 5: Range: standard IP address
0.0.0.0
The DNP TCP/UDP PORT NUMBER setting is for normal DNP operation. To close the port, set the port number to 0. The change
takes effect when the F35 is restarted.
The DNP UNSOL RESPONSE FUNCTION is set to “Disabled” for RS485 applications since there is no collision avoidance
mechanism. The DNP UNSOL RESPONSE TIMEOUT sets the time the F35 waits for a DNP master to confirm an unsolicited
response. The DNP UNSOL RESPONSE MAX RETRIES setting determines the number of times the F35 retransmits an
unsolicited response without receiving confirmation from the master; a value of “255” allows infinite re-tries. The DNP
UNSOL RESPONSE DEST ADDRESS is the DNP address to which all unsolicited responses are sent. The IP address to which
solicited responses are sent is determined by the F35 from the current TCP connection or the most recent UDP message.
The DNP scale factor settings are numbers used to scale analog input point values. These settings group the F35 analog
input data into the following types: current, voltage, power, energy, power factor, and other. Each setting represents the
scale factor for all analog input points of that type. For example, if the DNP VOLTAGE SCALE FACTOR setting is set to “1000,”
all DNP analog input points that are voltages are returned with values 1000 times smaller (for example, a value of 72000 V
on the F35 is returned as 72). These settings are useful when analog input values must be adjusted to fit within certain
ranges in DNP masters. Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (that is, the value is 10 times larger).
The DNP DEFAULT DEADBAND settings determine when to trigger unsolicited responses containing analog input data. These
settings group the F35 analog input data into the following types: current, voltage, power, energy, power factor, and other.
Each setting represents the default deadband value for all analog input points of that type. For example, to trigger
unsolicited responses from the F35 when any current values change by 15 A, the DNP CURRENT DEFAULT DEADBAND setting
is set to “15.” Note that these settings are the deadband default values. DNP object 34 points can be used to change
deadband values, from the default, for each individual DNP analog input point. For any change to take effect, restart the
relay. Whenever power is removed and re-applied to the F35, the default deadbands are in effect.
The DNP TIME SYNC IIN PERIOD setting determines how often the Need Time Internal Indication (IIN) bit is set by the F35.
Changing this time allows the DNP master to send time synchronization commands more or less often, as required.
The DNP MESSAGE FRAGMENT SIZE setting determines the size, in bytes, at which message fragmentation occurs. Large
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to
be necessary, which provides more robust data transfer over noisy communication channels.
5
Check the “DNP Points Lists” F35 web page to view the analog inputs and/or binary inputs points lists. This page
can be viewed with a web browser by entering the IP address of the F35 Ethernet port employed to access the F35
Main Menu, then by clicking the Device Information Menu item, then the DNP Points Lists item.
The DNP OBJECT 1 DEFAULT VARIATION to DNP OBJECT 32 DEFAULT VARIATION settings select the DNP default variation
number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation response when variation
0 is requested and/or in class 0, 1, 2, or 3 scans. See the DNP Implementation section in the UR Family Communications
Guide.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the F35 relay, DNP binary outputs are mapped to virtual inputs. However, some
legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support
the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP
master can operate a single point for both trip and close, or raise and lower, operations. The F35 can be configured to
support paired control points, with each paired control point operating two virtual inputs. The DNP NUMBER OF PAIRED
CONTROL POINTS setting allows configuration of 0 to 32 binary output paired controls. Points not configured as paired
operate on a one-to-one basis.
The DNP TCP CONNECTION TIMEOUT setting specifies a time delay for the detection of dead network TCP connections. If
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection is
aborted by the F35. This frees up the connection to be re-used by a client. For any change to take effect, restart the relay.
Up to 256 binary and up to 256 analog input points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104
protocol, can be configured. The value for each point is user-programmable and can be configured by assigning FlexLogic
operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) follows.
SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / IEC104 POINT LISTS BINARY INPUT / MSP POINTS
BINARY INPUT / MSP Point: 0 Range: FlexLogic operand
POINTS Off
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic operand. See the Introduction to FlexLogic section in this chapter for the range of
assignable operands.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the F35 is restarted.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) follows.
SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / IEC104 POINT LISTS ANALOG INPUT / MME
POINTS
ANALOG INPUT / MME Point: 0 Range: any FlexAnalog parameter
POINTS Off
5 Point: 1
Off
Range: any FlexAnalog parameter
Point: 255 Range: any FlexAnalog parameter
Off
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is
configured by assigning an appropriate FlexAnalog parameter to each point. See the FlexAnalog Parameters section in
Appendix A for the range of assignable parameters.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the F35 is restarted.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored.
The F35 is provided with optional IEC 61850 communications. This feature is specified as a software option at
the time of ordering. See the Order Codes section in chapter 2 for details.
The IEC 61850 settings are accessible in EnerVista software or a substation configuration language (SCL) generating tool.
The path is Settings > Product Setup > Communications > IEC 61850 or Settings > IEC 61850. The settings are not
accessible from the front panel of the device.
IEC 61850 messaging can form part of protection schemes. Consider IEC 61850 settings with the same criticality as
protection element settings. To ensure reliable performance of protection schemes utilizing IEC 61850 messaging,
route IEC 61850 traffic on a separate port from SCADA communications, or use redundant, independent ports, and
a high-speed network recovery method, such as PRP.
Overview
IEC 61850 is a series of international standards and technical reports applicable to power utility automation systems. It
includes semantics, abstract communication services, specific communication services, performance specifications,
network engineering guidelines, configuration description methodologies, and engineering processes. The standard
enables interoperability among intelligent electronic devices (IEDs) from different suppliers and interoperability among
software configuration tools from different suppliers. Interoperability in this case is the ability for IEDs to operate on the
same network or communication path sharing information and commands, and for configuration tools to understand
each other's configuration files.
The UR family supports a large subset of IEC 61850 features. These are detailed in the UR Family Communications Guide
and include the information model, GOOSE publish, GOOSE subscribe, buffered report server, unbuffered report server, and
Manufacturing Message Specification (MMS) query, read, write, and control services. In addition, the URs and their
EnerVista UR Setup software support IEC 61850 Substation Configuration Language (SCL) file import/export and merging.
Many settings of UR protection, control, and monitoring elements, that is to say elements that are not concerned with the
IEC 61850 protocol, can nevertheless be accessed via IEC 61850. These settings are documented elsewhere in this Settings
chapter. This section of the Settings chapter deals solely with the settings that configure the IEC 61850 protocol itself.
The maximum number of simultaneous clients supported by the UR family is five.
IEC 61850 protocol configuration settings are accessed through software panels that are selected either in the Online
Window area (see figure) or the Offline Window area in the EnerVista software.
The EnerVista software also includes an interface that is compatible with firmware versions 5.0 to 7.2 to configure
subscribers. Use the Simplified GOOSE Configurator in the Offline Window area.
Figure 5-18: IEC 61850 protocol panel in EnerVista software (Edition 2)
5 The IEC 61850 window is divided into a navigation pane on the left and a settings panel on the right. You expand and click
an option on the left to display its panel on the right. The following figure shows an example for Server Configuration. The
SETTING column contains the names of the settings, and the PARAMETER column is used to enter the settings. Hovering
the mouse over a setting name displays a tool-tip showing the 61850 information model name of the setting or its location
in SCL files.
Figure 5-19: IEC 61850 panel (Edition 2)
Opening the IEC 61850 window while online causes the UR Setup software to retrieve and import an SCL file from the F35.
This System Configuration Description (SCD) file contains all the settings in the UR at the time of the file request, both those
that are mapped into the IEC 61850 information model (that is, the "public" sections) and those that are not in the model
(that is, the "private" section). The UR EnerVista Setup software imports all of these settings into the current session, not just
those in the IEC 61850 window. To avoid loss of any unsaved setting changes made in other panels during the current
session, all other panels for the F35 must be closed before the IEC 61850 panel can be opened, and the software prompts
for this when applicable. Panels for other devices can be open concurrently to facilitate parameter coordination.
When CyberSentry security is enabled, editable settings depend on the user role logged in. For example, an Administrator
and Engineer can change settings. If prompted for a "Settings password," it means the Administrator or Engineer
password.
The Restore button restores settings in the window to their last saved values. The Default button reverts settings in the
window to factory default values or Oscillography, Data Logger, or FlexLogic Equation Editor pre-configured values. The
Reset button reverts all IEC 61850 settings to the factory default values, not just the current window. (In other settings
windows, the button reverts settings in the window to factory default values.)
When a setting is enabled, its panel continues to read Disabled until relaunched. There is no polling capability to update
automatically the IEC 61850 readings, so the panel needs to be closed then opened for the correct status to display. Good
practice is to close any panel not in use because changes being made by other users too are reflected only upon relaunch
of the panel.
Some of the IEC 61850 settings use floating point data, which guarantees accurate representation of real numbers up to
seven digits. Numbers with more than seven digits are approximated within a certain precision. This can result in
differences between what is entered and what is saved, and for example results in differences shown on a settings
comparison report.
Server configuration
The Server Configuration panel contains IEC 61850 settings relevant to the server functions of the IED implementation.
The path is Settings > Product Setup > Communications > IEC 61850 > Server Configuration.
The following settings are available, where <iedName> is a syntactic variable representing the present value of the IED
NAME setting.
5 IED NAME
Range: 1 to 58 VisibleString characters
Default: TEMPLATE
The value entered sets the IED name used by IEC 61850 for the F35. An IED name unique within the network must be
entered for proper operation. Valid characters are upper and lowercase letters, digits, and the underscore (_) character.
The first character must be a letter.
The IED NAME and the Product LD inst name comprise the <LDName> for a product. The longest LD inst are "Master"
and "System" at six characters, with Master being fixed and the others configurable with the configurable Logical device
feature. So the IED NAME needs to be restricted to 58 characters to meet a 64 character limit.
Access Point
Range: S1, S2, S3
Default: S1
This setting applies to IEC 61850 Edition 1. It is the subnetwork.
Location
Range: 0 to 255 ASCII characters
Default: Location
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.location. This data attribute is
provided by the protocol to allow the user to declare where the equipment is installed.
Latitude
Range: -90.000 to 90.000 degrees in steps of 0.001 degree
Default: 0.000 deg
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.latitude. This data attribute is provided
by the protocol to declare the geographical position of the device in WGS84 coordinates -latitude. Negative values
indicate a southern latitude. WGS refers to the world geodetic system, which is used in global positioning systems (GPS),
and 84 is the current version of the standard.
Longitude
Range: -180.000 to 180.000 degrees in steps of 0.001 degree
Default: 0.000 deg
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.longitude. This data attribute is
provided by the protocol to declare the geographical position of the device in WGS84 coordinates -longitude. Negative
values indicate a western longitude.
Altitude
Range: 0 to 10,0000 m in steps of 1 m
Default: 0 m
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.altitude. This data attribute is provided
by the protocol to declare the geographical position of the device in WGS84 coordinates - altitude.
Prefix for GGIO1
Range for Edition 2: 0 to 11 VisibleString characters
Range for Edition 1: 0 to 6 VisibleString characters
Default:
This setting sets the LN Prefix of the FlexLogic operand interface logical node GGIO1 that is described in the GGIO1
section later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first
character must be a letter. UR Setup software does not allow entry of a prefix that duplicates any other GGIO1 prefix
that is used by the product, such as ConIn and ConOut.
Prefix for GGIO2
Range for Edition 2: 0 to 11 VisibleString characters
Range for Edition 1: 0 to 6 VisibleString characters
Default:
This setting sets the LN Prefix of the Virtual Inputs Interface logical node GGIO2 that is described in the GGIO2 section
5
later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first character must
be a letter. UR Setup software does not allow entry of a prefix that duplicates any other GGIO2 prefix that is used by the
product.
Prefix for GGIO4
Range for Edition 2: 0 to 11 VisibleString characters
Range for Edition 1: 0 to 6 VisibleString characters
Default:
This setting sets the LN Prefix of the FlexAnalog operand interface logical node GGIO4 that is described in the GGIO4
section later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first
character must be a letter. UR Setup software does not allow entry of a prefix that duplicates any other GGIO4 prefix
that is used by the product.
LLN0.Mod.ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: sbo-with-normal-security
This setting specifies the control service that clients must use to control the TEST MODE FUNCTION of the F35. An "on"
control to <LDName>/LLN0.Mod changes TEST MODE FUNCTION to Disabled, an "on-blocked" control changes it to
Forcible, and a "test/blocked" changes it to Isolated.
Configuration Type
Range: G2, E3-2.0
Default: G2
This setting is read only. It specifies the method used to describe GOOSE subscription configuration in SCL. See the UR
Family Communications Guide for details. In the G2 mode, the CID file contains IED elements for IEDs subscribed to by
this IED containing GOOSE subscription information. In the E3 2.0 mode, the CID file has only one IED element and
GOOSE subscription information is coded in data objects in the standard LGOS logical node used to monitor reception of
the subscribed GOOSE. UR 7.30 or later accepts either mode. The set value is for the entire EnerVista installation and is
preserved between sessions. To change this global field, click File > Preferences and access the IEC 61850 panel; you do
not need to be connected to the device.
Logical devices
The Logical Devices panel contains IEC 61850 settings relevant to the configurable logical devices feature, wherein logical
device naming can be reconfigured and logical nodes re-assigned.
The path is Settings > Product Setup > Communications > IEC 61850 > Logical Devices.
Figure 5-21: Default IEC 61850 Logical Devices panel with devices middle and nodes right (Edition 2)
5
To configure logical devices and nodes:
1. Right-click an entry and edit an existing device, add a new one, or move a logical node. The rest of this section
explains the window and how to perform these actions.
The Logical Devices panel has middle and right panes. The middle pane has a list of the instantiated logical devices in the
sequence that they appear in SCL, with one device selected. The right pane has a list of the logical nodes presently
assigned to the selected logical device in lexicographic order by logical node name.
In the middle pane logical devices are shown with their product-related name, followed in brackets by their function-
related ldName, and followed by the value of their confRev. In the following example, by right-clicking and editing, the
Protection logical device has been set to instance name "Prot", the function-related name "Feeder1Prot" and the
configuration revision "2016-03-07 08:46." The text is clipped on the right if the line is longer than the available width. The
next paragraphs explain how to do this setup.
Figure 5-22: Protection logical node selected
5
Right-clicking a logical device displays the menu that allows insertion of a new logical device immediately below the
selected one, deletion of the selected logical device, or editing the selected logical device's parameters. The insert option is
disabled and greyed-out if there are already 16 logical devices instantiated. The delete option is disabled and greyed-out if
the selected logical device is Master or it contains any logical nodes other than LLN0.
Figure 5-23: Menu for logical node
If the insert option is selected, or the edit option is selected for other than the Master logical device, a logical device
parameters edit dialog opens.
If the edit option is selected for the Master logical device, the Product LD inst name setting is not editable.
Figure 5-25: Edit logical node
When the Ok button is clicked, the entered values for Product LD inst name and Functional ldName are checked for
uniqueness within the UR, and they are updated in the pane.
The settings are explained as follows, where <iedName> is a syntactic variable representing the present value of the IED
NAME setting. When adding or editing a logical device entry, these are the fields that need to be completed.
IED name and the logical device inst name must form an LDName that is unique within the network for proper operation.
It is recommended that the length of the IED NAME plus the length of this setting be not greater than 64 to respect the
requirements of IEC 61850 7 2:2010 22.2 for LDName.
The factory default configuration is for six logical devices with Product LD inst name settings and logical node
assignments as per the following table.
Table 5-10: Factory default logical nodes
Default logical Contains logical nodes modeling...
device inst name
Master communications, including GOOSE, reports, Remote I/O, Virtual Inputs, Modbus, DNP, and so on.
(root logical device; Setting group control.
name is fixed) This is the root logical device.
To comply with IEC 61850 7 1 Ed2 clause 6.4.5.1, all group L logical nodes (logical nodes with class names
begin with "L"), except LLN0, belonging to this IED are in this logical device.
Protection (Prot) protection functions
Control (Ctrl) control and monitoring functions
System power system devices: breakers, switches, CTs, VTs, and so on, including interface to these such as AC inputs,
contact I/O, transducer I/O, HardFiber I/O
Metering (Meter) metering and measurement, including Signal Sources
General (Gen) FlexLogic, virtual outputs, non-volatile latches, FlexElements, FlexMath, recording (for example oscillography),
security, front panel, clock
Functional ldName
Range: 0 to 64 VisibleString characters
Default: empty string
Each logical device has this setting. The value is configurable in all logical devices. Valid characters are upper and
lowercase letters, digits, and the underscore (_) character. If the number of characters entered is greater than zero, the
5
setting sets the value of the function-related name used in communications. If an ldName is entered, it must form an
LDName that is unique within the network for proper operation. The standard recommends choosing this name
according to IEC 81346-1. If the number of characters entered is zero, no function-related name is defined.
Throughout the remainder of this IEC 61850 section, <LDName> is a syntactic variable representing the present
LDName of the master logical device. In other contexts LDName can refer to some other logical device. Depending
on its context, <LDName> can be a product-related name or a function-related name.
configRev
Range: 0 to 255 ASCII characters
Default:
This data attribute is provided by the protocol to declare changes to the semantic of the data model of the UR. The intent
is that the user changes Master configRev each time that the semantic or data model changes, so that clients can
readily detect the change. A semantic change is a logical node getting a new semantic use; for example, an instance of
logical node CSWI is now serving a different physical switch, or an instance of a logical node PDIS is now used for
another zone. A data model change is a change in the presence of logical nodes, data objects, data attributes, or
instance names.
The scope of Maser configRev is the entire relay configuration, as the Master logical device is the root logical device.
Similar settings are provided for the other logical nodes; the scope of these other configRev settings is limited to the
corresponding logical device configuration.
paramRev
Range: -2,147,483,648 to 2,147,483,647
Default: 0
The configurable data attribute paramRev has a scope that includes the entire device, and thus is modified whenever
any setting in the device changes. The UR increments the value of paramRev by one whenever one or multiple setting
changes occurs in one Modbus write request by any means (front panel, Modbus, or MMS) other than by SCL file
download. Incrementing occurs whether or not the setting is represented in the information model. When a UR device or
EnerVista UR Setup accepts an SCL file, paramRev is set to the value in that SCL file. When EnerVista UR Setup changes
one or more settings, and prepares an SCL file, it increments paramRev to the next higher multiple of 10 000.
Each logical device has a name: LDName. (Note the upper case LD.) LDName has both a product-related form and
a function-related form as per IEC 61850 6:2009 8.5.3.
SCL files invariably use the product-related form of LDName. The product-related form is the concatenation of the
IED name of the device and the individual logical device's inst name. The IED name is the value of the "IED NAME"
setting on the Server Configuration panel, and the logical device inst names are each the value of the
corresponding "Product LD inst name" setting here. The "Product LD inst name" of the first logical device is fixed at
"Master".
Communications use the function-related form of LDName if a function-related name is defined, otherwise
communications use the product-related name. The function-related name is the value of the corresponding
"Functional ldName" setting if this setting is not empty, if empty the function-related name is not defined.
In SCL, the function-related name is specified by the LDevice element attribute ldName (note the lower case ld).
Absence of this attribute indicates the function-related name is not defined. In SCL the product-related name is
specified by the name attribute of the IED element and the inst attribute of the LDevice element.
In the right pane, logical nodes assigned permanently to the Master logical device and LLN0 in all logical devices are
greyed-out as shown earlier. These are not movable. Any other logical node can be dragged to any of the logical devices in
the middle pane, which causes that logical device to be re-assigned to that logical device. Right-clicking a logical node
device displays a menu that lists the logical devices that this logical node can be moved to. Clicking one of these re-assigns
the logical node. Other common keyboard and/or mouse action can be used to select one or more logical nodes and move
the selected nodes together.
GOOSE
The path is Settings > Product Setup > Communications > IEC 61850 > GOOSE.
• A v7.4 device cannot send an R-GOOSE message to non-R-GOOSE devices, such as v7.3 or v5.9 UR device
• UR devices with firmware below v7.3 can send a GOOSE message to a v7.4 device that has GOOSE as the active
protocol
R-GOOSE is available through the IEC 61850 software option. If R-GOOSE security is required, the CyberSentry
software option also must be purchased.
TxGOOSE
IEC 61850 GOOSE is an efficient method for simultaneous high-speed delivery of generic substation event information by a
publishing device to more than one subscribing device. A TxGOOSE is a UR element implementing a single IEC 61850
GOOSE message publishing service. The subscribing function in URs is performed by RxGOOSE elements, as described in
the next section. Each UR with IEC 61850 order code options has 16 TxGOOSE elements. Each TxGOOSE can either use the
original format specified in IEC 61850 8 1:2011 or the routable GOOSE (R-GOOSE; IEC 61850 Edition 2) format specified in
IEC TR 61850-90-5:2012. Each TxGOOSE element can publish the values of up to 64 attributes of the IEC 61850 nodes in the
UR.
Published TxGOOSE messages configured in the EnerVista UR Setup software can be subscribed by and the published
operand values understood by other UR devices. Furthermore, they can be subscribed to and understood by any device of
any manufacturer that implements the IEC 61850 edition 1.0 or 2.0 GOOSE subscription mechanism. The messages are
published with a multicast address so that the network sends the messages to all devices; any number of devices that
want to subscribe can.
For wide area protection, control, and monitoring schemes, R-GOOSE wraps the proven original format GOOSE in IP/UDP to
multicast (or unicast) the data over a Wide Area Network (WAN). Sample applications are Wide area Remedial Action
Scheme (RAS) and Under Voltage/ Frequency Load Shedding Schemes (UVLS/UFLS). R GOOSE uses IGMPv3 (Internet Group 5
Management Protocol version-3, RFC 3376) for multicasting.
The entities whose values are published in GOOSE messages are known as members. The members are itemized in an
ordered list known as a data set. Each TxGOOSE can use any one of the configured data sets. (See the DataSets section
later for details.) The performance of a TxGOOSE is determined by its dataset. Booleans in fast GOOSE datasets are
designed for the TT6 transfer time class (3 ms), while Booleans in the Normal datasets are designed for the TT3 class (100
ms). Due to the significant amount of CPU time required to compose a TT6 TxGOOSE message and the limited amount of
time allowed by the TT6 class, at most four of these can be configured in a given UR. So only four fast GOOSE are allowed
to be configured, and the UR software has a check to disallow the use of more than four fast datasets in GOOSE. If six fast
datasets are configured outside of UR software and the file sent directly to the relay, the relay rejects the file. The design
does allow six fast datasets to be used in report control blocks, which allows fast scanned data in reports.
Each enabled TxGOOSE transmits its message whenever a value change is detected in one or more of its members. If the
changed value is a Boolean in a fast dataset, then the change detect occurs in the TT6 detection time of 3 ms or less. If the
member is an analog value in a fast dataset, the change detect occurs in theTT3 time of 100 ms. In Normal GOOSE
Datasets, change detection for all dataset members occurs in the TT3 time of 100 ms. To guard against the possibility that
such a message is lost in the network before it reaches all subscribers, the message is quickly retransmitted several times.
To allow subscribers to verify that their link to the publisher and the publisher itself are healthy, each message is also
retransmitted periodically even while the values are unchanging. These latter messages are known as heartbeat
messages, while the former are known as event messages. Heartbeat messages also provide means for a subscriber
newly online to receive the published values in the absence of an event.
The details of TxGOOSE message construction are contained in the UR Family Communications Guide. Knowledge of these
details is not required to configure GOOSE.
The UR does not implement the Fixed-Length encoded GOOSE messages option specified in IEC 61850-8-1:2011 clause
A.3; the UR always uses the ASN.1 Basic encoding rules (as specified in ISO/IEC 8825-1) as specified in IEC 61850 edition 1.0
and as optional in IEC 61850 edition 2.0.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > TxGOOSE > TxGOOSE1 to access the
settings for the first TxGOOSE. The settings and functionality for the others are similar.
5
A data set needs to be set up and selected in the TxGOOSEx DatSet field for all content to display.
When saving changes, when a "dataset member is empty" message displays, you need to set the member in the bottom
right of the window.
TxGOOSE1 MODE
Range for Edition 2: Disabled, GOOSE, R-GOOSE
Range for Edition 1: Disabled, GOOSE
Default: Disabled
When set to Disabled, TxGOOSE1 messages are not published. When set to GOOSE, TxGOOSE1 messages are published
in IEC 61850 8 1:2011 GOOSE format. When set to R-GOOSE, TxGOOSE1 messages are published in Routable GOOSE
format according to IEC 61850 90-5, and the TxGOOSE1 DST MAC address is set to 00 00 00 00 00 00 and cannot be
changed.
TxGOOSE1 GoCB name
Range: 0 up to 32 VisibleString characters
Default: GoCB01
The entered value sets the GOOSE control block (GoCB) name value for TxGOOSE1.
An ObjectReference to the control block, which consists of the concatenation of the string "<LDName>/LLN0." and the
control block name, is published in the gocbRef field of TxGOOSE1 messages and is used by subscribers to discriminate
TxGOOSE1 messages from other GOOSE messages. <LDName> is a syntactic variable that is set to the value of setting
Master functional ldName if one or more characters have been entered to that setting, otherwise the value of setting IED
NAME suffixed with "Master".
TxGOOSE1 GoID
Range for Edition 2: 0 to 129 VisibleString characters
Range for Edition 1: 0 to 65 VisibleString characters
Default: TxGOOSE1
The entered value sets the goID value published in TxGOOSE1 messages, and can be used by subscribers to discriminate
the TxGOOSE1 messages from other GOOSE messages. Special characters are not allowed, such as <, >, &, ’, and ".
TxGOOSE1 DatSet
Range: None, TT6DataSet1,TT6 DataSet2, … TT3DataSet01,TT3 DataSet02, …
Default: None
This setting selects the published data set using the UR Setup software designator for the data set. If None is selected,
no TxGOOSE1 messages are sent.
The IEC 61850 name of the data sets are configured in the Datasets panel, as described later.
Some datasets are designed for the TT6 transfer time class (3 ms), while others are designed for the TT3 class (100 ms).
The performance of a TxGOOSE is determined by its dataset. Use TT6 datasets for trips and blocking applications, TT3
datasets for slow automatic interactions. The 61850 name of the datasets are configured in the Datasets panel.
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0." and the data
set name, is published in the datSet field of TxGOOSE1 messages and can be used by subscribers to discriminate
TxGOOSE1 messages from other GOOSE messages. <LDName> is a syntactic variable that is set to the value of setting
Master functional ldName if one or more characters have been entered to that setting, otherwise the value of setting IED
NAME suffixed with "Master".
To configure a DataSet, select it at the top of the window from the drop-down list. In the lower part of the window, drag
and drop configuration items to the right side. Dataset members configured here affect other Report or TxGOOSE
control blocks that use the same DataSet.
The performance of the TxGOOSE is determined by the performance of the selected dataset. When the selection is 5
TT3DataSet01, TT3DataSet02, … it is possible that transient events can be missed.
TxGOOSE1 DST MAC
Range: any 12 digit hexadecimal number
Default: 01-0C-CD-01-00-00
When the TxGOOSE1 MODE setting is R-GOOSE, the TxGOOSE1 DST MAC address is set to 00 00 00 00 00 00 and cannot be
changed. Otherwise, the value entered here sets the Ethernet destination Media Access Control (MAC) address in
published TxGOOSE1 messages. As the standard requires that the address have the multicast bit set TRUE, that is to say
the second digit is set to an odd number, messages transmitted have the multicast bit set TRUE no matter its value in
this setting.
The destination MAC address can be used by the network to restrict message delivery to selected devices that need to
receive them, reducing network load. This address also can be used by hardware in receiving devices to filter out
messages that are of no interest to them, reducing processor burden. Different filtering algorithms are implemented by
different devices. The standard recommends that the algorithm used by hardware of the receiving device be considered
when assigning destination multicast addresses.
Subscribers can use this address to discriminate TxGOOSE1 messages from other GOOSE messages.
TxGOOSE1 VLAN PRIORITY
Range: 0, 1, 2, 3, 4, 5, 6, 7, 5-4, 6-4, 6-5, 7-4, 7-5, 7-6
Default: 4
When the value entered is 0, 1, 2, 3, 4, 5, 6, or 7, the User Priority value in the IEEE 802.1Q VLAN tag included in published
TxGOOSE1 messages is set to that value. When one of the two-digit values is entered, the dynamic priority feature is
selected: the first event message has the User Priority value of the first digit, and User Priority is decremented in each
following message until reaching the value of the second digit. For instance, if the selected value is 7-5, then the User
Priority values in successive messages beginning with the message triggered by an event is 7, 6, 5, 5, 5, 5, 5, and so on.
Do not make a dynamic priority selection when standard behavior is required.
Network devices can forward a message with a higher priority value before a message with a lower priority value, which
speeds delivery of high-priority messages in heavily loaded networks. The standard recommends that higher-priority
messages, such as GOOSE, have priority values in the range of 4 to 7.
TxGOOSE1 VLAN ID
Range: 0 to 4095 in steps of 1
Default: 0
The value entered sets the VID value in the IEEE 802.1Q VLAN tag included in published TxGOOSE1 messages. VID can be
used by network devices to direct messages to only selected devices, reducing network burden. VID values of 0 and 1
are assigned by IEEE 802.1Q to other functions and are not to be used for GOOSE.
TxGOOSE1 ETYPE APPID
Range: 0 to 65535 in steps of 1
Default: 0
The value entered sets the APPID value in published GOOSE messages and can be used by subscribers to discriminate
TxGOOSE1 messages from other GOOSE messages.
The standard reserves the value range 0 to 16383 for GOOSE Type 1 (Fast messages), and reserves the value range
32768 to 41151 for GOOSE Type 1A (Trip messages). Some subscribers can process messages in the Type 1A range
faster than messages in the Type 1 range. The standard reserves the default value (0) to indicate lack of configuration.
The standard strongly recommends unique, source-orientated APPIDs within a given system.
TxGOOSE1 CONFREV
Range: 0 to 4294967295 in steps of 1
Default: 1
The entered value sets the confRev value in published GOOSE messages and can be used by subscribers to discriminate
TxGOOSE messages of the expected configuration revision from messages of a different revision. The standard requires
that CONFREV be incremented each time the members or the order of the members published is changed. The standard
states that the value of 0 is reserved.
This setting specifies the Ethernet ports for transmission of TxGOOSE1. When set to disabled, TxGOOSE1 messages are
not transmitted on any port no matter the state of GoEna. When set to Port-1, TxGOOSE1 is published over Ethernet
Port-1 only; while selecting Ports-1, 3 option, the same TxGOOSE1 is published to both Ports 1 and 3; and similarly if set
to Ports-1, 2, 3, all ports publish TxGOOSE1.
When setting PRT2 REDUNDANCY to Failover or to PRP, the TxGOOSE 1 port assignment needs to be set to ports 2
and 3 (Ports-2,3).
Also, Port 3 configuration in the CID file is ignored. The Port 3 ConnectedAP elements has no meaning, as ports 2
and 3 use the port 2 MAC address, IP address, and mask.
R-TxGOOSE1 IP CLASS
Range: 0 to 256 in steps of 1
Default: 46
This setting applies to IEC 61850 Edition 2.
When the TxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. Otherwise this setting
selects the IPv4 Differentiated Services Code Point-DSCP (formerly called TypeOfService-TOS) value. This value provides
priority routing, when supported in the routers. The default value is for Expedited Forwarding (101110B, 46 or 2EH).
R-TxGOOSE1 DST IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 224.0.0.0
This setting applies to IEC 61850 Edition 2.
When the TxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. Otherwise this setting
specifies destination IP address for the R-TXGOOSE1 that is entered in Standard IPV4 address format. The destination IP
address needs to be a valid multicast or unicast IP address. The value specified in this setting is mapped to IPv4 header
32 bit field for Destination IP Address while publishing R-GOOSE1. 5
The default IP address 224.0.0.0 is reserved, and hence not a valid multicast IP address.
The source IP address is that of the UR port from which the R-GOOSE messages are transmitted.
R-TxGOOSE1 SECURITY
Range: None, Signature, SignatureAndEncryption
Default: None
This setting applies to IEC 61850 Edition 2.
This setting specifies level of security (authentication/encryption) used for TxGOOSE1. None specifies no security
mechanisms are to be used. Signature specifies only signature (no encryption) is to be used. SignatureAndEncryption
specifies that both signature and encryption are to be used.
RxGOOSE
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages.
IEC 61850, GOOSE is an efficient method for simultaneous high-speed delivery of the same generic substation event
information by a publishing device to more than one subscribing device. An RxGOOSE is a UR element implementing a
single IEC 61850 GOOSE message subscribing service. The publishing function in URs is performed by TxGOOSE elements,
as described in the previous section.
Each UR with the IEC 61850 order code option has 64 RxGOOSE elements. Each RxGOOSE element can subscribe to GOOSE
messages from a specified publisher. Each RxGOOSE can either use the original format specified in IEC 61850 8 1:2011 or
the routable GOOSE (R-GOOSE; IEC 61850 Edition 2) format specified in IEC TR 61850-90-5:2012. Subscribed message
members can be DataObjects, SubDataObjects, DataAttributes or SubAttributes. In E2-2.0 mode members are restricted to
basic types BOOLEAN, FLOAT32, INT32, Dbpos, TimeStamp or Quality. Each subscribed message can contain up to 64
values. A member can be a structure containing several values; note that it is the number of values rather than the number
of members that are limited to 64.
GOOSE messages from any device of any manufacturer that implements the IEC 61850 Edition 1.0 or 2.0 GOOSE publish
service or the 61850-90-5 R-GOOSE service (IEC 61850 Edition 2) can be subscribed to. The UR accepts both the variable
length encoded GOOSE messages specified IEC 61850 8 1:2004 and the Fixed-Length encoded GOOSE messages as
specified in IEC 61850 8 1:2011 clause A.3.
Each enabled RxGOOSE monitors for interruption of the GOOSE messages it subscribes to based on the value in the
timeAllowedtoLive field of the last message received. If a new message is not received within that time interval, the
RxGOOSE assumes that connectivity is lost. FlexLogic operands (for example RxGOOSE1 On, RxGOOSE1 Off) reflect the
status of each RxGOOSE connectivity. An RxGOOSE connection is also considered lost after the UR finishes restart until a
message is received. While any RxGOOSE connectivity is lost, a common RxGOOSE Fail self-test is activated.
Messages that contain the value true in the ndsCom field are never accepted. Messages that contain the value true in the
simulation field (test field in edition 1.0 messages) are accepted only when the UR Test Mode Function setting is set to
Forcible or Isolated.
RxGOOSE messages can be received through any UR Ethernet port.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages >
RxGOOSE1 to access the settings that specify the messages to be accepted by the first RxGOOSE element. The settings
and functionality for the other RxGOOSE are similar. The following settings are available. They allow RxGOOSE1 to
recognize the GOOSE messages it is to accept. Most of these settings are automatically configured by UR Setup software
when an association to an RxGOOSE Boolean Input, RxGOOSE DPS Input, and/or RxGOOSE Analog Input is made as
described in the sections following this. For IEC 61850 Edition 2, settings R-RxGOOSE1 RECEPTION MODE, R-RxGOOSE1
SECURITY, and R-RxGOOSE SRC IP need to be manually completed as the information is not contained in publisher SCL.
Figure 5-28: IEC 61850 RxGOOSE Messages panel (Edition 2)
RxGOOSE1 MODE
Range for Edition 2: GOOSE, R-GOOSE
Range for Edition 1: GOOSE
Default: GOOSE
When set to GOOSE, TxGOOSE1 messages are published in IEC 61850 8 1:2011 GOOSE format. When set to R-GOOSE,
TxGOOSE1 messages are published in Routable GOOSE format according to IEC 61850 90-5. When set to R-GOOSE, the
R-RxGOOSE DST IP needs to be a valid multicast or unicast IP address.
RxGOOSE1 goID
Range: 0 to 129 VisibleString characters
Default: empty string
If the entered value has one or more characters, the goID field of incoming GOOSE messages must exactly match this
value for the message to be accepted as a valid RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1
does not check the value received in the goID field. Special characters are not allowed, such as <, >, &, ’, and ".
If the publisher is a UR 7.3x series device, this setting needs match the value of the publisher's TxGOOSE GoID setting.
RxGOOSE1 Dst MAC
Range: any 12 digit hexadecimal number
Default: 01-0C-CD-01-00-00
When the RxGOOSE1 MODE setting is R-GOOSE, the value of this setting is not used, the destination Media Access
Control (MAC) address for RxGOOSE1 messages is calculated based on the RxGOOSE DST IP address. Otherwise, set this
setting to the MAC address of the publisher. Only received GOOSE messages having a MAC address equal to this value
are accepted as valid RxGOOSE1 messages. An entered address of zero disables RxGOOSE1.
If the publisher is a UR series 7.3x device, the setting needs to match the value of the publisher’s TxGOOSE DST MAC
setting.
RxGOOSE1 ETYPE APPID
Range: 0 to 65535 in steps of 1
Default: 0
If the value entered is non-zero, the APPID field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the value entered is zero, RxGOOSE1 does not check the value
received in the APPID field.
If the publisher is a UR series 7.3x device, the setting needs to match the value of the publisher’s TxGOOSE ETYPE APPID
setting. 5
RxGOOSE1 GoCBRef
Range: 0 to 129 alphanumeric, underscore, slash and period characters, beginning with an alpha character
The gocbRef field of incoming GOOSE messages must match this value for the message to be accepted as a valid
RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1 is disabled. If not the empty string, the entry
needs to be an ACSI ObjectReference to the publishing control block in the format:
<LDName>/LLN0.<GoCBName>
where <LDName> is the function-related name if the logical device containing the publishing control block has "ldName"
configured, otherwise the product-related name of that logical device, and <GoCBName> is the name of the publishing
control block.
The F35 translates the ACSI format required for this setting to the MMS format used in GOOSE messages:
<LDName>/LLN0$GO$<GoCBName>
If the publisher is a UR 7.3x or 7.40 series device, <LDName> is the value of the publisher's Master functional ldName
setting if that setting is not empty, otherwise it is the value of the publisher's IED NAME suffixed with "Master". If the
publisher is a UR 7.3x series device, <GoCBName> is "GoCB" suffixed with the two digit TxGOOSE instance number, for
example "GoCB01". If the publisher is a UR 7.40 series device, <GoCBName> is as specified earlier in the TxGOOSE
section of this chapter.
RxGOOSE1 datSet
Range: 0 to 32 alphanumeric and underscore characters, beginning with an alpha character
Default: empty string
If the entered value has one or more characters, the datSet field of incoming GOOSE messages must exactly match this
value prefixed by <LDName>/LLN0$ for the message to be accepted as a valid RxGOOSE1 message. <LDName> is as
specified in the RxGOOSE GoCBRef setting above. If the entered value is the empty string, RxGOOSE1 does not check the
value received in the datSet field.
If the publisher is a UR 7.3x series device, set this setting to the value of the publisher's DataSetxx name setting, where xx
is the instance number of the data set selected by the publisher's TxGOOSE datSet setting. If the publisher is a UR 7.40
series device, datSet is as specified in the DataSets section of this chapter.
RxGOOSE1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
If the value entered is non-zero, the confRev field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the entered value is zero, RxGOOSE1 does not check the value
received in the confRev field.
If the publisher is a UR 7.3x series device, set this setting to match the value of the publisher's TxGOOSE ConfRev setting.
R-RxGOOSE1 RECEPTION MODE
Range: SSM, ASM, Unicast
Default: SSM
This setting applies to IEC 61850 Edition 2.
When the RxGOOSE1 MODE setting is other than R-GOOSE the value of this setting is not used. Otherwise it selects the
R-GOOSE reception mode.
R-RxGOOSE RECEPTION MODE specifies the R-RxGOOSE DST IP range. When set to SSM, R-RxGOOSE DST IP must be in
the range of 232.0.0.1 to 232.255.255.255. When set to ASM, R-RxGOOSE DST IP must be in the range of 224.0.0.1 to
239.255.255.255, excluding the SSM range. Note that the SSM range is inside the ASM range and therefore the ASM use
excludes the SSM range. The default destination IP address 224.0.0.0 is reserved, and hence not a valid multicast IP
address.
The reception modes are related to Layer-3 R-GOOSE reception from routers/WAN. The subscription to multicasting of R-
GOOSE is supported using IGMP Protocol Independent Multicast (PIM). It is made available in either Source Specific
Multicast (SSM) mode or Any Source Multicast (ASM) mode. Unicast (over UDP) mode can also be used. In case of
multicasting (IGMPv3 based SSM or ASM), the R-GOOSE subscriber device requests the Last Hop Router (LHR) to
subscribe to a specific multicasting group.
5 If the publisher is using a unicast destination IP address for this R-GOOSE, then set R-RxGOOSE1 RECEPTION MODE to
Unicast. Otherwise set R-RxGOOSE1 RECEPTION MODE to the SSM or ASM mode used by the local routers/firewalls.
R-RxGOOSE1 SRC IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 127.0.0.1
This setting applies to IEC 61850 Edition 2.
When the RxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. When the RxGOOSE1
MODE setting is R-GOOSE and the R-RxGOOSE RECEPTION MODE setting is ASM, the value of this setting is not used.
Otherwise the Source IP Address field of incoming R-GOOSE messages must exactly match this value for the message to
be accepted as a valid RxGOOSE1 message. Set this setting to the value of the source IP address used by the publisher.
For UR publishers, this value is in setting PRT# IP ADDRESS.
The UR does not validate the address entered. The default IP address 127.0.0.1 is a reserved, not a valid IP address. Enter
a valid IP source address.
R-RxGOOSE1 DST IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 224.0.0.0
This setting applies to IEC 61850 Edition 2.
When the RxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. Otherwise the
Destination IP Address field of incoming R GOOSE messages must exactly match this value for the message to be
accepted as a valid RxGOOSE1 message. Set this setting to the same value as the R-GOOSE publisher's Destination IP
Address. For UR publishers, this value is in setting R-TxGOOSE# DST IP.
The destination IP address needs to be a valid multicast or unicast IP address. The UR does not validate the address
entered. The default IP address 224.0.0.0 is reserved, and hence not a valid multicast IP address.
R-RxGOOSE1 SECURITY
Range: None, Signature, SignatureAndEncryption
Default: None
This setting applies to IEC 61850 Edition 2.
This setting specifies the level of security (authentication/encryption) used for RxGOOSE1. None indicates no security
mechanisms are in use. Signature indicates only signature (no encryption) is in use. SignatureAndEncryption indicates
that both signature and encryption are in use. Normally this setting is set to match the GOOSE publisher's security
method.
RxGOOSE1 Member 1
Range: End of List, BOOLEAN, FLOAT32, INT32, Dbpos (DPS), Quality, TimeStamp, Struct
Default: End of List
This setting specifies the type that the first member of incoming GOOSE messages must be for the message to be
accepted as a valid RxGOOSE1 message. There are similar settings for each of the up to 64 members that the UR is able
to subscribe to in a given GOOSE message. The member before the first member setting set to "End of List" must be the
last member of the message for the message to be accepted as a valid RxGOOSE1 message.
If the publisher is a UR 7.3x or 7.40 series device, set these settings to match the basic type of the members of the
publisher's data set selected by the publisher's TxGOOSE datSet setting.
If the publisher dataset includes members with structured data, that is, data attributes, sub-data objects, and/or data
attributes with sub-data attributes, configuration must use one of the new 7.40 UR Setup RxGOOSE Inputs pages. In this
case the Member setting displays as the product-related name used by the publishing IED of the data object or data
attribute, in standard SCSM format (e.g. Publisher1LD1/LLN0$ST$Off$stVal).
Note that a dataset can hold at most 64 basic data attribute values, and that a single structured data object or attribute
can contain multiple basic data attribute values. UR Setup software does not allow more that 64 basic data attribute
values to be entered, in which case the last several members settings cannot be changed from End of List.
Note that the publisher's name alone does not contain all the information required for subscription, additional publisher
information model information is stored elsewhere. For this reason, manual entry of the name is not supported.
RxGOOSE inputs
5
The values received by RxGOOSE elements need to be converted to FlexLogic or FlexAnalog operands so that they can be
used by other UR elements. This conversion is done by RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements.
Each RxGOOSE Boolean can convert the value of a specified Boolean value received by a specified RxGOOSE to a FlexLogic
operand. Each RxGOOSE DPS can convert the value of a specified Dbpos (Double bit position) value to four FlexLogic
operands, one for each of the four possible Dbpos states. Each RxGOOSE Analog can convert the value of a specified
FLOAT32 member to a FlexAnalog operand. Each of these operands reverts to its default state when the RxGOOSE
connectivity is lost. Other types of values can be present in subscribed GOOSE messages, but cannot be converted to
operands.
When an RxGOOSE Input is mapped to a value in the GOOSE message, the associated q value is validated, if the q value is
included in that GOOSE message as part of the data object.
The RxGOOSE Input value is reverted to its default value, if the associated:
• q.validity is invalid
• or q.test bit is set and the relay test mode is disabled
When the test mode function is Forcible or Isolated, the q.test bit is not validated. That means, when the relay is in Test or
Test/blocked mode, the q.test = False is treated same as q.test = True.
RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements are mapped to various data objects in
<iedName>Master/GGIO3. This is to allow reading of their values via MMS and to allow references to them in SCL files.
GGIO3 has no settings, nor is it visible in the UR Setup software. See the UR Family Communications Guide for more
information on GGIO3.
There are Add IED and Remove IED buttons. The Add IED button allows SCL files to be used, including ICD, CID, and SCD
(supported in version 7.40 and later). With SCL file import, for Edition 1 the IP address in the ConnectedAP element must
match one IP address of the device, while for Edition 2 one of the three IP addresses in the ConnectedAP element must
match. When the file format is SCD, the system lists all IEDs inside the SCD file and lets the user select the ones to add. The
figure shows a selection being made by importing a CID file using the Add IED function.
Figure 5-29: RxGOOSE Boolean panel (Edition 2)
Most of the settings are configured by drag-and-drop. However the ID, DEFAULT STATE, and EVENTS settings must be
individually entered when the factory default values are not acceptable.
RxGOOSE Boolean1 ID
Range: 0 to 20 characters
Default: RxG Bool1
This setting allows the user to assign descriptive text to the name of the RxGOOSE Boolean1 FlexLogic operand. The full
operand name is the value of this setting appended with " On". The basic and enhanced front panels display the first 17
characters of this setting plus " On" to fit the 20 character display.
RxGOOSE Boolean1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the RxGOOSE containing the value that drives the RxGOOSE Boolean1 FlexLogic operand. If set to
None, the RxGOOSE Boolean1 FlexLogic operand assumes its default state.
RxGOOSE Boolean1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE Boolean1 FlexLogic operand. A setting of 1
selects the first member, 2 selects the second member, and so on. Entering a number greater than the number of
members in the message and entering the number of a member which does not contain a BOOLEAN results in the
RxGOOSE Boolean1 FlexLogic operand assuming its default state. The Subscribed to column identifies the particular
Boolean subscribed to even if the member is a structure containing more than one Boolean.
RxGOOSE DPS1 ID
Range: 0 to 20 characters
Default: RxG DPS1
This setting allows the user to assign descriptive text to the names of the four RxGOOSE DPS1 FlexLogic operands. The
full operand name is the value of this setting appended with "Interm," "On," "Off," or "Bad." The basic and enhanced front
panels display the first 13 characters of this setting plus the state suffix to fit the 20 character display.
RxGOOSE DPS1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the GOOSE message containing the value that drives the RxGOOSE DPS1 FlexLogic operand. If set to
None, the RxGOOSE DPS1 FlexLogic operand assumes its default state.
RxGOOSE DPS1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE DPS1 FlexLogic operand. A setting of 1 selects
the first member, 2 selects the second member, and so on. Entering a number greater than the number of members in
the message and entering the number of a member that is not a Dbpos results in the RxGOOSE DPS1 FlexLogic operand
assuming its default state. In the case that the member is a structure containing more than one Dbpos, the Subscribed
to column identifies the particular Dbpos subscribed to.
RxGOOSE DSP1 DEFAULT STATE
Range: Intermediate-state, Off, On, Bad-state, Latest
Default: Latest
5 This setting selects the logic state for the data attribute @Master/GGIO3.IndPos01.stVal and the DPS FlexLogic operands
when the UR has just completed start-up and the selected RxGOOSE has not yet received a message, and when the
RxGOOSE has lost its connection with the publisher. When this setting is selected to Latest, the value of @Master/
GGIO3.IndPosψψ.stVal is Intermediate-state when the UR has just completed start-up and the selected RxGOOSE has
not yet received a message, and the latest received value when the RxGOOSE loses its connectivity with the publisher.
RxGOOSE DPS1 EVENTS
Range: Disabled, Enabled
Default: Disabled
This setting selects whether Off to On transitions of the RxGOOSE DPS1 FlexLogic operands are recorded by the event
recorder. If set to Enabled, Off to On transitions are recorded. On to Off transitions are never recorded, even if events are
enabled.
Reports
Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports.
Report settings
Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports > Report Settings.
ReportSettings rptID
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the RptID attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false. The RptID is the name of the report.
ReportSettings optFields
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the OptFlds attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings bufTime
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the BufTm attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings trgOps
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the TrgOps attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings intgPd
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the IntgPd attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
An IEC 61850 Report server is an efficient method to deliver generic substation event information from a single server to a
single client, such as a supervisory control IED. A Configurable Report is a UR element implementing an IEC 61850 Report
server, either of the buffered or unbuffered kind. The following table lists the number of Configurable Report elements.
Each Configurable Report element can report the values of up to 64 FlexLogic or FlexAnalog operands. Buffered report
elements queue value changes that occur while the client is offline and delivered when the client re-connects. Up to 512
events can be queued. Unbuffered control blocks purge all value change events when the connection to the client is lost;
any events that occur while the client is not connected are lost.
Table 5-11: Number of report elements
Number
Buffered reports 30
Unbuffered reports 18
When using IEC 61850 Edition 2, configurable Reports interoperate with any client device of any manufacturer that
conforms to the IEC 61850 edition 1.0 or 2.0 report client requirements.
When using IEC 61850 Edition 1, configurable Reports interoperate with any client device of any manufacturer that
conforms to the IEC 61850 edition 1.0 report client requirements.
The entities whose values are reported by a Configurable Report are known as members. The members are itemized in an
ordered list known as a data set. Each Configurable Report can use any one of the data sets provided that no more than
four data sets are used for reports. This restriction is to limit the amount of processing power that can be allocated to
reporting.
Each enabled Configurable Report transmits an update to its client whenever a value change is detected in one or more of
its members. Also, the control block can be configured to send integrity reports containing the present value of all
members either on demand from the client or periodically. A TCP handshaking mechanism causes messages that are not
5 read and acknowledged by the client to be retransmitted.
For a Configurable Report to operate, its members must be selected (that is, its data set configured) and a client must open
a connection to, configure, and enable its report control block. Control blocks and data sets can be pre-configured by
sending the F35 a CID file. See the UR Family Communications Guide for details. EnerVista UR Setup also can be used to
select the data set members and to pre-configure the control blocks.
Each buffered report has the following settings.
Buffered Report1 RptID
Range for Edition 2: 0 to 129 VisibleString characters
Range for Edition 1: 0 to 65 VisibleString characters
Default: empty string
The name of the report. The entered value sets the RptID value in Buffered Report1 messages, and it can be used by the
client to discriminate Buffered Report1 messages from other messages. If the number of characters entered is zero, the
value used for RptID in messages is an ObjectReference to the report's control block, that is, "<LDName>/
LLN0$BR$"BRCB01".
Buffered Report1 Name
Range: 0 to 32 VisibleString characters
Default: BRCB01
The entered value sets the report control block name value for Buffered Report1.
Buffered Report1 DatSet
Range: None, TT6DataSet1, TT6 DataSet2, …, TT3DataSet01, TT3DataSet02, …
Default: None
This setting selects the data set whose members' status is reported in Buffered Report1 messages using the UR Setup
software designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, as
described later.
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0$" and the data
set name, is used in the datSet field of report messages, and it can be used by the client to discriminate Buffered Report1
messages from other messages.
The performance of the report is determined by the performance of the selected dataset. When the selection is
TT3DataSet01, TT3DataSet02, … it is possible that transient events can be missed.
To configure a DataSet, select it at the top of the window from the drop-down list, for example DataSet02 shown in the
previous figure. In the lower part of the window, drag and drop configuration items to the right side. For example select
the ST Ind001 stVal item and drag it to DataSet Member 1. Dataset members configured here affect other Report or
TxGOOSE control blocks that use the same DataSet.
Buffered Report1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
The entered value sets the confRev value in Buffered Report1 messages, and it can be used by clients to discriminate
report messages of the expected configuration revision from messages of a different revision. The standard requires
that confRev be incremented each time the members or the order of the members is changed, and each time the data
set name is changed. The standard states that the value of 0 is reserved.
Buffered Report1 OptFlds
Range: The check box for each individual bit can be enabled or not (see figure)
Default: All bits enabled/ true
The OptFlds setting is bitstring that controls which of the optional fields are included in report messages. The figure
shows the available option bits. To reduce message size, uncheck any fields that are not needed.
Figure 5-33: Options for buffered report messages (Edition 2)
DataSets
Navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets.
As mentioned in the preceding GOOSE and Reports sections, the members whose values are communicated by these
services are itemized in an ordered list known as a data set. Each UR with the IEC 61850 option has 18 data sets (six fast
and 12 slow). Each data set can contain as many as 64 members. Any data set can be used simultaneously by any number
of TxGOOSE elements and/or by any number of Configurable Report elements. UR Setup software can configure any
FlexLogic operands and any FlexAnalog operands as members.
Figure 5-34: IEC 61850 DataSets (Edition 2) 5
UR Setup software requires data set members to be IEC 61850 data objects or data attributes with Functional Constraint
ST or MX. Certain FlexLogic and FlexAnalog operands have factory-assigned data attributes as tabulated in the UR Family
Communications Guide. All FlexLogic and FlexAnalog operands can be user-assigned to GGIO1 or GGIO4 data attributes,
so that operands without factory-assigned data attributes can still have their values published. See the GGIO1 and GGIO4
sections later for details.
Datasets used by TxGOOSE1, TxGOOSE2, and/or by reports also provide a chatter suppression service for their Boolean
members. Oscillation in a value, also known as chatter, can be caused by errors in logic programming, inadequate
hysteresis (deadband) on a threshold, or a failed station component. Chatter can flood a communications network with
GOOSE messages, degrading response time for all users. If chatter is detected in a Boolean member, TxGOOSE suspends
GOOSE event message triggering and report message triggering from that member for as long as the condition exists, and
for a minimum period of one second. While sending is suspended, a self-test message identifying the specific data item
detected as oscillating is activated.
For a summary of the panels in which the data sets are used, the path is Settings > Product Setup > Communications >
IEC 61850 > DataSets > Summary.
For the settings, navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets > TT6DataSet1 for the
first data set.
Copy and paste functions are available when right-clicking a DataSet. They allow the target dataset to be configured
based on its order code. If some dataset items are not supported, they are not pasted, and a warning message shows a list
of dataset items that were not supported and not pasted. The DataSet name is not copied or pasted. In short, use this
feature to copy a DataSet Member setting and paste it into another Member setting, a text file, or Word, as examples.
Figure 5-35: Member right-click
DataSet01 name
Range: 0 to 32 VisibleString characters
Default: DataSet01
The value entered sets the name of the data set, which is required to be unique within the UR for proper operation. The
value entered sets the name of the data set, which is required to be unique within the UR for proper operation. Fast
datasets start with TT6, and slow datasets start with TT3. Up to six fast datasets are allowed. Up to four fast GOOSE
datasets are allowed.
An ObjectReference to the data set consists of a string that is the concatenation of "<LDName>/LLN0$" and the
DataSet01 name setting value. An ObjectReference to the data set is published in the datSet field of TxGOOSE messages,
and it can be used by subscribers to discriminate the messages of that TxGOOSE from other GOOSE messages. An
ObjectReference to the data set is optionally published in the DatSet field of Report messages. Valid characters are
upper and lowercase letters, digits, and the underscore (_) character. The first character must be a letter.
DataSet01 shared by
Range: 0 to 32 VisibleString characters
Default:
Names of all control blocks that use this DataSet. Read-only field.
DataSet01 Member1
Range: End of List or any instantiated 61850 data object or data attribute with Functional Constraint ST or MX
Default: End of List
This setting specifies the first member in TxGOOSE1 messages. There is a similar setting for each of the up to 64
members that the UR allows in a Dataset. Only values of members before the first set to End of List are published.
Select the member from the drop-down list. Or right-click an entry to copy, paste, delete, or insert.
Product setup
Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup.
Security
This setting applies to IEC 61850 Edition 2.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup > Security.
Figure 5-36: IEC 61850 Security 5
SecGSAL1.SecDataClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model that clients must use to clear security data via commands to
SecGSAL1.SecDataClr. "sbo" here is select-before-operate.
SecGSAL1.OpCntRs ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model that clients must use to clear security data via commands to SecGSAL1.OpCntRs.
"sbo" here is select-before-operate.
Demand
Deadband parameters of measured values related to the Demand metering are configured here.
Energy
Deadband parameters of measured values related to the Energy metering are configured here.
TmClkLTMS1.TmnsDelta.db
Range: 0.000 to 100.000 %
Default: 0.000 %
This setting is a deadband setting and is used by the relay to determine when to update the "mag" and "cVal" values
from the associated "instMag" and "instCVal" values. The value shall represent the percentage of difference between
maximum and minimum in units of 0.001%. The minimum and maximum values for TmnsDelta data object are
-500000000 ns and 500000000 ns respectively and for example, a setting value of 0.002% results in the dead banded
value of (500000000 - (-500000000)) * 0.002 / 100 = 20000 ns. The default setting value of 0.000% does not update the
"mag" and "cVal" values.
Deadband settings
A deadband is a range in which no action occurs, usually expressed as a percentage.
The IEC 61850 panels contain hundreds of deadband settings, such as in the following panels: Product Setup > Real Time
Clock, FlexLogic, Control Elements, and GGIO4. Each panel is not outlined here. The FlexLogic category applies to IEC 61850
Edition 2.
Deadband setting names all end either with "DB" or .db. As they all work the same way, but each on a different analog
value, a single description applicable to all deadband settings is given here. The analog value that each deadband setting
applies is usually obvious from the name of the setting. However, a tabulation of the analog values and their associated
deadband setting can be found in the UR Family Communications Guide.
Figure 5-38: Deadband settings with .db suffix (Edition 2)
GOOSE, buffered report, and unbuffered report messages are for the most part transmitted only when there is a value
change in one or more of their members. Most analog values continuously dither by an amount that is not significant.
Were a report to be sent each time an insignificant analog value change occurred, then the communications network
5
floods with GOOSE and report messages, degrading response time for all users.
To control this, a deadband setting is provided for each analog value. Also, in addition to the present actual value of each
analog ("instMag" in the following figure), there is a deadbanded value ("mag" in the figure), which is updated with the
present value only when the difference between the two exceeds the deadband setting (db in the figure). Changes to this
deadbanded value trigger transmissions when included in GOOSE and report data sets.
Figure 5-39: Deadband settings
Deadband settings are entered in UR Setup software in units of percent of the difference between the "max." and "min." of
the associated analog value. A zero deadband setting suppresses transmission triggering. The range of deadband settings
is 0.000 to 100.000% in steps of 0.001. The default value is 0.000%.
GGIO4 elements have individual settings for "min." and "max." The min. and max. for FlxEIGAPC#.OpSig.db (FLEXELEMENT #
OpSig) are -50 pu and +50 pu respectively. The min. value for all other quantities is 0. The max. values are as follows:
• Phase current — 46 x phase CT primary setting
• Neutral current — 46 x ground CT primary setting
• Ground current (sensitive ground CT) — 4.6 x sensitive ground CT primary setting
• Phase, phase-to-phase, and sequence voltage — 275 x phase VT ratio setting
Signal sources
Deadband parameters of measured values related to the signal sources are configured here.
Breakers
The UR breaker control and status monitoring elements have certain settings that configure how the IEC 61850 protocol
interacts with these elements. These settings are described in this section. See the Breakers section in the System Setup
section of this chapter for details on the operation of breaker control elements.
Navigate to Settings > Communications > IEC 61850 > System Setup > Breakers > Breaker 1 to access the settings that
configure the IEC 61850 protocol interface with the first breaker control and status monitoring element. The settings and
functionality for the others are similar.
5 Figure 5-40: IEC 61850 Breaker panel (Edition 2)
Switches
The UR disconnect switch control and status monitoring elements have certain settings that configure how the IEC 61850
protocol interacts with these elements. These settings are described in this section. See the Settings > System Setup >
Disconnect Switches section later in this chapter for details on the operation of the disconnect switch control elements.
Navigate to Settings > Product Setup > Communications > IEC 61850 > System Setup > Switches > Switch 1 to access
the settings that configure the IEC 61850 protocol interface with the first disconnect switch control and status monitoring
element. The settings and functionality for the others are similar.
Disc0XSWI1.InRef5.setSrcRef OPERAND
Range: any FlexLogic operand
Default: OFF
This setting is used to select a FlexLogic operand that declares to IEC 61850 services that disconnect switch 1 is selected
for local control. While the selected operand is asserted, Disc0XSWI1.Loc.stVal is true and IEC 61850 commands to
DiscCSWI1.Pos and Disc0XSWI1.Pos are not accepted, and a Negative Response (-Rsp) is issued with the REASON CODE
of Blocked-by-switching-hierarchy.
XSWI1 INTERLOCK OPN
5
Range: any FlexLogic operand
Default: ON
This setting is used to select a FlexLogic operand that declares to IEC 61850 services that interlocking conditions are not
acceptable for opening disconnect switch 1. While the selected operand is asserted, the value of DiscCILO.EnaOpn.stVal
is false. If a SelectWithValue or Operate service with ctlVal false and with Check.Interlock-check true is requested of
DiscCSWI1.Pos or Disc0XSWI1.Pos and the selected operand is not activated, a Negative Response (-Rsp) is issued with
the REASON CODE of Blocked-by-interlocking.
XSWI1 INTERLOCK CLS
Range: any FlexLogic operand
Default: ON
This setting is used to select a FlexLogic operand that declares to IEC 61850 services that interlocking conditions are not
acceptable for closing disconnect switch 1. While the selected operand is asserted, the value of DiscCILO.EnaCls.stVal is
false. If a SelectWithValue or Operate service with ctlVal true and with Check.Interlock-check true is requested of
DiscCSWI1.Pos or Disc0XSWI1.Pos and the selected operand is not activated, a Negative Response (-Rsp) is issued with
the REASON CODE of Blocked-by-interlocking.
XSWI1 Pos ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: sbo-with-enhanced-security
This setting selects the control model that clients must use to successfully control the disconnect switch 1 signals
marked Disc0XCBR1.PosOpn.ctlVal and Disc0XCBR1.PosCls.ctlVal on the Disconnect Switch Logic diagram in the Settings
> System Setup section later. These signals force a disconnect switch trip or close control while the operand selected by
setting XSWI1 ST.LOC OPERAND is not active.
"sbo" here is select-before-operate. Enhanced security means that the F35 reports to the client the disconnect switch 1
position the end of the command sequence.
Setting Groups
The UR implements a setting groups element as detailed in the Control Elements > Setting Groups section of this chapter.
The active setting group and the setting group open for edits can be selected via MMS commands SelectActiveSG and
SelectEditSG. The setting related to these IEC 61850 commands are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Control Elements > Setting Groups to access
the setting that configures the IEC 61850 setting group commands.
appear in the software. See the UR Family Communications Guide for MMS and SCL access. Note that if you update the IEC
61850 settings in the EnerVista software by writing to them by MMS while the corresponding IEC 61850 panel is open in
EnerVista, you need to close then open the panel in EnerVista for the correct readings to display.
IEC 61850 protocol configuration settings are accessed through software panels that are selected either in the Online
Window area (see figure) or the Offline Window area in the EnerVista software.
The EnerVista software also includes an interface that is compatible with firmware versions 5.0 to 7.2 to configure
subscribers. Use the Simplified GOOSE Configurator in the Offline Window area.
Figure 5-43: IEC 61850 protocol panel in EnerVista software (Edition 2)
The IEC 61850 window is divided into a navigation pane on the left and a settings panel on the right. You expand and click
an option on the left to display its panel on the right. The following figure shows an example for Server Configuration. The
SETTING column contains the names of the settings, and the PARAMETER column is used to enter the settings. Hovering
the mouse over a setting name displays a tool-tip showing the 61850 information model name of the setting or its location
in SCL files.
Figure 5-44: IEC 61850 panel (Edition 2)
Opening the IEC 61850 window while online causes the UR Setup software to retrieve and import an SCL file from the F35.
This System Configuration Description (SCD) file contains all the settings in the UR at the time of the file request, both those
that are mapped into the IEC 61850 information model (that is, the "public" sections) and those that are not in the model
(that is, the "private" section). The UR EnerVista Setup software imports all of these settings into the current session, not just
those in the IEC 61850 window. To avoid loss of any unsaved setting changes made in other panels during the current
session, all other panels for the F35 must be closed before the IEC 61850 panel can be opened, and the software prompts
for this when applicable. Panels for other devices can be open concurrently to facilitate parameter coordination.
When CyberSentry security is enabled, editable settings depend on the user role logged in. For example, an Administrator
and Engineer can change settings. If prompted for a "Settings password," it means the Administrator or Engineer
password.
The Restore button restores settings in the window to their last saved values. The Default button reverts settings in the
window to factory default values or Oscillography, Data Logger, or FlexLogic Equation Editor pre-configured values. The
Reset button reverts all IEC 61850 settings to the factory default values, not just the current window. (In other settings
windows, the button reverts settings in the window to factory default values.)
When a setting is enabled, its panel continues to read Disabled until relaunched. There is no polling capability to update
automatically the IEC 61850 readings, so the panel needs to be closed then opened for the correct status to display. Good
practice is to close any panel not in use because changes being made by other users too are reflected only upon relaunch
of the panel.
Some of the IEC 61850 settings use floating point data, which guarantees accurate representation of real numbers up to
seven digits. Numbers with more than seven digits are approximated within a certain precision. This can result in
differences between what is entered and what is saved, and for example results in differences shown on a settings
comparison report.
Create CID and settings files
When the Save button is clicked in the online IEC 61850 window, UR Setup software prepares a configured IED description
(CID) file containing all the settings of the UR and sends the CID file to the F35. Upon receipt, the F35 checks the CID file for
5
correctness, going out of service, then back into service when the CID file is accepted. The software displays a message
when the F35 is running the new settings, confirming successful transfer. This process can take a minute or so due to the
amount of processing required by the software and the F35.
When the Save button is clicked in the offline IEC 61850 window, UR Setup software saves to local storage, for example the
hard drive, a .urs file containing all settings of the UR.
Server configuration
The Server Configuration panel contains IEC 61850 settings relevant to the server functions of the IED implementation.
The path is Settings > Product Setup > Communications > IEC 61850 > Server Configuration.
The following settings are available, where <iedName> is a syntactic variable representing the present value of the IED
NAME setting.
5 IED NAME
Range: 1 to 58 VisibleString characters
Default: TEMPLATE
The value entered sets the IED name used by IEC 61850 for the F35. An IED name unique within the network must be
entered for proper operation. Valid characters are upper and lowercase letters, digits, and the underscore (_) character.
The first character must be a letter.
The IED NAME and the Product LD inst name comprise the <LDName> for a product. The longest LD inst are "Master"
and "System" at six characters, with Master being fixed and the others configurable with the configurable Logical device
feature. So the IED NAME needs to be restricted to 58 characters to meet a 64 character limit.
Access Point
Range: S1, S2, S3
Default: S1
This setting applies to IEC 61850 Edition 1. It is the subnetwork.
Location
Range: 0 to 255 ASCII characters
Default: Location
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.location. This data attribute is
provided by the protocol to allow the user to declare where the equipment is installed.
Latitude
Range: -90.000 to 90.000 degrees in steps of 0.001 degree
Default: 0.000 deg
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.latitude. This data attribute is provided
by the protocol to declare the geographical position of the device in WGS84 coordinates -latitude. Negative values
indicate a southern latitude. WGS refers to the world geodetic system, which is used in global positioning systems (GPS),
and 84 is the current version of the standard.
Longitude
Range: -180.000 to 180.000 degrees in steps of 0.001 degree
Default: 0.000 deg
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.longitude. This data attribute is
provided by the protocol to declare the geographical position of the device in WGS84 coordinates -longitude. Negative
values indicate a western longitude.
Altitude
Range: 0 to 10,0000 m in steps of 1 m
Default: 0 m
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.altitude. This data attribute is provided
by the protocol to declare the geographical position of the device in WGS84 coordinates - altitude.
Prefix for GGIO1
Range for Edition 2: 0 to 11 VisibleString characters
Range for Edition 1: 0 to 6 VisibleString characters
Default:
This setting sets the LN Prefix of the FlexLogic operand interface logical node GGIO1 that is described in the GGIO1
section later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first
character must be a letter. UR Setup software does not allow entry of a prefix that duplicates any other GGIO1 prefix
that is used by the product, such as ConIn and ConOut.
Prefix for GGIO2
Range for Edition 2: 0 to 11 VisibleString characters
Range for Edition 1: 0 to 6 VisibleString characters
Default:
This setting sets the LN Prefix of the Virtual Inputs Interface logical node GGIO2 that is described in the GGIO2 section
5
later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first character must
be a letter. UR Setup software does not allow entry of a prefix that duplicates any other GGIO2 prefix that is used by the
product.
Prefix for GGIO4
Range for Edition 2: 0 to 11 VisibleString characters
Range for Edition 1: 0 to 6 VisibleString characters
Default:
This setting sets the LN Prefix of the FlexAnalog operand interface logical node GGIO4 that is described in the GGIO4
section later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first
character must be a letter. UR Setup software does not allow entry of a prefix that duplicates any other GGIO4 prefix
that is used by the product.
LLN0.Mod.ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: sbo-with-normal-security
This setting specifies the control service that clients must use to control the TEST MODE FUNCTION of the F35. An "on"
control to <LDName>/LLN0.Mod changes TEST MODE FUNCTION to Disabled, an "on-blocked" control changes it to
Forcible, and a "test/blocked" changes it to Isolated.
Configuration Type
Range: G2, E3-2.0
Default: G2
This setting is read only. It specifies the method used to describe GOOSE subscription configuration in SCL. See the UR
Family Communications Guide for details. In the G2 mode, the CID file contains IED elements for IEDs subscribed to by
this IED containing GOOSE subscription information. In the E3 2.0 mode, the CID file has only one IED element and
GOOSE subscription information is coded in data objects in the standard LGOS logical node used to monitor reception of
the subscribed GOOSE. UR 7.30 or later accepts either mode. The set value is for the entire EnerVista installation and is
preserved between sessions. To change this global field, click File > Preferences and access the IEC 61850 panel; you do
not need to be connected to the device.
Logical devices
The Logical Devices panel contains IEC 61850 settings relevant to the configurable logical devices feature, wherein logical
device naming can be reconfigured and logical nodes re-assigned.
The path is Settings > Product Setup > Communications > IEC 61850 > Logical Devices.
Figure 5-46: Default IEC 61850 Logical Devices panel with devices middle and nodes right (Edition 2)
5
To configure logical devices and nodes:
1. Right-click an entry and edit an existing device, add a new one, or move a logical node. The rest of this section
explains the window and how to perform these actions.
The Logical Devices panel has middle and right panes. The middle pane has a list of the instantiated logical devices in the
sequence that they appear in SCL, with one device selected. The right pane has a list of the logical nodes presently
assigned to the selected logical device in lexicographic order by logical node name.
In the middle pane logical devices are shown with their product-related name, followed in brackets by their function-
related ldName, and followed by the value of their confRev. In the following example, by right-clicking and editing, the
Protection logical device has been set to instance name "Prot", the function-related name "Feeder1Prot" and the
configuration revision "2016-03-07 08:46." The text is clipped on the right if the line is longer than the available width. The
next paragraphs explain how to do this setup.
Figure 5-47: Protection logical node selected
5
Right-clicking a logical device displays the menu that allows insertion of a new logical device immediately below the
selected one, deletion of the selected logical device, or editing the selected logical device's parameters. The insert option is
disabled and greyed-out if there are already 16 logical devices instantiated. The delete option is disabled and greyed-out if
the selected logical device is Master or it contains any logical nodes other than LLN0.
Figure 5-48: Menu for logical node
If the insert option is selected, or the edit option is selected for other than the Master logical device, a logical device
parameters edit dialog opens.
If the edit option is selected for the Master logical device, the Product LD inst name setting is not editable.
Figure 5-50: Edit logical node
When the Ok button is clicked, the entered values for Product LD inst name and Functional ldName are checked for
uniqueness within the UR, and they are updated in the pane.
The settings are explained as follows, where <iedName> is a syntactic variable representing the present value of the IED
NAME setting. When adding or editing a logical device entry, these are the fields that need to be completed.
IED name and the logical device inst name must form an LDName that is unique within the network for proper operation.
It is recommended that the length of the IED NAME plus the length of this setting be not greater than 64 to respect the
requirements of IEC 61850 7 2:2010 22.2 for LDName.
The factory default configuration is for six logical devices with Product LD inst name settings and logical node
assignments as per the following table.
Table 5-12: Factory default logical nodes
Default logical Contains logical nodes modeling...
device inst name
Master communications, including GOOSE, reports, Remote I/O, Virtual Inputs, Modbus, DNP, and so on.
(root logical device; Setting group control.
name is fixed) This is the root logical device.
To comply with IEC 61850 7 1 Ed2 clause 6.4.5.1, all group L logical nodes (logical nodes with class names
begin with "L"), except LLN0, belonging to this IED are in this logical device.
Protection (Prot) protection functions
Control (Ctrl) control and monitoring functions
System power system devices: breakers, switches, CTs, VTs, and so on, including interface to these such as AC inputs,
contact I/O, transducer I/O, HardFiber I/O
Metering (Meter) metering and measurement, including Signal Sources
General (Gen) FlexLogic, virtual outputs, non-volatile latches, FlexElements, FlexMath, recording (for example oscillography),
security, front panel, clock
Functional ldName
Range: 0 to 64 VisibleString characters
Default: empty string
Each logical device has this setting. The value is configurable in all logical devices. Valid characters are upper and
lowercase letters, digits, and the underscore (_) character. If the number of characters entered is greater than zero, the
5
setting sets the value of the function-related name used in communications. If an ldName is entered, it must form an
LDName that is unique within the network for proper operation. The standard recommends choosing this name
according to IEC 81346-1. If the number of characters entered is zero, no function-related name is defined.
Throughout the remainder of this IEC 61850 section, <LDName> is a syntactic variable representing the present
LDName of the master logical device. In other contexts LDName can refer to some other logical device. Depending
on its context, <LDName> can be a product-related name or a function-related name.
configRev
Range: 0 to 255 ASCII characters
Default:
This data attribute is provided by the protocol to declare changes to the semantic of the data model of the UR. The intent
is that the user changes Master configRev each time that the semantic or data model changes, so that clients can
readily detect the change. A semantic change is a logical node getting a new semantic use; for example, an instance of
logical node CSWI is now serving a different physical switch, or an instance of a logical node PDIS is now used for
another zone. A data model change is a change in the presence of logical nodes, data objects, data attributes, or
instance names.
The scope of Maser configRev is the entire relay configuration, as the Master logical device is the root logical device.
Similar settings are provided for the other logical nodes; the scope of these other configRev settings is limited to the
corresponding logical device configuration.
paramRev
Range: -2,147,483,648 to 2,147,483,647
Default: 0
The configurable data attribute paramRev has a scope that includes the entire device, and thus is modified whenever
any setting in the device changes. The UR increments the value of paramRev by one whenever one or multiple setting
changes occurs in one Modbus write request by any means (front panel, Modbus, or MMS) other than by SCL file
download. Incrementing occurs whether or not the setting is represented in the information model. When a UR device or
EnerVista UR Setup accepts an SCL file, paramRev is set to the value in that SCL file. When EnerVista UR Setup changes
one or more settings, and prepares an SCL file, it increments paramRev to the next higher multiple of 10 000.
Each logical device has a name: LDName. (Note the upper case LD.) LDName has both a product-related form and
a function-related form as per IEC 61850 6:2009 8.5.3.
SCL files invariably use the product-related form of LDName. The product-related form is the concatenation of the
IED name of the device and the individual logical device's inst name. The IED name is the value of the "IED NAME"
setting on the Server Configuration panel, and the logical device inst names are each the value of the
corresponding "Product LD inst name" setting here. The "Product LD inst name" of the first logical device is fixed at
"Master".
Communications use the function-related form of LDName if a function-related name is defined, otherwise
communications use the product-related name. The function-related name is the value of the corresponding
"Functional ldName" setting if this setting is not empty, if empty the function-related name is not defined.
In SCL, the function-related name is specified by the LDevice element attribute ldName (note the lower case ld).
Absence of this attribute indicates the function-related name is not defined. In SCL the product-related name is
specified by the name attribute of the IED element and the inst attribute of the LDevice element.
In the right pane, logical nodes assigned permanently to the Master logical device and LLN0 in all logical devices are
greyed-out as shown earlier. These are not movable. Any other logical node can be dragged to any of the logical devices in
the middle pane, which causes that logical device to be re-assigned to that logical device. Right-clicking a logical node
device displays a menu that lists the logical devices that this logical node can be moved to. Clicking one of these re-assigns
the logical node. Other common keyboard and/or mouse action can be used to select one or more logical nodes and move
the selected nodes together.
GOOSE
The path is Settings > Product Setup > Communications > IEC 61850 > GOOSE.
• A v7.4 device cannot send an R-GOOSE message to non-R-GOOSE devices, such as v7.3 or v5.9 UR device
• UR devices with firmware below v7.3 can send a GOOSE message to a v7.4 device that has GOOSE as the active
protocol
R-GOOSE is available through the IEC 61850 software option. If R-GOOSE security is required, the CyberSentry
software option also must be purchased.
TxGOOSE
IEC 61850 GOOSE is an efficient method for simultaneous high-speed delivery of generic substation event information by a
publishing device to more than one subscribing device. A TxGOOSE is a UR element implementing a single IEC 61850
GOOSE message publishing service. The subscribing function in URs is performed by RxGOOSE elements, as described in
the next section. Each UR with IEC 61850 order code options has 16 TxGOOSE elements. Each TxGOOSE can either use the
original format specified in IEC 61850 8 1:2011 or the routable GOOSE (R-GOOSE; IEC 61850 Edition 2) format specified in
IEC TR 61850-90-5:2012. Each TxGOOSE element can publish the values of up to 64 attributes of the IEC 61850 nodes in the
UR.
Published TxGOOSE messages configured in the EnerVista UR Setup software can be subscribed by and the published
operand values understood by other UR devices. Furthermore, they can be subscribed to and understood by any device of
any manufacturer that implements the IEC 61850 edition 1.0 or 2.0 GOOSE subscription mechanism. The messages are
published with a multicast address so that the network sends the messages to all devices; any number of devices that
want to subscribe can.
For wide area protection, control, and monitoring schemes, R-GOOSE wraps the proven original format GOOSE in IP/UDP to
multicast (or unicast) the data over a Wide Area Network (WAN). Sample applications are Wide area Remedial Action
Scheme (RAS) and Under Voltage/ Frequency Load Shedding Schemes (UVLS/UFLS). R GOOSE uses IGMPv3 (Internet Group 5
Management Protocol version-3, RFC 3376) for multicasting.
The entities whose values are published in GOOSE messages are known as members. The members are itemized in an
ordered list known as a data set. Each TxGOOSE can use any one of the configured data sets. (See the DataSets section
later for details.) The performance of a TxGOOSE is determined by its dataset. Booleans in fast GOOSE datasets are
designed for the TT6 transfer time class (3 ms), while Booleans in the Normal datasets are designed for the TT3 class (100
ms). Due to the significant amount of CPU time required to compose a TT6 TxGOOSE message and the limited amount of
time allowed by the TT6 class, at most four of these can be configured in a given UR. So only four fast GOOSE are allowed
to be configured, and the UR software has a check to disallow the use of more than four fast datasets in GOOSE. If six fast
datasets are configured outside of UR software and the file sent directly to the relay, the relay rejects the file. The design
does allow six fast datasets to be used in report control blocks, which allows fast scanned data in reports.
Each enabled TxGOOSE transmits its message whenever a value change is detected in one or more of its members. If the
changed value is a Boolean in a fast dataset, then the change detect occurs in the TT6 detection time of 3 ms or less. If the
member is an analog value in a fast dataset, the change detect occurs in theTT3 time of 100 ms. In Normal GOOSE
Datasets, change detection for all dataset members occurs in the TT3 time of 100 ms. To guard against the possibility that
such a message is lost in the network before it reaches all subscribers, the message is quickly retransmitted several times.
To allow subscribers to verify that their link to the publisher and the publisher itself are healthy, each message is also
retransmitted periodically even while the values are unchanging. These latter messages are known as heartbeat
messages, while the former are known as event messages. Heartbeat messages also provide means for a subscriber
newly online to receive the published values in the absence of an event.
The details of TxGOOSE message construction are contained in the UR Family Communications Guide. Knowledge of these
details is not required to configure GOOSE.
The UR does not implement the Fixed-Length encoded GOOSE messages option specified in IEC 61850-8-1:2011 clause
A.3; the UR always uses the ASN.1 Basic encoding rules (as specified in ISO/IEC 8825-1) as specified in IEC 61850 edition 1.0
and as optional in IEC 61850 edition 2.0.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > TxGOOSE > TxGOOSE1 to access the
settings for the first TxGOOSE. The settings and functionality for the others are similar.
5
A data set needs to be set up and selected in the TxGOOSEx DatSet field for all content to display.
When saving changes, when a "dataset member is empty" message displays, you need to set the member in the bottom
right of the window.
TxGOOSE1 MODE
Range for Edition 2: Disabled, GOOSE, R-GOOSE
Range for Edition 1: Disabled, GOOSE
Default: Disabled
When set to Disabled, TxGOOSE1 messages are not published. When set to GOOSE, TxGOOSE1 messages are published
in IEC 61850 8 1:2011 GOOSE format. When set to R-GOOSE, TxGOOSE1 messages are published in Routable GOOSE
format according to IEC 61850 90-5, and the TxGOOSE1 DST MAC address is set to 00 00 00 00 00 00 and cannot be
changed.
TxGOOSE1 GoCB name
Range: 0 up to 32 VisibleString characters
Default: GoCB01
The entered value sets the GOOSE control block (GoCB) name value for TxGOOSE1.
An ObjectReference to the control block, which consists of the concatenation of the string "<LDName>/LLN0." and the
control block name, is published in the gocbRef field of TxGOOSE1 messages and is used by subscribers to discriminate
TxGOOSE1 messages from other GOOSE messages. <LDName> is a syntactic variable that is set to the value of setting
Master functional ldName if one or more characters have been entered to that setting, otherwise the value of setting IED
NAME suffixed with "Master".
TxGOOSE1 GoID
Range for Edition 2: 0 to 129 VisibleString characters
Range for Edition 1: 0 to 65 VisibleString characters
Default: TxGOOSE1
The entered value sets the goID value published in TxGOOSE1 messages, and can be used by subscribers to discriminate
the TxGOOSE1 messages from other GOOSE messages. Special characters are not allowed, such as <, >, &, ’, and ".
TxGOOSE1 DatSet
Range: None, TT6DataSet1,TT6 DataSet2, … TT3DataSet01,TT3 DataSet02, …
Default: None
This setting selects the published data set using the UR Setup software designator for the data set. If None is selected,
no TxGOOSE1 messages are sent.
The IEC 61850 name of the data sets are configured in the Datasets panel, as described later.
Some datasets are designed for the TT6 transfer time class (3 ms), while others are designed for the TT3 class (100 ms).
The performance of a TxGOOSE is determined by its dataset. Use TT6 datasets for trips and blocking applications, TT3
datasets for slow automatic interactions. The 61850 name of the datasets are configured in the Datasets panel.
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0." and the data
set name, is published in the datSet field of TxGOOSE1 messages and can be used by subscribers to discriminate
TxGOOSE1 messages from other GOOSE messages. <LDName> is a syntactic variable that is set to the value of setting
Master functional ldName if one or more characters have been entered to that setting, otherwise the value of setting IED
NAME suffixed with "Master".
To configure a DataSet, select it at the top of the window from the drop-down list. In the lower part of the window, drag
and drop configuration items to the right side. Dataset members configured here affect other Report or TxGOOSE
control blocks that use the same DataSet.
The performance of the TxGOOSE is determined by the performance of the selected dataset. When the selection is 5
TT3DataSet01, TT3DataSet02, … it is possible that transient events can be missed.
TxGOOSE1 DST MAC
Range: any 12 digit hexadecimal number
Default: 01-0C-CD-01-00-00
When the TxGOOSE1 MODE setting is R-GOOSE, the TxGOOSE1 DST MAC address is set to 00 00 00 00 00 00 and cannot be
changed. Otherwise, the value entered here sets the Ethernet destination Media Access Control (MAC) address in
published TxGOOSE1 messages. As the standard requires that the address have the multicast bit set TRUE, that is to say
the second digit is set to an odd number, messages transmitted have the multicast bit set TRUE no matter its value in
this setting.
The destination MAC address can be used by the network to restrict message delivery to selected devices that need to
receive them, reducing network load. This address also can be used by hardware in receiving devices to filter out
messages that are of no interest to them, reducing processor burden. Different filtering algorithms are implemented by
different devices. The standard recommends that the algorithm used by hardware of the receiving device be considered
when assigning destination multicast addresses.
Subscribers can use this address to discriminate TxGOOSE1 messages from other GOOSE messages.
TxGOOSE1 VLAN PRIORITY
Range: 0, 1, 2, 3, 4, 5, 6, 7, 5-4, 6-4, 6-5, 7-4, 7-5, 7-6
Default: 4
When the value entered is 0, 1, 2, 3, 4, 5, 6, or 7, the User Priority value in the IEEE 802.1Q VLAN tag included in published
TxGOOSE1 messages is set to that value. When one of the two-digit values is entered, the dynamic priority feature is
selected: the first event message has the User Priority value of the first digit, and User Priority is decremented in each
following message until reaching the value of the second digit. For instance, if the selected value is 7-5, then the User
Priority values in successive messages beginning with the message triggered by an event is 7, 6, 5, 5, 5, 5, 5, and so on.
Do not make a dynamic priority selection when standard behavior is required.
Network devices can forward a message with a higher priority value before a message with a lower priority value, which
speeds delivery of high-priority messages in heavily loaded networks. The standard recommends that higher-priority
messages, such as GOOSE, have priority values in the range of 4 to 7.
TxGOOSE1 VLAN ID
Range: 0 to 4095 in steps of 1
Default: 0
The value entered sets the VID value in the IEEE 802.1Q VLAN tag included in published TxGOOSE1 messages. VID can be
used by network devices to direct messages to only selected devices, reducing network burden. VID values of 0 and 1
are assigned by IEEE 802.1Q to other functions and are not to be used for GOOSE.
TxGOOSE1 ETYPE APPID
Range: 0 to 65535 in steps of 1
Default: 0
The value entered sets the APPID value in published GOOSE messages and can be used by subscribers to discriminate
TxGOOSE1 messages from other GOOSE messages.
The standard reserves the value range 0 to 16383 for GOOSE Type 1 (Fast messages), and reserves the value range
32768 to 41151 for GOOSE Type 1A (Trip messages). Some subscribers can process messages in the Type 1A range
faster than messages in the Type 1 range. The standard reserves the default value (0) to indicate lack of configuration.
The standard strongly recommends unique, source-orientated APPIDs within a given system.
TxGOOSE1 CONFREV
Range: 0 to 4294967295 in steps of 1
Default: 1
The entered value sets the confRev value in published GOOSE messages and can be used by subscribers to discriminate
TxGOOSE messages of the expected configuration revision from messages of a different revision. The standard requires
that CONFREV be incremented each time the members or the order of the members published is changed. The standard
states that the value of 0 is reserved.
This setting specifies the Ethernet ports for transmission of TxGOOSE1. When set to disabled, TxGOOSE1 messages are
not transmitted on any port no matter the state of GoEna. When set to Port-1, TxGOOSE1 is published over Ethernet
Port-1 only; while selecting Ports-1, 3 option, the same TxGOOSE1 is published to both Ports 1 and 3; and similarly if set
to Ports-1, 2, 3, all ports publish TxGOOSE1.
When setting PRT2 REDUNDANCY to Failover or to PRP, the TxGOOSE 1 port assignment needs to be set to ports 2
and 3 (Ports-2,3).
Also, Port 3 configuration in the CID file is ignored. The Port 3 ConnectedAP elements has no meaning, as ports 2
and 3 use the port 2 MAC address, IP address, and mask.
R-TxGOOSE1 IP CLASS
Range: 0 to 256 in steps of 1
Default: 46
This setting applies to IEC 61850 Edition 2.
When the TxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. Otherwise this setting
selects the IPv4 Differentiated Services Code Point-DSCP (formerly called TypeOfService-TOS) value. This value provides
priority routing, when supported in the routers. The default value is for Expedited Forwarding (101110B, 46 or 2EH).
R-TxGOOSE1 DST IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 224.0.0.0
This setting applies to IEC 61850 Edition 2.
When the TxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. Otherwise this setting
specifies destination IP address for the R-TXGOOSE1 that is entered in Standard IPV4 address format. The destination IP
address needs to be a valid multicast or unicast IP address. The value specified in this setting is mapped to IPv4 header
32 bit field for Destination IP Address while publishing R-GOOSE1. 5
The default IP address 224.0.0.0 is reserved, and hence not a valid multicast IP address.
The source IP address is that of the UR port from which the R-GOOSE messages are transmitted.
R-TxGOOSE1 SECURITY
Range: None, Signature, SignatureAndEncryption
Default: None
This setting applies to IEC 61850 Edition 2.
This setting specifies level of security (authentication/encryption) used for TxGOOSE1. None specifies no security
mechanisms are to be used. Signature specifies only signature (no encryption) is to be used. SignatureAndEncryption
specifies that both signature and encryption are to be used.
RxGOOSE
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages.
IEC 61850, GOOSE is an efficient method for simultaneous high-speed delivery of the same generic substation event
information by a publishing device to more than one subscribing device. An RxGOOSE is a UR element implementing a
single IEC 61850 GOOSE message subscribing service. The publishing function in URs is performed by TxGOOSE elements,
as described in the previous section.
Each UR with the IEC 61850 order code option has 64 RxGOOSE elements. Each RxGOOSE element can subscribe to GOOSE
messages from a specified publisher. Each RxGOOSE can either use the original format specified in IEC 61850 8 1:2011 or
the routable GOOSE (R-GOOSE; IEC 61850 Edition 2) format specified in IEC TR 61850-90-5:2012. Subscribed message
members can be DataObjects, SubDataObjects, DataAttributes or SubAttributes. In E2-2.0 mode members are restricted to
basic types BOOLEAN, FLOAT32, INT32, Dbpos, TimeStamp or Quality. Each subscribed message can contain up to 64
values. A member can be a structure containing several values; note that it is the number of values rather than the number
of members that are limited to 64.
GOOSE messages from any device of any manufacturer that implements the IEC 61850 Edition 1.0 or 2.0 GOOSE publish
service or the 61850-90-5 R-GOOSE service (IEC 61850 Edition 2) can be subscribed to. The UR accepts both the variable
length encoded GOOSE messages specified IEC 61850 8 1:2004 and the Fixed-Length encoded GOOSE messages as
specified in IEC 61850 8 1:2011 clause A.3.
Each enabled RxGOOSE monitors for interruption of the GOOSE messages it subscribes to based on the value in the
timeAllowedtoLive field of the last message received. If a new message is not received within that time interval, the
RxGOOSE assumes that connectivity is lost. FlexLogic operands (for example RxGOOSE1 On, RxGOOSE1 Off) reflect the
status of each RxGOOSE connectivity. An RxGOOSE connection is also considered lost after the UR finishes restart until a
message is received. While any RxGOOSE connectivity is lost, a common RxGOOSE Fail self-test is activated.
Messages that contain the value true in the ndsCom field are never accepted. Messages that contain the value true in the
simulation field (test field in edition 1.0 messages) are accepted only when the UR Test Mode Function setting is set to
Forcible or Isolated.
RxGOOSE messages can be received through any UR Ethernet port.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages >
RxGOOSE1 to access the settings that specify the messages to be accepted by the first RxGOOSE element. The settings
and functionality for the other RxGOOSE are similar. The following settings are available. They allow RxGOOSE1 to
recognize the GOOSE messages it is to accept. Most of these settings are automatically configured by UR Setup software
when an association to an RxGOOSE Boolean Input, RxGOOSE DPS Input, and/or RxGOOSE Analog Input is made as
described in the sections following this. For IEC 61850 Edition 2, settings R-RxGOOSE1 RECEPTION MODE, R-RxGOOSE1
SECURITY, and R-RxGOOSE SRC IP need to be manually completed as the information is not contained in publisher SCL.
Figure 5-53: IEC 61850 RxGOOSE Messages panel (Edition 2)
RxGOOSE1 MODE
Range for Edition 2: GOOSE, R-GOOSE
Range for Edition 1: GOOSE
Default: GOOSE
When set to GOOSE, TxGOOSE1 messages are published in IEC 61850 8 1:2011 GOOSE format. When set to R-GOOSE,
TxGOOSE1 messages are published in Routable GOOSE format according to IEC 61850 90-5. When set to R-GOOSE, the
R-RxGOOSE DST IP needs to be a valid multicast or unicast IP address.
RxGOOSE1 goID
Range: 0 to 129 VisibleString characters
Default: empty string
If the entered value has one or more characters, the goID field of incoming GOOSE messages must exactly match this
value for the message to be accepted as a valid RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1
does not check the value received in the goID field. Special characters are not allowed, such as <, >, &, ’, and ".
If the publisher is a UR 7.3x series device, this setting needs match the value of the publisher's TxGOOSE GoID setting.
RxGOOSE1 Dst MAC
Range: any 12 digit hexadecimal number
Default: 01-0C-CD-01-00-00
When the RxGOOSE1 MODE setting is R-GOOSE, the value of this setting is not used, the destination Media Access
Control (MAC) address for RxGOOSE1 messages is calculated based on the RxGOOSE DST IP address. Otherwise, set this
setting to the MAC address of the publisher. Only received GOOSE messages having a MAC address equal to this value
are accepted as valid RxGOOSE1 messages. An entered address of zero disables RxGOOSE1.
If the publisher is a UR series 7.3x device, the setting needs to match the value of the publisher’s TxGOOSE DST MAC
setting.
RxGOOSE1 ETYPE APPID
Range: 0 to 65535 in steps of 1
Default: 0
If the value entered is non-zero, the APPID field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the value entered is zero, RxGOOSE1 does not check the value
received in the APPID field.
If the publisher is a UR series 7.3x device, the setting needs to match the value of the publisher’s TxGOOSE ETYPE APPID
setting. 5
RxGOOSE1 GoCBRef
Range: 0 to 129 alphanumeric, underscore, slash and period characters, beginning with an alpha character
The gocbRef field of incoming GOOSE messages must match this value for the message to be accepted as a valid
RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1 is disabled. If not the empty string, the entry
needs to be an ACSI ObjectReference to the publishing control block in the format:
<LDName>/LLN0.<GoCBName>
where <LDName> is the function-related name if the logical device containing the publishing control block has "ldName"
configured, otherwise the product-related name of that logical device, and <GoCBName> is the name of the publishing
control block.
The F35 translates the ACSI format required for this setting to the MMS format used in GOOSE messages:
<LDName>/LLN0$GO$<GoCBName>
If the publisher is a UR 7.3x or 7.40 series device, <LDName> is the value of the publisher's Master functional ldName
setting if that setting is not empty, otherwise it is the value of the publisher's IED NAME suffixed with "Master". If the
publisher is a UR 7.3x series device, <GoCBName> is "GoCB" suffixed with the two digit TxGOOSE instance number, for
example "GoCB01". If the publisher is a UR 7.40 series device, <GoCBName> is as specified earlier in the TxGOOSE
section of this chapter.
RxGOOSE1 datSet
Range: 0 to 32 alphanumeric and underscore characters, beginning with an alpha character
Default: empty string
If the entered value has one or more characters, the datSet field of incoming GOOSE messages must exactly match this
value prefixed by <LDName>/LLN0$ for the message to be accepted as a valid RxGOOSE1 message. <LDName> is as
specified in the RxGOOSE GoCBRef setting above. If the entered value is the empty string, RxGOOSE1 does not check the
value received in the datSet field.
If the publisher is a UR 7.3x series device, set this setting to the value of the publisher's DataSetxx name setting, where xx
is the instance number of the data set selected by the publisher's TxGOOSE datSet setting. If the publisher is a UR 7.40
series device, datSet is as specified in the DataSets section of this chapter.
RxGOOSE1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
If the value entered is non-zero, the confRev field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the entered value is zero, RxGOOSE1 does not check the value
received in the confRev field.
If the publisher is a UR 7.3x series device, set this setting to match the value of the publisher's TxGOOSE ConfRev setting.
R-RxGOOSE1 RECEPTION MODE
Range: SSM, ASM, Unicast
Default: SSM
This setting applies to IEC 61850 Edition 2.
When the RxGOOSE1 MODE setting is other than R-GOOSE the value of this setting is not used. Otherwise it selects the
R-GOOSE reception mode.
R-RxGOOSE RECEPTION MODE specifies the R-RxGOOSE DST IP range. When set to SSM, R-RxGOOSE DST IP must be in
the range of 232.0.0.1 to 232.255.255.255. When set to ASM, R-RxGOOSE DST IP must be in the range of 224.0.0.1 to
239.255.255.255, excluding the SSM range. Note that the SSM range is inside the ASM range and therefore the ASM use
excludes the SSM range. The default destination IP address 224.0.0.0 is reserved, and hence not a valid multicast IP
address.
The reception modes are related to Layer-3 R-GOOSE reception from routers/WAN. The subscription to multicasting of R-
GOOSE is supported using IGMP Protocol Independent Multicast (PIM). It is made available in either Source Specific
Multicast (SSM) mode or Any Source Multicast (ASM) mode. Unicast (over UDP) mode can also be used. In case of
multicasting (IGMPv3 based SSM or ASM), the R-GOOSE subscriber device requests the Last Hop Router (LHR) to
subscribe to a specific multicasting group.
5 If the publisher is using a unicast destination IP address for this R-GOOSE, then set R-RxGOOSE1 RECEPTION MODE to
Unicast. Otherwise set R-RxGOOSE1 RECEPTION MODE to the SSM or ASM mode used by the local routers/firewalls.
R-RxGOOSE1 SRC IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 127.0.0.1
This setting applies to IEC 61850 Edition 2.
When the RxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. When the RxGOOSE1
MODE setting is R-GOOSE and the R-RxGOOSE RECEPTION MODE setting is ASM, the value of this setting is not used.
Otherwise the Source IP Address field of incoming R-GOOSE messages must exactly match this value for the message to
be accepted as a valid RxGOOSE1 message. Set this setting to the value of the source IP address used by the publisher.
For UR publishers, this value is in setting PRT# IP ADDRESS.
The UR does not validate the address entered. The default IP address 127.0.0.1 is a reserved, not a valid IP address. Enter
a valid IP source address.
R-RxGOOSE1 DST IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 224.0.0.0
This setting applies to IEC 61850 Edition 2.
When the RxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. Otherwise the
Destination IP Address field of incoming R GOOSE messages must exactly match this value for the message to be
accepted as a valid RxGOOSE1 message. Set this setting to the same value as the R-GOOSE publisher's Destination IP
Address. For UR publishers, this value is in setting R-TxGOOSE# DST IP.
The destination IP address needs to be a valid multicast or unicast IP address. The UR does not validate the address
entered. The default IP address 224.0.0.0 is reserved, and hence not a valid multicast IP address.
R-RxGOOSE1 SECURITY
Range: None, Signature, SignatureAndEncryption
Default: None
This setting applies to IEC 61850 Edition 2.
This setting specifies the level of security (authentication/encryption) used for RxGOOSE1. None indicates no security
mechanisms are in use. Signature indicates only signature (no encryption) is in use. SignatureAndEncryption indicates
that both signature and encryption are in use. Normally this setting is set to match the GOOSE publisher's security
method.
RxGOOSE1 Member 1
Range: End of List, BOOLEAN, FLOAT32, INT32, Dbpos (DPS), Quality, TimeStamp, Struct
Default: End of List
This setting specifies the type that the first member of incoming GOOSE messages must be for the message to be
accepted as a valid RxGOOSE1 message. There are similar settings for each of the up to 64 members that the UR is able
to subscribe to in a given GOOSE message. The member before the first member setting set to "End of List" must be the
last member of the message for the message to be accepted as a valid RxGOOSE1 message.
If the publisher is a UR 7.3x or 7.40 series device, set these settings to match the basic type of the members of the
publisher's data set selected by the publisher's TxGOOSE datSet setting.
If the publisher dataset includes members with structured data, that is, data attributes, sub-data objects, and/or data
attributes with sub-data attributes, configuration must use one of the new 7.40 UR Setup RxGOOSE Inputs pages. In this
case the Member setting displays as the product-related name used by the publishing IED of the data object or data
attribute, in standard SCSM format (e.g. Publisher1LD1/LLN0$ST$Off$stVal).
Note that a dataset can hold at most 64 basic data attribute values, and that a single structured data object or attribute
can contain multiple basic data attribute values. UR Setup software does not allow more that 64 basic data attribute
values to be entered, in which case the last several members settings cannot be changed from End of List.
Note that the publisher's name alone does not contain all the information required for subscription, additional publisher
information model information is stored elsewhere. For this reason, manual entry of the name is not supported.
RxGOOSE inputs
5
The values received by RxGOOSE elements need to be converted to FlexLogic or FlexAnalog operands so that they can be
used by other UR elements. This conversion is done by RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements.
Each RxGOOSE Boolean can convert the value of a specified Boolean value received by a specified RxGOOSE to a FlexLogic
operand. Each RxGOOSE DPS can convert the value of a specified Dbpos (Double bit position) value to four FlexLogic
operands, one for each of the four possible Dbpos states. Each RxGOOSE Analog can convert the value of a specified
FLOAT32 member to a FlexAnalog operand. Each of these operands reverts to its default state when the RxGOOSE
connectivity is lost. Other types of values can be present in subscribed GOOSE messages, but cannot be converted to
operands.
When an RxGOOSE Input is mapped to a value in the GOOSE message, the associated q value is validated, if the q value is
included in that GOOSE message as part of the data object.
The RxGOOSE Input value is reverted to its default value, if the associated:
• q.validity is invalid
• or q.test bit is set and the relay test mode is disabled
When the test mode function is Forcible or Isolated, the q.test bit is not validated. That means, when the relay is in Test or
Test/blocked mode, the q.test = False is treated same as q.test = True.
RxGOOSE Boolean, RxGOOSE DPS, and RxGOOSE Analog elements are mapped to various data objects in
<iedName>Master/GGIO3. This is to allow reading of their values via MMS and to allow references to them in SCL files.
GGIO3 has no settings, nor is it visible in the UR Setup software. See the UR Family Communications Guide for more
information on GGIO3.
There are Add IED and Remove IED buttons. The Add IED button allows SCL files to be used, including ICD, CID, and SCD
(supported in version 7.40 and later). With SCL file import, for Edition 1 the IP address in the ConnectedAP element must
match one IP address of the device, while for Edition 2 one of the three IP addresses in the ConnectedAP element must
match. When the file format is SCD, the system lists all IEDs inside the SCD file and lets the user select the ones to add. The
figure shows a selection being made by importing a CID file using the Add IED function.
Figure 5-54: RxGOOSE Boolean panel (Edition 2)
Most of the settings are configured by drag-and-drop. However the ID, DEFAULT STATE, and EVENTS settings must be
individually entered when the factory default values are not acceptable.
RxGOOSE Boolean1 ID
Range: 0 to 20 characters
Default: RxG Bool1
This setting allows the user to assign descriptive text to the name of the RxGOOSE Boolean1 FlexLogic operand. The full
operand name is the value of this setting appended with " On". The basic and enhanced front panels display the first 17
characters of this setting plus " On" to fit the 20 character display.
RxGOOSE Boolean1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the RxGOOSE containing the value that drives the RxGOOSE Boolean1 FlexLogic operand. If set to
None, the RxGOOSE Boolean1 FlexLogic operand assumes its default state.
RxGOOSE Boolean1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE Boolean1 FlexLogic operand. A setting of 1
selects the first member, 2 selects the second member, and so on. Entering a number greater than the number of
members in the message and entering the number of a member which does not contain a BOOLEAN results in the
RxGOOSE Boolean1 FlexLogic operand assuming its default state. The Subscribed to column identifies the particular
Boolean subscribed to even if the member is a structure containing more than one Boolean.
RxGOOSE DPS1 ID
Range: 0 to 20 characters
Default: RxG DPS1
This setting allows the user to assign descriptive text to the names of the four RxGOOSE DPS1 FlexLogic operands. The
full operand name is the value of this setting appended with "Interm," "On," "Off," or "Bad." The basic and enhanced front
panels display the first 13 characters of this setting plus the state suffix to fit the 20 character display.
RxGOOSE DPS1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the GOOSE message containing the value that drives the RxGOOSE DPS1 FlexLogic operand. If set to
None, the RxGOOSE DPS1 FlexLogic operand assumes its default state.
RxGOOSE DPS1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE DPS1 FlexLogic operand. A setting of 1 selects
the first member, 2 selects the second member, and so on. Entering a number greater than the number of members in
the message and entering the number of a member that is not a Dbpos results in the RxGOOSE DPS1 FlexLogic operand
assuming its default state. In the case that the member is a structure containing more than one Dbpos, the Subscribed
to column identifies the particular Dbpos subscribed to.
RxGOOSE DSP1 DEFAULT STATE
Range: Intermediate-state, Off, On, Bad-state, Latest
Default: Latest
5 This setting selects the logic state for the data attribute @Master/GGIO3.IndPos01.stVal and the DPS FlexLogic operands
when the UR has just completed start-up and the selected RxGOOSE has not yet received a message, and when the
RxGOOSE has lost its connection with the publisher. When this setting is selected to Latest, the value of @Master/
GGIO3.IndPosψψ.stVal is Intermediate-state when the UR has just completed start-up and the selected RxGOOSE has
not yet received a message, and the latest received value when the RxGOOSE loses its connectivity with the publisher.
RxGOOSE DPS1 EVENTS
Range: Disabled, Enabled
Default: Disabled
This setting selects whether Off to On transitions of the RxGOOSE DPS1 FlexLogic operands are recorded by the event
recorder. If set to Enabled, Off to On transitions are recorded. On to Off transitions are never recorded, even if events are
enabled.
Reports
Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports.
Report settings
Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports > Report Settings.
ReportSettings rptID
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the RptID attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false. The RptID is the name of the report.
ReportSettings optFields
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the OptFlds attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings bufTime
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the BufTm attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings trgOps
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the TrgOps attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
ReportSettings intgPd
Range: Dyn, Conf
Default: Dyn
When set to Dyn, the IntgPd attribute in any buffered and unbuffered report control block can be modified by an MMS
client while the control block's RptEna attribute is false.
An IEC 61850 Report server is an efficient method to deliver generic substation event information from a single server to a
single client, such as a supervisory control IED. A Configurable Report is a UR element implementing an IEC 61850 Report
server, either of the buffered or unbuffered kind. The following table lists the number of Configurable Report elements.
Each Configurable Report element can report the values of up to 64 FlexLogic or FlexAnalog operands. Buffered report
elements queue value changes that occur while the client is offline and delivered when the client re-connects. Up to 512
events can be queued. Unbuffered control blocks purge all value change events when the connection to the client is lost;
any events that occur while the client is not connected are lost.
Table 5-13: Number of report elements
Number
Buffered reports 30
Unbuffered reports 18
When using IEC 61850 Edition 2, configurable Reports interoperate with any client device of any manufacturer that
conforms to the IEC 61850 edition 1.0 or 2.0 report client requirements.
When using IEC 61850 Edition 1, configurable Reports interoperate with any client device of any manufacturer that
conforms to the IEC 61850 edition 1.0 report client requirements.
The entities whose values are reported by a Configurable Report are known as members. The members are itemized in an
ordered list known as a data set. Each Configurable Report can use any one of the data sets provided that no more than
four data sets are used for reports. This restriction is to limit the amount of processing power that can be allocated to
reporting.
Each enabled Configurable Report transmits an update to its client whenever a value change is detected in one or more of
its members. Also, the control block can be configured to send integrity reports containing the present value of all
members either on demand from the client or periodically. A TCP handshaking mechanism causes messages that are not
5 read and acknowledged by the client to be retransmitted.
For a Configurable Report to operate, its members must be selected (that is, its data set configured) and a client must open
a connection to, configure, and enable its report control block. Control blocks and data sets can be pre-configured by
sending the F35 a CID file. See the UR Family Communications Guide for details. EnerVista UR Setup also can be used to
select the data set members and to pre-configure the control blocks.
Each buffered report has the following settings.
Buffered Report1 RptID
Range for Edition 2: 0 to 129 VisibleString characters
Range for Edition 1: 0 to 65 VisibleString characters
Default: empty string
The name of the report. The entered value sets the RptID value in Buffered Report1 messages, and it can be used by the
client to discriminate Buffered Report1 messages from other messages. If the number of characters entered is zero, the
value used for RptID in messages is an ObjectReference to the report's control block, that is, "<LDName>/
LLN0$BR$"BRCB01".
Buffered Report1 Name
Range: 0 to 32 VisibleString characters
Default: BRCB01
The entered value sets the report control block name value for Buffered Report1.
Buffered Report1 DatSet
Range: None, TT6DataSet1, TT6 DataSet2, …, TT3DataSet01, TT3DataSet02, …
Default: None
This setting selects the data set whose members' status is reported in Buffered Report1 messages using the UR Setup
software designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, as
described later.
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0$" and the data
set name, is used in the datSet field of report messages, and it can be used by the client to discriminate Buffered Report1
messages from other messages.
The performance of the report is determined by the performance of the selected dataset. When the selection is
TT3DataSet01, TT3DataSet02, … it is possible that transient events can be missed.
To configure a DataSet, select it at the top of the window from the drop-down list, for example DataSet02 shown in the
previous figure. In the lower part of the window, drag and drop configuration items to the right side. For example select
the ST Ind001 stVal item and drag it to DataSet Member 1. Dataset members configured here affect other Report or
TxGOOSE control blocks that use the same DataSet.
Buffered Report1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
The entered value sets the confRev value in Buffered Report1 messages, and it can be used by clients to discriminate
report messages of the expected configuration revision from messages of a different revision. The standard requires
that confRev be incremented each time the members or the order of the members is changed, and each time the data
set name is changed. The standard states that the value of 0 is reserved.
Buffered Report1 OptFlds
Range: The check box for each individual bit can be enabled or not (see figure)
Default: All bits enabled/ true
The OptFlds setting is bitstring that controls which of the optional fields are included in report messages. The figure
shows the available option bits. To reduce message size, uncheck any fields that are not needed.
Figure 5-58: Options for buffered report messages (Edition 2)
DataSets
Navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets.
As mentioned in the preceding GOOSE and Reports sections, the members whose values are communicated by these
services are itemized in an ordered list known as a data set. Each UR with the IEC 61850 option has 18 data sets (six fast
and 12 slow). Each data set can contain as many as 64 members. Any data set can be used simultaneously by any number
of TxGOOSE elements and/or by any number of Configurable Report elements. UR Setup software can configure any
FlexLogic operands and any FlexAnalog operands as members.
Figure 5-59: IEC 61850 DataSets (Edition 2) 5
UR Setup software requires data set members to be IEC 61850 data objects or data attributes with Functional Constraint
ST or MX. Certain FlexLogic and FlexAnalog operands have factory-assigned data attributes as tabulated in the UR Family
Communications Guide. All FlexLogic and FlexAnalog operands can be user-assigned to GGIO1 or GGIO4 data attributes,
so that operands without factory-assigned data attributes can still have their values published. See the GGIO1 and GGIO4
sections later for details.
Datasets used by TxGOOSE1, TxGOOSE2, and/or by reports also provide a chatter suppression service for their Boolean
members. Oscillation in a value, also known as chatter, can be caused by errors in logic programming, inadequate
hysteresis (deadband) on a threshold, or a failed station component. Chatter can flood a communications network with
GOOSE messages, degrading response time for all users. If chatter is detected in a Boolean member, TxGOOSE suspends
GOOSE event message triggering and report message triggering from that member for as long as the condition exists, and
for a minimum period of one second. While sending is suspended, a self-test message identifying the specific data item
detected as oscillating is activated.
For a summary of the panels in which the data sets are used, the path is Settings > Product Setup > Communications >
IEC 61850 > DataSets > Summary.
For the settings, navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets > TT6DataSet1 for the
first data set.
Copy and paste functions are available when right-clicking a DataSet. They allow the target dataset to be configured
based on its order code. If some dataset items are not supported, they are not pasted, and a warning message shows a list
of dataset items that were not supported and not pasted. The DataSet name is not copied or pasted. In short, use this
feature to copy a DataSet Member setting and paste it into another Member setting, a text file, or Word, as examples.
Figure 5-60: Member right-click
DataSet01 name
Range: 0 to 32 VisibleString characters
Default: DataSet01
The value entered sets the name of the data set, which is required to be unique within the UR for proper operation. The
value entered sets the name of the data set, which is required to be unique within the UR for proper operation. Fast
datasets start with TT6, and slow datasets start with TT3. Up to six fast datasets are allowed. Up to four fast GOOSE
datasets are allowed.
An ObjectReference to the data set consists of a string that is the concatenation of "<LDName>/LLN0$" and the
DataSet01 name setting value. An ObjectReference to the data set is published in the datSet field of TxGOOSE messages,
and it can be used by subscribers to discriminate the messages of that TxGOOSE from other GOOSE messages. An
ObjectReference to the data set is optionally published in the DatSet field of Report messages. Valid characters are
upper and lowercase letters, digits, and the underscore (_) character. The first character must be a letter.
DataSet01 shared by
Range: 0 to 32 VisibleString characters
Default:
Names of all control blocks that use this DataSet. Read-only field.
DataSet01 Member1
Range: End of List or any instantiated 61850 data object or data attribute with Functional Constraint ST or MX
Default: End of List
This setting specifies the first member in TxGOOSE1 messages. There is a similar setting for each of the up to 64
members that the UR allows in a Dataset. Only values of members before the first set to End of List are published.
Select the member from the drop-down list. Or right-click an entry to copy, paste, delete, or insert.
Product setup
Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup.
Security
This setting applies to IEC 61850 Edition 2.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup > Security.
Figure 5-61: IEC 61850 Security 5
SecGSAL1.SecDataClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model that clients must use to clear security data via commands to
SecGSAL1.SecDataClr. "sbo" here is select-before-operate.
SecGSAL1.OpCntRs ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model that clients must use to clear security data via commands to SecGSAL1.OpCntRs.
"sbo" here is select-before-operate.
Demand
Deadband parameters of measured values related to the Demand metering are configured here.
Energy
Deadband parameters of measured values related to the Energy metering are configured here.
TmClkLTMS1.TmnsDelta.db
Range: 0.000 to 100.000 %
Default: 0.000 %
This setting is a deadband setting and is used by the relay to determine when to update the "mag" and "cVal" values
from the associated "instMag" and "instCVal" values. The value shall represent the percentage of difference between
maximum and minimum in units of 0.001%. The minimum and maximum values for TmnsDelta data object are
-500000000 ns and 500000000 ns respectively and for example, a setting value of 0.002% results in the dead banded
value of (500000000 - (-500000000)) * 0.002 / 100 = 20000 ns. The default setting value of 0.000% does not update the
"mag" and "cVal" values.
Deadband settings
A deadband is a range in which no action occurs, usually expressed as a percentage.
The IEC 61850 panels contain hundreds of deadband settings, such as in the following panels: Product Setup > Real Time
Clock, FlexLogic, Control Elements, and GGIO4. Each panel is not outlined here. The FlexLogic category applies to IEC 61850
Edition 2.
Deadband setting names all end either with "DB" or .db. As they all work the same way, but each on a different analog
value, a single description applicable to all deadband settings is given here. The analog value that each deadband setting
applies is usually obvious from the name of the setting. However, a tabulation of the analog values and their associated
deadband setting can be found in the UR Family Communications Guide.
Figure 5-63: Deadband settings with .db suffix (Edition 2)
GOOSE, buffered report, and unbuffered report messages are for the most part transmitted only when there is a value
change in one or more of their members. Most analog values continuously dither by an amount that is not significant.
Were a report to be sent each time an insignificant analog value change occurred, then the communications network
5
floods with GOOSE and report messages, degrading response time for all users.
To control this, a deadband setting is provided for each analog value. Also, in addition to the present actual value of each
analog ("instMag" in the following figure), there is a deadbanded value ("mag" in the figure), which is updated with the
present value only when the difference between the two exceeds the deadband setting (db in the figure). Changes to this
deadbanded value trigger transmissions when included in GOOSE and report data sets.
Figure 5-64: Deadband settings
Deadband settings are entered in UR Setup software in units of percent of the difference between the "max." and "min." of
the associated analog value. A zero deadband setting suppresses transmission triggering. The range of deadband settings
is 0.000 to 100.000% in steps of 0.001. The default value is 0.000%.
GGIO4 elements have individual settings for "min." and "max." The min. and max. for FlxEIGAPC#.OpSig.db (FLEXELEMENT #
OpSig) are -50 pu and +50 pu respectively. The min. value for all other quantities is 0. The max. values are as follows:
• Phase current — 46 x phase CT primary setting
• Neutral current — 46 x ground CT primary setting
• Ground current (sensitive ground CT) — 4.6 x sensitive ground CT primary setting
• Phase, phase-to-phase, and sequence voltage — 275 x phase VT ratio setting
Signal sources
Deadband parameters of measured values related to the signal sources are configured here.
Breakers
The UR breaker control and status monitoring elements have certain settings that configure how the IEC 61850 protocol
interacts with these elements. These settings are described in this section. See the Breakers section in the System Setup
section of this chapter for details on the operation of breaker control elements.
Navigate to Settings > Communications > IEC 61850 > System Setup > Breakers > Breaker 1 to access the settings that
configure the IEC 61850 protocol interface with the first breaker control and status monitoring element. The settings and
functionality for the others are similar.
5 Figure 5-65: IEC 61850 Breaker panel (Edition 2)
Switches
The UR disconnect switch control and status monitoring elements have certain settings that configure how the IEC 61850
protocol interacts with these elements. These settings are described in this section. See the Settings > System Setup >
Disconnect Switches section later in this chapter for details on the operation of the disconnect switch control elements.
Navigate to Settings > Product Setup > Communications > IEC 61850 > System Setup > Switches > Switch 1 to access
the settings that configure the IEC 61850 protocol interface with the first disconnect switch control and status monitoring
element. The settings and functionality for the others are similar.
Disc0XSWI1.InRef5.setSrcRef OPERAND
Range: any FlexLogic operand
Default: OFF
This setting is used to select a FlexLogic operand that declares to IEC 61850 services that disconnect switch 1 is selected
for local control. While the selected operand is asserted, Disc0XSWI1.Loc.stVal is true and IEC 61850 commands to
DiscCSWI1.Pos and Disc0XSWI1.Pos are not accepted, and a Negative Response (-Rsp) is issued with the REASON CODE
of Blocked-by-switching-hierarchy.
XSWI1 INTERLOCK OPN
5
Range: any FlexLogic operand
Default: ON
This setting is used to select a FlexLogic operand that declares to IEC 61850 services that interlocking conditions are not
acceptable for opening disconnect switch 1. While the selected operand is asserted, the value of DiscCILO.EnaOpn.stVal
is false. If a SelectWithValue or Operate service with ctlVal false and with Check.Interlock-check true is requested of
DiscCSWI1.Pos or Disc0XSWI1.Pos and the selected operand is not activated, a Negative Response (-Rsp) is issued with
the REASON CODE of Blocked-by-interlocking.
XSWI1 INTERLOCK CLS
Range: any FlexLogic operand
Default: ON
This setting is used to select a FlexLogic operand that declares to IEC 61850 services that interlocking conditions are not
acceptable for closing disconnect switch 1. While the selected operand is asserted, the value of DiscCILO.EnaCls.stVal is
false. If a SelectWithValue or Operate service with ctlVal true and with Check.Interlock-check true is requested of
DiscCSWI1.Pos or Disc0XSWI1.Pos and the selected operand is not activated, a Negative Response (-Rsp) is issued with
the REASON CODE of Blocked-by-interlocking.
XSWI1 Pos ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: sbo-with-enhanced-security
This setting selects the control model that clients must use to successfully control the disconnect switch 1 signals
marked Disc0XCBR1.PosOpn.ctlVal and Disc0XCBR1.PosCls.ctlVal on the Disconnect Switch Logic diagram in the Settings
> System Setup section later. These signals force a disconnect switch trip or close control while the operand selected by
setting XSWI1 ST.LOC OPERAND is not active.
"sbo" here is select-before-operate. Enhanced security means that the F35 reports to the client the disconnect switch 1
position the end of the command sequence.
Setting Groups
The UR implements a setting groups element as detailed in the Control Elements > Setting Groups section of this chapter.
The active setting group and the setting group open for edits can be selected via MMS commands SelectActiveSG and
SelectEditSG. The setting related to these IEC 61850 commands are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Control Elements > Setting Groups to access
the setting that configures the IEC 61850 setting group commands.
FltRptRFLO1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo"
here is select-before-operate. Enhanced security means that the F35 reports to the client the breaker 1 position at the
end of the command sequence.
LLN0.EvtRcdClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR EVENT RECORDS.
LPHD1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR ALL RELAY RECORDS.
OscRDRE1.RcdTrg.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command FORCE TRIGGER.
OscRDRE1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
5 This setting selects the control model clients must use to successfully control the command CLEAR OSCILLOGRAPHY.
DatLogRDRE1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR DATA LOGGER.
CBArc0SCBR1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
DmdMtrMMTR1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
EnrMtrMMTR1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
GGIO1
GGIO1 is a UR feature that allows up to 128 UR FlexLogic operands to be user-mapped to IEC 61850 information model
data attributes.
For the value of a FlexLogic operand to be read via MMS, included in TxGOOSE messages, or included in buffered/
unbuffered reports, the value must be assigned to a data attribute. GGIO1 allows those FlexLogic operands that have not
yet been factory-assigned to a data attribute to be user-assigned to a generic data attribute, and thus have their values
included in IEC 61850 communications.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO1 to access the settings for GGIO1.
GGIO1 INDICATION 1
Range: any FlexLogic operand
Default: OFF
This setting selects the FlexLogic operand whose value is mapped into the IEC 61850 data attribute
<LDName>/GGIO1.Ind001.stVal. See the FlexLogic section in this chapter for a list of FlexLogic operands.
GGIO1 INDICATION 2
Range: any FlexLogic operand
5
Default: OFF
Selects the FlexLogic operand mapped to <LDName>/GGIO1.Ind002.stVal, and so on.
GGIO2
Virtual Inputs are controllable FlexLogic operands that can be controlled via IEC 61850 commands to GGIO2, by DNP, by
Modbus, and by the UR front panel. The settings related to these IEC 61850 commands are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO2 to access the settings that
configure the IEC 61850 protocol interface for Virtual Input commands.
Figure 5-70: GGIO2 panel (Edition 2)
GGIO4
GGIO4 is a UR feature that allows up to 32 UR FlexAnalog operands to be user-mapped to an IEC 61850 information model
data attribute.
For the value of a FlexAnalog operand to be read via MMS, included in TxGOOSE messages, or included in buffered/
unbuffered reports, the value must be assigned to a data attribute. GGIO4 allows those FlexAnalog operands that have not
yet been factory-assigned to a data attribute to be user-assigned to a generic data attribute, and thus have their values
included in IEC 61850 communications.
Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO4 > GGIO4.AnIn1 to access the
settings for the first GGIO4 value. The settings and functionality for the others are similar.
Figure 5-71: GGIO4 panel (Edition 2)
ANALOG IN 1 VALUE
Range: any FlexAnalog operand
Default: OFF
This setting selects the FlexAnalog operand whose value is mapped into the IEC 61850 data attribute
<LDName>/GGIO4.AnIn01.instMag.f. The value of the FlexAnalog operand is converted automatically to the format and
scaling required by the standard, that is to say primary amperes, primary volts, and so on. See Appendix A for a list of
FlexAnalog operands.
ANALOG IN 1 DB
Range: 0.000 to 100.000% in steps of 0.001
Default: 0.000%
This setting specifies the deadband for the ANALOG IN 1 VALUE. The deadband is used to determine when to update the
deadbanded magnitude from the instantaneous magnitude. The deadband is a percentage of the difference between
the "max." and "min." values. Here, the "max." and "min." are as specified by the settings ANALOG IN 1 MAX and ANALOG IN
1 MIN.
See the Deadband Settings section earlier for a description of deadbanded values.
ANALOG IN 1 MIN
Range: -1000000000.000 to 1000000000.000 in steps of 0.001
Default: 0.000
This setting specifies the "min." value used in deadband calculations. The scaling of this setting is the same as used by
<LDName>/GGIO4.AnIn01.instMag.f. This setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of
the large range of this setting, not all possible values can be stored. Some values are rounded to the closest possible
floating point number.
ANALOG IN 1 MAX
Range: -1000000000.000 to 1000000000.000 in steps of 0.001
Default: 1000000.000
This setting specifies the "max." value used in deadband calculations. The scaling of this setting is the same as used by
<LDName>/GGIO4.AnIn01.instMag.f. This setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of
the large range of this setting, not all possible values can be stored. Some values are rounded to the closest possible
floating point number.
The F35 contains an embedded web server and can display pages in a web browser. The web pages are organized as a
series of menus that can be accessed starting at the F35 “Main Menu.” Web pages are read-only and are available
showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the
F35 and a computer to an Ethernet network, then enter the IP address of the F35 Ethernet port in a web browser.
To close the port, set the port number to 0.
Any change takes effect when the F35 is restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the F35 over a network. The F35 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained
from the F35 contains a list and description of all available files, for example event records and oscillography.
The "put" function is not for security reasons. You can enter a "get" command but not a "put" command.
TFTP MAIN UDP PORT NUMBER — To close the port, set the port number to 0. Any change takes effect when the F35 is
restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
IEC 60870-5-104 is a transmission protocol for network access, specifically for communication between a control station
and substation over a TCP/IP network.
The F35 supports the IEC 60870-5-104 protocol. This protocol is enabled when the SETTINGS PRODUCT SETUP
COMMUNICATIONS PROTOCOL setting is set to IEC 60870-5-104. The F35 can be used as an IEC 60870-5-104 slave device
5 connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the F35 maintains two
sets of IEC 60870-5-104 data change buffers, ideally no more than two masters actively communicate with the F35 at one
time.
The IEC ------- DEFAULT THRESHOLD settings are used to determine when to trigger spontaneous responses containing
M_ME_NC_1 analog data. These settings group the F35 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the F35 when any current values change by 15 A, the IEC CURRENT DEFAULT THRESHOLD
setting is set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of measured
value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the F35, the default thresholds are in effect.
The IEC REDUNDANCY setting decides whether multiple client connections are accepted or not. If redundancy is set to Yes,
two simultaneous connections can be active at any given time.
IEC TCP PORT NUMBER — To close the port, set the port number to 0. Any change takes effect when the F35 is restarted.
IEC COMMON ADDRESS OF ASDU — The change takes effect when the F35 is restarted.
IEC CYCLIC DATA PERIOD — The change takes effect when the F35 is restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 60870-5-104 PROTOCOL IEC NETWORK CLIENT
ADDRESSES
IEC NETWORK CLIENT ADDRESS 1: Range: standard IPV4 address format
CLIENT ADDRESSES 0.0.0.0
CLIENT ADDRESS 5: Range: standard IPV4 address format
0.0.0.0
The F35 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to
which the F35 can connect. A maximum of two simultaneous connections are supported at any given time.
The F35 is provided with optional Ethernet Global Data (EGD) communications capability. This feature is
specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
Ethernet Global Data (EGD) is a suite of protocols used for the real-time transfer of data for display and control purposes.
The relay can be configured to ‘produce’ EGD data exchanges, and other devices can be configured to ‘consume’ EGD data
exchanges. The number of produced exchanges (up to three), the data items in each exchange (up to 50), and the
exchange production rate can be configured.
The relay supports one fast EGD exchange and two slow EGD exchanges. There are 20 data items in the fast-produced
EGD exchange and 50 data items in each slow-produced exchange.
EGD cannot be used to transfer data between UR series relays. The relay supports EGD production only. An EGD exchange
is not be transmitted unless the destination address is non-zero, and at least the first data item address is set to a valid 5
Modbus register address. The default setting value of “0” is considered invalid.
Fast exchanges (50 to 1000 ms) are generally used in control schemes. The F35 has one fast exchange (exchange 1) and
two slow exchanges (exchange 2 and 3).
The settings menu for the fast EGD exchange follows.
SETTINGS PRODUCT SETUP COMMUNICATIONS EGD PROTOCOL FAST PROD EXCH 1 CONFIGURATION
FAST PROD EXCH 1 EXCH 1 FUNCTION: Range: Disable, Enable
CONFIGURATION Disable
Slow EGD exchanges (500 to 1000 ms) are generally used for the transfer and display of data items. The settings for the
fast and slow exchanges are as follows.
EXCH 1 DESTINATION — This setting specifies the destination IP address of the produced EGD exchange. This is usually
unicast or broadcast.
EXCH 1 DATA RATE — This setting specifies the rate at which this EGD exchange is transmitted. If the setting is 50 ms, the
exchange data is updated and sent once every 50 ms. If the setting is 1000 ms, the exchange data is updated and sent
once per second. EGD exchange 1 has a setting range of 50 to 1000 ms. Exchanges 2 and 3 have a setting range of 500 to
1000 ms.
EXCH 1 DATA ITEM 1 to 20/50 — These settings specify the data items that are part of this EGD exchange. Almost any data
from the F35 memory map can be configured to be included in an EGD exchange. The settings are the starting Modbus
register address for the data item in decimal format. See the Modbus memory map in the UR Series Communications
Guide for details. The Modbus memory map display shows addresses in hexadecimal format. Convert these hex values to
decimal format before entering them as values for these setpoints.
To select a data item to be part of an exchange, it is only necessary to choose the starting Modbus address of the item.
That is, for items occupying more than one Modbus register (for example, 32 bit integers and floating point values), only the
first Modbus address is required. The EGD exchange configured with these settings contains the data items up to the first
setting that contains a Modbus address with no data, or 0. That is, if the first three settings contain valid Modbus addresses
and the fourth is 0, the produced EGD exchange contains three data items.
5
5.3.5.17 IEC 60870-5-103 protocol
SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 60870-5-103
IEC103 IEC103 COMMON Range: 0 to 254 in steps of 1
PROTOCOL ADDRESS OF ASDU: 0
The F35 is provided with optional IEC 60870-5-103 communications capability. This feature is specified as a
software option at the time of ordering. See the Order Codes section in chapter 2 for details.
IEC 60870-5-103 is a companion standard to the IEC 60870-5 suite of standards for transmission protocols. It defines
messages and procedures for interoperability between protection equipment and devices of a control system in a
substation for communicating on a serial line.
The IEC 60870-5-103 protocol is enabled when the SETTINGS PRODUCT SETUP COMMUNICATIONS PROTOCOL setting
is set to IEC 60870-5-103.
The IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial communication, exchanging
information with a control system. In the context of this protocol, the protection equipment is the slave and the control
system is the master. The communication is based on a point-to-point principle. The master must be able to interpret the
IEC 60870-5-103 communication messages.
The binary input points are mapped using elements from a list of possible FlexLogic operands. A maximum of 96 binary
inputs (points) can be mapped this way.
The IEC 60870-5-103 point list always starts with point 0 and ends at the first "Off" value. Since the IEC 60870-5-103 point
list must be in a continuous block, any points assigned after the first "Off" point are ignored.
For each defined point, set appropriate values for the Function Type (FUN) and Information Number (INF), which form the
Information Object Identifier field of the ASDU, as defined in IEC 60870-5-103.
The binary input points are sent as Class 1 data. They are sent either as a response to a general interrogation received
from the controller or reported spontaneously. Spontaneous transmission occurs as a response to cyclic Class 2 requests.
If the F35 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the
control field of the response).
For any change to take effect, restart the relay.
5 ASDU 1 ANALOG 1
Off
Range: FlexAnalog parameter
Pt = 0.017 * P
For a max power 100000 KW * 2.4 = 240000 KW, we transmit
Pt = 0.017 * 240000 = 4080
A value above 240 MW is indicated by overflow.
5 COMMAND 1
COMMAND 31
Commands are received as General Command (Type Identification 20). The user can configure the action to perform when
an ASDU command comes.
A list of available mappings is provided on the F35. This includes 64 virtual inputs (see the following table). The ON and OFF
for the same ASDU command can be mapped to different virtual inputs.
Each command is identified by the unique combination made by the function type (FUN) and information number (INF). If
the master sends an ASDU command that does not have the FUN and INF of any configured command, the relay rejects it.
Table 5-14: Commands mapping table
Description Value
Off 0
Virtual Input 1 1
Virtual Input 2 2
... ...
Virtual Input 64 64
This setting applies to the USB port on the graphical front panel.
5
This setting enables/disables the USB port on the graphical front panel. When the port function is "Enabled," a standard
USB serial cable allows a computer running the EnerVista UR Setup software to retrieve, display, and write settings either
individually or collectively, to display status and actual values, to initiate controls, and to retrieve and display event records,
oscillography records, data logger records, and disturbance records. Installation of the EnerVista software automatically
installs the drivers required to use this USB port.
DNP is not available using the USB port on the graphical front panel.
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the address
in the ADDRESS line (converted from hex to decimal format). The corresponding value (if programmed) displays in the VALUE
line. A value of “0” in subsequent register ADDRESS lines automatically returns values for the previous ADDRESS lines
incremented by 1. An address value of “0” in the initial register means “none” and values of “0” display for all registers.
Different ADDRESS values can be entered as required in any of the register positions.
The UR Family Communications Guide outlines the Modbus memory map. The map is also viewable in a web browser;
enter the IP address of the F35 in a web browser and click the option.
5.3.7.1 Menu
SETTINGS PRODUCT SETUP REAL TIME CLOCK
REAL TIME SYNCRONIZING SOURCE: Range: None, PP/IRIG-B/PTP/Other, IRIG-B/PP/PTP/
CLOCK None Other, PP/PTP/IRIG-B/Other
The relay contains a real time clock (RTC) to create time stamps for communications protocols as well as for historical data,
such as event records and oscillography. When the relay restarts, the RTC initializes from an onboard battery-backed
clock, which has the same accuracy as an electronic watch, approximately ±1 minute per month (~23 ppm). Once the RTC
is synchronized with the Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchronizing
time delivered to the relay. While the RTC is not synchronized via PTP or IRIG-B, or the relay determines that it has an offset
5 possibly greater than 10 µs from the international time standard, the CLOCK UNSYNCHRONIZED FlexLogic operand is
activated.
The SYNCHRONIZING SOURCE setting displays in the software when the relay includes the IEEE 1588 software option. The
setting configures the priority sequence of the time synchronization source, to determine which of the available external
time sources to use for time synchronization. A setting of None causes the RTC and the synchrophasor clock to free-run,
and the clock can be changed from the front panel or from communications protocols. A setting of PP/IRIG-B/PTP/Other,
IRIG-B/PP/PTP/Other, or PP/PTP/IRIG-B/Other causes the relay to track the first source named that is enabled and
operational, or free-run if none of these are available. Here, PP means a time source that is strictly compliant with PP, PTP
means a time source that is not strictly compliant with PP, and Other means any less precise source (SNTP, IEC 103, IEC 104,
Modbus, or DNP). When a time source fails or recovers, the relay automatically transfers synchronization as required by
this setting.
When the relay does not have the IEEE 1588 software option and this setting does not display, it uses IRIG-B when enabled
and operational, then failing that SNTP when configured and operational, and otherwise it free-runs unless the clock is
changed from the front panel or from communications protocols.
Setup for IRIG-B is illustrated in the Installation chapter.
For the Other protocols, whenever a time synchronization message is received through any of the active protocols, the F35
clock updates. However, given that IEC 60870-5-103, IEC 60870-5-104, Modbus, and DNP are low-accuracy time
synchronization methods, avoid their use for synchronization when better accuracy time protocols, such as IRIG-B and PTP,
are active in the system. If IRIG-B or PTP is used to update the relay clock, the other protocols (such as SNTP) are not
allowed to update, even if active.
See the COMMANDS SET DATE AND TIME menu section of this manual to manually set the RTC.
The REAL TIME CLOCK EVENTS setting allows changes to the date and/or time to be captured in the event record. The event
records the RTC time before the adjustment. A Date/Time Changed event is generated when:
• The real time clock changed from SNTP/PTP/IRIG-B and the time difference is more than one second
• The real time clock changed from the front panel or via Modbus register. The relay always generates this event
regardless of the time difference.
• The Daylight Saving Time (DST) setting gets enabled and the current relay time is already in the DST zone
• The real time clock enters or leaves DST
To enable IRIG-B synchronization, the input IRIG-B SIGNAL TYPE must be set to DC Shift or Amplitude Modulated. IRIG-B
synchronization can be disabled by making this setting None.
Clocks can be synchronized locally among several relays using the computer time. When using a time source, such as IRIG-
B, the time is overwritten eventually by the time source. To synchronize clocks among UR devices:
1. In the EnerVista software, expand the main menu in the Online Window area and select the Synchronize Devices
entry. The window opens. The software prompts to acknowledge any offline devices.
2. Click the Synchronize Devices button at the top of the window, and confirm the action at the prompt. The devices
assume the time of the computer being used.
To configure and enable PTP and/or SNTP, or to set local time parameters (for example time zone, daylight savings), use the
following sections.
The F35 is provided with optional Precision Time Protocol capability. This feature is specified as the IEEE 1588
software option at the time of ordering. See the Order Codes section in chapter 2 for details.
The F35 supports the Precision Time Protocol (PTP) specified in IEEE Std 1588 2008 using the Power Profile (PP) specified in
IEEE Std C37.238 2011. This enables the relay to synchronize to the international time standard over an Ethernet network
that implements PP.
The relay can be configured to operate on some PTP networks that are not strictly PP. Time accuracy can be less than
specified for a PP network. Tolerated deviations from strict PP include 1) missing declaration of PP compliance in the
messages, 2) connection to a network device that does not support the PTP peer delay mechanism, 3) jitter substantially
greater than 1 µs in received event messages, and 4) certain non-compliant announce and sync message update rates.
The relay implements PTP according to IEEE Std 1588 2008 and the equivalent IEC 61588:2009(E), sometimes referred to as
version 2 PTP. It does not support the previous version of the standard (version 1).
PTP is a protocol that allows multiple clocks in a network to synchronize with one another. It permits synchronization
accuracies better than 1 ns, but this requires that each and every component in the network achieve very high levels of
accuracy and a very high baud rate, faster than normally used for relay communications. When operating over a generic
Ethernet network, time error can amount to 1 ms or more. PP is a profile of PTP which specifies a limited subset of PTP
suitable for use in power system protection, control, automation, and data communication applications, and thereby
facilitates interoperability between different vendor’s clocks and switches. PP specifies a worst-case delivered time error of
less than 1 µs over a 16-hop network.
In a PTP system and in a PP system, the clocks automatically organize themselves into a master-slave synchronization
hierarchy with the “best” clock available making itself the "grandmaster" at the top of the hierarchy; all others make
themselves “slaves” and track the grandmaster. Typically the grandmaster clock receives its time from GPS satellites or
some other link to the international time standard. If the grandmaster fails, the next “best” clock available in the domain
assumes the grandmaster role. When a clock on start-up discovers that it is “better” than the present grandmaster, it
assumes the grandmaster role and the previous grandmaster reverts to slave. The F35 qualification mechanism accepts a
potential master clock as a new grandmaster, when in a four-second interval it has received three announce messages
from it, all better than the present grandmaster clock and better than any other announce in this interval.
Time messages issued by the grandmaster are delayed as they pass through the network both due to the finite speed of
the signal in the interconnecting fiber or wire, and due to processing delays in the Ethernet switches. Each clock and switch
implementing PP measures the propagation delay to each of its PP neighbors, and compensates for these delays in the
time received. Each network device implementing PP measures the processing delay it introduces in each time message
and compensates for this delay in the time it transmits. As a result, the time delivered to end-devices such as the UR are
virtually identical to the grandmaster time. If one of the network devices in the hierarchy does not fully implement PP, the
associated propagation delay and/or latency may not be compensated for, and the time received at the end-device can be
in error by more than 100 µs.
See the preceding Real Time Clock section for a description of when time values received via PTP are used to update the
relay’s real time clock.
The following settings are available for configuring the relay for PTP. The PTP menu displays only when the option was
purchased.
STRICT POWER PROFILE — Power profile (IEEE Std C37.238 2011) requires that the relay only select a power profile compliant
5 clock as a grandmaster, that the delivered time have worst-case error of ±1 µs, and that the peer delay mechanism be
implemented. With the strict power profile setting enabled, the relay only selects as master the clocks displaying the
IEEE_C37_238 identification codes. It uses a port only when the peer delay mechanism is operational. With the strict power
profile setting disabled, the relay uses clocks without the power profile identification when no power profile clocks are
present, and uses ports even if the peer delay mechanism is non-operational. This setting applies to all of the relay’s PTP
capable ports.
PTP DOMAIN NUMBER — Set this setting to the domain number of the grandmaster-capable clock(s) to be synchronized to. A
network can support multiple time distribution domains, each distinguished with a unique domain number. More
commonly, there is a single domain using the default domain number zero.
This setting applies to all of the relay’s PTP capable ports.
PTP VLAN PRIORITY — This setting selects the value of the priority field in the 802.1Q VLAN tag in request messages issued
by the relay’s peer delay mechanism. In compliance with PP the default VLAN priority is 4, but it is recommended that it be
set to 7 in accordance with PTP. Depending on the characteristics of the device to which the relay is linked directly, VLAN
Priority can have no effect.
This setting applies to all of the relay’s PTP capable ports.
PTP VLAN ID — This setting selects the value of the ID field in the 802.1Q VLAN tag in request messages issued by the relay’s
peer delay mechanism. It is provided in compliance with PP. As these messages have a destination address that indicates
they are not to be bridged, their VLAN ID serves no function, and so can be left at its default value. Depending on the
characteristics of the device to which the relay is linked directly, VLAN ID can have no effect. This setting applies to all of
the relay’s PTP capable ports.
PORT 1 ... 3 FUNCTION — While this port setting is selected to disabled, PTP is disabled on this port. The relay does not
generate or listen to PTP messages on this port.
PORT 1 ... 3 PATH DELAY ADDER — The time delivered by PTP is advanced by the time value in this setting prior to the time
being used to synchronize the relay’s real time clock. This is to compensate to the extent practical for time delivery delays
not compensated for in the network. In a fully compliant PP network, the peer delay and the processing delay mechanisms
compensate for all the delays between the grandmaster and the relay. In such networks, make this setting zero.
In networks containing one or more switches and/or clocks that do not implement both of these mechanisms, not all
delays are compensated, so the time of message arrival at the relay is later than the time indicated in the message. This
setting can be used to approximately compensate for this delay. However, as the relay is not aware of network switching
that dynamically changes the amount of uncompensated delay, there is no setting that always and completely corrects
for uncompensated delay. A setting can be chosen that reduces the worst-case error to half of the range between
minimum and maximum uncompensated delay, if these values are known.
PORT 1 ... 3 PATH DELAY ASSYMMETRY — This setting corresponds to “delayAsymmetry” in PTP, which is used by the peer delay
mechanism to compensate for any difference in the propagation delay between the two directions of a link. Except in
unusual cases, the two fibers are of essentially identical length and composition, so make this setting zero.
In unusual cases where the length of the link is different in different directions, set this setting to the number of
nanoseconds the Ethernet propagation delay to the relay is longer than the mean of path propagation delays to and from
the relay. For instance, if it is known say from the physical length of the fibers and the propagation speed in the fibers that
the delay from the relay to the Ethernet switch it is connected to is 9000 ns and that the delay from the switch to the relay
is 11000 ns, then the mean delay is 10000 ns, and the path delay asymmetry is 11000 - 10000 = +1000 ns.
The F35 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the F35 can obtain clock time over
an Ethernet network. The F35 acts as an SNTP client to receive time values from redundant SNTP/NTP servers, usually a
dedicated product using a GPS receiver to provide an accurate time. One or two SNTP servers can be used; use of both
servers for redundancy is recommended but not required.
To use SNTP, enable the function and set SNTP SERVER1 IP ADDR and/or SNTP SERVER2 IP ADDR to the SNTP/NTP server IP
addresses. The F35 attempts to obtain time values from the SNTP SERVER1 SNTP/NTP server. If SERVER1 is not available/
reachable, the F35 switches to the SNTP SERVER2 to get the time value and vice versa.
Since many time values are obtained and averaged, it generally takes three to four minutes until the F35 clock is closely
synchronized with the SNTP/NTP server. It can take up to 20 minutes for the F35 to signal an SNTP self-test error if the
server is offline, depending on the number and SNTP server modes. Broadcast mode timeout is 10 minutes and unicast
timeout is 80 seconds (corresponds to three unicast request retries).
SNTP FUNCTION — Enables or disables the SNTP feature on the F35.
SNTP SERVER1 IP ADDR — The F35 uses the SERVER1 address to contact an SNTP/NTP server to obtain time values. When the
SNTP FUNCTION setting is set to enabled or on startup if the setting is enabled, the F35 SNTP client requests SERVER1 for the
time value. If the SERVER1 channel fails or is not reachable, the F35 switches to SERVER2 SNTP/NTP server.
If SERVER1 SNTP server is set to 127.0.0.1, the F35 considers the SERVER1 SNTP server to be unconfigured.
To use SERVER1 SNTP in broadcast mode, set the SNTP SERVER1 IP ADDR setting to "0.0.0.0" and SNTP FUNCTION to "Enabled."
The F35 SNTP client then listens to SNTP messages sent to the "all ones" broadcast address for the subnet. The F35 waits
up to 18 minutes (>1024 seconds) without receiving an SNTP broadcast message before switching to the alternate
channel.
SNTP SERVER2 IP ADDR — The F35 uses this address to contact an SNTP/NTP server if SERVER1 channel fails or is not
reachable. If SERVER2 SNTP server is set to 127.0.0.1, the F35 considers the SERVER2 SNTP server to be unconfigured.
To use SERVER2 SNTP in broadcast mode, set the SNTP SERVER2 IP ADDR setting to "0.0.0.0" and SNTP FUNCTION to "Enabled."
The F35 SNTP client then listens to SNTP messages sent to the "all ones" broadcast address for the subnet. The F35 waits
up to 18 minutes (>1024 seconds) without receiving an SNTP broadcast message before switching to the alternate
channel.
SNTP SERVER1 UDP PORT — This setting is 123 for normal SNTP operation. If SERVER1 SNTP is not required, close the port by
changing this setting to zero.
SNTP SERVER2 UDP PORT — This setting is 123 for normal SNTP operation. If SERVER2 SNTP is not required, close the port by
changing this setting to zero.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
If SERVER1 IP ADDR and UDP PORT settings match the SERVER2 IP ADDR and UDP PORT settings, the F35 considers only
the SERVER1 SNTP server as being configured and an SNTP Failure error message generates. The failure message
also displays when both servers are unavailable.
DST START DAY: Range: Sunday to Saturday (all days of the week)
Sunday
DST STOP DAY: Range: Sunday to Saturday (all days of the week)
Sunday
The F35 maintains two times: local time and Universal Coordinated Time (UTC). Local time can be provided by IRIG-B
signals. UTC time is provided by SNTP servers.
The real-time clock (RTC) and time stamps reported in historical records and communication protocols can be incorrect if
the Local Time settings are not configured properly.
See the IRIG-B section in the Installation chapter for guidance on these settings when using an IRIG-B source that sets the
IRIG-B control bits according to IEEE Std 1344-1995.
LOCAL TIME OFFSET FROM UTC — Used to specify the local time zone offset from UTC (Greenwich Mean Time) in hours. Time
zones in the eastern hemisphere have positive values; time zones in the western hemisphere have negative values. A value
of zero causes the relay to use UTC for local time. This setting has two uses. When the system RTC is synchronized with a
communications protocol providing only local time or it is free-running, the offset setting is used to calculate UTC from the
local time these provide. When the RTC is synchronized with a communications protocol providing only UTC (such as PTP or
SNTP), the time offset setting is used to determine local time from the UTC provided. PTP
ALTERNATE_TIME_OFFSET_INDICATOR TLVs are not used to calculate local time.
DAYLIGHT SAVINGS TIME and DST — Can be used to allow the relay to follow the DST rules of the local time zone. Note that
when IRIG-B time synchronization is active, the local time in the IRIG-B signal contains any daylight savings time offset and
so the DST settings are ignored.
The F35 relay supports one fault report and an associated fault locator per CT bank to a maximum of five. The signal
source and trigger condition, as well as the characteristics of the line or feeder, are entered in this menu.
The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in
the FaultReport.txt file includes:
• Fault report number
• Name of the relay, programmed by the user
• Firmware revision of the relay
• Date and time of trigger
• Name of trigger (specific operand)
• Line or feeder ID via the name of a configured signal source
The FAULT REP 1 SYSTEM Z0 MAG and FAULT REP 1 SYSTEM Z0 ANGLE settings are used only when the VT SUBSTITUTION setting
value is “I0”. The magnitude is to be entered in secondary ohms. This impedance is an average system equivalent behind
the relay. It can be calculated as zero-sequence Thevenin impedance at the local bus with the protected line/feeder
disconnected. The method is accurate only if this setting matches perfectly the actual system impedance during the fault.
If the system exhibits too much variability, this approach is questionable and the fault location results for single-line-to-
ground faults is trusted accordingly. Keep in mind that grounding points in the vicinity of the installation impact the system
zero-sequence impedance (grounded loads, reactors, zig-zag transformers, shunt capacitor banks, and so on).
5.3.9 Oscillography
5.3.9.1 Menu
SETTINGS PRODUCT SETUP OSCILLOGRAPHY
OSCILLOGRAPHY NUMBER OF RECORDS: Range: 1 to 64 in steps of 1
5
DIGITAL CHANNELS
See below 5
ANALOG CHANNELS See below
Oscillography records contain waveforms captured at the sampling rate as well as other relay data at the point of trigger.
Oscillography records are triggered by a programmable FlexLogic operand. Multiple oscillography records can be captured
simultaneously.
To retrieve an Oscillography record from a relay:
1. If not yet set up for oscillography, configure settings under Settings > Product Setup > Oscillography in the EnerVista
software.
2. Access Actual Values > Records > Oscillography in the EnerVista software.
3. In the window that opens, select the record number. The highest number is the most recent record (Newest Record
Number).
4. Click the Read button to get the waveform. When available, waveforms are displayed graphically, and otherwise error
messages display.
5. In the waveform window that opens, you can save the file, for example with the CFG extension.
When EnerVista UR Setup creates a new settings file, a Smart defaults feature automatically enters a basic oscillography
configuration. The basic configuration changes the factory default values to make the number of samples per cycle 32,
adds a selection of digital and analog channels that are often of interest, and adds a FlexLogic equation to trigger
oscillography. Review and update this basic configuration as required for the application at hand.
The NUMBER OF RECORDS is selectable, but the number of cycles captured in a single record varies considerably based on
other factors, such as sample rate and the number of operational modules. There is a fixed amount of data storage for
oscillography; the more data captured, the less the number of cycles captured per record. See the ACTUAL VALUES
RECORDS OSCILLOGRAPHY menu to view the number of cycles captured per record. The following table provides sample
configurations with corresponding cycles/record. The minimum number of oscillographic records is three.
TRIGGER MODE — A new record automatically overwrites an older record when TRIGGER MODE is set to “Automatic
Overwrite.”
TRIGGER POSITION — Set this to a percentage of the total buffer size (for example, 10%, 50%, 75%, and so on). A trigger
position of 25% consists of 25% pre- and 75% post-trigger data.
TRIGGER SOURCE — Always captured in oscillography and can be any FlexLogic parameter (element state, contact input,
virtual output, and so on). The relay sampling rate is 64 samples per cycle.
AC INPUT WAVEFORMS — Determines the sampling rate at which AC input signals (that is, current and voltage) are stored.
Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of
the relay, which is always 64 samples per cycle. That is, it has no effect on the fundamental calculations of the device.
5 When changes are made to the oscillography settings, all existing oscillography records are cleared.
DIGITAL 1(63) CHANNEL — This setting selects the FlexLogic operand state recorded in an oscillography trace. The length of
each oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored.
To populate quickly the rows in the Offline Window, use Ctrl C/V to copy/paste, or click then double-click a row to display a
quick selection window.
Figure 5-74: Quick selection window
These settings select the metering actual value recorded in an oscillography trace. The length of each oscillography trace
depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. The parameters available
in a given relay depend on
• the type of relay,
• the type and number of CT/VT hardware modules installed, and
• the type and number of analog input hardware modules installed
A list of all possible analog metering actual value parameters is presented in Appendix A: FlexAnalog Parameters. The
parameter index number shown in any of the tables is used to expedite the selection of the parameter on the relay display.
It can be time-consuming to scan through the list of parameters via the relay keypad and display — entering this number
via the relay keypad causes the corresponding parameter to display.
All eight CT/VT module channels are stored in the oscillography file. The CT/VT module channels are named as follows:
<slot_letter><terminal_number>—<I or V><phase A, B, or C, or 4th input>
The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IB
designates the IB signal on terminal 2 of the CT/VT module in slot F.
If there are no CT/VT modules and analog input modules, no analog traces appear in the file; only the digital traces appear. 5
5.3.10 Data logger
SETTINGS PRODUCT SETUP DATA LOGGER
DATA LOGGER DATA LOGGER MODE: Range: Continuous, Trigger
Continuous
DATA LOGGER CONFIG: Range: Not applicable - shows computed data only
0 CHNL x 0.0 DAYS
The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data can
be downloaded to EnerVista UR Setup and displayed with parameters on the vertical axis and time on the horizontal axis.
All data is stored in non-volatile memory, so the information is retained when power to the relay is lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use. The
following table outlines examples of storage capacities for a system frequency of 60 Hz.
Changing any setting affecting data logger operation clears data in the log.
5 DATA LOGGER MODE — This setting configures the mode in which the data logger operates. When set to “Continuous,” the
data logger actively records any configured channels at the rate as defined by the DATA LOGGER RATE. The data logger is
idle in this mode when no channels are configured. When set to “Trigger,” the data logger records any configured channels
at the instance of the rising edge of the DATA LOGGER TRIGGER source FlexLogic operand. The data logger ignores all
subsequent triggers and continues to record data until the active record is full. Once the data logger is full, a CLEAR DATA
LOGGER command is required to clear the data logger record before a new record can be started. Performing the CLEAR
DATA LOGGER command also stops the current record and resets the data logger to be ready for the next trigger.
DATA LOGGER TRIGGER — This setting selects the signal used to trigger the start of a new data logger record. Any FlexLogic
operand can be used as the trigger source. This setting only applies when the mode is set to “Trigger.”
DATA LOGGER RATE — This setting selects the time interval at which the actual value data is recorded.
DATA LOGGER CHNL 1(16) — This setting selects the metering actual value that is to be recorded in Channel 1(16) of the data
log. The parameters available in a given relay are dependent on: the type of relay, the type and number of CT/VT hardware
modules installed, and the type and number of Analog Input hardware modules installed. Upon startup, the relay
automatically prepares the parameter list. A list of all possible analog metering actual value parameters is shown in
Appendix A: FlexAnalog Parameters. The parameter index number shown in any of the tables is used to expedite the
selection of the parameter on the relay display. It can be time-consuming to scan through the list of parameters via the
relay keypad/display—entering this number via the relay keypad causes the corresponding parameter to display.
DATA LOGGER CONFIG — This display presents the total amount of time that the Data Logger can record the channels not
selected to “Off” without overwriting old data.
5.3.11 Demand
SETTINGS PRODUCT SETUTP DEMAND
DEMAND CRNT DEMAND METHOD: Range: Thermal Exponential, Block Interval, Rolling
Thermal Exponential Demand
The relay measures current demand on each phase, and three-phase demand for real, reactive, and apparent power.
Current and Power methods can be chosen separately for the convenience of the user. Settings are provided to allow the
user to emulate common electrical utility demand measuring techniques, for statistical or control purposes. If the CRNT
DEMAND METHOD is set to "Block Interval" and the DEMAND TRIGGER is set to “Off,” Method 2 is used as follows. If DEMAND
TRIGGER is assigned to any other FlexLogic operand, Method 2a is used as follows.
The relay can be set to calculate demand by any of the following three methods.
Eq. 5-6
where
d = demand value after applying input quantity for time t (in minutes)
D = input quantity (constant)
k = 2.3 / thermal 90% response time
The figure shows the 90% thermal response time characteristic of 15 minutes. A setpoint establishes the time to reach
90% of a steady-state value, just as the response time of an analog instrument. A steady state value applied for twice the
5
response time indicates 99% of the value.
Figure 5-75: Thermal demand characteristic
Demand (%)
5.3.11.3 Calculation method 2a: Block interval (with start demand interval logic trigger)
This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over
the interval between successive Start Demand Interval logic input pulses. Each new value of demand becomes available at
the end of each pulse. Assign a FlexLogic operand to the DEMAND TRIGGER setting to program the input for the new
demand interval pulses.
If no trigger is assigned in the DEMAND TRIGGER setting and the CRNT DEMAND METHOD is "Block Interval," use
calculation method 2. If a trigger is assigned, the maximum allowed time between two trigger signals is 60 minutes.
If no trigger signal appears within 60 minutes, demand calculations are performed and available, and the algorithm
resets and starts the new cycle of calculations. The minimum required time for trigger contact closure is 20 µs.
The LEDs can be customized to illuminate when a selected FlexLogic operand is in the logic 1 state. The trip and alarm
LEDs can also be customized in a similar manner. To ensure correct functionality of all LEDs, an LED test feature is also
provided.
When enabled, the LED test can be initiated from any digital input or user-programmable condition, such as a user-
programmable pushbutton. The control operand is configured under the LED TEST CONTROL setting. The test covers all
LEDs, including the LEDs of the optional user-programmable pushbuttons.
For the enhanced and basic front panels, the test consists of the following three stages:
1. All 62 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is “burned.” This stage lasts as
long as the control input is on, up to a maximum of one minute. After one minute, the test ends.
2. All the LEDs are turned off, and then one LED at a time turns on for one second, then back off. The test routine starts at
the top left panel, moving from the top to bottom of each LED column. This test checks for hardware failures that lead
to more than one LED being turned on from a single logic point. This stage can be interrupted at any time.
3. All the LEDs are turned on. One LED at a time turns off for one second, then back on. The test routine starts at the top
left panel moving from top to bottom of each column of the LEDs. This test checks for hardware failures that lead to
more than one LED being turned off from a single logic point. This stage can be interrupted at any time.
For the graphical front panel, the test consists of the following stages:
1. All 22 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is "burned." This stage lasts as
long as the control input is on, up to a maximum of one minute. After one minute, the test ends.
2. All the LEDs are turned off, and then one LED at a time turns on with the orange color for one second, then back off.
The test routine starts at the top left panel, moving from the top to bottom for all 14 LEDs. Then the eight pushbutton
LEDs are tested in the same manner. This test checks for hardware failures that lead to more than one LED being
turned on from a single logic point. This stage can be interrupted at any time.
3. All the LEDs are turned on with the orange color. One LED at a time turns off for one second, then back on. The test
routine starts at the top left panel moving from top to bottom for all 14 LEDs. Then the eight pushbutton LEDs are
tested in the same manner. This test checks for hardware failures that lead to more than one LED being turned off
from a single logic point. This stage can be interrupted at any time.
4. Additionally, stages 2 and 3 are repeated twice for the five device status LEDs and nine event cause LEDs, one time 5
with green color on and the other with red color on.
When testing is in progress, the LEDs are controlled by the test sequence, rather than the protection, control, and
monitoring features. However, the LED control mechanism accepts all the changes to LED states generated by the relay
and stores the actual LED states (on or off) in memory. When the test completes, the LEDs reflect the actual state resulting
from relay response during testing. The reset pushbutton does not clear any targets when the LED Test is in progress.
A dedicated FlexLogic operand, LED TEST IN PROGRESS, is set for the duration of the test. When the test sequence is initiated,
the LED TEST INITIATED event is stored in the event recorder.
The entire test procedure is user-controlled. In particular, stage 1 can last as long as necessary, and stages 2 and 3 can be
interrupted. The test responds to the position and rising edges of the control input defined by the LED TEST CONTROL
setting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is
executed.
READY TO TEST
Reset the
LED TEST IN PROGRESS
rising edge of the
operand
control input
Set the
LED TEST IN PROGRESS
operand
control input is on
STAGE 1 time-out
(all LEDs on) (1 minute)
5
Wait 1 second
control input
rising edge
STAGE 3
of the control
(one LED off at a time) input
842011A1.CDR
Application example 1
Assume one needs to check if any of the LEDs is “burned” through user-programmable pushbutton 1. Apply the following
settings.
Configure user-programmable pushbutton 1 by making the following entries in the SETTINGS PRODUCT SETUP USER-
PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu. (The option does not display when not purchased.)
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.10 s”
Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the SETTINGS
PRODUCT SETUP USER-PROGRAMMABLE LEDS LED TEST menu:
LED TEST FUNCTION: “Enabled”
LED TEST CONTROL: “PUSHBUTTON 1 ON”
The test is initiated when the user-programmable pushbutton 1 is pressed. Keep the pushbutton pressed for as long as the
LEDs are being visually inspected. When finished, release the pushbutton. The relay then automatically starts stage 2. At
this point, test can be cancelled by pressing the pushbutton.
Application example 2
Assume one needs to check if any LEDs are “burned” as well as exercise one LED at a time to check for other failures. This
is to be performed via user-programmable pushbutton 1.
After applying the settings in application example 1, hold down the pushbutton as long as necessary to test all LEDs. When
finished, release the pushbutton so that the relay then automatically starts stage 2. When stage 2 is completed, stage 3
starts automatically. The test can be cancelled at any time by pressing the pushbutton.
The trip and alarm LEDs are in the first LED column (enhanced and graphical front panels) and on LED panel 1 (basic front
panel). Each LED can be programmed to turn on when the selected FlexLogic operand is in the logic 1 state.
For the enhanced and basic front panels, there are 48 amber LEDs across the relay LED panels. Each of these indicators
can be programmed to illuminate when the selected FlexLogic operand is in the logic 1 state.
For the basic front panel, the LEDs are located as follows:
• LED Panel 2 — User-programmable LEDs 1 through 24
• LED Panel 3 — User programmable LEDs 25 through 48
For the enhanced front panel, the LEDs are located as follows: 5
• LED column 2 — User-programmable LEDs 1 through 12
• LED column 3 — User-programmable LEDs 13 through 24
• LED column 4 — User-programmable LEDs 25 through 36
• LED column 5 — User-programmable LEDs 37 through 48
See the LED Indicators section in chapter 4 for information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the LED 1 TYPE setting is “Self-
Reset” (the default setting), the LED illumination tracks the state of the selected LED operand. If the LED 1 TYPE setting is
“Latched,” the LED, once lit, remains so until reset by the front panel RESET button, from a remote device via a
communications channel, or from any programmed operand, even if the LED operand state de-asserts.
Table 5-17: Recommended settings for user-programmable LEDs
Setting Parameter Setting Parameter
LED 1 operand SETTING GROUP ACT 1 LED 13 operand Off
LED 2 operand SETTING GROUP ACT 2 LED 14 operand BREAKER 2 OPEN
LED 3 operand SETTING GROUP ACT 3 LED 15 operand BREAKER 2 CLOSED
LED 4 operand SETTING GROUP ACT 4 LED 16 operand BREAKER 2 TROUBLE
LED 5 operand SETTING GROUP ACT 5 LED 17 operand SYNC 1 SYNC OP
LED 6 operand SETTING GROUP ACT 6 LED 18 operand SYNC 2 SYNC OP
LED 7 operand Off LED 19 operand Off
LED 8 operand Off LED 20 operand Off
LED 9 operand BREAKER 1 OPEN LED 21 operand AR ENABLED
LED 10 operand BREAKER 1 CLOSED LED 22 operand AR DISABLED
LED 11 operand BREAKER 1 TROUBLE LED 23 operand AR RIP
LED 12 operand Off LED 24 operand AR LO
See the figure in the Setting Groups section of the Control Elements section later in this chapter for an example of group
activation.
For the graphical front panel, the event cause LED settings select the FlexLogic operands that control the LEDs.
LED 1 TYPE — If set to "Self-Reset," the LED illumination tracks the state of the selected LED operand. If set to "Latched," the
LED, once lit, remains so even the LED operand state already de-asserts, until reset by the front panel RESET button, from a
remote device via a communications channel, or from any programmed operand.
The table outlines default input operand and output operands for each event cause LED.
Table 5-18: Default input and output operand for event cause LEDs
LED Default input operand Output operand Default color
Event Cause LED 1 LED PICKUP EVENT CAUSE LED 1 Green
Event Cause LED 2 LED VOLTAGE EVENT CAUSE LED 2 Orange
DIRECT DEVICE OFF Range: Disabled, Enabled. Valid for units equipped
FUNCTION: Enabled with Direct Input/Output module.
All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets.
This settings menu allows enabling and disabling of most minor self-test alarms.
When in the Disabled mode, minor alarms do not assert a FlexLogic operand, write to the event recorder, or display target
messages. Moreover, they do not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in Enabled mode,
minor alarms continue to function along with other major and minor alarms. See the Relay Self-tests section in chapter 7
for information on major and minor self-test alarms.
When using the graphical front panel and setting annunciator alarms, the function needs to be enabled here too, else the
alarm is not triggered.
Control pushbuttons
842813A1.CDR
An additional four control pushbuttons are included on the basic front panel when the F35 is ordered with the 12 user-
programmable pushbutton option.
USER 4
842733A2.CDR
Control pushbuttons are not typically used for critical operations and are not protected by the control password. However,
by supervising their output operands, the user can dynamically enable or disable control pushbuttons for security reasons.
Each control pushbutton asserts its own FlexLogic operand. Each operand need to be configured appropriately to perform
the required function. Each operand remains asserted as long as the pushbutton is pressed and resets when the
pushbutton is released. A dropout delay of 100 ms is incorporated to ensure fast pushbutton manipulation is recognized
by various features that can use control pushbuttons as inputs.
An event is logged in the event record (as per user setting) when a control pushbutton is pressed. No event is logged when
5 the pushbutton is released. The front panel keys (including control keys) cannot be operated simultaneously—a given key
must be released before the next one can be pressed.
Figure 5-79: Control pushbutton logic
SETTING
CONTROL PUSHBUTTON
{
1 FUNCTION:
Enabled=1
SETTINGS
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
CONTROL:
When applicable
AND RUN
Enabled=1
OFF TIMER
SYSTEM SETUP/ FLEXLOGIC OPERAND
BREAKERS/BREAKER 2/ ON 0 CONTROL PUSHBTN 1 ON
BREAKER 2 PUSHBUTTON 100 msec
CONTROL:
842010A2.CDR
Enabled=1
5
The F35 is provided with this optional feature, specified as an option at the time of ordering. Using the order
code for your device, see the order codes in chapter 2 for details.
User-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off) information. The
number depends on the front panel ordered.
• Enhanced horizontal front panel — 16 user-programmable pushbuttons
• Enhanced vertical front panel — 6 user-programmable pushbuttons
• Basic horizontal front panel — 12 user-programmable pushbuttons
• Graphical front panel — 16 user-programmable pushbuttons (eight physical pushbuttons, eight graphical interface
pushbuttons)
User-programmable pushbuttons require a front panel with that option. If the front panel was ordered separately,
update the EnerVista software under Maintenance > Change Front Panel.
The digital state can be entered locally (by directly pressing the front panel pushbutton or optional graphical front panel
interface) or remotely (via FlexLogic operands) into FlexLogic equations, protection elements, and control elements. Typical
applications include breaker control, autorecloser blocking, and setting groups changes. For example, set pushbuttons 1 to
5 to select settings groups 1 to 5, or set pushbutton 1 to clear event records. The user-programmable pushbuttons are
under the control level of password protection.
Example
To clear event records using pushbutton 1, set Settings > Product Setup > Clear Relay Records > Clear Event Records to
FlexLogic operand PUSHBUTTON 1 ON. Then program the pushbutton by setting Settings > Product Setup > User-
Programmable Pushbuttons > Pushbutton 1 Function to "Self-reset." For a graphical front panel, to use a side
pushbutton 9 to 16 to clear the event records, it also needs to be programmed in a single-line diagram.
The figures show user-configurable pushbuttons for the front panels.
842814A1.CDR
1 3 5 7 9 11
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL
2 4 6 8 10 12
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL
842779A1.cdr
5
1 5
2 6
3 7
4 8
RESET ESC
ENTER
859761A1.CDR
Front panel pushbuttons and LEDs can be custom labelled as outlined in the Front Panel Labelling section in the previous
chapter.
Each pushbutton asserts its own “On” and “Off” FlexLogic operands (for example, PUSHBUTTON 1 ON and PUSHBUTTON 1 OFF).
These operands are available for each pushbutton and are used to program specific actions. If any pushbutton is active,
the ANY PB ON operand is asserted.
Each pushbutton has an associated LED indicator. By default, this indicator displays the present status of the
corresponding pushbutton (on or off). However, each LED indicator can be assigned to any FlexLogic operand through the
PUSHBTN 1 LED CTL setting.
The activation and deactivation of user-programmable pushbuttons depends on whether latched or self-reset mode is
programmed.
• Latched mode — In latched mode, a pushbutton can be set (activated) by asserting the operand assigned to the
PUSHBTN 1 SET setting, by directly pressing the associated front panel pushbutton, or with the graphical front panel
interface. The state of each pushbutton is stored in non-volatile memory and maintained through a loss of control
power.
The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the PUSHBTN 1 RESET
setting, by directly pressing the active front panel pushbutton, or with the graphical front panel interface.
It can also be programmed to reset automatically through the PUSHBTN 1 AUTORST and PUSHBTN 1 AUTORST DELAY
settings. These settings enable the autoreset timer and specify the associated time delay. The autoreset timer can be
used in select-before-operate (SBO) breaker control applications, where the command type (close/open) or breaker
location (feeder number) must be selected prior to command execution. The selection must reset automatically if
control is not executed within a specified time period.
• Self-reset mode — In self-reset mode, a user-programmable pushbutton can be set (activated) by asserting the
operand assigned to the PUSHBTN 1 SET setting, by pressing the front panel pushbutton, or by the graphical front panel
interface. A pushbutton remains active for the time it is pressed physically or pressed in the graphical front panel
interface, plus the dropout time specified in the PUSHBTN 1 DROP-OUT TIME setting. If the pushbutton is activated via
FlexLogic, the pulse duration is specified by the PUSHBTN 1 DROP-OUT TIME only. The time the operand assigned to the
PUSHBTN 1 SET setting remains On has no effect on the pulse duration.
The pulse duration of the remote set or local front panel pushbutton must be at least 50 ms to operate the
pushbutton. This allows the user-programmable pushbuttons to properly operate during power cycling events and
various system disturbances that can cause transient assertion of the operating signals.
The local and remote operation of each user-programmable pushbutton can be inhibited through the PUSHBTN 1 LOCAL
and PUSHBTN 1 REMOTE settings. If local inhibit is applied, the pushbutton ignores set and reset commands executed
through the front panel pushbuttons. If remote inhibit is applied, the pushbutton ignores set and reset commands
executed through FlexLogic operands.
The inhibit functions are not applied to the autoreset feature. The inhibit function can be used in SBO control operations to
prevent user-programmable pushbutton activation and ensuring “one-at-a-time” select operation. 5
The inhibit functions can also be used to prevent pushbutton activation from the accidental pressing of the front panel
pushbuttons. The separate inhibit of the local and remote operation simplifies the implementation of local/remote control
supervision.
Pushbutton states can be logged by the event recorder. User-defined messages can also be associated with each
pushbutton and displayed on basic and enhanced front panels when the user-programmable pushbutton is activated, and
when in the latched mode when the user-programmable pushbutton is deactivated. With the graphical front panel
interface, instead of messages, the status of user-programmable pushbuttons can display on a single-line diagram and
can also display in annunciator page windows and in actual values page cells.
For the graphical front panel, the pushbuttons 1 to 8 are linked to the eight physical pushbuttons, and pushbuttons 9 to 16
are mapped to the graphical interface pushbuttons. To set the buttons for pushbuttons 9 to 16, access Settings > Product
Setup > Graphical Panel > Single Line Diagram Editor, click the PB symbol in the toolbox, then configure pushbuttons 9 to
16.
PUSHBUTTON 1 FUNCTION — This setting selects the mode of the pushbutton (Self-Reset, Latched, Disabled). If set to
“Disabled,” the pushbutton is not active and the corresponding FlexLogic operands (both “On” and “Off”) are de-asserted. If
set to "Latched," the pushbutton remains on until reset.
PUSHBTN 1 ID TEXT — This setting specifies the top 20-character line of the user-programmable pushbutton message and is
intended to provide ID information of the pushbutton. For example, the text displays in the Event Record. See the User-
definable Displays section in this chapter for instructions on how to enter alphanumeric characters from the keypad. On a
graphical front panel, this setting instead controls the label of the user-programmable pushbutton component on single-
line diagrams.
PUSHBTN 1 ON TEXT — This setting specifies the bottom 20-character line of the user-programmable pushbutton message
and is displayed when the pushbutton is in the “on” position. See the User-definable Displays section for instructions on
entering alphanumeric characters from the keypad. On a graphical front panel, this setting instead controls the on status
text of the user-programmable pushbutton component on single-line diagrams. This setting is not applied to the physical
pushbuttons on the graphical front panel.
PUSHBTN 1 OFF TEXT — This setting specifies the bottom 20-character line of the user-programmable pushbutton message
and displays when the pushbutton is deactivated and the PUSHBUTTON 1 FUNCTION is “Latched.” A message does not
display when the PUSHBUTTON 1 FUNCTION is “Self-reset” as the pushbutton operand status is implied to be “Off” upon its
release. The length of the “Off” message is configured with the PRODUCT SETUP DISPLAY PROPERTIES FLASH MESSAGE
TIME setting. On a graphical front panel, this setting instead controls the off status text of the user-programmable
pushbutton component on single-line diagrams. This setting is not applied to the physical pushbuttons on the graphical
front panel.
PUSHBTN 1 HOLD — This setting specifies the time required for a front panel pushbutton to be pressed before it is deemed
active. This timer is reset upon release of the pushbutton. Note that user-programmable pushbutton operation requires the
front panel pushbutton to be pressed a minimum of 50 ms. This minimum time is required prior to activating the user-
programmable pushbutton hold timer.
PUSHBTN 1 SET — This setting assigns the FlexLogic operand serving to activate the user-programmable pushbutton
element. The duration of the incoming set signal must be at least 50 ms.
PUSHBTN 1 RESET — This setting assigns the FlexLogic operand serving to deactivate the user-programmable pushbutton
element. This setting is applicable only if the user-programmable pushbutton is in "Latched" mode.
PUSHBTN 1 AUTORST — This setting enables the user-programmable pushbutton autoreset feature. This setting is applicable
only if the pushbutton is in “Latched” mode.
PUSHBTN 1 AUTORST DELAY — This setting specifies the time delay for automatic reset of the pushbutton when in "Latched"
mode.
PUSHBTN 1 REMOTE — This setting assigns the FlexLogic operand serving to inhibit user-programmable pushbutton
operation from the operand assigned to the PUSHBTN 1 SET or PUSHBTN 1 RESET settings.
PUSHBTN 1 LOCAL — This setting assigns the FlexLogic operand serving to inhibit user-programmable pushbutton operation
from the front panel pushbuttons. This inhibit functionality is not applicable to pushbutton autoreset.
5 PUSHBTN 1 DROP-OUT TIME — This setting applies only to “Self-Reset” mode and specifies the duration of the user-
programmable pushbutton active status after the front panel pushbutton or graphical front panel interface pushbutton
has been released. When activated remotely, this setting specifies the entire activation time of the pushbutton; the length
of time the operand selected by PUSHBTN 1 SET remains on has no effect on the pulse duration.
PUSHBTN 1 LED CTL — This setting assigns the FlexLogic operand serving to drive the front panel pushbutton LED. If this
setting is “Off,” then LED operation is directly linked to the PUSHBUTTON 1 ON operand. This setting is not applied to
Pushbuttons 9 to 16 on the graphical front panel, where the label background shows the orange glow color for the "on"
state.
PUSHBTN 1 MESSAGE — This setting controls the behavior of the user-programmable pushbutton on message that is
programmed in the PUSHBTN 1 ID and PUSHBTN 1 ON TEXT settings, and the behavior of the user-programmable pushbutton
off message that is programmed in the PUSHBTN 1 ID and PUSHBTN 1 OFF TEXT settings. This settings has no effect on the
graphical front panel.
When set to "Disabled", user-programmable pushbutton messages do not display. Otherwise the on message displays
when the user-programmable pushbutton becomes activated, and if in the "Latched" mode the off message displays when
the user-programmable pushbutton becomes deactivated.
When set to "Normal", the duration the message displays is as specified by the FLASH MESSAGE TIME setting.
When set to "High Priority", the duration of the off message is as specified by the FLASH MESSAGE TIME setting, but the on
message is displayed as long as the user-programmable pushbutton is activated. While activated, target and other
messages are suppressed. To allow front panel keypad operation, when a keypad button is pressed the message is
supressed for 10 seconds.
PUSHBUTTON 1 EVENTS — If this setting is enabled, each user-programmable pushbutton state change is logged as an
event into the event recorder.
The figures show the user-programmable pushbutton logic.
SETTING 0 OR
PUSHBTN 1 SET
Off = 0 TIMER
50 ms Non-volatile latch
SETTING AND S
AND
0
PUSHBTN 1 REMOTE Latch
Off = 0 R
TIMER
SETTING 200 ms
PUSHBUTTON 1 OFF
0
SETTING
PUSHBTN 1 RESET AND
Off = 0
OR To user-programmable
SETTING OR PUSHBUTTON ON pushbuttons logic
SETTING sheet 2
PUSHBTN 1 AUTORST DELAY
PUSHBTN 1 AUTORST
TPKP
= Enabled
AND AND
= Disabled
5
0
TIMER
FLEXLOGIC OPERAND 200 ms OR
PUSHBUTTON 1 ON
0
SETTING
AND PUSHBTN 1 DROP-OUT TIME
0
OR
TRST
AND
842237A1.CDR
OFF MESSAGE
ENGAGE MESSAGE
SETTING
LATCHED FLASH MESSAGE TIME
SETTINGS
0 PUSHBTN ID TEXT
AND
OR TRST = XXXXXXXXXX
PUSHBTN OFF TEXT
= XXXXXXXXXX
Instantaneous
From user-programmable reset * Enhanced and standard front panels
pushbuttons logic sheet 1
FLEXLOGIC OPERAND
LATCHED/SELF-RESET
AND PUSHBUTTON 1 OFF
FLEXLOGIC OPERAND
PUSHBUTTON ON PUSHBUTTON 1 ON
ON MESSAGE
SETTING ENGAGE MESSAGE
PUSHBTN 1 MESSAGE
AND
= Disabled
= High Priority SETTINGS
= Normal PUSHBTN ID TEXT
= XXXXXXXXXX
OR
PUSHBTN ON TEXT
SETTING
= XXXXXXXXXX
FLASH MESSAGE TIME
0 Enhanced and standard front panels
AND
TRST The message is temporarily removed if
5
any keypad button is pressed. Ten
seconds of keypad inactivity restores
Instantaneous
Instantaneous reset is executed if any reset * the message.
front panel button is pressed or any new
target or message becomes active.
This feature provides a mechanism where any of 256 selected FlexLogic operand states can be used for efficient
monitoring. The feature allows user-customized access to the FlexLogic operand states in the relay. The state bits are
packed so that 16 states are readable in a single Modbus register. The state bits can be configured so that all states of
interest are available in a minimum number of Modbus registers.
The state bits can be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. Sixteen registers accommodate the 256
state bits.
5.3.17.1 Menu
SETTINGS PRODUCT SETUP USER-DEFINABLE DISPLAYS
USER-DEFINABLE INVOKE AND SCROLL: Range: FlexLogic operand
DISPLAYS Off
Any existing system display can be automatically copied into an available user display by selecting the existing display and
pressing the ENTER key. The display then prompts with ADD TO USER DISPLAY LIST? After selecting “Yes,” a message
indicates that the selected display has been added to the user display list. When this type of entry occurs, the sub-menus
are automatically configured with the proper content—this content can be edited subsequently.
This menu is used to enter user-defined text and user-selected Modbus-registered data fields into the particular user
display. Each user display consists of two 20-character lines (top and bottom). The tilde (~) character is used to mark the
start of a data field – the length of the data field needs to be accounted for. Up to five separate data fields can be entered
in a user display – the nth tilde (~) refers to the nth item.
A user display can be entered from the front panel keypad or the EnerVista interface (preferred for convenience). The
following procedure shows how to enter text characters in the top and bottom lines from the front panel keypad:
1. Select the line to be edited.
2. Press the decimal key to enter text edit mode.
3. Use either VALUE key to scroll through the characters. A space is selected like a character.
4. Press the decimal key to advance the cursor to the next position.
5. Repeat step 3 and continue entering characters until the desired text is displayed.
6. The HELP key can be pressed at any time for context sensitive help information.
7. Press the ENTER key to store the new settings.
To enter a numerical value for any of the five items (the decimal form of the selected Modbus address) from the front panel
keypad, use the number keypad. Use the value of “0” for any items not being used. Use the HELP key at any selected
system display (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the
Modbus address, then manually convert it to decimal form before entering it (EnerVista usage conveniently facilitates this
conversion).
Use the MENU key to go to the user displays menu to view the user-defined content. The current user displays show in
sequence, changing every four seconds. While viewing a user display, press the ENTER key and then select the ‘Yes” option
to remove the display from the user display list. Use the MENU key again to exit the user displays menu.
An example of user display setup and result is shown as follows.
5 USER DISPLAY 1
DISP 1 TOP LINE: Shows user-defined text with first tilde marker
Current X ~ A
DISP 1 BOTTOM LINE: Shows user-defined text with second tilde marker
Current Y ~ A
If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the bottom
line only. The units are only displayed on both lines if the units specified both the top and bottom line items are different.
5.3.18.1 Menu
SETTINGS PRODUCT SETUP DIRECT I/O
DIRECT I/O DIRECT OUTPUTS Range: 1 to 16 in steps of 1
DEVICE ID: 1
UNRETURNED
MESSAGES ALARM CH2
5
This option is available when an Inter-Relay Communications card is specified at the time of ordering (see the
Order Code tables). With the option, direct inputs/outputs display by default. When you enable the
teleprotection feature, direct I/O is not visible.
Direct inputs and outputs exchange status information (inputs and outputs) between UR-series relays connected directly
via type 7 digital communications cards. The mechanism is very similar to IEC 61850 GOOSE, except that communications
takes place over a non-switchable isolated network and is optimized for speed. On type 7 cards that support two channels,
direct output messages are sent from both channels simultaneously. This effectively sends direct output messages both
ways around a ring configuration. On type 7 cards that support one channel, direct output messages are sent only in one
direction. Messages are resent (forwarded) when it is determined that the message did not originate at the receiver.
Direct Inputs and Outputs are initiated automatically and start running once at least one Direct Output in the given UR is
set to anything but Off.
Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive. As such, they cannot be used
simultaneously. Once teleprotection inputs and outputs are enabled, direct inputs and outputs are disabled, and
vice versa.
Direct output message timing is similar to GOOSE message timing. Integrity messages (with no state changes) are sent at
least every 1000 ms. Messages with state changes are sent within the main pass scanning the inputs and asserting the
outputs unless the communication channel bandwidth has been exceeded. Two self-tests are performed and signaled by
the following FlexLogic operands:
• DIRECT RING BREAK (direct input/output ring break). This FlexLogic operand indicates that direct output messages sent
from a UR-series relay are not being received back by the relay.
• DIRECT DEVICE 1 OFF to DIRECT DEVICE 16 OFF (direct device offline). These FlexLogic operands indicate that direct output
messages from at least one direct device are not being received.
Direct input and output settings are similar to remote input and output settings. The equivalent of the remote device name
strings for direct inputs and outputs is the DIRECT OUTPUT DEVICE ID setting, which identifies the relay in all direct output
messages. All UR-series IEDs in a ring need to have unique numbers assigned. The IED ID is used to identify the sender of
the direct input and output message.
If the direct input and output scheme is configured to operate in a ring (DIRECT I/O CH1 RING CONFIGURATION or DIRECT I/O
CH2 RING CONFIGURATION is “Yes”), all direct output messages are received back. If not, the direct input/output ring break
self-test is triggered. The self-test error is signaled by the DIRECT RING BREAK FlexLogic operand.
Select the DIRECT I/O DATA RATE to match the data capabilities of the communications channel. All IEDs communicating
over direct inputs and outputs must be set to the same data rate. UR-series IEDs equipped with dual-channel
communications cards apply the same data rate to both channels. Delivery time for direct input and output messages is
approximately 0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each "bridge."
Table 5-19: Direct input and output data rates
Module Supported data rates
2A, 2B 64 kbps
2E, 2F 64 kbps
2G, 2H 128 kbps
2I, 2J 64 kbps, 128 kbps
72, 73 64 kbps, 128 kbps
74, 75 64 kbps
76, 77 64 kbps
7A, 7B, 7C, 7D 64 kbps, 128 kbps
7E, 7F, 7G 64 kbps
5 7H, 7I, 7J, 7K 64 kbps, 128 kbps
7L, 7M, 7N, 7P, 7Q 64 kbps
7R, 7S 64 kbps
7T, 7W 64 kbps
The G.703 modules are fixed at 64 kbps. The DIRECT I/O DATA RATE setting is not applicable to these modules.
The DIRECT I/O CHANNEL CROSSOVER setting applies to a F35 with dual-channel communication cards and allows crossing
over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network
regardless of the physical media of the two communication channels.
The following application examples illustrate the basic concepts for direct input and output configuration. See the Inputs
and Outputs section in this chapter for information on configuring FlexLogic operands (flags, bits) to be exchanged.
Figure 5-85: Input and output extension via direct inputs and outputs
TX1
UR IED 1
RX1
TX1
UR IED 2
RX1
842711A1.CDR
UR IED 1 BLOCK
842712A1.CDR
For increased reliability, a dual-ring configuration (shown as follows) is recommended for this application.
Figure 5-87: Interlocking bus protection scheme via direct inputs/outputs
TX1 RX1
UR IED 1
RX2 TX2
TX2 RX2
UR IED 3
RX1 TX1
842716A1.CDR
UR IED 1 UR IED 2
UR IED 3 842713A1.CDR
A permissive pilot-aided scheme can be implemented in a two-ring configuration, shown as follows (IEDs 1 and 2
constitute a first ring, while IEDs 2 and 3 constitute a second ring).
Figure 5-89: Single-channel open loop configuration
UR IED 3
RX1 5
TX1
842714A1.CDR
TX1 RX1
UR IED 3
RX2 TX2
842715A1.CDR
The F35 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is
available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The
monitoring function counts all incoming messages, including messages that failed the CRC check. A separate counter
adds up messages that failed the CRC check. When the failed CRC counter reaches the user-defined level specified by the
CRC ALARM CH1 THRESHOLD setting within the user-defined message count CRC ALARM 1 CH1 COUNT, the DIR IO CH1 CRC
ALARM FlexLogic operand is set.
When the total message counter reaches the user-defined maximum specified by the CRC ALARM CH1 MESSAGE COUNT
setting, both the counters reset and the monitoring process is restarted.
Configure the operand to drive an output contact, user-programmable LED, or selected communication-based output.
Latching and acknowledging conditions—if required—are programmed accordingly.
The CRC alarm function is available on a per-channel basis. The total number of direct input and output messages that
failed the CRC check is available as the ACTUAL VALUES STATUS DIRECT INPUTS CRC FAIL COUNT CH1 actual value.
• Message count and length of the monitoring window — To monitor communications integrity, the relay sends 1
message per second (at 64 kbps) or 2 messages per second (at 128 kbps) even if there is no change in the direct
outputs. For example, setting the CRC ALARM CH1 MESSAGE COUNT to “10000,” corresponds a time window of about 160
minutes at 64 kbps and 80 minutes at 128 kbps. If the messages are sent faster as a result of direct outputs activity,
the monitoring time interval shortens. Take this into account when determining the CRC ALARM CH1 MESSAGE COUNT
setting. For example, if the requirement is a maximum monitoring time interval of 10 minutes at 64 kbps, then the CRC
ALARM CH1 MESSAGE COUNT is set to 10 60 1 = 600.
• Correlation of failed CRC and bit error rate (BER) — The CRC check can fail if one or more bits in a packet are
corrupted. Therefore, an exact correlation between the CRC fail rate and the BER is not possible. Under certain
assumptions an approximation can be made as follows. A direct input and output packet containing 20 bytes results
in 160 bits of data being sent and therefore, a transmission of 63 packets is equivalent to 10,000 bits. A BER of 10–4
implies 1 bit error for every 10000 bits sent or received. Assuming the best case of only 1 bit error in a failed packet,
having 1 failed packet for every 63 received is about equal to a BER of 10–4.
The F35 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring
configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned
messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of
unreturned messages. This function counts all the outgoing messages and a separate counter adds the messages have
failed to return. When the unreturned messages counter reaches the user-definable level specified by the UNRET MSGS
ALARM CH1 THRESHOLD setting and within the user-defined message count UNRET MSGS ALARM CH1 COUNT, the DIR IO CH1
UNRET ALM FlexLogic operand is set.
When the total message counter reaches the user-defined maximum specified by the UNRET MSGS ALARM CH1 MESSAGE
COUNT setting, both the counters reset and the monitoring process is restarted.
Configure the operand to drive an output contact, user-programmable LED, or selected communication-based output.
Latching and acknowledging conditions, if required, are programmed accordingly.
The unreturned messages alarm function is available on a per-channel basis and is active only in the ring configuration.
The total number of unreturned input and output messages is available as the ACTUAL VALUES STATUS DIRECT INPUTS
UNRETURNED MSG COUNT CH1 actual value.
5.3.19 Teleprotection
SETTINGS PRODUCT SETUP TELEPROTECTION
TELEPROTECTION TELEPROTECTION Range: Disabled, Enabled
FUNCTION: Disabled
This option is available when an Inter-Relay Communications card is specified at the time of ordering (see the
Order Code tables). With the option, direct inputs/outputs display by default. When you enable the
teleprotection feature, direct I/O is not visible.
Digital teleprotection transfers protection commands between two or three relays in a secure, fast, dependable, and
deterministic way. Possible applications are permissive or blocking pilot schemes and direct transfer trip (DTT).
Teleprotection can be applied over any analog or digital channels and any communications media, such as direct fiber,
copper wires, optical networks, or microwave radio links. A mixture of communication media is possible.
Once teleprotection is enabled and the teleprotection input/outputs are configured, data packets are transmitted
continuously every 1/4 cycle (3/8 cycle if using C37.94 modules) from peer-to-peer. Security of communication channel
data is achieved by using CRC-32 on the data packet.
Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive. As such, they cannot be used
simultaneously. Once teleprotection inputs and outputs are enabled, direct inputs and outputs are blocked, and
vice versa.
5 NUMBER OF TERMINALS — Specifies whether the teleprotection system operates between two peers or three peers.
NUMBER OF CHANNELS — Specifies how many channels are used. If the NUMBER OF TERMINALS is “3” (three-terminal system),
set the NUMBER OF CHANNELS to “2.” For a two-terminal system, the NUMBER OF CHANNELS can set to “1” or “2” (redundant
channels).
LOCAL RELAY ID NUMBER, TERMINAL 1 RELAY ID NUMBER, and TERMINAL 2 RELAY ID NUMBER — In installations that use
multiplexers or modems, it is desirable to ensure that the data used by the relays protecting a given line is from the correct
relays. The teleprotection function performs this check by reading the message ID sent by transmitting relays and
comparing it to the programmed ID in the receiving relay. This check is also used to block inputs if inadvertently set to
loopback mode or data is being received from a wrong relay by checking the ID on a received channel. If an incorrect ID is
found on a channel during normal operation, the TELEPROT CH1 ID FAIL or TELEPROT CH2 ID FAIL FlexLogic operand is set,
driving the event with the same name and blocking the teleprotection inputs. For commissioning purposes, the result of
channel identification is also shown in the STATUS CHANNEL TESTS VALIDITY OF CHANNEL CONFIGURATION actual
value. The default value of “0” for the LOCAL RELAY ID NUMBER indicates that relay ID is not to be checked. On two- terminals
two-channel systems, the same LOCAL RELAY ID NUMBER is transmitted over both channels; as such, only the TERMINAL 1 ID
NUMBER has to be programmed on the receiving end.
5.3.20 Installation
SETTINGS PRODUCT SETUP INSTALLATION
INSTALLATION RELAY SETTINGS: Range: Not Programmed, Programmed
Not Programmed
RELAY SETTINGS — To safeguard against the installation of a relay without any entered settings, the unit does not allow
signaling of any output relay until RELAY SETTINGS is set to "Programmed." This setting is "Not Programmed" by default. The
UNIT NOT PROGRAMMED self-test error message displays until the relay is put into the "Programmed" state.
RELAY NAME — This setting allows the user to uniquely identify a relay. This name appears on generated reports.
5
The remote resources settings configure a F35 with a process bus module to work with HardFiber Bricks. Remote
resources configuration is only available through the EnerVista software, and is not available through the F35 front panel.
A Brick provides eight AC measurements, along with contact inputs, DC analog inputs, and contact outputs, to be the
remote interface to field equipment such as circuit breakers and transformers. The F35 with a process bus module has
access to all of the capabilities of up to eight Bricks. Remote resources settings configure the point-to-point connection
between specific fiber optic ports on the F35 process card and specific Brick. The relay is then configured to measure
specific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
The configuration process for remote resources is straightforward and consists of the following steps.
• Configure the field units. This establishes the point-to-point connection between a specific port on the relay process
bus module, and a specific digital core on a specific Brick. This is a necessary first step in configuring a process bus
relay.
• Configure the AC banks. This sets the primary and secondary quantities and connections for currents and voltages. AC
bank configuration also provides a provision for redundant measurements for currents and voltages, a powerful
reliability improvement possible with process bus.
• Configure signal sources. This functionality of the F35 has not changed other than the requirement to use currents
and voltages established by AC bank configuration under the remote resources menu.
• Configure field contact inputs, field contact outputs, RTDs, and transducers as required for the application's
functionality. These inputs and outputs are the physical interface to circuit breakers, transformers, and other
equipment. They replace the traditional contact inputs and outputs located at the relay to virtually eliminate copper
wiring.
• Configure shared inputs and outputs as required for the application's functionality. Shared inputs and outputs are
distinct binary channels that provide high-speed protection quality signaling between relays through a Brick.
For additional information on how to configure a relay with a process bus module, see the HardFiber Process Bus System
Instruction Manual.
PHASE CT F1 Range: 1 A, 5 A
SECONDARY: 1 A
GROUND CT F1 Range: 1 A, 5 A
SECONDARY: 1 A
Because energy parameters are accumulated, record these values and then reset immediately prior to changing CT
characteristics.
Six banks of phase and ground CTs can be set, where the current banks are denoted in the following format (X represents
the module slot position letter):
Xa, where X = {F, M, U} and a = {1, 5}
5 See the Introduction to AC Sources section at the beginning of this chapter for details.
These settings are critical for all features that have settings dependent on current measurements. When the relay is
ordered, the CT module must be specified to include a standard or sensitive ground input. As the phase CTs are connected
in wye (star), the calculated phasor sum of the three phase currents (IA + IB + IC = neutral current = 3Io) is used as the input
for the neutral overcurrent elements. In addition, a zero-sequence (core balance) CT which senses current in all of the
circuit primary conductors, or a CT in a neutral grounding conductor can also be used. For this configuration, the ground
CT primary rating must be entered. To detect low level ground fault currents, the sensitive ground input can be used. In this
case, the sensitive ground CT primary rating must be entered. See chapter 3 for more details on CT connections.
Enter the rated CT primary current values. For both 1000:5 and 1000:1 CTs, the entry would be 1000. For correct operation,
the CT secondary rating must match the setting (which must also correspond to the specific CT connections used).
The following example illustrates how multiple CT inputs (current banks) are summed as one source current. Given the
following current banks:
• F1: CT bank with 500:1 ratio
• F5: CT bank with 1000:1 ratio
• M1: CT bank with 800:1 ratio
The following rule applies:
SRC 1 = F1 + F5 + M1 Eq. 5-7
1 pu is the highest primary current. In this case, 1000 is entered and the secondary current from the 500:1 and 800:1 ratio
CTs are adjusted to that created by a 1000:1 CT before summation. If a protection element is set up to act on SRC 1
currents, then a pickup level of 1 pu operates on 1000 A primary.
The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A).
Because energy parameters are accumulated, these values should be recorded and then reset immediately prior to
changing VT characteristics.
Three banks of phase/auxiliary VTs can be set, where voltage banks are denoted in the following format (X represents the
module slot position letter):
Xa, where X = {F, M, U} and a = {5}
See the Introduction to AC Sources section at the beginning of this chapter for details.
With VTs installed, the relay can perform voltage measurements as well as power calculations. Enter the PHASE VT F5
CONNECTION made to the system as “Wye” or “Delta.” An open-delta source VT connection is entered as “Delta.”
The nominal PHASE VT F5 SECONDARY voltage setting is the voltage across the relay input terminals when nominal
voltage is applied to the VT primary.
For example, on a system with a 13.8 kV nominal primary voltage and with a 14400:120 volt VT in a delta
connection, the secondary voltage is 115; that is, (13800 / 14400) × 120. For a wye connection, the voltage value
entered must be the phase to neutral voltage, which is 115 = 66.4.
5
On a 14.4 kV system with a delta connection and a VT primary to secondary turns ratio of 14400:120, the voltage
value entered is 120; that is, 14400 / 120.
If the PHASE VT F5 CONNECTION is set to “Delta”, the relay does not calculate voltage harmonics.
FREQUENCY AND PHASE Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
REFERENCE: SRC 1
The power system NOMINAL FREQUENCY value is used as a default to set the digital sampling rate if the system frequency
cannot be measured from available signals. This can happen if the signals are not present or are heavily distorted. Before
reverting to the nominal frequency, the frequency tracking algorithm holds the last valid frequency measurement for a
safe period of time while waiting for the signals to reappear or for the distortions to decay.
The phase sequence of the power system is required to properly calculate sequence components and power parameters.
The PHASE ROTATION setting matches the power system phase sequence and informs the relay of the actual system phase
sequence, either ABC or ACB. CT and VT inputs on the relay, labelled as A, B, and C, must be connected to system phases A,
B, and C for correct operation.
The FREQUENCY AND PHASE REFERENCE setting determines which signal source is used (and hence which AC signal) for
phase angle reference. The AC signal used is prioritized based on the AC inputs configured for the signal source. Phase
voltages takes precedence, followed by auxiliary voltage, then phase currents, and finally ground current.
For three phase selection, phase A is used for angle referencing (VANGLE REF = VA), while Clarke transformation of the phase
signals is used for frequency metering and tracking (VFREQUENCY = (2VA - VB - VC) / 3) for better performance during fault,
open pole, and VT and CT fail conditions.
The phase reference and frequency tracking AC signals are selected based upon the source configuration, regardless of
whether or not a particular signal is actually applied to the relay.
Phase angle of the reference signal always displays zero degrees and all other phase angles are relative to this signal. If the
pre-selected reference signal is not measurable at a given time, the phase angles are not referenced.
The phase angle referencing is done via a phase locked loop, which can synchronize independent UR-series relays if they
have the same AC signal reference. This results in very precise correlation of phase angle indications between different UR-
series relays.
FREQUENCY TRACKING is set to “Disabled” only in unusual circumstances; consult GE Grid Solutions for special variable-
frequency applications.
The frequency tracking feature functions only when the F35 is in the “Programmed” mode. If the F35 is “Not
Programmed,” then metering values are available but can exhibit significant errors.
5
5.5.3 Signal sources
SETTINGS SYSTEM SETUP SIGNAL SOURCES SOURCE 1(6)
SOURCE 1 SOURCE 1 NAME: Range: up to 20 alphanumeric characters
SRC 1
SOURCE 1 PHASE CT: Range: None, F1,... up to any 6 CTs. Only Phase CT
None inputs are displayed.
SOURCE 1 GROUND CT: Range: None, F1,... up to any 6 CTs. Only Ground CT
None inputs are displayed.
Identical menus are available for each source. The "SRC 1" text can be replaced by with a user-defined name appropriate
for the associated source.
The first letter in the source identifier represents the module slot position. The number directly following this letter
represents either the first bank of four channels (1, 2, 3, 4) called “1” or the second bank of four channels (5, 6, 7, 8) called
“5” in a particular CT/VT module. See the Introduction to AC Sources section at the beginning of this chapter for details.
It is possible to select the sum of all CT combinations. The first channel displayed is the CT to which all others are referred.
For example, the selection “F1+F5” indicates the sum of each phase from channels “F1” and “F5,” scaled to whichever CT
has the higher ratio. Selecting “None” hides the associated actual values.
The approach used to configure the AC sources consists of several steps; first step is to specify the information about each
CT and VT input. For CT inputs, this is the nominal primary and secondary current. For VTs, this is the connection type, ratio
and nominal secondary voltage. Once the inputs have been specified, the configuration for each source is entered,
including specifying which CTs are summed together.
5
SOURCE 1 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 1 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old
SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 2 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 2 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old
SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 6 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 6 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old 827092A3.CDR
The disturbance detector responds to the change in currents of twice the current cut-off level. The default cut-off threshold
is 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting
(PRODUCT SETUP DISPLAY PROPERTIES CURRENT CUT-OFF LEVEL) controls the sensitivity of the disturbance detector
accordingly.
This configuration can be used on a two-winding transformer, with one winding connected into a breaker-and-a-half
system. The following figure shows the arrangement of sources used to provide the functions required in this application,
and the CT/VT inputs that are used to provide the data.
Figure 5-93: Example of use of sources
F1 DSP Bank
F5
Source 1 Source 2
Amps Amps
Source 3
51BF-1 51BF-2
U1 Volts Amps
5 A W Var 87T
A W Var 51P
Volts Amps
M1
M1 Source 4
UR Relay
M5
827794A1.CDR
Y LV D HV AUX
SRC 1 SRC 2 SRC 3
Phase CT M1 F1+F5 None
Ground CT M1 None None
Phase VT M5 None None
Aux VT None None U1
5.5.4 Breakers
SETTINGS SYSTEM SETUP BREAKERS BREAKER 1(6)
BREAKER 1 BREAKER 1 Range: Disabled, Enabled
FUNCTION: Disabled
The breaker control element contains the auxiliary logic for status and serves as the interface for opening and closing of a
circuit breaker from protection, autoreclose, SCADA, or through the front panel interface. The breaker control element can
be used to create interlocking functionality. For greater security in determination of the breaker position, both the 52/a and
52/b auxiliary contacts are used with reporting of the discrepancy between them.
To use this element, configure the contact outputs that trip and close the breaker to use FlexLogic operands BREAKER 1 OFF
CMD (or BREAKER 1 TRIP A/B/C in the case of single-pole tripping) and BREAKER 1 ON CMD, and configure the breaker control
element inputs as described here.
A description of the operation of the breaker control and status monitoring features from the front panel is provided in
chapter 4.
There are two breaker control elements for each CT/VT module installed. The following settings are available for each
breaker control element.
BREAKER 1 FUNCTION — This setting enables and disables the operation of the breaker 1 control feature.
BREAKER1 PUSH BUTTON CONTROL — Set to “Enable” to allow front panel pushbutton open/close control operations.
BREAKER1 TAGGING — Set to "Enable" to allow the graphical front panel to tag breaker 1. When tagged, the following
operations are disabled: pushbutton open/close, IEC 61850 open/close, and close command initiated by BREAKER 1 CLOSE
setting. The trip command issued by the Trip Out element or BREAKER 1 OPEN setting is not affected.
5 BREAKER1 SUBSTITUTN — Set to "Enable" to allow the graphical front panel to substitute breaker 1 status. When substituted,
breaker 1 control open/close status is forced to the substituted value.
BREAKER1 BYPASS — Set to "Enable" to allow the graphical front panel to bypass breaker 1 interlocking. When asserted,
BREAKER 1 BLK OPEN and BREAKER 1 BLK CLOSE settings are bypassed.
BREAKER1 AR BLOCK —Set to "Enable" to generate an operand to block the Autoreclose element.
The Autoreclose element is not automatically inhibited by BLOCK AR from the front panel. If the autoreclose scheme needs
to be inhibited, set setting AR BLOCK in the corresponding autoreclose element with the BREAKER 1 BLK RCLS operand.
BREAKER 1 NAME — Assign a user-defined name (up to six characters) to the breaker. This name is used in flash messages
related to breaker 1.
BREAKER 1 MODE — Selects “3-Pole” mode, where all breaker poles are operated simultaneously, or “1-Pole” mode where all
breaker poles are operated either independently or simultaneously.
BREAKER 1 OPEN — Selects an operand that when activated, and unless blocked, initiates the Breaker 1 open and individual
phase trip commands.
BREAKER 1 BLK OPEN — Selects an operand that prevents initiation of Breaker 1 open and individual phase trip commands.
This setting can be used for blocking circuit breaker tripping for instance when breaker monitoring detects conditions such
as low SF6 gas density during which breaker opening can cause damage.
BREAKER 1 CLOSE — Selects an operand that when activated, and unless blocked, initiates the Breaker 1 close commands.
BREAKER 1 BLK CLOSE — Selects an operand that prevents initiation of Breaker 1 close commands. This setting can be used
for blocking circuit breaker closing, for instance to prevent closing into a closed ground switch.
BREAKER1 A/3P CLSD — Selects an operand, usually a contact input connected to a breaker auxiliary position tracking
mechanism. This input is for a normally-open 52/a status input that creates a logic 1 when the breaker is closed. If the
BREAKER 1 MODE setting is selected as "3-Pole," this setting selects a single 52/a input as the operand used to track the
breaker open or closed position. If the mode is selected as "1-Pole," the input mentioned is used to track phase A and the
BREAKER 1 B and BREAKER 1 C settings select operands to track phases B and C, respectively.
BREAKER1 A/3P OPND — Selects an operand, usually a contact input, that is for a normally-closed 52/b status input that
creates a logic 1 when the breaker is open. If a separate 52/b contact input is not available, then the inverted 52/a status
signal or the inverted BREAKER 1 CLOSED status signal can be used.
BREAKER 1 B CLOSED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase B closed position as outlined for phase A.
BREAKER 1 B OPENED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase B opened position as outlined for phase A.
BREAKER 1 C CLOSED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase C closed position as outlined for phase A.
BREAKER 1 C OPENED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase C opened position as outlined for phase A.
BREAKER 1 TOPERATE — This setting specifies the required interval to overcome transient disagreement between the 52/a
and 52/b auxiliary contacts during breaker operation. If transient disagreement still exists after this time has expired, the
BREAKER 1 BAD STATUS FlexLogic operand is asserted for alarm or blocking purposes.
BREAKER 1 EXT ALARM — This setting selects an operand, usually an external contact input connected to a breaker alarm
reporting contact. While the selected operand is active, the BREAKER 1 TROUBLE operand is activated.
BREAKER 1 ALARM DELAY — This setting specifies the delay interval during which a disagreement of status among the three-
pole position tracking operands does not declare a pole disagreement. This allows for non-simultaneous operation of the
poles.
BREAKER 1 OPEN SEAL-IN — This setting specifies the seal-in time of the three-pole open command initiated by either the
Trip Out element or a manual open command to the circuit breaker.
MANUAL CLOSE RECAL1 TIME — This setting specifies the seal-in time of the close commands due to an operator-initiated
manual close command to the circuit breaker.
BREAKER 1 OUT OF SV — Selects an operand indicating that breaker 1 is out-of-service.
5
BREAKER 1 RACKED-IN — This setting selects a contact input to show whether the breaker is racked-in or racked-out. The
racked-in or racked-out status is used to indicate dynamically the status of breaker symbol, only applied in the single-line
diagram in the graphical front panel. If this setting is set to Off, the racked status is not considered.
FLEXLOGIC OPERAND
BREAKER 1 TAG ON
SETTING
BREAKER 1 PUSHBUTTON
CONTROL
= Enabled AND
USER 3 OFF/ON
To open BKR1-(Name)
OR
Breaker 1 Open
From graphical front panel
FLEXLOGIC OPERAND
SETTING (on IEC 61850 page) AND BREAKER 1 MNL OPEN
XCBR1 ST.LOC OPERAND: OR
5
FLEXLOGIC OPERAND
OPERANDS
On D60, L60, L90 from OR
Trip Output AND BREAKER 1 TRIP
OFF CMD
C
AND
Brk0XCBR1.BlkOpn.ctVal = On
From IEC 61850 protocol
SETTING OR Bkr0XCBR1.BlkOpn.stVal
BREAKER 1 BLK OPEN To IEC 61850 protocol
Off = 0
AND
FLEXLOGIC OPERAND
BREAKER 1 BYPASS ON
Breaker 1 Close
From graphical front panel
OR AND
AND
BkrCSWI1.Pos.ctlVal = on FLEXLOGIC OPERAND
OR
Bkr0XCBR1.Pos.ctlVal = on OR AND BREAKER 1 MNL CLS
SETTING
From IEC 61850 protocol AND
MANUAL CLOSE RECAL1 TIME
SETTING T PKP
BREAKER 1 CLOSE
AND 0
Off = 0
AND
Bkr0XCBR1.BlkCls.ctlVal = on
From IEC 61850 protocol
OR Bkr0XCBR1.BlkCls.stVal
SETTING To IEC 61850 protocol
BREAKER 1 BLK CLOSE
AND
Off = 0
Enable to sheet 2
859719A1.CDR
SETTING
BREAKER 1 MODE
= 1-Pole
= 3-Pole
FLEXLOGIC OPERANDS
BREAKER 1 SUBD CLSD
BREAKER 1 SUBD OPEN FLEXLOGIC OPERAND
BKR1 A CLOSED AND BREAKER 1 ΦA CLSD
SETTING AND
BREAKER 1 ΦA/3P CLSD FLEXLOGIC OPERAND
OR BKR1 A OPENED AND BREAKER 1 ΦA OPEN
= Off AND
AND
SETTING FLEXLOGIC OPERAND
BREAKER 1 ΦA/3P OPND AND BREAKER 1 ΦA INTERM
OR SETTING
= Off AND
AND BREAKER 1 TOPERATE FLEXLOGIC OPERAND
OR T PKP AND BREAKER 1 ΦA BAD ST
0
AND
FLEXLOGIC OPERAND
BKR1 B CLOSED AND BREAKER 1 ΦB CLSD
SETTING AND
BREAKER 1 ΦB CLSD FLEXLOGIC OPERAND
OR BKR1 B OPENED AND BREAKER 1 ΦB OPEN
= Off AND
AND
SETTING FLEXLOGIC OPERAND
BREAKER 1 ΦB OPENED AND BREAKER 1 ΦB INTERM
OR AND
= Off AND
OR SETTING
FLEXLOGIC OPERAND
BREAKER 1 TOPERATE
AND AND BREAKER 1 ΦB BAD ST
T PKP
0
FLEXLOGIC OPERAND
BKR1 C CLOSED AND BREAKER 1 ΦC CLSD
SETTING AND
FLEXLOGIC OPERAND
5
BREAKER 1 ΦC CLSD
OR BKR1 C OPENED AND BREAKER 1 ΦC OPEN
= Off AND
AND
SETTING FLEXLOGIC OPERAND
BREAKER 1 ΦC OPENED AND BREAKER 1 ΦC INTERM
OR AND
= Off AND
OR SETTING
FLEXLOGIC OPERAND
BREAKER 1 TOPERATE
AND AND BREAKER 1 ΦC BAD ST
T PKP
0 FLEXLOGIC OPERAND
OR BREAKER 1 BAD STATUS
SETTING
FLEXLOGIC OPERAND
BREAKER 1 EXT ALARM
AND BREAKER 1 TROUBLE
= Off OR
BKR1 A OPENED
AND FLEXLOGIC OPERAND
BKR1 B OPENED
AND BREAKER 1 OPEN
BKR1 C OPENED OR
AND
FLEXLOGIC OPERAND
BKR1 A CLOSED AND BREAKER 1 ANY P OPEN
BKR1 B CLOSED AND
BKR1 C CLOSED
FLEXLOGIC OPERAND
AND BREAKER 1 1P OPEN
XOR
SETTING
BREAKER 1 OUT OF SV FLEXLOGIC OPERAND
= Off AND BREAKER 1 OOS
Enable
to sheet 3 859763A1.vsd
Figure 5-96: Dual breaker / graphical front panel control logic (Sheet 3 of 3)
from sheet 2
SETTING Enable
BREAKER 1 TAGGING
= Enabled Non-volatile,
Reset-dominant
Breaker 1 Tag S FLEXLOGIC OPERAND
Latch BREAKER 1 TAG ON
Breaker 1 Remove Tag
OR R BREAKER 1 TAG OFF
From graphical front panel
SETTING
BREAKER 1 SUBSTITUTN
= Enabled Non-volatile,
Reset-dominant
Breaker 1 Substitute Open S FLEXLOGIC OPERAND
Latch BREAKER 1 SUBD OPEN
Breaker 1 Remove Substitution
OR R
SETTING
BREAKER 1 BYPASS
= Enabled Non-volatile,
Reset-dominant
Breaker 1 Bypass S FLEXLOGIC OPERAND
Latch BREAKER 1 BYPASS ON
5
Breaker 1 Remove Bypass
From graphical front panel OR R BREAKER 1 BYPASS OFF
The breaker element has direct hard-coded connections to the IEC 61850 model as shown in the logic diagram. This allows
remote open/close operation of each breaker, using either CSWI or XCBR IEC 61850 logical nodes. IEC 61850 select-before-
operate functionality, local/remote switch functionality, along with blocking of open/close commands are provided. Note
that the dwell time for the IEC 61850 trip and close commands shown is one protection pass only. To maintain the close/
open command for a certain time, do so by setting the seal-in timers BREAKER 1 OPEN SEAL-IN and MANUAL CLOSE RECAL1
TIME, on the contact outputs using the "Seal-in" setting, in the Trip Output element, and/or in FlexLogic.
SWITCH 1 SUBSTITUTN:
Disabled
Range: Disabled, Enabled 5
SWITCH 1 BYPASS: Range: Disabled, Enabled
Disabled
The disconnect switch control element contains the auxiliary logic for status and serves as the interface for opening and
closing of disconnect switches from SCADA or through the front panel interface. The disconnect switch control element
can be used to create interlocking functionality. For greater security in determination of the switch pole position, both the
89/a and 89/b auxiliary contacts are used with reporting of the discrepancy between them. There are eight disconnect
switch control elements for each CT/VT module installed.
To use this element, configure the contact outputs that open and close the disconnect switch to use FlexLogic operands
SWITCH 1 OFF CMD and SWITCH 1 ON CMD, and configure the disconnect switch control element's inputs as outlined here.
SWITCH 1 FUNCTION — This setting enables and disables operation of the disconnect switch element.
SWITCH 1 NAME — Assign a user-defined name (up to six characters) to the disconnect switch. This name is used in flash
messages related to disconnect switch 1.
SWITCH 1 MODE — This setting selects “3-Pole” mode, where disconnect switch poles have a single common auxiliary
switch, or “1-Pole” mode where each disconnect switch pole has its own auxiliary switch.
SWITCH 1 OPEN — This setting selects an operand that when activated, and unless blocked, initiates the disconnect switch 1
open command.
SWITCH 1 BLK OPEN — This setting selects an operand that prevents initiation of the disconnect switch 1 command. This
setting can be used to block the disconnect switch from opening, for instance when switchyard monitoring indicates that
current exceeding the switch's interrupting rating can be flowing through the switch.
SWITCH 1 CLOSE — This setting selects an operand that when activated, and unless blocked, initiates the disconnect switch
1 close command.
SWITCH 1 BLK CLOSE — This setting selects an operand that prevents initiation of disconnect switch 1 close commands. This
setting can be used to block the disconnect switch from closing, for instance to prevent closing into a closed ground
switch.
SWTCH 1A/3P CLSD — This setting selects an operand, usually a contact input connected to a disconnect switch auxiliary
position tracking mechanism. This input is for a normally-open 89/a status input that creates a logic 1 when the
disconnect switch is closed. If the SWITCH 1 MODE setting is selected as “3-Pole,” this setting selects a single 89/a input as
the operand used to track the disconnect switch open or closed position. If the mode is selected as “1-Pole,” the input
mentioned is used to track phase A and the SWITCH 1 B and SWITCH 1 C settings select operands to track phases B and
C, respectively.
SWTCH 1 A/3P OPND — This setting selects an operand, usually a contact input, that is for a normally-closed 89/b status
input that creates a logic 1 when the disconnect switch is open. If a separate 89/b contact input is not available, then an
inverted 89/a status signal can be used.
SWITCH 1 B CLOSED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase B closed position as outlined for phase A.
SWITCH 1 B OPENED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase B opened position as outlined for phase A.
5 SWITCH 1 C CLOSED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase C closed position as outlined for phase A.
SWITCH 1 C OPENED — If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase C opened position as outlined for phase A.
SWITCH 1 PUSH BUTTON CONTROL — Set to "Enable" to allow front panel pushbutton open/close control operations.
SWITCH 1 TAGGING — Set to "Enable" to allow the graphical front panel to tag switch 1. When tagged, the following
operations are disabled:
• Pushbutton Open/Close
• IEC 61850 Open/Close
• Open command initiated by SWITCH 1 OPEN setting
• Close command initiated by SWITCH 1 CLOSE setting
SWITCH 1 SUBSTITUTN — Set to "Enable" to allow the graphical front panel to substitute switch 1 status. When substituted,
switch 1 control open/close status is forced to the substituted value.
SWITCH 1 BYPASS —Set to "Enable" to allow the graphical front panel to bypass switch 1 interlocking. When asserted,
SWITCH 1 BLK OPEN and SWITCH 1 BLK CLOSE settings are bypassed.
SWITCH 1 OPEN SEAL-IN — This setting specifies the seal-in time of the open command due to an operator-initiated manual
open command to the disconnect switch.
SWITCH 1 CLOSE SEAL-IN — This setting specifies the seal-in time of the close command due to an operator-initiated manual
close command to the disconnect switch.
SWITCH 1 TOPERATE — This setting specifies the required interval to overcome transient disagreement between the 89/a
and 89/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the SWITCH 1 BAD STATUS FlexLogic operand is asserted for alarm or blocking purposes.
SWITCH 1 ALARM DELAY — This setting specifies the delay interval during which a disagreement of status among the pole
position tracking operands do not declare a pole disagreement. This allows for non-simultaneous operation of the poles.
IEC 61850 functionality is permitted when the F35 is in “Programmed” mode and not in local control mode.
The switch element has direct hard-coded connections to the IEC 61850 model as shown in the logic diagrams. This allows
remote open/close operation of each switch, using either CSWI or XSWI IEC 61850 logical nodes. IEC 61850 select-before-
operate functionality, local/remote switch functionality, along with blocking open/close commands are provided. Note that
the dwell time for the IEC 61850 trip and close commands shown is one protection pass only. To maintain close/open
command for a certain time, do so using the seal-in timers SWITCH 1 OPEN SEAL-IN and SWITCH 1 CLOSE SEAL-IN, on the
contact outputs using the "Seal-in" setting, or in FlexLogic.
Figure 5-97: Disconnect switch control logic (sheet 1 of 3)
SETTING
SWITCH 1 FUNCTION
= Enabled
FLEXLOGIC OPERAND
SWITCH 1 TAG ON
SETTING
SWITCH 1 PUSHBUTTON
CONTROL = Enabled
AND
SWITCH 1 Open
From graphical front panel
SETTING
SWITCH 1 OPEN
= Off
AND
T PKP
0 AND
5
AND
DiscCSWI1.BlkOpn.ctlVal = on
From IEC 61850 protocol
SETTING OR Disc0XSWI1.BlkOpn.stVal
SWITCH 1 BLOCK OPEN To IEC 61850 protocol
= Off
AND
FLEXLOGIC OPERAND
SWITCH 1 BYPASS ON
AND
SWITCH 1 Close
From graphical front panel
AND
OR
DiscCSWI1.Pos.ctlVal = on
OR FLEXLOGIC OPERAND
Disc0XSWI1.Pos.ctlVal = on SETTING
OR AND SWITCH 1 ON CMD
From IEC 61850 protocol SWITCH 1 CLOSE SEAL-IN
T PKP
SETTING 0 AND
SWITCH 1 CLOSE
AND
= Off
AND
DiscCSWI1.BlkCls.ctlVal = on
From IEC 61850 protocol
OR Disc0XSWI1.BlkCls.stVal
SETTING To IEC 61850 protocol
SWITCH 1 BLK CLOSE AND Enable
= Off to sheet 2 859765A1.vsd
SETTING
SWITCH 1 MODE
= 1-Pole
= 3-Pole
FLEXLOGIC OPERANDS
SWITCH 1 SUBD CLSD
SWITCH 1 SUBD OPEN FLEXLOGIC OPERAND
SW1 A CLOSED AND SWITCH 1 ΦA CLSD
SETTING AND
SWITCH 1 ΦA/3P CLSD FLEXLOGIC OPERAND
OR SW1 A OPENED AND SWITCH 1 ΦA OPEN
= Off AND
AND
SETTING FLEXLOGIC OPERAND
SWITCH 1 ΦA/3P OPND AND SWITCH 1 ΦA INTERM
OR SETTING
= Off AND
AND SWITCH 1 TOPERATE FLEXLOGIC OPERAND
OR T PKP AND SWITCH 1 ΦA BAD ST
0
AND
FLEXLOGIC OPERAND
SW1 B CLOSED AND SWITCH 1 ΦB CLSD
SETTING AND
SWITCH 1 ΦB CLSD FLEXLOGIC OPERAND
OR SW1 B OPENED AND SWITCH 1 ΦB OPEN
= Off AND
AND
SETTING FLEXLOGIC OPERAND
SWITCH 1 ΦB OPENED AND SWITCH 1 ΦB INTERM
OR AND
= Off AND
OR SETTING
FLEXLOGIC OPERAND
SWITCH 1 TOPERATE
AND AND SWITCH 1 ΦB BAD ST
T PKP
0
FLEXLOGIC OPERAND
SW1 C CLOSED AND SWITCH 1 ΦC CLSD
SETTING AND
SWITCH 1 ΦC CLSD FLEXLOGIC OPERAND
OR SW1 C OPENED AND SWITCH 1 ΦC OPEN
5
= Off AND
AND
SETTING FLEXLOGIC OPERAND
SWITCH 1 ΦC OPENED AND SWITCH 1 ΦC INTERM
OR AND
= Off AND
OR SETTING
FLEXLOGIC OPERAND
SWITCH 1 TOPERATE
AND AND SWITCH 1 ΦC BAD ST
T PKP
0 FLEXLOGIC OPERAND
OR SWITCH 1 BAD STATUS
FLEXLOGIC OPERAND
AND SWITCH 1 TROUBLE
OR
SW1 A OPENED
AND FLEXLOGIC OPERAND
SW1 B OPENED
AND SWITCH 1 OPEN
SW1 C OPENED OR
AND
Enable
to sheet 3 859766A1.vsd
Figure 5-99: Disconnect switch control graphical front panel logic (sheet 3 of 3)
From sheet 2
SETTING Enable
SWITCH 1 TAGGING
= Enabled Non-volatile,
Reset-dominant
SWITCH 1 Tag S FLEXLOGIC OPERAND
Latch SWITCH 1 TAG ON
SWITCH 1 Remove Tag
OR R SWITCH 1 TAG OFF
From graphical front panel
SETTING
SWITCH 1 SUBSTITUTN
= Enabled Non-volatile,
Reset-dominant
SWITCH 1 Substitute Open S FLEXLOGIC OPERAND
Latch SWITCH 1 SUBD OPEN
SWITCH 1 Remove Substitution
OR R
SETTING
SWITCH 1 BYPASS
= Enabled Non-volatile,
Reset-dominant
SWITCH 1 Bypass S FLEXLOGIC OPERAND
SWITCH 1 Remove Bypass Latch SWITCH 1 BYPASS ON
From graphical front panel OR R SWITCH 1 BYPASS OFF
859767A1.vsd
5.5.6 FlexCurves
5.5.6.1 Settings
5
SETTINGS SYSTEM SETUP FLEXCURVES FLEXCURE A(D)
FLEXCURVE A FLEXCURVE A TIME AT Range: 0 to 65535 ms in steps of 1
0.00 xPKP: 0 ms
FlexCurves A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98
and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter
a custom FlexCurve, enter the reset and operate times (using the VALUE keys) for each selected pickup point (using the
MESSAGE up/down keys) for the required protection curve (A, B, C, or D).
The relay using a given FlexCurve applies linear approximation for times between the user-entered points. Take
care when setting the two points that are close to the multiple of pickup of 1; that is, 0.98 pu and 1.03 pu. It is
recommended to set the two times to a similar value, otherwise the linear approximation can result in undesired
behavior for the operating quantity that is close to 1.00 pu.
Addr: Adds the time specified in this field (in ms) to each
curve operating time value.
The Multiplier and Adder settings only affect the curve portion of the characteristic and not the MRT and HCT
settings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio.
5.5.6.4 Example
A composite curve can be created from the GE_111 standard with MRT = 200 ms and HCT initially disabled and then 5
enabled at eight times pickup with an operating time of 30 ms. At approximately four times pickup, the curve operating
time is equal to the MRT and from then onwards the operating time remains at 200 ms.
Figure 5-101: Composite recloser curve with HCT disabled
842719A1.CDR
With the HCT feature enabled, the operating time reduces to 30 ms for pickup multiples exceeding eight times pickup.
842720A1.CDR
Configuring a composite curve with an increase in operating time at increased pickup multiples is not allowed. If
this is attempted, the EnerVista software generates an error message and discards the proposed changes.
1 GE106
0.5
0.2
TIME (sec)
GE103
GE104 GE105
0.1
0.05
GE101 GE102
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842723A1.CDR
50
20 GE142
10
5
GE138
TIME (sec)
1 GE120
GE113
0.5
0.2
0.1
0.05
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842725A1.CDR
5
Figure 5-105: Recloser curves GE134, GE137, GE140, GE151, and GE201
50
20
10
GE201
TIME (sec)
GE151
2
GE134 GE140
1
GE137
0.5
50
GE152
20
TIME (sec)
GE141
10
GE131
5
GE200
2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842728A1.CDR
5
Figure 5-107: Recloser curves GE133, GE161, GE162, GE163, GE164, and GE165
50
20
GE164
10
2
TIME (sec)
GE162
1
0.5
GE133
0.2
GE165
0.1
0.05
GE161
0.02 GE163
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842729A1.CDR
Figure 5-108: Recloser curves GE116, GE117, GE118, GE132, GE136, and GE139
20
GE132
10
1
TIME (sec)
0.5 GE139
0.2
GE136
0.1
GE116
0.05
GE118 GE117
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842726A1.CDR
5
Figure 5-109: Recloser curves GE107, GE111, GE112, GE114, GE115, GE121, and GE122
20
10
5
GE122
2
1
TIME (sec)
0.5
GE114
0.2
GE111
GE121
0.1
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842724A1.CDR
50
20
GE202
10
TIME (sec)
GE135
2 GE119
0.5
0.2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842727A1.CDR
5
5.6 FlexLogic
5.6.1 FlexLogic operands
For flexibility, the arrangement of internal digital logic combines fixed and user-programmed parameters. Logic upon
which individual features are designed is fixed, and all other logic, from contact input signals through elements or
combinations of elements to contact outputs, is variable. The user has complete control of all variable logic through
FlexLogic. In general, the system receives analog and digital inputs that it uses to produce analog and digital outputs. The
figure shows major subsystems of a generic UR-series relay involved in this process.
CTs DSP
VTs (A/D) FlexLogic™ Virtual
equations outputs
Calculate
DCmA parameters Measuring
Analog and
or
input decision Digital Flags
RTD
(A/D) elements elements
inputs
V I
Contact Form-A and
inputs FlexLogic™ SCR only
Block counters
operation Contact
(each outputs
element)
Keypad
Virtual Remote
inputs (FlexLogic operands) outputs
OR
Remote Display
inputs Control and LEDs
(GOOSE) and Display
monitoring
features
fiber Analog
Direct output (D/A)
G.703 inputs
RS422 (dcmA)
5
(Status) Fiber
Direct
G.703
outputs
RS422
(Actual values) (Status)
827022A7.cdr
The states of all digital signals used in the F35 are represented by flags (or FlexLogic operands, which are described later in
this section). A digital “1” is represented by a set flag. Any external contact change-of-state can be used to block an
element from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output. The state
of the contact input can be displayed locally or viewed remotely via the communications facilities provided. If a simple
scheme where a contact input is used to block an element is wanted, this selection is made when programming the
element. This capability also applies to the other features that set flags: elements, virtual inputs, remote inputs, schemes,
and human operators.
If more complex logic than shown in the figure is required, it is implemented via FlexLogic. For example, to have the closed
state of contact input H7a and the operated state of the phase undervoltage element block the operation of the phase
time overcurrent element, the two control input states are programmed in a FlexLogic equation. This equation ANDs the
two control inputs to produce a virtual output that is then selected when programming the phase time overcurrent to be
used as a blocking input. Virtual outputs can only be created by FlexLogic equations.
Traditionally, protective relay logic has been relatively limited. Any unusual applications involving interlocks, blocking, or
supervisory functions had to be hard-wired using contact inputs and outputs. FlexLogic minimizes the requirement for
auxiliary components and wiring while making more complex schemes possible.
The logic that determines the interaction of inputs, elements, schemes, and outputs is field-programmable through the use
of logic equations that are sequentially processed. The use of virtual inputs and outputs in addition to hardware is
available internally and on the communication ports for other relays to use (distributed FlexLogic).
FlexLogic allows users to customize the relay through a series of equations that consist of operators and operands. The
operands are the states of inputs, elements, schemes, and outputs. The operators are logic gates, timers, and latches (with
set and reset inputs). A system of sequential operations allows any combination of operands to be assigned as inputs to
specified operators to create an output. The final output of an equation is a numbered register called a virtual output.
Virtual outputs can be used as an input operand in any equation, including the equation that generates the output, as a
seal-in or other type of feedback.
A FlexLogic equation consists of parameters that are either operands or operators. Operands have a logic state of 1 or 0.
Operators provide a defined function, such as an AND gate or a Timer. Each equation defines the combinations of
parameters to be used to set a Virtual Output flag. Evaluation of an equation results in either a 1 (=ON, or flag set) or 0
(=OFF, or flag not set). Each equation is evaluated at least four times every power system cycle.
Some types of operands are present in the relay in multiple instances, for example contact and remote inputs. These types
of operands are grouped together (for presentation purposes only) on the front panel display. The table lists characteristics
of the different types of operands.
Table 5-21: F35 FlexLogic operand types
Operand type State Example of format Characteristics
[Input Is ‘1’ (= ON) if...]
Contact Input On Cont Ip On Voltage is applied presently to the input (external contact
closed)
Off Cont Ip Off Voltage is not applied presently to the input (external
contact open)
Contact Output Contact Closed Cont Op 1 Closed Contact output is closed
(type Form-A contact
Current On Cont Op 1 Ion Current is flowing through the contact
only)
Voltage On Cont Op 1 VOn Voltage exists across the contact
Voltage Off Cont Op 1 VOff Voltage does not exist across the contact
Direct Input On DIRECT INPUT 1 On The direct input is presently in the ON state
Element Pickup PHASE TOC1 PKP The tested parameter is presently above the pickup setting
5 (Analog) of an element that responds to rising values or below the
pickup setting of an element that responds to falling values
Dropout PHASE TOC1 DPO This operand is the logical inverse of the above PKP
operand
Operate PHASE TOC1 OP The tested parameter has been above/below the pickup
setting of the element for the programmed delay time, or
has been at logic 1 and is now at logic 0 but the reset timer
has not finished timing
Block PHASE TOC1 BLK The output of the comparator is set to the block function
Element Pickup Dig Element 1 PKP The input operand is at logic 1
(Digital)
Dropout Dig Element 1 DPO This operand is the logical inverse of the above PKP
operand
Operate Dig Element 1 OP The input operand has been at logic 1 for the programmed
pickup delay time, or has been at logic 1 for this period and
is now at logic 0 but the reset timer has not finished timing
Element Higher than Counter 1 HI The number of pulses counted is above the set number
(Digital Counter)
Equal to Counter 1 EQL The number of pulses counted is equal to the set number
Lower than Counter 1 LO The number of pulses counted is below the set number
Fixed On On Logic 1
Off Off Logic 0
RxGOOSE Boolean On RxGOOSE Boolean 1 On The RxGOOSE Boolean is presently in the ON state
Virtual Input On Virt Ip 1 On The virtual input is presently in the ON state
Virtual Output On Virt Op 1 On The virtual output is presently in the set state (that is,
evaluation of the equation that produces this virtual output
results in a "1")
The following table lists the operands available for the relay. The operands can be viewed online by entering the IP address
of the relay in a web browser and accessing the Device Information Menu.
5 ELEMENT:
NEG SEQ TOC2
NEUTRAL IOC1 PKP
Same set of operands as shown for NEG SEQ TOC1
Neutral instantaneous overcurrent 1 has picked up
Neutral NEUTRAL IOC1 OP Neutral instantaneous overcurrent 1 has operated
instantaneous NEUTRAL IOC1 DPO Neutral instantaneous overcurrent 1 has dropped out
overcurrent
NEUTRAL IOC2 to 12 Same set of operands as shown for NEUTRAL IOC1
ELEMENT: NEUTRAL OV1 PKP Neutral overvoltage element 1 has picked up
Neutral overvoltage NEUTRAL OV1 DPO Neutral overvoltage element 1 has dropped out
NEUTRAL OV1 OP Neutral overvoltage element 1 has operated
NEUTRAL OV2 to 3 Same set of operands as shown for NEUTRAL OV1
ELEMENT: NEUTRAL TOC1 PKP Neutral time overcurrent 1 has picked up
Neutral time NEUTRAL TOC1 OP Neutral time overcurrent 1 has operated
overcurrent NEUTRAL TOC1 DPO Neutral time overcurrent 1 has dropped out
NEUTRAL TOC2 to 6 Same set of operands as shown for NEUTRAL TOC1
ELEMENT: PID 1 RAISE
PID regulator PID 1 LOWER
PID 2 RAISE
PID 2 LOWER
PID 3 RAISE
PID 3 LOWER
PID 4 RAISE
PID 4 LOWER
ELEMENT: PHASE IOC1 PKP At least one phase of phase instantaneous overcurrent 1 has picked up
Phase instantaneous PHASE IOC1 OP At least one phase of phase instantaneous overcurrent 1 has operated
overcurrent PHASE IOC1 DPO All phases of phase instantaneous overcurrent 1 have dropped out
PHASE IOC1 PKP A Phase A of phase instantaneous overcurrent 1 has picked up
PHASE IOC1 PKP B Phase B of phase instantaneous overcurrent 1 has picked up
PHASE IOC1 PKP C Phase C of phase instantaneous overcurrent 1 has picked up
PHASE IOC1 OP A Phase A of phase instantaneous overcurrent 1 has operated
PHASE IOC1 OP B Phase B of phase instantaneous overcurrent 1 has operated
PHASE IOC1 OP C Phase C of phase instantaneous overcurrent 1 has operated
PHASE IOC1 DPO A Phase A of phase instantaneous overcurrent 1 has dropped out
PHASE IOC1 DPO B Phase B of phase instantaneous overcurrent 1 has dropped out
PHASE IOC1 DPO C Phase C of phase instantaneous overcurrent 1 has dropped out
PHASE IOC2 to 12 Same set of operands as shown for PHASE IOC1
Some operands can be re-named. These are the names of the breakers in the breaker control feature, the ID (identification)
of contact inputs and outputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name or
ID of any of these operands, the assigned name appears in the relay list of operands. The default names are shown in the
FlexLogic operands table.
The characteristics of the logic gates are tabulated in the following table, and the operators available in FlexLogic are
listed in the FlexLogic operators table.
FlexLogic provides built-in latches that by definition have a memory action, remaining in the set state after the set
input has been asserted. These built-in latches are reset dominant, meaning that if logical "1" is applied to both set
and reset entries simultaneously, then the output of the latch is logical "0." However, they are volatile, meaning that
they reset upon removal of control power.
When making changes to FlexLogic entries in the settings, all FlexLogic equations are re-compiled whenever any
new FlexLogic entry value is entered, and as a result of the re-compile all latches are reset automatically.
To implement FlexLogic using a graphical user interface, see the FlexLogic Design and Monitoring using Engineer
section in the previous chapter.
Virtual output 2
Set
state = On
Latch
Virtual input 1 OR #1 Reset
state = On
XOR
Digital element 1 Timer 2
state = Pickup Time Delay Operate output
OR #2
on dropout relay H1
Digital element 2 Timer 1
(200 ms)
state = Operated Time delay
AND on pickup
(800 ms)
Contact input H1c
state = Closed 827025A2.CDR
1. Inspect the example logic diagram to determine if the required logic can be implemented with the FlexLogic
operators. If this is not possible, the logic must be altered until this condition is satisfied. Once done, count the inputs
to each gate to verify that the number of inputs does not exceed the FlexLogic limits, which is unlikely but possible. If
the number of inputs is too high, subdivide the inputs into multiple gates to produce an equivalent. For example, if 25
inputs to an AND gate are required, connect Inputs 1 through 16 to AND(16), 17 through 25 to AND(9), and the outputs
from these two gates to AND(2).
Inspect each operator between the initial operands and final virtual outputs to determine if the output from the
operator is used as an input to more than one following operator. If so, the operator output must be assigned as a
virtual output.
For the example shown, the output of the AND gate is used as an input to both OR#1 and Timer 1, and must therefore
be made a virtual output and assigned the next available number (that is, Virtual Output 3). The final output must also
be assigned to a virtual output as virtual output 4, which is programmed in the contact output section to operate relay
H1 (that is, contact output H1).
Therefore, the required logic can be implemented with two FlexLogic equations with outputs of virtual output 3 and
virtual output 4, shown as follows.
Figure 5-113: Logic example with virtual outputs
Virtual output 1
state = On
Virtual output 2
Set
state = On
Latch
OR #1 Reset
Virtual input 1
state = On Timer 2
XOR Time delay
Digital element 1 OR #2 Virtual output 4
on dropout
state = Pickup
(200 ms)
827026A2.CDR
5 2. Prepare a logic diagram for the equation to produce virtual output 3, as this output is used as an operand in the virtual
output 4 equation (create the equation for every output that is used as an operand first, so that when these operands
are required they already have been evaluated and assigned to a specific virtual output). The logic for virtual output 3
is shown as follows with the final output assigned.
Figure 5-114: Logic for virtual output 3
Digital element 2
state= Operated
3. Prepare a logic diagram for virtual output 4, replacing the logic ahead of virtual output 3 with a symbol identified as
virtual output 3, shown as follows.
Virtual output 1
state = On
Virtual output 2
Set
state = On
Latch
OR #1 Reset
Virtual input 1
state = On Timer 2
XOR Time delay
OR #2 Virtual output 4
Digital element 1 on dropout
state = Pickup
(200 ms)
Timer 1
Virtual output 3 Time delay
state = On on pickup
(800 ms)
Contact input H1c
state = Closed
827028A2.CDR
4. Program the FlexLogic equation for virtual output 3 by translating the logic into available FlexLogic parameters. The
equation is formed one parameter at a time until the required logic is complete. It is generally easier to start at the
output end of the equation and work back towards the input, as shown in the following steps. It is also recommended
to list operator inputs from bottom to top. For demonstration, the final outputs are arbitrarily identified as parameter
99, and each preceding parameter decremented by one in turn. Until accustomed to using FlexLogic, it is suggested
that a worksheet with a series of cells marked with the arbitrary parameter numbers be prepared shown as follows.
Figure 5-116: FlexLogic worksheet
5
01
02
03
04
05
.....
97
98
99
827029A1.VSD
– 95: The last step in the procedure is to specify the upper input to the AND gate, the operated state of digital
element 2. This operand is "DIG ELEM 2 OP".
Writing the parameters in numerical order forms the equation for virtual output 3:
[95] DIG ELEM 2 OP
[96] Cont Ip H1c On
[97] NOT
[98] AND(2)
[99] = Virt Op 3
It is now possible to check that this selection of parameters produces the required logic by converting the set of
parameters into a logic diagram. The result of this process is shown in the figure, which is compared to the logic for
virtual output 3 diagram as a check.
Figure 5-117: FlexLogic equation for virtual output 3
FlexLogic entry:
95
Dig Element 2 (DE2) OP
AND Virtual output 3
FlexLogic entry:
96
Cont Ip 2 On (H1c)
FlexLogic entry:
97
NOT
FlexLogic entry:
98
AND (2)
FlexLogic entry:
99
= Virt Op 3 (VO3)
827030A2.CDR
6. Repeating the process described for virtual output 3, select the FlexLogic parameters for Virtual Output 4.
– 99: The final output of the equation is virtual output 4, which is parameter “= Virt Op 4".
5 – 98: The operator preceding the output is timer 2, which is operand “TIMER 2". Note that the settings required for
the timer are established in the timer programming section.
– 97: The operator preceding timer 2 is OR #2, a 3-input OR, which is parameter “OR(3)”.
– 96: The lowest input to OR #2 is operand “Cont Ip H1c On”.
– 95: The center input to OR #2 is operand “TIMER 1".
– 94: The input to timer 1 is operand “Virt Op 3 On".
– 93: The upper input to OR #2 is operand “LATCH (S,R)”.
– 92: There are two inputs to a latch, and the input immediately preceding the latch reset is OR #1, a 4-input OR,
which is parameter “OR(4)”.
– 91: The lowest input to OR #1 is operand “Virt Op 3 On".
– 90: The input just above the lowest input to OR #1 is operand “XOR(2)”.
– 89: The lower input to the XOR is operand “DIG ELEM 1 PKP”.
– 88: The upper input to the XOR is operand “Virt Ip 1 On".
– 87: The input just below the upper input to OR #1 is operand “Virt Op 2 On".
– 86: The upper input to OR #1 is operand “Virt Op 1 On".
– 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On".
The equation for virtual output 4 is:
[85] Virt Op 4 On
[86] Virt Op 1 On
[87] Virt Op 2 On
[88] Virt Ip 1 On
[89] DIG ELEM 1 PKP
[90] XOR(2)
[91] Virt Op 3 On
[92] OR(4)
[93] LATCH (S,R)
[94] Virt Op 3 On
[95] TIMER 1
[96] Cont Ip H1c On
[97] OR(3)
[98] TIMER 2
[99] = Virt Op 4
Now check that the selection of parameters produce the required logic by converting the set of parameters into a
logic diagram. The result is shown in the figure, which is compared to the logic for virtual output 4 diagram as a check.
Figure 5-118: FlexLogic equation for virtual output 4
FlexLogic entry:
85 Virt Op 4 On (VO4)
FlexLogic entry:
86 Virt Op 1 On (VO1)
FlexLogic entry:
87 Virt Op 2 On (VO2)
FlexLogic entry: Set
88 Latch
Virt Ip 1 On (VI1)
XOR OR Reset
FlexLogic entry:
89 Dig Element 1 (DE1) PKP
FlexLogic entry:
90 XOR (2 Input)
FlexLogic entry:
91 Virt Op 3 On (VO3)
OR T2 Virtual output 4
FlexLogic entry:
92 OR (4 Input)
FlexLogic entry:
93 Latch (Set, Reset)
FlexLogic entry:
94 Virt Op 3 On (VO3) T1
FlexLogic entry:
95 Timer 1
FlexLogic entry:
96
5
Cont Ip 2 On (H1c)
FlexLogic entry:
97 OR (3 Input)
FlexLogic entry:
98 Timer 2
FlexLogic entry:
99 =Virt Op 4 (VO4) 827031A2.CDR
7. Now write the complete FlexLogic expression required to implement the logic, making an effort to assemble the
equation in an order where Virtual Outputs that are used as inputs to operators are created before needed. In cases
where a lot of processing is required to perform logic, this can be difficult to achieve, but in most cases does not cause
problems as all logic is calculated at least four times per power frequency cycle. The possibility of a problem caused by
sequential processing emphasizes the necessity to test the performance of FlexLogic before it is placed in service.
In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the following
order:
DIG ELEM 2 OP
Cont Ip H1c On
NOT
AND(2)
= Virt Op 3
Virt Op 4 On
Virt Op 1 On
Virt Op 2 On
Virt Ip 1 On
DIG ELEM 1 PKP
XOR(2)
Virt Op 3 On
OR(4)
LATCH (S,R)
Virt Op 3 On
TIMER 1
Cont Ip H1c On
OR(3)
TIMER 2
= Virt Op 4
END
In this expression, the virtual output 4 input to the four-input OR is listed before it is created. This is typical of a form of
feedback, in this case, used to create a seal-in effect with the latch, and is correct.
8. Always test the logic after it is loaded into the relay, in the same way as has been used in the past. Testing can be
simplified by placing an "END" operator within the overall set of FlexLogic equations. The equations are evaluated up
to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.
There are 1,024 FlexLogic entries available, numbered from 1 to 1024, with default END entry settings. If a "Disabled"
element is selected as a FlexLogic entry, the associated state flag is never set to ‘1’. Press the +/– key when editing
FlexLogic equations to quickly scan through the major parameter types.
There are 32 identical FlexLogic timers available. These timers are used as operators for FlexLogic equations.
TIMER 1 TYPE — Selects the time measurement unit.
TIMER 1 PICKUP DELAY — Sets the time delay to pickup. If a pickup delay is not required, set this function to "0."
TIMER 1 DROPOUT DELAY — Sets the time delay to dropout. If a dropout delay is not required, set this function to "0."
5.6.7 FlexElements
SETTINGS FLEXLOGIC FLEXELEMENTS FLEXELEMENT 1(16)
FLEXELEMENT 1 FLEXELEMENT 1 Range: Disabled, Enabled
FUNCTION: Disabled
FLEXELEMENT 1
EVENTS: Disabled
Range: Disabled, Enabled 5
A FlexElement is a universal comparator used to monitor any analog actual value calculated by the relay or a net
difference of any two analog actual values of the same type. The effective operating signal can be treated as a signed
number or its absolute value can be used.
FlexElements run every half power cycle (every four protection passes).
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period
of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold, as
per your choice.
SETTING
SETTINGS
FLEXELEMENT 1
FUNCTION: FLEXELEMENT 1 INPUT MODE:
Enabled = 1
FLEXELEMENT 1 COMP MODE:
FLEXELEMENT 1 DIRECTION:
SETTING
FLEXELEMENT 1 PICKUP:
FLEXELEMENT 1 BLK:
FLEXELEMENT 1 INPUT
AND HYSTERESIS:
Off = 0
FLEXELEMENT 1 dt UNIT: SETTINGS
FxE 1 PKP
ACTUAL VALUE
FlexElement 1 OpSig
842004A4.CDR
5
FLEXELEMENT 1 +IN — This setting specifies the first (non-inverted) input to the FlexElement. Zero is assumed as the input if
this setting is set to “Off.” For proper operation of the element, at least one input must be selected. Otherwise, the element
does not assert its output operands.
FLEXELEMENT 1 –IN — Specifies the second (inverted) input to the FlexElement. Zero is assumed as the input if this setting is
set to “Off.” For proper operation of the element, at least one input must be selected. Otherwise, the element does not
assert its output operands. This input is used to invert the signal if needed for convenience, or to make the element
respond to a differential signal, such as for a top-bottom oil temperature differential alarm. The element does not operate
if the two input signals are of different types, for example if one tries to use active power and phase angle to build the
effective operating signal.
The element responds directly to the differential signal if the FLEXELEMENT 1 INPUT MODE setting is set to “Signed” The
element responds to the absolute value of the differential signal if this setting is set to “Absolute.” Sample applications for
the “Absolute” setting include monitoring the angular difference between two phasors with a symmetrical limit angle in
both directions, monitoring power regardless of its direction, or monitoring a trend.
The element responds directly to its operating signal—as defined by the FLEXELEMENT 1 +IN, FLEXELEMENT 1 –IN and
FLEXELEMENT 1 INPUT MODE settings—if the FLEXELEMENT 1 COMP MODE setting is set to “Level.” The element responds to the
rate of change of its operating signal if the FLEXELEMENT 1 COMP MODE setting is set to “Delta.” In this case, the
FLEXELEMENT 1 dt UNIT and FLEXELEMENT 1 dt settings specify how the rate of change is derived.
FLEXELEMENT 1 DIRECTION — Enables the relay to respond to either high or low values of the operating signal. The following
figure explains the application of the FLEXELEMENT 1 DIRECTION, FLEXELEMENT 1 PICKUP, and FLEXELEMENT 1 HYSTERESIS
settings.
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over
HYSTERESIS = % of PICKUP
FlexElement 1 OpSig
PICKUP
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under
HYSTERESIS = % of PICKUP
FlexElement 1 OpSig
PICKUP
842705A1.CDR
In conjunction with the FLEXELEMENT 1 INPUT MODE setting, the element can be programmed to provide two extra
characteristics, as shown in the following figure.
FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Signed;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Absolute;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under;
5 FLEXELEMENT INPUT
MODE = Signed;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Absolute;
FlexElement 1 OpSig
842706A2.CDR
FLEXELEMENT 1 PICKUP — This setting specifies the operating threshold for the effective operating signal of the element. If
set to “Over,” the element picks up when the operating signal exceeds the FLEXELEMENT 1 PICKUP value. If set to “Under,” the
element picks up when the operating signal falls below the FLEXELEMENT 1 PICKUP value.
FLEXELEMENT 1 HYSTERESIS — This setting controls the element dropout. Notice that both the operating signal and the
pickup threshold can be negative, facilitating applications such as reverse power alarm protection. The FlexElement can be
programmed to work with all analog actual values measured by the relay. The FLEXELEMENT 1 PICKUP setting is entered in
per-unit values using the following definitions of the base units.
Table 5-25: FlexElement base units
Unit Description
BREAKER ACC ARCING AMPS BASE = 2000 kA2 cycle
(Brk X Acc Arc Amp A, B, and C)
BREAKER ARCING AMPS BASE = 1 kA2 cycle
(Brk X Arc Amp A, B, and C)
Unit Description
DCmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs
DELTA TIME BASE = 1 µs
FAULT LOCATION BASE = Line Length as specified in Fault Report
FREQUENCY fBASE = 1 Hz
PHASE ANGLE BASE = 360 degrees (see the UR angle referencing convention)
POWER FACTOR PFBASE = 1.00
RTDs BASE = 100°C
SOURCE CURRENT IBASE = maximum nominal primary RMS value of the +IN and –IN inputs
SOURCE ENERGY EBASE = 10000 MWh or MVAh, respectively
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER PBASE = maximum value of VBASE IBASE for the +IN and –IN inputs
SOURCE THD & HARMONICS BASE = 1%
SOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputs
FLEXELEMENT 1 HYSTERESIS — This setting defines the pickup–dropout relation of the element by specifying the width of the
hysteresis loop as a percentage of the pickup value as shown in the FlexElement Direction, Pickup, and Hysteresis diagram.
FLEXELEMENT 1 dt UNIT — Specifies the time unit for the setting FLEXELEMENT 1 dt. This setting is applicable only if
FLEXELEMENT 1 COMP MODE is set to “Delta.”
FLEXELEMENT 1 dt — Specifies duration of the time interval for the rate of change mode of operation. This setting is
applicable only if FLEXELEMENT 1 COMP MODE is set to “Delta.”
FLEXELEMENT 1 PKP DELAY — Specifies the pickup delay of the element. 5
FLEXELEMENT 1 RST DELAY — Specifies the reset delay of the element.
The non-volatile latches provide a permanent logical flag that is stored safely and do not reset upon restart after the relay
is powered down. Typical applications include sustaining operator commands or permanently blocking relay functions,
such as Autorecloser, until a deliberate interface action resets the latch.
LATCH 1 TYPE — This setting characterizes Latch 1 to be Set- or Reset-dominant.
LATCH 1 SET — If asserted, the specified FlexLogic operands 'sets' Latch 1.
LATCH 1 RESET — If asserted, the specified FlexLogic operand 'resets' Latch 1.
Enabled=1 RUN
SETTING
LATCH 1 SET:
FLEXLOGIC OPERANDS
Off=0 SET LATCH 1 ON
LATCH 1 OFF
SETTING
LATCH 1 RESET:
5 ON
OFF
ON
OFF
ON
Previous
OFF
Previous
State State
OFF ON OFF ON
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correct
this issue.
A time dial multiplier setting allows selection of a multiple of the base curve shape (where the time dial multiplier = 1) with
the curve shape (CURVE) setting. Unlike the electromechanical time dial equivalent, operate times are directly proportional
to the time multiplier (TD MULTIPLIER) setting value. For example, all times for a multiplier of 10 are 10 times the multiplier 1
or base curve values. Setting the multiplier to zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal energy capacity memory variable. When this variable
indicates that the energy capacity has reached 100%, a time overcurrent element operates. If less than 100% energy
capacity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the pickup value,
the variable must be reduced. Two methods of this resetting operation are available: “Instantaneous” and “Timed.” The
“Instantaneous” selection is intended for applications with other relays, such as most static relays, which set the energy
capacity directly to zero when the current falls below the reset threshold. The “Timed” selection can be used where the
relay must coordinate with electromechanical relays.
IEEE curves
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve classifications for
extremely, very, and moderately inverse curves. The IEEE curves are derived from the operate and reset time equations.
Eq. 5-8
where
T = operate time (in seconds)
TDM = Multiplier setting
I = input current
Ipickup = Pickup Current setting
A, B, p = constants defined in the table
TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”)
tr = characteristic constant defined in the table
Table 5-27: IEEE inverse time curve constants
IEEE curve shape A B p tr
IEEE Extremely Inverse 28.2 0.1217 2.0000 29.1
IEEE Very Inverse 19.61 0.491 2.0000 21.6
IEEE Moderately Inverse 0.0515 0.1140 0.02000 4.85
IEC curves
For European applications, the relay offers three standard curves defined in IEC 255-4 and British standard BS142. These
are defined as IEC Curve A, IEC Curve B, and IEC Curve C. The IEC curves are derived by the operate and reset time
equations.
Eq. 5-9
where
T = operate time (in seconds)
TDM = Multiplier setting
I = input current
Ipickup = Pickup Current setting
K, E = constants defined in the table
tr = characteristic constant defined in the table
TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”)
Table 5-29: IEC (BS) inverse time curve constants
IEC (BS) curve shape K E tr
IEC Curve A (BS142) 0.140 0.020 9.7 5
IEC Curve B (BS142) 13.500 1.000 43.2
IEC Curve C (BS142) 80.000 2.000 58.2
IEC Short Inverse 0.050 0.040 0.500
IAC curves
The curves for the General Electric type IAC relay family are derived from the formulae:
Eq. 5-10
5
where
T = operate time (in seconds)
TDM = Multiplier setting
I = Input current
Ipkp = Pickup Current setting
A to E = constants defined in the table
tr = characteristic constant defined in the table
TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”)
Table 5-31: GE type IAC inverse time curve constants
IAC curve shape A B C D E tr
IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461 6.008
IAC Very Inverse 0.0900 0.7955 0.1000 –1.2885 7.9586 4.678
IAC Inverse 0.2078 0.8630 0.8000 –0.4180 0.1947 0.990
IAC Short Inverse 0.0428 0.0609 0.6200 –0.0010 0.0221 0.222
I2t curves
The I2t curves are derived as follows:
Eq. 5-11
where
T = Operate time (in seconds)
TDM = Multiplier setting
I = Input current
Ipickup = Pickup Current setting
TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”)
FlexCurves
FlexCurves are described in the FlexCurves section later in this chapter. The curve shapes for the FlexCurves are derived
from the formulae:
Eq. 5-12
Eq. 5-13
where
T = operate time (in seconds)
TDM = Multiplier setting
I = Input Current
Ipickup = Pickup Current setting
TRESET = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)
5
Definite time curve
The Definite Time curve shape operates as soon as the pickup level is exceeded for a specified period of time. The base
definite time curve delay is in seconds. The curve multiplier of 0.00 to 600.00 makes this delay adjustable from
instantaneous to 600.00 seconds in steps of 10 ms. The definite time curve shapes are defined as follows:
Eq. 5-14
Eq. 5-15
where
T = Operate Time (in seconds)
TDM = Multiplier setting
I = Input Current
Ipickup = Pickup Current setting
TRESET = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)
Recloser curves
The F35 uses the FlexCurve feature to facilitate programming of 41 recloser curves. See the FlexCurves settings section
earlier in this chapter for details.
PHASE TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
PHASE TOC1
EVENTS: Disabled
Range: Disabled, Enabled 5
The phase time overcurrent element can provide a specified time-delay operating characteristic versus the applied current
or be used as a simple definite time element. The phase current input quantities can be programmed as fundamental
phasor magnitude or total waveform RMS magnitude as required by the application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (see the Inverse TOC Curve Characteristics
section earlier for details on curve setup, trip times, and reset operation). When the element is blocked, the time
accumulator resets according to the reset characteristic. For example, if the element reset characteristic is set to
“Instantaneous” and the element is blocked, the time accumulator clears immediately.
The PHASE TOC1 PICKUP setting can be reduced dynamically by a voltage restraint feature (when enabled). This is
accomplished via the multipliers (Mvr) corresponding to the phase-phase voltages of the voltage restraint characteristic
curve (see the figure); the pickup level is calculated as Mvr times the PHASE TOC1 PICKUP setting. If the voltage restraint
feature is disabled, the pickup level always remains at the setting value.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Phase-Phase Voltage ÷ VT Nominal Phase-phase Voltage
VOLTAGE RESTRAINT CHARACTERISTIC FOR PHASE TIME O/C
818784A4.CDR
FUNCTION — This setting enables and disables the phase time overcurrent protection element.
SIGNAL SOURCE — Selects the signal source for the phase time overcurrent protection element.
INPUT — Selects how phase current input quantities are interpreted by the F35. Inputs can be selected as fundamental
phasor magnitudes or total waveform RMS magnitudes as required by the application.
PICKUP — Specifies the phase time overcurrent pickup level in per-unit values.
SETTING
PHASE TOC1
BLOCK-A :
Off=0
SETTING
PHASE TOC1
BLOCK-B:
Off=0
SETTING
SETTING
PHASE TOC1
PHASE TOC1 INPUT:
BLOCK-C:
PHASE TOC1
Off=0 PICKUP:
PHASE TOC1
SETTING CURVE:
PHASE TOC1 PHASE TOC1
SOURCE: TD MULTIPLIER:
IA
PHASE TOC1
IB RESET: FLEXLOGIC OPERAND
IC AND RUN PHASE TOC1 A PKP
IA PICKUP
Seq=ABC Seq=ACB PHASE TOC1 A DPO
MULTIPLY INPUTS
RUN
t PHASE TOC1 A OP
VAB VAC Set
Calculate Multiplier Set Pickup AND RUN PHASE TOC1 B PKP
RUN
Multiplier-Phase A IB PICKUP
Set PHASE TOC1 B DPO
VBC VBA Set Pickup
Calculate Multiplier t PHASE TOC1 B OP
RUN
Multiplier-Phase B
Set AND RUN PHASE TOC1 C PKP
VCA VCB IC PICKUP
Calculate Multiplier Set Pickup PHASE TOC1 C DPO
Multiplier-Phase C
t PHASE TOC1 C OP
SETTING OR PHASE TOC1 PKP
PHASE TOC1 VOLT
RESTRAINT:
5
OR PHASE TOC1 OP
Enabled
827072A5.CDR
PHASE IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The phase instantaneous overcurrent element can be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude. For timing curves, see the publication
Instantaneous Overcurrent (IOC) Element Response to Saturated Waveforms in UR Series Relays (GET-8400A).
FUNCTION — This setting enables and disables the phase instantaneous overcurrent protection element.
SOURCE — Selects the signal source for the phase instantaneous overcurrent protection element.
PICKUP — Specifies the phase instantaneous overcurrent pickup level in per-unit values.
DELAY —Delays the assertion of the PHASE IOC OP operands. It is used to achieve timing coordination with other elements
and relays.
RESET DELAY — Specifies a delay for the reset of the phase instantaneous overcurrent element between the operate output
state and the return to logic 0 after the input passes outside the defined pickup range. This setting is used to ensure that
the relay output contacts are closed long enough to ensure reception by downstream equipment.
BLOCK A — Assertion of the operand assigned to this setting block’s phase A of the phase instantaneous overcurrent
element.
EVENTS — Enables and disables the logging of phase instantaneous overcurrent events in the sequence of events recorder.
5
= IA FLEXLOGIC OPERANDS
AND RUN TPKP
= IB PHASE IOC1 A OP
IC > Pickup PHASE IOC1 B OP
= IC TRST
PHASE IOC1 C OP
5.7.4.1 Menu
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) NEUTRAL CURRENT
NEUTRAL CURRENT NEUTRAL TOC 1 See below
NEUTRAL TOC 6
NEUTRAL TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The neutral time overcurrent element can provide a desired time-delay operating characteristic versus the applied current
5
or be used as a simple definite time element. The neutral current input value is a quantity calculated as 3Io from the phase
currents and can be programmed as fundamental phasor magnitude or total waveform RMS magnitude as required by the
application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (see the Inverse TOC Curve Characteristics
section for details on curve setup, trip times, and reset operation). When the element is blocked, the time accumulator
resets according to the reset characteristic. For example, if the element reset characteristic is set to “Instantaneous” and
the element is blocked, the time accumulator clears immediately.
NEUTRAL TOC1 FUNCTION — This setting enables and disables the neutral time overcurrent protection element.
NEUTRAL TOC1 SIGNAL SOURCE — This setting selects the signal source for the neutral time overcurrent protection element.
NEUTRAL TOC1 INPUT — This setting selects how neutral current input quantities are interpreted by the F35. Inputs can be
selected as fundamental phasor magnitudes or total waveform RMS magnitudes as required by the application.
NEUTRAL TOC1 PICKUP — This setting specifies the neutral time overcurrent pickup level in per-unit values.
NEUTRAL TOC1 CURVE — This setting selects the inverse time overcurrent curve style.
NEUTRAL TOC1 TD MULTIPLIER — This setting specifies a multiple of the base curve shape specified by the CURVE setting.
Programming this value to zero results in an instantaneous response to all current levels above pickup.
NEUTRAL TOC1 RESET — The “Instantaneous” reset method is intended for applications with other relays, such as most static
relays, which set the energy capacity directly to zero when the current falls below the reset threshold. The “Timed” reset
method can be used where the relay must coordinate with electromechanical relays.
NEUTRAL TOC1 BLOCK — Assertion of the operand assigned to this setting blocks operation of the neutral time overcurrent
element.
NEUTRAL TOC1 EVENTS — This setting enables and disables the logging of neutral time overcurrent events in the sequence
of events recorder.
SETTINGS
NEUTRAL TOC1
INPUT:
SETTING NEUTRAL TOC1
NEUTRAL TOC1 PICKUP:
FUNCTION: NEUTRAL TOC1
Enabled = 1 CURVE:
NEUTRAL TOC1
TD MULTIPLIER:
NEUTRAL TOC 1 FLEXLOGIC OPERANDS
SETTING
RESET: NEUTRAL TOC1 PKP
NEUTRAL TOC1
AND RUN IN PICKUP NEUTRAL TOC1 DPO
SOURCE:
NEUTRAL TOC1 OP
IN t
I
SETTING
NEUTRAL TOC1
BLOCK:
Off = 0 827034A4.VSD
NEUTRAL IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The neutral instantaneous overcurrent element can be used as an instantaneous function with no intentional delay or as a
definite time function. The element essentially responds to the magnitude of a neutral current fundamental frequency
phasor calculated from the phase currents. A positive-sequence restraint is applied for better performance. A small portion
(6.25%) of the positive-sequence current magnitude is subtracted from the zero-sequence current magnitude when
forming the operating quantity of the element as follows:
Iop = 3 x (|I_0| - K x |I_1|) where K = 1/16 Eq. 5-16
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from:
• System unbalances under heavy load conditions
• Transformation errors of current transformers (CTs) during double-line and three-phase faults
• Switch-off transients during double-line and three-phase faults
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on how test currents are injected into the relay (single-phase injection):
Eq. 5-17
NEUTRAL IOC1 FUNCTION — This setting enables and disables the neutral instantaneous overcurrent protection element.
NEUTRAL IOC1 SIGNAL SOURCE — This setting selects the signal source for the neutral instantaneous overcurrent protection
element.
NEUTRAL IOC1 PICKUP — This setting specifies the neutral instantaneous overcurrent pickup level in per-unit values.
NEUTRAL IOC1 PICKUP DELAY — This setting delays the assertion of the NEUTRAL IOC OP operands. It is used to achieve timing
coordination with other elements and relays.
NEUTRAL IOC1 RESET DELAY — This setting specifies a delay for the reset of the neutral instantaneous overcurrent element
between the operate output state and the return to logic 0 after the input passes outside the defined pickup range. This
setting is used to ensure that the relay output contacts are closed long enough to ensure reception by downstream
equipment.a
NEUTRAL IOC1 BLOCK — Assertion of the operand assigned to this setting blocks operation of the neutral instantaneous
overcurrent element.
NEUTRAL IOC1 EVENTS — This setting enables and disables the logging of neutral instantaneous overcurrent events in the
sequence of events recorder.
Figure 5-127: Neutral IOC1 logic
SETTING
SETTINGS
NEUTRAL IOC1 FUNCTION:
Enabled=1
SETTING
NEUTRAL IOC1
PICKUP DELAY :
5
FLEXLOGIC OPERANDS
NEUTRAL IOC1
NEUTRAL IOC1 PICKUP: NEUTRAL IOC1 PKP
RESET DELAY :
SETTING NEUTRAL IOC1 DPO
AND RUN tPKP
tRST NEUTRAL IOC1 OP
NEUTRAL IOC1 BLOCK: 3( I_0 - K I_1 ) PICKUP
Off=0
SETTING
I_0
827035A5.CDR
WATTMETRIC GND FLT 1 Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
WATTMETRIC GND FLT 1 PWR PKP — This setting specifies the operating point of the element. A value of 1 pu is a product of
the 1 pu voltage as specified for the overvoltage condition of this element, and 1 pu current as specified for the
overcurrent condition of this element.
WATTMETRIC GND FLT 1 REF PWR — This setting is used to calculate the inverse time characteristic delay (defined by Sref in
the following equations). A value of 1 pu represents the product of a 1 pu voltage (as specified in the overvoltage condition
for this element) and a 1 pu current (as specified in the overcurrent condition for this element.
WATTMETRIC GND FLT 1 ECA — This setting adjusts the maximum torque angle of the element. The operating power is
calculated as:
S_op = Re(Vn(In x 1ECA)*) Eq. 5-18
where
* indicates complex conjugate
By varying the element characteristic angle (ECA), the element can be made to respond to forward or reverse direction in
inductive, resistive, or capacitive networks as shown in the Wattmetric Characteristic Angle Response diagram.
WATTMETRIC GND FLT 1 PWR PKP DEL — This setting defines a definite time delay before the inverse time characteristic is
activated. If the curve selection is set as “Definite Time”, the element operates after this security time delay. If the curve
selection is “Inverse” or one of the FlexCurves, the element uses both the definite and inverse time timers simultaneously.
The definite time timer, specified by this setting, is used and when expires it releases the inverse time timer for operation
(torque control).
WATTMETRIC GND FLT 1 CURVE — Choose one of three methods to delay the operate signal once all conditions are met to
discriminate fault direction.
The “Definite Time” selection allows for a fixed time delay defined by the WATTMETRIC GND FLT 1 PWR PKP DEL setting.
The “Inverse” selection allows for inverse time characteristics delay defined by the following formula:
5
Eq. 5-19
where
m is a multiplier defined by the multiplier setting
Sref is the multiplier setting
Sop is the operating power at the time
This timer starts after the definite time timer expires.
The four FlexCurves allow for custom user-programmable time characteristics. When working with FlexCurves, the
element uses the operate to pickup ratio, and the multiplier setting is not applied:
Eq. 5-20
Again, the FlexCurve timer starts after the definite time timer expires.
INDUCTIVE NETWORK
Vn Vn
In In
RESISTIVE NETWORK
Vn Vn
In In
5
In In
CAPACITIIVE NETWORK
Vn Vn
837804A1.CDR
WATTMETRIC GND FLT 1 MULTIPLIER — This setting is applicable if the WATTMETRIC GND FLT 1 CURVE is set to Inverse and
defines the multiplier factor for the inverse time delay.
GROUND CURRENT
5.7.6 Ground current
SETTINGS SETTINGS
WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
SOURCE: PWR PICKUP:
WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
CURRENT: SETTING SETTINGS
OC PICKUP:
Calculated: Measured: WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
WATTMETRIC GND FLT 1
Neutral, In Ground, Ig ECA: OV PICKUP: CURVE:
SETTING
WATTMETRIC GND FLT 1 WATTMETRIC GND FLT 1
GROUND TOC1
VOLTAGE: S = V*conj (I*exp(-j*ECA)) SOP > PWR PICKUP WATTMETRIC GND FLT 1 REF PWR:
1 FUNCTION:
WATTMETRIC GND FLT 1
Enabled = 1
OC PKP DEL:
WATT GND FLT 1 BLK:
AND
FLEXLOGIC OPERAND
Off = 0
tPKP WATTMETRIC 1 PKP
0
See below
837033A4.CDR
5-247
GROUPED ELEMENTS
5
GROUPED ELEMENTS CHAPTER 5: SETTINGS
GROUND TOC6
GROUND TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
This element can provide a required time-delay operating characteristic versus the applied current or be used as a simple
definite time element. The ground current input value is the quantity measured by the ground input CT and is the
fundamental phasor or RMS magnitude. Two methods of resetting operation are available: “Timed” and “Instantaneous”
(see the Inverse TOC Curve Characteristics section for details). When the element is blocked, the time accumulator resets
according to the reset characteristic. For example, if the element reset characteristic is set to “Instantaneous” and the
element is blocked, the time accumulator clears immediately.
GROUND TOC1 FUNCTION — This setting enables and disables the ground time overcurrent protection element.
GROUND TOC1 SIGNAL SOURCE — This setting selects the signal source for the ground time overcurrent protection element.
GROUND TOC1 INPUT — This setting selects how ground current input quantities are interpreted by the F35. Inputs can be
selected as fundamental phasor magnitudes or total waveform RMS magnitudes as required by the application.
GROUND TOC1 PICKUP — This setting specifies the ground time overcurrent pickup level in per-unit values.
GROUND TOC1 CURVE — This setting selects the inverse time overcurrent curve style.
GROUND TOC1 TD MULTIPLIER — This setting specifies a multiple of the base curve shape specified by the CURVE setting.
Programming this value to zero results in an instantaneous response to all current levels above pickup.
GROUND TOC1 RESET — The “Instantaneous” reset method is intended for applications with other relays, such as most static
relays, which set the energy capacity directly to zero when the current falls below the reset threshold. The “Timed” reset
method can be used where the relay must coordinate with electromechanical relays.
GROUND TOC1 BLOCK — Assertion of the operand assigned to this setting blocks operation of the ground time overcurrent
element.
GROUND TOC1 EVENTS — This setting enables and disables the logging of ground time overcurrent events in the sequence
of events recorder.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
This channel can be also equipped with a sensitive input. The conversion range of a sensitive channel is from 0.002
to 4.6 times the CT rating.
SETTINGS
GROUND TOC1
INPUT:
SETTING GROUND TOC1
GROUND TOC1 PICKUP:
FUNCTION: GROUND TOC1
Enabled = 1 CURVE:
GROUND TOC1
TD MULTIPLIER:
GROUND TOC 1 FLEXLOGIC OPERANDS
SETTING
RESET: GROUND TOC1 PKP
GROUND TOC1
AND RUN IG PICKUP GROUND TOC1 DPO
SOURCE:
GROUND TOC1 OP
IG t
SETTING
I
5
GROUND TOC1
BLOCK:
827036A4.VSD
Off = 0
GROUND IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The ground instantaneous overcurrent element can be used as an instantaneous element with no intentional delay or as a
definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental
phasor magnitude.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
This channel can be equipped with a standard or sensitive input. The conversion range of a sensitive channel is
from 0.002 to 4.6 times the CT rating.
FLEXLOGIC OPERANDS
GROUND IOC1 PKP
SETTING GROUND IOIC DPO
GROUND IOC1
SETTINGS GROUND IOC1 OP
FUNCTION:
Enabled = 1 GROUND IOC1 PICKUP
SETTING DELAY:
GROUND IOC1 GROUND IOC1 RESET
SETTING
PICKUP: DELAY:
GROUND IOC1
AND RUN tPKP
SOURCE:
IG
IG PICKUP tRST
SETTING
GROUND IOC1
BLOCK:
827037A5.VSD
Off = 0
For information on the negative sequence time overcurrent curves, see the Inverse Time Overcurrent Curves section
earlier.
NEG SEQ TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The negative-sequence time overcurrent element can be used to determine and clear unbalance in the system. The input
for calculating negative-sequence current is the fundamental phasor value.
Two methods of resetting operation are available; “Timed” and “Instantaneous” (see the Inverse TOC Curve Characteristics
section earlier for details on curve setup, trip times and reset operation). When the element is blocked, the time
accumulator resets according to the reset characteristic. For example, if the element reset characteristic is set to
“Instantaneous” and the element is blocked, the time accumulator clears immediately.
Figure 5-132: Negative sequence TOC1 logic
SETTING
SETTING
Off=0
t
SETTING
NEG SEQ IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The negative-sequence instantaneous overcurrent element can be used as an instantaneous function with no intentional
delay or as a definite time function. The element responds to the negative-sequence current fundamental frequency
phasor magnitude (calculated from the phase currents) and applies a positive-sequence restraint for better performance:
a small portion (12.5%) of the positive-sequence current magnitude is subtracted from the negative-sequence current
magnitude when forming the operating quantity.
Iop = |I_2| - K x |I_1| where K = 1/8 Eq. 5-21
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence
currents resulting from
• System unbalances under heavy load conditions
• Transformation errors of current transformers (CTs) during three-phase faults
• Fault inception and switch-off transients during three-phase faults
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on how the test currents are injected into the relay (single-phase injection:
Iop = 0.2917 x Iinjected; three-phase injection, opposite rotation: Iop = Iinjected).
Figure 5-133: Negative sequence IOC1 logic
SETTING
SETTING
Enabled=1
SETTING
NEG SEQ IOC1
PICKUP DELAY:
FLEXLOGIC OPERANDS
NEG SEQ IOC1
NEG SEQ IOC1 PICKUP: NEG SEQ IOC1 PKP
RESET DELAY:
SETTING NEG SEQ IOC1 DPO
AND RUN tPKP
tRST NEG SEQ IOC1 OP
NEG SEQ IOC1 BLOCK: I_2 - K I_1 PICKUP
Off=0
SETTING
I_2 827058A6.CDR
5.7.8.1 Menu
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) VOLTAGE ELEMENTS
VOLTAGE ELEMENTS PHASE See below
UNDERVOLTAGE1
PHASE
UNDERVOLTAGE3
•
also be used to block the functioning of other elements through the block feature of those elements.
Source transfer schemes — In the event of an undervoltage, a transfer signal can be generated to transfer a load
5
from its normal source to a standby or emergency power source.
The undervoltage elements can be programmed to have a definite time delay characteristic. The definite time curve
operates when the voltage drops below the pickup level for a specified period of time. The time delay is adjustable from 0
to 600.00 seconds in steps of 0.01. The undervoltage elements can also be programmed to have an inverse time delay
characteristic.
The undervoltage delay setting defines the family of curves shown as follows.
Eq. 5-22
where
T = operating time
D = undervoltage delay setting (D = 0.00 operates instantaneously)
V = secondary voltage applied to the relay
Vpickup = pickup level
Time (seconds)
% of voltage pickup
842788A1.CDR
At 0% of pickup, the operating time equals the PHASE UNDERVOLTAGE DELAY setting.
PHASE UV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
This element is used to give a time-delay operating characteristic versus the applied fundamental voltage (phase-to-
ground or phase-to-phase for wye VT connection, or phase-to-phase for delta VT connection) or as a definite time
element. The element resets instantaneously if the applied voltage exceeds the dropout voltage. The delay setting selects
the minimum operating time of the phase undervoltage. The minimum voltage setting selects the operating voltage below
which the element is blocked (a setting of “0” allows a dead source to be considered a fault condition).
}
VBG or VBC < Minimum
VAB AND RUN VCG or VCA< PICKUP PHASE UV1 C PKP
VCG or VCA < Minimum
VBC t PHASE UV1 C DPO
VCA PHASE UV1 C OP
Source VT = Wye V
FLEXLOGIC OPERAND
SETTING OR PHASE UV1 PKP
827039AC.CDR
There are three phase overvoltage elements available. A phase overvoltage element is used as an instantaneous element
with no intentional time delay or as a definite time element. The input voltage is the phase-to-phase voltage, either
measured directly from delta-connected VTs or as calculated from phase-to-ground (wye) connected VTs. The figure
shows specific voltages to be used for each phase.
FLEXLOGIC OPERAND
OR PHASE OV1 PKP
827066A8.CDR
If the source VT is wye-connected, then the phase overvoltage pickup condition is V > x Pickup for VAB, VBC, and
VCA.
NEUTRAL OV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
There are three neutral overvoltage elements available. The neutral overvoltage element can be used to detect
asymmetrical system voltage condition due to a ground fault or to the loss of one or two phases of the source. The
element responds to the system neutral voltage (3V_0), calculated from the phase voltages. The nominal secondary
voltage of the phase voltage channels entered under SETTINGS SYSTEM SETUP AC INPUTS VOLTAGE BANK PHASE
VT SECONDARY is the p.u. base used when setting the pickup level.
The neutral overvoltage element can provide a time-delayed operating characteristic versus the applied voltage (initialized
from FlexCurves A, B, or C) or be used as a definite time element. The NEUTRAL OV1 PICKUP DELAY setting applies only if the
NEUTRAL OV1 CURVE setting is “Definite Time.” The source assigned to this element must be configured for a phase VT.
VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to
be wye-connected.
Figure 5-137: Neutral overvoltage1 logic
SETTING
NEUTRAL OV1
FUNCTION:
SETTING SETTING
Enabled=1
NEUTRAL OV1 PICKUP
NEUTRAL OV1 PICKUP: DELAY :
SETTING
AND RUN NEUTRAL OV1 RESET
DELAY :
NEUTRAL OV1 BLOCK:
NEUTRAL OV1 CURVE :
Off=0
FLEXLOGIC OPERANDS
3V_0< Pickup tPKP
t NEUTRAL OV1 OP
SETTING tRST
NEUTRAL OV1 DPO
NEUTRAL OV1 SIGNAL
SOURCE: NEUTRAL OV1 PKP
ZERO SEQ VOLT (V_0)
827848A3.CDR
AUX UV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The F35 contains one auxiliary undervoltage element for each VT bank. This element monitors undervoltage conditions of
the auxiliary voltage.
The AUX UV1 PICKUP selects the voltage level at which the time undervoltage element starts timing. The nominal secondary
voltage of the auxiliary voltage channel entered under SETTINGS SYSTEM SETUP AC INPUTS VOLTAGE BANK X5
AUXILIARY VT X5 SECONDARY is the per-unit base used when setting the pickup level.
The AUX UV1 DELAY setting selects the minimum operating time of the auxiliary undervoltage element.
Both AUX UV1 PICKUP and AUX UV1 DELAY settings establish the operating curve of the undervoltage element. The auxiliary
undervoltage element can be programmed to use either definite time delay or inverse time delay characteristics. The
operating characteristics and equations for both definite and inverse time delay are as for the phase undervoltage
element.
The element resets instantaneously. The minimum voltage setting selects the operating voltage below which the element
is blocked.
827849A3.CDR
AUX OV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
The F35 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage
conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM
SETUP AC INPUTS VOLTAGE BANK X5 AUXILIARY VT X5 SECONDARY is the per-unit (pu) base used when setting the
pickup level.
The trip bus element allows aggregating outputs of protection and control elements without using FlexLogic and assigning
them a simple and effective manner. Each trip bus can be assigned for either trip or alarm actions. Simple trip conditioning
such as latch, delay, and seal-in delay are available.
The easiest way to assign element outputs to a trip bus is through the EnerVista software under Settings > Protection
Summary. Navigate to a specific protection or control protection element and check the bus box by hovering over the
blank check box and selecting an option that displays. Once the required element is selected for a specific bus, a list of
element operate-type operands are displayed and can be assigned to a trip bus. If more than one operate-type operand is
required, it can be assigned directly from the trip bus menu.
Figure 5-140: Trip bus fields in the protection summary
SETTINGS
TRIP BUS 1 FLEXLOGIC OPERAND
FUNCTION
TRIP BUS 1 PKP
= Enabled
TRIP BUS 1 BLOCK AND
= Off
SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
= Off
OR
FLEXLOGIC OPERAND
RESET OP 842023A1.CDR
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the GROUPED
ELEMENTS settings menu. The active setting group can be indicated on the front display of the UR by configuring User-
Programmable LEDs to display the state of the SETTING GROUP ACT FlexLogic operands.
SETTING GROUPS FUNCTION — When Enabled, allows setting groups other than group 1 (the default active group) to be
activated. The default setting group is forced active while the SETTING GROUPS FUNCTION setting is Disabled.
SETTING GROUPS BLK — Prevents the active setting group from changing when the selected FlexLogic operand is "On." This
can be useful in applications where it is undesirable to change the settings under certain conditions, such as during a
control sequence.
GROUP 2 ACTIVATE ON to GROUP 6 ACTIVATE ON — Selects a FlexLogic operand which, when set, makes the particular setting
group active for use by any grouped element. A priority scheme ensures that only one group is active at a given time — the
highest-numbered group that is activated by its ACTIVATE ON parameter takes priority over the lower-numbered groups.
There is no activate on setting for group 1 (the default active group), because group 1 automatically becomes active if no
other group is active.
SETTING GROUP 1 NAME to SETTING GROUP 6 NAME — Allows the user to assign a name to each of the six settings groups.
Once programmed, this name appears on the second line of the GROUPED ELEMENTS SETTING GROUP 1(6) menu display.
The relay can be set up via a FlexLogic equation to receive requests to activate or de-activate a particular non-default
settings group. The following FlexLogic equation (see the following figure) illustrates requests via remote communications
(for example, VIRTUAL INPUT 1 ON) or from a local contact input (for example, CONTACT IP 1 ON) to initiate the use of a
particular settings group, and requests from several overcurrent pickup measuring elements to inhibit the use of the
particular settings group. The assigned VIRTUAL OUTPUT 1 operand is used to control the “On” state of a particular settings
group.
Figure 5-142: Example of FlexLogic control of a setting group
1 VIRT IP 1 ON (VI1)
OR (2)
2 CONT IP 1 ON (H5A)
3 OR (2)
AND (3) = VIRT OP 1 (VO1)
4 PHASE TOC1 PKP
5 NOT
7 NOT
5 8 AND (3)
9 = VIRT OP 1 (VO1)
10 END
842789A1.CDR
A setting group selection can also be made by the IEC 61850 MMS service SelectActiveSG to the control block @Master/
LLN0.SGCB. The priority scheme mentioned makes active the highest numbered group selected by SelectActiveSG or the
GROUP ACTIVATE ON settings. The SelectActiveSG selection has a default value of 1, so until a higher SelectActiveSG
selection is received, the GROUP ACTIVATE ON settings control the active group.
The most recent SelectActiveSG selection is preserved while the UR is powered down or reset.
If it becomes necessary to cancel the SelectActiveSG selection without using a SelectActiveSG service request, change the
SETTING GROUPS FUNCTION setting to Disabled. This resets the SelectActiveSG selection to 1.
The selector switch element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic.
The element provides for two control inputs. The step-up control allows stepping through selector position one step at a 5
time with each pulse of the control input, such as a user-programmable pushbutton. The three-bit control input allows
setting the selector to the position defined by a three-bit word.
The element allows pre-selecting a new position without applying it. The pre-selected position gets applied either after
time-out or upon acknowledgement via separate inputs (user setting). The selector position is stored in non-volatile
memory. Upon power-up, either the previous position is restored or the relay synchronizes to the current three-bit word
(user setting). Basic alarm functionality alerts the user under abnormal conditions; for example, the three-bit control input
being out of range.
A selector switch runs every two power cycles.
SELECTOR 1 FULL RANGE — This setting defines the upper position of the selector. When stepping up through available
positions of the selector, the upper position wraps up to the lower position (position 1). When using a direct three-bit control
word for programming the selector to a desired position, the change would take place only if the control word is within the
range of 1 to the SELECTOR FULL RANGE. If the control word is outside the range, an alarm is established by setting the
SELECTOR ALARM FlexLogic operand for three seconds.
SELECTOR 1 TIME-OUT — This setting defines the time-out period for the selector. This value is used by the relay in the
following two ways. When the SELECTOR STEP-UP MODE is “Time-out,” the setting specifies the required period of inactivity
of the control input after which the pre-selected position is automatically applied. When the SELECTOR STEP-UP MODE is
“Acknowledge,” the setting specifies the period of time for the acknowledging input to appear. The timer is re-started by
any activity of the control input. The acknowledging input must come before the SELECTOR 1 TIME-OUT timer expires;
otherwise, the change does not take place and an alarm is set.
SELECTOR 1 STEP-UP — This setting specifies a control input for the selector switch. The switch is shifted to a new position at
each rising edge of this signal. The position changes incrementally, wrapping up from the last (SELECTOR 1 FULL RANGE) to
the first (position 1). Consecutive pulses of this control operand must not occur faster than every 50 ms. After each rising
edge of the assigned operand, the time-out timer is restarted and the SELECTOR SWITCH 1: POS Z CHNG INITIATED target
message is displayed, where Z the pre-selected position. The message is displayed for the time specified by the FLASH
MESSAGE TIME setting. The pre-selected position is applied after the selector times out (“Time-out” mode), or when the
acknowledging signal appears before the element times out (“Acknowledge” mode). When the new position is applied, the
relay displays the SELECTOR SWITCH 1: POSITION Z IN USE message. Typically, a user-programmable pushbutton is
configured as the stepping up control input.
SELECTOR 1 STEP-UP MODE — This setting defines the selector mode of operation. When set to “Time-out,” the selector
changes its position after a pre-defined period of inactivity at the control input. The change is automatic and does not
require any explicit confirmation of the intent to change the selector's position. When set to “Acknowledge,” the selector
changes its position only after the intent is confirmed through a separate acknowledging signal. If the acknowledging
signal does not appear within a pre-defined period of time, the selector does not accept the change and an alarm is
established by setting the SELECTOR STP ALARM output FlexLogic operand for three seconds.
SELECTOR 1 ACK — This setting specifies an acknowledging input for the stepping up control input. The pre-selected
position is applied on the rising edge of the assigned operand. This setting is active only under “Acknowledge” mode of
operation. The acknowledging signal must appear within the time defined by the SELECTOR 1 TIME-OUT setting after the last
activity of the control input. A user-programmable pushbutton is typically configured as the acknowledging input.
SELECTOR 1 3BIT A0, A1, and A2 — These settings specify a three-bit control input of the selector. The three-bit control word
pre-selects the position using the following encoding convention:
A2 A1 A0 Position
0 0 0 rest
0 0 1 1
0 1 0 2
0 1 1 3
1 0 0 4
1 0 1 5
5 1
1
1
1
0
1
6
7
The “rest” position (0, 0, 0) does not generate an action and is intended for situations when the device generating the three-
bit control word is having a problem. When SELECTOR 1 3BIT MODE is “Time-out,” the pre-selected position is applied in
SELECTOR 1 TIME-OUT seconds after the last activity of the three-bit input. When SELECTOR 1 3BIT MODE is “Acknowledge,”
the pre-selected position is applied on the rising edge of the SELECTOR 1 3BIT ACK acknowledging input.
The stepping up control input (SELECTOR 1 STEP-UP) and the three-bit control inputs (SELECTOR 1 3BIT A0 through A2) lock-out
mutually: once the stepping up sequence is initiated, the three-bit control input is inactive; once the three-bit control
sequence is initiated, the stepping up input is inactive.
SELECTOR 1 3BIT MODE — This setting defines the selector mode of operation. When set to “Time-out,” the selector changes
its position after a pre-defined period of inactivity at the control input. The change is automatic and does not require
explicit confirmation to change the selector position. When set to “Acknowledge,” the selector changes its position only
after confirmation via a separate acknowledging signal. If the acknowledging signal does not appear within a pre-defined
period of time, the selector rejects the change and an alarm established by invoking the SELECTOR BIT ALARM FlexLogic
operand for three seconds.
SELECTOR 1 3BIT ACK — This setting specifies an acknowledging input for the three-bit control input. The pre-selected
position is applied on the rising edge of the assigned FlexLogic operand. This setting is active only under the
“Acknowledge” mode of operation. The acknowledging signal must appear within the time defined by the SELECTOR TIME-
OUT setting after the last activity of the three-bit control inputs. Note that the stepping up control input and three-bit
control input have independent acknowledging signals (SELECTOR 1 ACK and SELECTOR 1 3BIT ACK, accordingly).
SELECTOR 1 POWER-UP MODE — This setting specifies the element behavior on power up of the relay.
When set to “Restore,” the last position of the selector (stored in the non-volatile memory) is restored after powering up the
relay. If the position restored from memory is out of range, position 0 (no output operand selected) is applied and an alarm
is set (SELECTOR 1 PWR ALARM).
When set to “Synchronize,” the selector switch acts as follows. For two power cycles, the selector applies position 0 to the
switch and activates SELECTOR 1 PWR ALARM. After two power cycles expire, the selector synchronizes to the position
dictated by the three-bit control input. This operation does not wait for time-out or the acknowledging input. When the
synchronization attempt is unsuccessful (that is, the three-bit input is not available (0,0,0) or out of range), then the selector
switch output is set to position 0 (no output operand selected) and an alarm is established (SELECTOR 1 PWR ALARM).
The operation of “Synch/Restore” mode is similar to the “Synchronize” mode. The only difference is that after an
unsuccessful synchronization attempt, the switch attempts to restore the position stored in the relay memory. The “Synch/
Restore” mode is useful for applications where the selector switch is employed to change the setting group in redundant
(two relay) protection schemes.
SELECTOR 1 EVENTS — If enabled, the following events are logged:
The following figures illustrate the operation of the selector switch. In these diagrams, “T” represents a time-out setting.
STEP-UP
T T
3BIT A0
3BIT A1
3BIT A2
T T
POS 1
POS 2
5 POS 3
POS 4
POS 5
POS 6
POS 7
BIT 0
BIT 1
BIT 2
STP ALARM
BIT ALARM
ALARM
842737A1.CDR
STEP-UP
ACK
3BIT A0
3BIT A1
3BIT A2
3BIT ACK
POS 1
POS 2
POS 3
5
POS 4
POS 5
POS 6
POS 7
BIT 0
BIT 1
BIT 2
STP ALARM
BIT ALARM
ALARM
842736A1.CDR
Application example
Consider an application where the selector switch is used to control setting groups 1 through 4 in the relay. The setting
groups are to be controlled from both user-programmable pushbutton 1 and from an external device via contact inputs 1
through 3. The active setting group is to be available as an encoded three-bit word to the external device and SCADA via
output contacts 1 through 3. The pre-selected setting group is to be applied automatically after five seconds of inactivity
of the control inputs. When the relay powers up, it is to synchronize the setting group to the three-bit control input.
Make the following changes to setting group control in the SETTINGS CONTROL ELEMENTS SETTING GROUPS menu:
SETTING GROUPS FUNCTION: “Enabled”
SETTING GROUPS BLK: “Off”
GROUP 2 ACTIVATE ON: “SELECTOR 1 POS 2"
GROUP 3 ACTIVATE ON: “SELECTOR 1 POS 3"
GROUP 4 ACTIVATE ON: “SELECTOR 1 POS 4"
GROUP 5 ACTIVATE ON: “Off”
GROUP 6 ACTIVATE ON: “Off”
Make the following changes to selector switch element in the SETTINGS CONTROL ELEMENTS SELECTOR SWITCH
SELECTOR SWITCH 1 menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3:
SELECTOR 1 FUNCTION: “Enabled”
SELECTOR 1 FULL-RANGE: “4”
SELECTOR 1 STEP-UP MODE: “Time-out”
SELECTOR 1 TIME-OUT: “5.0 s”
SELECTOR 1 STEP-UP: “PUSHBUTTON 1 ON”
SELECTOR 1 ACK: “Off”
SELECTOR 1 3BIT A0: “CONT IP 1 ON”
SELECTOR 1 3BIT A1: “CONT IP 2 ON”
SELECTOR 1 3BIT A2: “CONT IP 3 ON”
SELECTOR 1 3BIT MODE: “Time-out”
SELECTOR 1 3BIT ACK: “Off”
SELECTOR 1 POWER-UP MODE: “Synchronize”
Now, assign the contact output operation (assume the H6E module) to the selector switch element by making the following
changes in the SETTINGS INPUTS/OUTPUTS CONTACT OUTPUTS menu:
5 OUTPUT H1 OPERATE: “SELECTOR 1 BIT 0"
OUTPUT H2 OPERATE: “SELECTOR 1 BIT 1"
OUTPUT H3 OPERATE: “SELECTOR 1 BIT 2"
Finally, assign configure user-programmable pushbutton 1 by making the following changes in the SETTINGS PRODUCT
SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu:
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBUTTON 1 DROP-OUT TIME: “0.10 s”
The figure shows the logic for the selector switch.
OR
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
842012A2.CDR
5
5.8.5 Underfrequency (ANSI 81U)
SETTINGS CONTROL ELEMENTS UNDERFREQUENCY UNDERFREQUENCY 1(6)
UNDERFREQUENCY 1 UNDFREQ 1 FUNCTION: Range: Disabled, Enabled
Disabled
The steady-state frequency of a power system is a certain indicator of the existing balance between the generated power
and the load. Whenever this balance is disrupted through the loss of an important generating unit or the isolation of part
of the system from the rest of the system, the effect is a reduction in frequency. If the control systems of the system
generators do not respond fast enough, the system can collapse. A reliable method to quickly restore the balance between
load and generation is to automatically disconnect selected loads, based on the actual system frequency. This technique,
called “load-shedding,” maintains system integrity and minimize widespread outages. After the frequency returns to
normal, the load can be restored automatically or manually.
UNDERFREQ 1 SOURCE — This setting is used to select the source for the signal to be measured. The element first checks for
a live phase voltage available from the selected source. If voltage is not available, the element attempts to use a phase
current. If neither voltage nor current is available, the element does not operate, as it does not measure a parameter
below the minimum voltage/current setting.
UNDERFREQ 1 MIN VOLT/AMP — Selects the minimum per unit voltage or current level required to allow the underfrequency
element to operate. This threshold is used to prevent an incorrect operation because there is no signal to measure.
UNDERFREQ 1 PICKUP — Selects the level at which the underfrequency element is to pickup. For example, if the system
frequency is 60 Hz and the load shedding is required at 59.5 Hz, the setting is 59.50 Hz.
Figure 5-146: Underfrequency logic
SETTING
UNDERFREQ 1 FUNCTION:
Enabled=1
5
SETTING UNDERFREQ 1 DPO
SETTING tPKP
UNDERFREQ 1 0 < f < PICKUP tRST UNDERFREQ 1 OP
UNDERFREQ 1 SOURCE: ACTUAL VALUES MIN VOLT / AMP:
Level < Min
VOLT / AMP 827079A9.CDR
Frequency
AR1 DELAY 2:
0.000 s
Range: 0.00 to 655.35 s in steps of 0.01 5
AR1 RESET LOCKOUT Range: 0.00 to 655.35 s in steps of 0.01
DELAY: 60.000
The F35 is provided with this optional feature, specified as an option at the time of ordering. Using the order
code for your device, see the order codes in chapter 2 for details.
The maximum number of autoreclosure elements available is equal to the number of installed CT banks.
The autoreclosure feature is intended for use with transmission and distribution lines, in three-pole tripping schemes for
single breaker applications. Up to four selectable reclosures "shots" are possible prior to locking out. Each shot has an
independently settable dead time. The protection settings can be changed between shots if required, using FlexLogic.
Logic inputs are available for disabling or blocking the scheme.
Faceplate panel LEDs indicate the state of the autoreclose scheme as follows:
• Reclose Enabled — The scheme is enabled and can reclose if initiated
• Reclose Disabled — The scheme is disabled
• Reclose In Progress — An autoreclosure has been initiated but the breaker has not yet been signaled to close
• Reclose Locked Out — The scheme has generated the maximum number of breaker closures allowed and, as the fault
persists, does not close the breaker again; known as "Lockout." The scheme can also be sent in "Lockout" when the
incomplete sequence timer times out or when a block signal occurs while in "reclose in progress." The scheme must be
reset from Lockout in order to perform reclose for further faults.
The reclosure scheme is considered enabled when all of the following conditions are true:
• The AR1 FUNCTION is set to “Enabled”
• The scheme is not in the "Lockout" state
• The "Block" input is not asserted
• The AR1 BLK TIME UPON MNL CLS timer is not active
The autoreclose scheme is initiated by a trip signal from any selected protection feature operand. The scheme is initiated
provided the circuit breaker is in the closed state before protection operation.
The reclose-in-progress (RIP) is set when a reclosing cycle begins following a reclose initiate signal. Once the cycle is
successfully initiated, the RIP signal seals-in and the scheme continues through its sequence until one of the following
conditions is satisfied:
• The close signal is issued when the dead timer times out, or
• The scheme goes to lockout
While RIP is active, the scheme checks that the breaker is open and the shot number is below the limit, and then begins
measuring the dead time.
Each of the four possible shots has an independently settable dead time. Two additional timers can be used to increase the
initial set dead times 1 to 4 by a delay equal to AR1 DELAY 1 or AR1 DELAY 2 or the sum of these two delays depending on the
selected settings. This offers enhanced setting flexibility using FlexLogic operands to turn the two additional timers “on”
and “off.” These operands can possibly include AR1 SHOT CNT =n, SETTING GROUP ACT 1, and so on. The autoreclose provides
up to maximum 4 selectable shots. Maximum number of shots can be dynamically modified through the settings AR1
REDUCE MAX TO 1 (2, 3), using the appropriate FlexLogic operand.
Scheme lockout blocks all phases of the reclosing cycle, preventing automatic reclosure, if any of the following occurs:
• The maximum shot number was reached
5 • A "Block" input is in effect (for instance, Breaker Failure or bus differential protection operated)
• The "Incomplete Sequence" timer times out
The recloser is latched in the Lockout state until a "reset from lockout" signal is asserted, either from a manual close of the
breaker or from a manual reset command (local or remote). The reset from lockout can be accomplished by operator
command, by manually closing the breaker, or whenever the breaker has been closed and stays closed for a preset time.
After the dead time elapses, the scheme issues the close signal. The close signal is latched until the breaker closes or the
scheme goes to Lockout.
A reset timer output resets the recloser following a successful reclosure sequence. The reset time is based on the breaker
"reclaim time," which is the minimum time required between successive reclose sequences.
5.8.6.1 Settings
AR1 INITIATE — Selects the FlexLogic operand that initiates the scheme, typically the trip signal from protection.
AR1 BLOCK — Selects the FlexLogic operand that blocks the autoreclosure initiate (it can be from the breaker failure, bus
differential protection, and so on).
AR1 MAX NUMBER OF SHOTS — Specifies the number of reclosures that can be attempted before reclosure goes to “Lockout”
because the fault is permanent.
AR1 REDUCE MAX TO 1(3) — Selects the FlexLogic operand that changes the maximum number of shots from the initial
setting to 1, 2, or 3, respectively.
AR1 MANUAL CLOSE — Selects the logic input set when the breaker is manually closed.
AR1 MNL RST FRM LO — Selects the FlexLogic operand that resets the autoreclosure from Lockout condition. Typically this is
a manual reset from lockout, local or remote.
AR1 RESET LOCKOUT IF BREAKER CLOSED — This setting allows the autoreclose scheme to reset from Lockout if the breaker
has been manually closed and stays closed for a preset time. In order for this setting to be effective, disable the next
setting (AR1 RESET LOCKOUT ON MANUAL CLOSE).
AR1 RESET LOCKOUT ON MANUAL CLOSE — This setting allows the autoreclose scheme to reset from Lockout when the
breaker is manually closed regardless if the breaker remains closed or not. This setting overrides the previous setting (AR1
RESET LOCKOUT IF BREAKER CLOSED).
AR1 BLK TIME UPON MNL CLS — The autoreclose scheme can be disabled for a programmable time delay after the
associated circuit breaker is manually closed. This prevents reclosing onto a fault after a manual close. This delay must be
longer than the slowest expected trip from any protection not blocked after manual closing. If no overcurrent trips occur
after a manual close and this time expires, the autoreclose scheme is enabled.
AR1 DEAD TIME 1 to AR1 DEAD TIME 4 — These are the intentional delays before first, second, third, and fourth breaker
automatic reclosures (1st, 2nd, and 3rd shots), respectively. Set them longer than the estimated deionizing time following a
three pole trip.
AR1 ADD DELAY 1 — This setting selects the FlexLogic operand that introduces an additional delay (Delay 1) to the initial set
Dead Time (1 to 4). When this setting is “Off,” Delay 1 is by-passed.
AR1 DELAY 1 — This setting establishes the extent of the additional dead time Delay 1.
AR1 ADD DELAY 2 — This setting selects the FlexLogic operand that introduces an additional delay (Delay 2) to the initial set
Dead Time (1 to 4). When this setting is “Off”, Delay 2 is by-passed.
AR1 DELAY 2 — This setting establishes the extent of the additional dead time Delay 2.
AR1 RESET LOCKOUT DELAY — This setting establishes how long the breaker stays closed after a manual close command, in
order for the autorecloser to reset from Lockout.
AR1 RESET TIME — A reset timer output resets the recloser following a successful reclosure sequence. The setting is based
on the breaker "reclaim time," which is the minimum time required between successive reclose sequences.
AR1 INCOMPLETE SEQ TIME — This timer defines the maximum time interval allowed for a single reclose shot. It is started
whenever a reclosure is initiated and is active when the scheme is in the "reclose-in-progress" state. If all conditions
allowing a breaker closure are not satisfied when this time expires, the scheme goes to Lockout.
5
This timer must be set to a delay less than the reset timer.
5-274
FLEXLOGIC OPERAND
AR1 BLK FROM MAN CLS
CONTROL ELEMENTS
FLEXLOGIC OPERAND
Enabled
AR1 ENABLED (Default)
SETTING
Off = 0
AR Initiate
Bkr Is Closed
Shot cnt = Max
SETTING (Default)
To sheet 2
SETTING
AR1 INCOMPLETE SEQ
SETTING AR1 RESET LOCKOUT TIME:
AR1 RESET LOCKOUT IF DELAY:
OR LO
BREAKER CLOSED: OR
AND LO
O
On=1 0 AND
SETTING
AR1 RESET LOCKOUT ON
MANUAL CLOSE:
AND OR
On=1 AND
SETTING
Reset From LO
AR1 MNL RST FROM LO:
827081AE.CDR
Off = 0
S
FLEXLOGIC OPERAND
Latch AR 1 CLOSE
SHOT COUNTER
FLEXLOGIC OPERANDS
OR R
Shot cnt = 4 AR 1 SHOT CNT = 4
Close Increment
shot Shot cnt = 3 AR 1 SHOT CNT = 3
Reset from LO OR
AND O
MAX = 1 AND
OR AND
MAX = 4
AND
Figure 5-148: Autorecloser logic (Sheet 2 of 2)
AND
SETTING
Off = 0
SETTING
Off = 0
SETTING
Off = 0
827082A7.CDR
5-275
CONTROL ELEMENTS
5
5
5-276
CONTROL ELEMENTS
BREAKER
STATUS
PROT TIME OPENING TIME CLOSING TIME PROT TIME OPENING TIME
BKR CLOSED
BKR OPEN
AUTO RECLOSE
DEAD TIME
SETTING
DIGITAL ELEMENT 01
FUNCTION: SETTINGS
Enabled = 1 DIGITAL ELEMENT 01
SETTING PICKUP DELAY:
DIGITAL ELEMENT 01 DIGITAL ELEMENT 01 FLEXLOGIC OPERANDS
SETTING
NAME: RESET DELAY:
DIGITAL ELEMENT 01 DIG ELEM 01 DPO
AND RUN tPKP
INPUT: DIG ELEM 01 PKP
Off = 0 DIG ELEM 01 OP
INPUT = 1 tRST
SETTING
DIGITAL ELEMENT 01
BLOCK:
Off = 0 827042A2.VSD
H1a
I
H1b DC–
V DC+
H1c 52a Trip coil
I = current monitor
V = voltage monitor 827073A2.CDR
Assume the output contact H1 is a trip contact. Using the contact output settings, this output is given an ID name; for
example, “Cont Op 1." Assume a 52a breaker auxiliary contact is connected to contact input H7a to monitor breaker status.
Using the contact input settings, this input is given an ID name, for example, “Cont Ip 1," and is set “On” when the breaker is
closed. The settings to use digital element 1 to monitor the breaker trip circuit are indicated (EnerVista example shown).
The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring and
solid-state contact with voltage monitoring.
5 COUNTER 1
COUNTER 1
FUNCTION: Disabled
Range: Disabled, Enabled
There are eight identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions
from Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of
an external contact (for example, breaker auxiliary switch), or pulses from a watt-hour meter.
COUNTER 1 UNITS — Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted. The
units label appears in the corresponding actual values status.
COUNTER 1 PRESET — Sets the count to a required preset value before counting operations begin, as in the case where a
substitute relay is to be installed in place of an in-service relay, or while the counter is running.
COUNTER 1 COMPARE — Sets the value to which the accumulated count value is compared. Three FlexLogic output
operands are provided to indicate if the present value is ‘more than (HI)’, ‘equal to (EQL)’, or ‘less than (LO)’ the set value.
COUNTER 1 UP — Selects the FlexLogic operand for incrementing the counter. If an enabled UP input is received when the
accumulated value is at the limit of +2,147,483,647 counts, the counter rolls over to –2,147,483,648.
COUNTER 1 DOWN — Selects the FlexLogic operand for decrementing the counter. If an enabled DOWN input is received
when the accumulated value is at the limit of –2,147,483,648 counts, the counter rolls over to +2,147,483,647.
COUNTER 1 BLOCK — Selects the FlexLogic operand for blocking the counting operation. All counter operands are blocked.
CNT1 SET TO PRESET — Selects the FlexLogic operand used to set the count to the preset value. The counter sets to the
preset value in the following situations:
• When the counter is enabled and the CNT1 SET TO PRESET operand has the value 1 (when the counter is enabled and
CNT1 SET TO PRESET operand is 0, the counter sets to 0)
• When the counter is running and the CNT1 SET TO PRESET operand changes the state from 0 to 1 (CNT1 SET TO PRESET
changing from 1 to 0 while the counter is running has no effect on the count)
• When a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the value 1
(when a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the value 0, the
counter sets to 0)
COUNTER 1 RESET — Selects the FlexLogic operand for setting the count to either “0” or the preset value depending on the
state of the CNT1 SET TO PRESET operand.
COUNTER 1 FREEZE/RESET — Selects the FlexLogic operand for capturing (freezing) the accumulated count value into a 5
separate register with the date and time of the operation, and resetting the count to “0.”
COUNTER 1 FREEZE/COUNT — Selects the FlexLogic operand for capturing (freezing) the accumulated count value into a
separate register with the date and time of the operation, and continuing counting. The present accumulated value and
captured frozen value with the associated date/time stamp are available as actual values. If control power is interrupted,
the accumulated and frozen values are saved into non-volatile memory during the power-down operation.
SETTING
COUNTER 1 FUNCTION:
SETTINGS
Enabled = 1
COUNTER 1 NAME:
SETTING AND COUNTER 1 UNITS:
COUNTER 1 PRESET:
COUNTER 1 UP:
RUN
Off = 0 SETTING
FLEXLOGIC
COUNTER 1 COMPARE: OPERANDS
SETTING
CALCULATE Count more than Comp. COUNTER 1 HI
COUNTER 1 DOWN: VALUE Count equal to Comp. COUNTER 1 EQL
Off = 0 Count less than Comp. COUNTER 1 LO
SETTING
COUNTER 1 BLOCK:
Off = 0 SET TO PRESET VALUE
5 Off = 0
This feature allows switching between two input arguments defined by 8 bits each. The bits are specified by FlexLogic
operands. The feature could be viewed as an integrated two-position switch for 8 logic signals.
Typically this element is applied in conjunction with the Digitizer and 8-bit Comparator features.
The switch runs every half power cycle (every four protection passes).
8BIT SW 1 ARG A0 to 8BIT SW 1 ARG A7 — These settings specify FlexLogic operands that constitute the first (A) input of the
switch. These operands are routed to the output operands if the control input is in the "Off" position.
BIT SW 1 ARG B0 to 8BIT SW 1 ARG B7 — These settings specify FlexLogic operands that constitute the second (B) input of the
switch. These operands are routed to the output operands if the control input is in the "On" position.
8BIT SW 1 CONTROL — This setting specifies FlexLogic operands to control the routing between the A and B inputs of the
switch. If the control operand is in the "Off" state, the first (A) input is switched to the output. If the control operand is in the
"On" state, the second (B) input is switched to the output. The switching takes place instantaneously.
Figure 5-154: 8-bit switch logic
SETTING
8BIT SWITCH 1
FUNCTION:
Enabled = 1 RUN
SETTINGS
8BIT SW 1 ARG A0:
Off = 0 FLEXLOGIC OPERAND
8BIT SW 1 ARG B0: 8BIT SWITCH 1 BIT 0
Off = 0
8BIT SW 1 ARG A1:
Off = 0 FLEXLOGIC OPERAND
8BIT SW 1 ARG B1: 8BIT SWITCH 1 BIT 1
Off = 0
8BIT SW 1 ARG A2:
FLEXLOGIC OPERAND
5
Off = 0
8BIT SW 1 ARG B2: 8BIT SWITCH 1 BIT 2
Off = 0
8BIT SW 1 ARG A3:
Off = 0 FLEXLOGIC OPERAND
8BIT SW 1 ARG B3: 8BIT SWITCH 1 BIT 3
Off = 0
8BIT SW 1 ARG A4:
Off = 0 FLEXLOGIC OPERAND
8BIT SW 1 ARG B4: 8BIT SWITCH 1 BIT 4
Off = 0
8BIT SW 1 ARG A5:
Off = 0 FLEXLOGIC OPERAND
8BIT SW 1 ARG B5: 8BIT SWITCH 1 BIT 5
Off = 0
8BIT SW 1 ARG A6:
Off = 0 FLEXLOGIC OPERAND
8BIT SW 1 ARG B6: 8BIT SWITCH 1 BIT 6
Off = 0
8BIT SW 1 ARG A7:
Off
Off = 0 FLEXLOGIC OPERAND
8BIT SW 1 ARG B7: 8BIT SWITCH 1 BIT 7
On
Off = 0
SETTING
8BIT SW 1 CONTROL:
Off = 0
842017A1.CDR
5.8.10.1 Menu
SETTINGS CONTROL ELEMENTS MONITORING ELEMENTS
MONITORING BREAKER 1 See below
ELEMENTS ARCING CURRENT
BREAKER 6
ARCING CURRENT
BREAKER
FLASHOVER 2
BKR 1 ARC AMP Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
There is one breaker arcing current element available per CT bank, with a minimum of two elements. This element
calculates an estimate of the per-phase wear on the breaker contacts by measuring and integrating the current squared
passing through the breaker contacts as an arc. These per-phase values are added to accumulated totals for each phase
and compared to a programmed threshold value. When the threshold is exceeded in any phase, the relay can set an
output operand to “1.” The accumulated value for each phase can be displayed as an actual value.
The operation of the scheme is shown in the following logic diagram. The same output operand that is selected to operate
the output relay used to trip the breaker, indicating a tripping sequence has begun, is used to initiate this feature. A time
delay is introduced between initiation and the starting of integration to prevent integration of current flow through the
breaker before the contacts have parted. This interval includes the operating time of the output relay, any other auxiliary
relays, and the breaker mechanism. For maximum measurement accuracy, measure the interval between change-of-state
of the operand (from 0 to 1) and contact separation for the specific installation. Integration of the measured current
continues for 100 ms, which is expected to include the total arcing period.
The feature is programmed to perform fault duration calculations. Fault duration is defined as a time between operation of
the disturbance detector occurring before initiation of this feature, and reset of an internal low-set overcurrent function. 5
Correction is implemented to account for a non-zero reset time of the overcurrent function.
Breaker arcing currents and fault duration values are available under the ACTUAL VALUES RECORDS MAINTENANCE
BREAKER 1(6) menus.
BKR 1 ARC AMP INT-A(C) — Select the same output operands that are configured to operate the output relays used to trip the
breaker. In three-pole tripping applications, configure the same operand to initiate arcing current calculations for poles A,
B, and C of the breaker. In single-pole tripping applications, configure per-pole tripping operands to initiate the calculations
for the poles that are actually tripped.
BKR 1 ARC AMP DELAY — This setting is used to program the delay interval between the time the tripping sequence is
initiated and the time the breaker contacts are expected to part, starting the integration of the measured current.
BKR 1 ARC AMP LIMIT — Selects the threshold value above which the output operand is set.
BKR 1 CLR ARC AMPS — Selects a FLexLogic Operand to clear the accumulated I2t values (kA2-cycle), reset fault duration
items (breaker operating time), clear ARCING AMPS (kA2-cycle) and AMP MAX (kA) values of the last event.
BKR 1 INTERUPTION RATING — This setting specifies the maximum symmetrical interruption rating of the circuit breaker.
Total Area =
Breaker
Arcing
Current
(kA cycle)
Programmable
Start Delay 100 ms
Start Stop
Integration Integration
827792A1.CDR
SETTING
BREAKER 1 ARCING
AMP INIT - B:
Off = 0
BREAKER 1 ARCING SETTING ACTUAL VALUES
AMP INIT - C :
AND BREAKER 1 ARCING BKR 1 AMP MAX FA
Off = 0 AMP DELAY: BKR 1 AMP MAX FB
100 ms
BKR 1 AMP MAX FC
OR 0 CALCULATE CALCULATE
0 SETTING
AND OR RUN Interruption Rating
Select greatest FLEXLOGIC OPERANDS
value RUN
Imax > Interruption Rating BKR ARC 1 MAX OP
RUN
SETTING Integrate
BREAKER 1 ARCING Add to SETTING
AMP SOURCE : RUN Accumulator BREAKER 1 ARCING
2
IA IA - Cycle AMP LIMIT : FLEXLOGIC OPERANDS
Select
2 2
Figure 5-156: Breaker arcing current logic
ACTUAL VALUES
BKR 1 ARCING AMP FA
BKR 1 ARCING AMP FB
BKR 1 ARCING AMP FC
827071A5CDR
5-287
CONTROL ELEMENTS
5
CONTROL ELEMENTS CHAPTER 5: SETTINGS
BKR 1 ARC AMP Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
There is one breaker arcing current element available per CT bank, with a minimum of two elements. This element
calculates an estimate of the per-phase wear on the breaker contacts by measuring and integrating the current squared
passing through the breaker contacts as an arc. These per-phase values are added to accumulated totals for each phase
and compared to a programmed threshold value. When the threshold is exceeded in any phase, the relay can set an
output operand to “1.” The accumulated value for each phase can be displayed as an actual value.
The operation of the scheme is shown in the following logic diagram. The same output operand that is selected to operate
the output relay used to trip the breaker, indicating a tripping sequence has begun, is used to initiate this feature. A time
delay is introduced between initiation and the starting of integration to prevent integration of current flow through the
breaker before the contacts have parted. This interval includes the operating time of the output relay, any other auxiliary
relays, and the breaker mechanism. For maximum measurement accuracy, measure the interval between change-of-state
of the operand (from 0 to 1) and contact separation for the specific installation. Integration of the measured current
continues for 100 ms, which is expected to include the total arcing period.
The feature is programmed to perform fault duration calculations. Fault duration is defined as a time between operation of
the disturbance detector occurring before initiation of this feature, and reset of an internal low-set overcurrent function.
Correction is implemented to account for a non-zero reset time of the overcurrent function.
Breaker arcing currents and fault duration values are available under the ACTUAL VALUES RECORDS MAINTENANCE
BREAKER 1(6) menus.
BKR 1 ARC AMP INT-A(C) — Select the same output operands that are configured to operate the output relays used to trip the
breaker. In three-pole tripping applications, configure the same operand to initiate arcing current calculations for poles A,
B, and C of the breaker. In single-pole tripping applications, configure per-pole tripping operands to initiate the calculations
for the poles that are actually tripped.
BKR 1 ARC AMP DELAY — This setting is used to program the delay interval between the time the tripping sequence is
initiated and the time the breaker contacts are expected to part, starting the integration of the measured current.
BKR 1 ARC AMP LIMIT — Selects the threshold value above which the output operand is set.
BKR 1 CLR ARC AMPS — Selects a FLexLogic Operand to clear the accumulated I2t values (kA2-cycle), reset fault duration
items (breaker operating time), clear ARCING AMPS (kA2-cycle) and AMP MAX (kA) values of the last event.
BKR 1 INTERUPTION RATING — This setting specifies the maximum symmetrical interruption rating of the circuit breaker.
Total Area =
Breaker
Arcing
Current
(kA cycle)
Programmable
Start Delay 100 ms
Start Stop
Integration Integration
827792A1.CDR
5-290
SETTING
AND 0
BREAKER 1 ARCING AND
AMP BLOCK :
Off = 0
SETTING
BREAKER 1 ARCING
AMP INIT - B:
Off = 0
BREAKER 1 ARCING SETTING ACTUAL VALUES
AMP INIT - C :
AND BREAKER 1 ARCING BKR 1 AMP MAX FA
Off = 0 AMP DELAY: BKR 1 AMP MAX FB
100 ms
BKR 1 AMP MAX FC
OR 0 CALCULATE CALCULATE
0 SETTING
AND OR RUN Interruption Rating
Select greatest FLEXLOGIC OPERANDS
value RUN
Imax > Interruption Rating BKR ARC 1 MAX OP
BKR ARC 1 MAX DPO
Calculate Imax
RUN
SETTING Integrate
BREAKER 1 ARCING Add to SETTING
AMP SOURCE : RUN Accumulator BREAKER 1 ARCING
IA IA 2 - Cycle AMP LIMIT : FLEXLOGIC OPERANDS
Select
2
Figure 5-158: Breaker arcing current logic
ACTUAL VALUES
BKR 1 ARCING AMP FA
BKR 1 ARCING AMP FB
BKR 1 ARCING AMP FC
827071A5CDR
Breaker flashover
SETTINGS CONTROL ELEMENTS MONITORING ELEMENTS BREAKER FLASHOVER 1(2)
BREAKER BKR 1 FLSHOVR Range: Disabled, Enabled
FLASHOVER 1 FUNCTION: Disabled
BKR 1 FLSHOVR SIDE 1 Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SRC: SRC 1
BKR 1 FLSHOVR SIDE 2 Range: None, SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC
SRC: None 6
Voltages must be present prior to flashover conditions. If the three VTs are placed after the breaker on the line (or
feeder), and the downstream breaker is open, the measured voltage is zero and the flashover element is not
initiated.
The flashover detection resets if the current drops back to zero, the breaker closes, or the selected FlexLogic operand for
supervision changes to high. Using supervision through the BRK 1 FLSHOVR SPV A, BRK 1 FLSHOVR SPV B, and BRK 1 FLSHOVR
SPV c settings is recommended by selecting a trip operand that does not allow the flashover element to pickup prior to the
trip.
The flashover detection can be used for external alarm, re-tripping the breaker, or energizing the lockout relay.
Consider the following configuration:
Bus
CTs Breaker
Line/Feeder
Bus VTs
842746A1.CDR
The source 1 (SRC1) phase currents are feeder CTs and phase voltages are bus VTs, and Contact Input 1 is set as Breaker
52a contact. The conditions prior to flashover detection are:
5 •
•
52a status = 0
VAg, VBg, or VCg is greater than the pickup setting
• IA, IB, IC = 0; no current flows through the breaker
• VA is greater than pickup (not applicable in this scheme)
The conditions at flashover detection are:
• 52a status = 0
• IA, IB, or IC is greater than the pickup current flowing through the breaker
• VA is greater than pickup (not applicable in this scheme)
Bus
CTs Breaker
Line/Feeder
VTs
VTs
842745A1.CDR
The source 1 (SRC1) phase currents are CTs and phase voltages are bus VTs. The source 2 (SRC2) phase voltages are line
VTs. Contact input 1 is set as the breaker 52a contact (optional).
The conditions prior to flashover detection are:
• VA is greater than pickup
• IA, IB, IC = 0; no current flows through the breaker
• 52a status = 0 (optional)
The conditions at flashover detection are:
• VA is less than pickup
• VAg, VBg, or VCg is lower than the pickup setting
• IA, IB, or IC is greater than the pickup current flowing through the breaker
• 52a status = 0 (optional) 5
The element operates only when phase-to-ground voltages are connected to relay terminals. The flashover
element does not operate if delta voltages are applied.
Settings
BRK 1 FLSHOVR SIDE 1 SRC — This setting specifies a signal source used to provide three-phase voltages and three-phase
currents from one side of the current breaker. The source selected as a setting and must be configured with breaker phase
voltages and currents, even if only three VTs are available across the breaker.
BRK 1 FLSHOVR SIDE 2 SRC — This setting specifies a signal source used to provide another set of three phase voltages
whenever six VTs are available across the breaker.
BRK 1 STATUS CLSD A to BRK 1 STATUS CLSD C — These settings specify FlexLogic operands to indicate the open status of the
breaker. A separate FlexLogic operand can be selected to detect individual breaker pole status and provide flashover
detection. The recommended setting is 52a breaker contact or another operand defining the breaker poles open status.
BRK 1 FLSHOVR V PKP — This setting specifies a pickup level for the phase voltages from both sides of the breaker. If six VTs
are available, opening the breaker leads to two possible combinations – live voltages from only one side of the breaker, or
live voltages from both sides of the breaker. Either case sets the scheme for flashover detection upon detection of voltage
above the selected value. Set BRK FLSHOVR V PKP to 85 to 90% of the nominal voltage.
BRK 1 FLSHOVR DIFF V PKP — This setting specifies a pickup level for the phase voltage difference when two VTs per phase
are available across the breaker. The pickup voltage difference should be below the monitored voltage difference when
close or open breaker resistors are left in service. The setting is selected as primary volts difference between the sources.
BRK 1 FLSHOVR AMP PKP — This setting specifies the normal load current which can flow through the breaker. Depending on
the flashover protection application, the flashover current can vary from levels of the charging current when the line is de-
energized (all line breakers open), to well above the maximum line (feeder) load (line/feeder connected to load).
BRK 1 FLSHOVR SPV A to BRK 1 FLSHOVR SPV C — These settings specify FlexLogic operands (per breaker pole) that supervise
the operation of the element per phase. Supervision can be provided by operation of other protection elements, breaker
failure, and close and trip commands. A six-cycle time delay applies after the selected FlexLogic operand resets.
BRK FLSHOVR PKP DELAY — This setting specifies the time delay to operate after a pickup condition is detected.
SETTINGS
Phase B logic
RESET
SETTINGS
5 cycle
BRK 1 STATUS CLSD A:
0 OR
SET SETTING
VA
BRK 1 FLSHOVR AMP PKP:
VB
VC RUN
IA IA > PKP
IB
AND
IC
SETTINGS
SETTING
BRK 1 FLSHOVR SIDE 2
SRC: BRK 1 FLSHOVR DIFF V
PKP:
SRC 1, SRC 2, … , SRC 6, none
RUN
Va DVA > PKP
DVA = | VA - Va |
Vb
Vc 842018A2.CDR
5-295
CONTROL ELEMENTS
5
CONTROL ELEMENTS CHAPTER 5: SETTINGS
One breaker restrike element is provided for each DSP in the F35.
According to IEEE standard C37.100 entitled IEEE Standard Definitions for Power Switchgear, restrike is defined as “a
resumption of current between the contacts of a switching device during an opening operation after an interval of zero
current of ¼ cycle at normal frequency or longer.”
Figure 5-160: Typical restrike waveform and detection flag
10
8
6
4
current (amps)
2
0.01 0.03
0 time (ms)
0.02 0.05
–2
–4
–6
–8
OPERATE
–10
834764A1.CDR
The breaker restrike algorithm responds to a successful interruption of the phase current following a declaration of
capacitor bank offline as per the breaker pole indication. If a high-frequency or system frequency current with a
magnitude greater than the threshold is resumed at least ¼ of a cycle later than the phase current interruption, then a
breaker restrike condition is declared in the corresponding phase and the BRK RESTRIKE 1 OP operand asserts for a short
period of time. The user can add counters and other logic to facilitate the decision making process as to the appropriate
actions upon detecting a single restrike or a series of consecutive restrikes.
A restrike event (FlexLogic operand) is declared if all of the following hold:
• The current is initially interrupted
• The breaker status is open
• An elevated high frequency current condition occurs (if the BREAKER RESTRIKE 1 HF DETECT setting is Enabled, otherwise
the condition is bypassed), and
• The current subsequently drops out again
The algorithm is illustrated in the following state machine diagram.
Figure 5-161: Algorithm illustration of state machine to detect restrike
Breaker open
command or breaker
open state
Capacitor bank
offline
Breaker
close
Current
Capacitor bank
interruption
Breaker online
(overcurrent)
close
High-frequency
5
elevated current Breaker close
(if enabled)
Current
interruption
(overcurrent)
Restrike detected:
OP state asserted
834768A2.CDR
In this way, a distinction is made between a self-extinguishing restrike and permanent breaker failure condition. The latter
can be detected by the breaker failure function or a regular instantaneous overcurrent element. Also, a fast succession of
restrikes is picked up by breaker failure or instantaneous overcurrent protection.
The following settings are available for each element.
BREAKER RESTRIKE 1 FUNCTION — Enables and disables operation of the breaker restrike detection element.
BRK RSTR 1 BLOCK — Blocks operation of the breaker restrike detection element.
BREAKER RESTRIKE 1 SOURCE — Selects the source of the current for this element. This source must have a valid CT bank
assigned.
BREAKER RESTRIKE 1 PICKUP — Specifies the pickup level of the overcurrent detector in per-unit values of CT nominal
current.
BREAKER RESTRIKE 1 RESET DELAY — Specifies the reset delay for this element. When set to “0 ms,” then FlexLogic operand is
picked up for only 1/8th of the power cycle.
BREAKER RESTRIKE 1 HF DETECT — Enables/disables high-frequency (HF) pattern detection when breaker restrike occurs.
High-frequency pattern is typical for capacitor bank, cables, and long transmission lines applications.
BRK RSTR 1 BRK OPEN — Assigns a FlexLogic operand indicating the open position of the breaker. It must be logic “1” when
the breaker is open. It is important to assign either 52 contact with this setting or breaker close command with BRK RSTR 1
CLS CMD setting to give clear indication to the relay about breaker status.
BRK RSTR 1 OPEN CMD — Assigns a FlexLogic operand indicating a breaker open command. It must be logic “1” when the
breaker is opened, either manually or from protection logic.
BRK RSTR 1 CLS CMD — Assigns a FlexLogic operand indicating a breaker close command. It must be logic “1” when the
breaker is closed.
Figure 5-162: Breaker restrike logic
SETTING
BREAKER RESTRIKE 1
FUNCTION
= Enabled
5 SETTING
BKR RSTR 1 OPEN CMD
OR
OR BKR RESTRIKE 1 OP
= Off
AND
SETTING
BKR RSTR 1 CLS CMD
= Off 834012A2.CDR
There are two incipient cable fault detection elements for each CT/VT module in the relay.
Before a permanent cable fault occurs, there are usually signs of degrading insulation manifesting itself as a short, mostly
half-cycle spikes asserting at the phase voltage peak. Due to shortness of such spikes, they are not usually detected by the
instantaneous protection of the feeder, which operates on the RMS or fundamental component of the phase current with a
relatively high pickup.
The number of detected incipient faults in each phase is counted and available in the ACTUAL VALUES STATUS
INCIPIENT FAULT menus. The counters can be reset with the COMMANDS CLEAR RECORDS CLEAR INCIPENT FAULT
COUNTERS command.
Changes to any of the incipient cable fault detector settings resets of the number of the incipient faults detected to
zero.
To provide a clear timing indication when the incipient fault occurred, the incipient fault event is time-stamped with
the time the fault actually occurred. However, the FlexLogic operand is asserted four cycles later, when the incipient
fault pattern is confirmed and therefore detected.
The figure illustrates a recorded field case of an incipient phase B fault. The top portion of the figure shows the raw A, B,
and C currents. The bottom portion shows the neutral current (blue) and reveals the fault period from under the load and
the superimposed phase B current (red). The superimposed current shows two fault current blips as the data slides through
the two-cycle memory window. During the actual fault, the neutral current and the superimposed phase B currents closely
correspond, confirming the incipient fault hypothesis and identifying the affected phase.
Figure 5-163: Illustration of the incipient fault detector algorithm
1.0
Phase C
0 Phase A
Phase B
–0.5
0.62 0.64 0.66 0.68 0.70 0.72 0.74
1.0
–1.0
IFB
–2.0
0.62 0.64 0.66 0.68 0.7 0.72 0.74
832774A1.CDR
The following settings are available for each incipient cable fault detector.
INCIPIENT FAULT 1 FUNCTION — This setting enables and disables operation of the incipient fault detection element.
INCIPNT FLT 1 BLOCK — Blocks operation of the incipient cable fault detector element. Assertion of the FlexLogic operand
assigned to this setting blocks operation.
INCIPIENT FAULT 1 SOURCE — Selects a current source for the incipient cable fault detector element. This source must be
assigned a valid CT bank.
INCIPIENT FAULT 1 PICKUP — Specifies the pickup level of the overcurrent detector in per-unit values of the CT nominal
current.
INCIPNT FLT 1 MODE — There are two modes of operation available for the incipient cable fault detector element. In the
“Number of counts” mode, a trip is initiated only after the selected number of faults is detected. In the “Counts per window”
mode, a trip is initiated only after the selected number of faults is detected within the time specified by the INCIPNT FLT 1
DETECT WINDOW setting.
INCIPIENT FLT 1 TRIP COUNTS NUMBER — Selects the number of faults required to initiate a trip.
INCIPNT FLT 1 DETECT WINDOW — Specifies a time window for “Counts per window” mode of operation.
INCIPIENT FAULT 1 RESET DELAY — Specifies a reset time for the output after the trip is initiated.
= IB 0
= IC
Imag – Imag
´ > PICKUP TRST
= IN
where Imag
´ is 2 cycles old FLEXLOGIC OPERANDS
INCIPNT FLT 1 PKP A
INCIPNT FLT 1 PKP B
INCIPNT FLT 1 PKP C
OR INCIPNT FLT 1 PKP
5 ACTUAL VALUES
INCIPIENT FAULT 1 PH A
FAULTS
INCIPIENT FAULT 1 PH B
FAULTS
COMMAND INCIPIENT FAULT 1 PH C
CLEAR INCIPIENT FAULT FAULTS
COUNTERS
RESET
= Yes
832028A1.CDR
Different means of detection are required for each class. An indication of class A failures is a significant level of negative-
sequence voltage, whereas an indication of class B failures is when positive sequence current is present and there is an
insignificant amount of positive sequence voltage. Also, a rapid decrease in the phase voltages magnitude from a healthy
voltage level without disturbance in current can indicate VT fuse fail conditions. These noted indications of fuse failure can
also be present when faults are present on the system, so a means of detecting faults and inhibiting fuse failure
declarations during these events is provided.
Once the fuse failure condition is declared, it is sealed-in until the cause that generated it disappears.
An additional condition is introduced to inhibit a fuse failure declaration when the monitored circuit is de-energized;
positive-sequence voltage and current are both below threshold levels.
VT FUSE FAILURE 1 FUNCTION — Enables and disables the fuse failure feature for Source 1 VT Fuse Fail.
NEUTRAL WIRE OPEN 1 DETECTION — Enables and disables the VT neutral wire open detection function. When the VT is
connected in Delta, do not enable this function because there is no neutral wire for Delta connected VT.
NEUTRAL WIRE OPEN 1 3 HRAM PKP — Specifies the pickup level of 3rd harmonic of 3V0 signal for the NEUTRAL WIRE OPEN
DETECTION logic to pick up.
Base voltage for this element is PHASE VT SECONDARY setting in the case of WYE VTs and (PHASE VT SECONDARY)/ in case
of DELTA VTs. The setting is found under SETTINGS SYSTEM SETUP AC INPUTS VOLTAGE BANK PHASE VT SECONDARY.
Figure 5-165: VT fuse fail logic
SETTING VA’, VB’ and VC’ are the
Function voltage magnitude of one OR
Enabled = 1 cycle before
AND
COMPARATORS FAULT
Run
|VA’|-|VA| > 0.2 pu
& |VA’| > 0.8 pu
Run
5
|VB’|-|VB| > 0.2 pu OR
SOURCE 1 & |VB’| > 0.8 pu SETTING
VA Run VT FUSE FAILURE 1
|VC’|-|VC| > 0.2 pu ALARM DELAY
VB & |VC’| > 0.8 pu FLEXLOGIC OPERAND
tPKP
VC Run SRC1 VT FF ALARM
0
V_2 V_2 > 0.1 pu OR
V_1 Run
I_1 V_1 < 0.05 pu
AND FUSE
Run
FAIL
I_1 > 0.075 pu
TIMER
Run 2 cycles SET
TIMER AND OR
V_1 < 0.80 pu 0
2 cycles
FLEXLOGIC OPERANDS
Run AND
I_1 < 0.05 pu Latch SRC1 VT FUSE FAIL OP
20 cycles
SRC1 VT FUSE FAIL DPO
FLEXLOGIC OPERANDS
SRC1 50DD OP
OPEN POLE OP
The OPEN POLE OP operand applies
to the C60, D60, L60, L90, and N60 AND
TIMER
OR 30 cycles RESET
AND 0
Reset-dominant
FLEXLOGIC OPERAND
AND SRC1 VT FUSE FAIL VOL LOSS
TIMER
SETTING 5 cycles
AND
3 HARM PKP
0
AND Run FLEXLOGIC OPERAND
SETTING 3V_0 3rd Harm >setting OR SRC1 VT NEU WIRE OPEN
TIMER
Neutral Wire Open Detect
0
Enabled = 1
AND 20 cycles
SOURCE 1 FLEX-ANALOG
3V_0 (3rd Harmonic) SRC1 3V0 3nd Harmonic
842235A1.vsd
5 THERMAL PROTECTION 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
The thermal overload protection element corresponds to the IEC 255-8 standard and is used to detect thermal overload
conditions in protected power system elements. Choosing an appropriate time constant element can be used to protect
different elements of the power system. The cold curve characteristic is applied when the estimated Ip current is less than
10% of the base current. If Ip current is greater or equal than 10% than the base current, then the hot curve characteristic
is applied. Ip current is estimated with a fixed time constant for both cooling and heating that reaches to the final value in
two seconds on a step change (either step up or step down) signal.
The IEC255-8 cold curve is defined as follows:
Eq. 5-23
Eq. 5-24
where
top = time to operate
τop = thermal protection trip time constant
I = measured overload RMS current
Ip = measured load RMS current before overload occurs
k = IEC 255-8 k-factor applied to IB, defining maximum permissible current above nominal current
IB = protected element base (nominal) current
To ensure element accuracy for high overcurrent conditions, the maximum value of I/(k x IB) is limited to 8, even when
realistically it is exceeding this value.
The reset time of the thermal overload protection element is also time delayed using following formula:
Eq. 5-25
where
τrst = thermal protection trip time constant
Tmin = a minimum reset time setting
Figure 5-166: IEC 255-8 sample operate and reset curves
100
Tmin = 10
10
τrst = 30
τop = 30
5
t (min)
0.1
0.01
0.1 1 10 100
I / Ipkp
827724A1.CDR
The thermal overload protection element estimates accumulated thermal energy E using the following equations
calculated each power cycle. When current is greater than the pickup level, In > k × IB, element starts increasing the
thermal energy:
Eq. 5-26
When current is less than the dropout level, In > 0.97 × k × IB, the element starts decreasing the thermal energy:
Eq. 5-27
where
∆t is the power cycle duration
n is the power cycle index
top(In) is the trip time calculated at index n as per the IEC255-8 cold curve or hot curve equations
trst(In) is the reset time calculated at index n as per the reset time equation
In is the measured overload RMS current at index n
En is the accumulated energy at index n
En – 1 is the accumulated energy at index n – 1
The thermal overload protection element removes the THERMAL PROT 1 OP output operand when E < 0.05. In case of
emergency, the thermal memory and THERMAL PROT 1 OP output operand can be reset using THERM PROT 1 RESET setting. All
calculations are performed per phase. If the accumulated energy reaches value 1 in any phase, the thermal overload
protection element operates and only resets when energy is less than 0.05 in all three phases.
Table 5-34: Typical time constants
Protected equipment Time constant Minimum reset time
Capacitor bank 10 minutes 30 minutes
Overhead line 10 minutes 20 minutes
Air-core reactor 40 minutes 30 minutes
Busbar 60 minutes 20 minutes
5 Underground cable 20 to 60 minutes 60 minutes
The figure shows the logic for the thermal overload protection element.
Figure 5-167: Thermal overload protection logic
SETTINGS
Function
Enabled = 1
Block AND
Off = 0
SETTINGS
Reset Time Constant
Minimum Reset Time
RUN
E < 0.1
SETTING
Reset
Off = 0 Reset E to 0
827013A3.CDR
The broken conductor function detects a transmission line broken conductor condition or a single-pole breaker
malfunction condition by checking the phase current input signals and the I_2 / I_1 ratio. The intent is to detect a single-
phase broken conductor only. As such, two-phase or three-phase broken conductors cannot be detected.
5
To distinguish between single-phase disappearance and system disturbance in all three phases (such as load change and
switching), the broken conductor element monitors the change in all three phase currents at the present instance and at
four cycles previous. It also monitors changes in the I_2 / I_1 ratio, I_1 minimum, and I_1 maximum.
Do not use the broken conductor function to respond to fault transients and single-pole tripping/reclosing conditions.
Therefore, program the time delay to a sufficient length to ensure coordination with the breaker dead time of the recloser
function.
BROKEN CONDUCTOR 1 FUNCTION — This setting enables and disables the broken conductor function.
BROKEN CONDUCTOR 1 SOURCE — Selects a signal source used to provide three-phase current inputs to this function.
BROKEN CONDUCTOR 1 I2/I1 RATIO — This setting specifies the ratio of negative-sequence current to positive-sequence
current. When one phase conductor is broken, the I_2 / I_1 ratio with a balanced remaining two phases is 50%. So
normally you this setting below 50% (for example, to 30%).
BROKEN CONDUCTOR 1 I1 MIN — This setting specifies the minimum positive-sequence current supervision level. Ensure this
setting is programmed to a sufficient level to prevent I_2 / I_1 from erratic pickup due to a low I_1 signal. However, do not
set this setting too high, since the broken conductor condition cannot be detected under light load conditions when I_1 is
less than the value specified by this setting.
BROKEN CONDUCTOR 1 I1 MAX — This setting specifies the maximum I_1 level allowed for the broken conductor function to
operate. When I_1 exceeds this setting, this it is considered a fault. In order for this function to not respond to any fault
conditions, set this setting to less than the maximum load current.
BROKEN CONDUCTOR 1 PKP DELAY — This setting specifies the pickup time delay for this function to operate after assertion
of the broken conductor pickup FlexLogic operand.
5-306
CONTROL ELEMENTS
SETTINGS
BROKEN CONDUCTOR 1
FUNCTION:
Enabled = 1
BROKEN CONDCT 1 BLK: AND
SETTINGS
Off = 0
BROKEN CONDUCTOR 1
I1 MAX:
BROKEN CONDUCTOR 1
SETTING I2/I1 RATIO:
SETTINGS
BROKEN CONDUCTOR 1 Run
BROKEN CONDUCTOR 1
SOURCE: I1 MIN:
|I1 | < I1 MAX SETTING
I2 Run |I2| / |I1| > RATIO
BROKEN CONDUCTOR 1
I1 |I1 > I1 MIN I1 MAX:
Ia |Ia| < I1 MIN FLEXLOGIC OPERAND
tPKP
|Ib| < I1 MIN AND BROKEN CONDUCT 1 OP
Ib AND
0
Ic |Ic| < I1 MIN
|Ia’| - |Ia| > 0.05 pu
Ic
|Ib’| - |Ib| > 0.05 pu 2 cyc
AND OR
|Ic’| - |Ic| > 0.05 pu
0 OR
Where I’ is four cycles old
FLEXLOGIC OPERAND
BROKEN CONDUCT 1 PKP
AND
Figure 5-168: Broken conductor detection logic
COLD LOAD 1 PICKUP Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
SOURCE: SRC 1
Cold load is the restoration of current into the system after being off. A cold load condition can be caused by a prolonged
outage of the load, by opening of the circuit breaker, or by a loss of supply even if the breaker remains closed. Upon the
return of the source, the circuit experiences inrush current into connected transformers, accelerating currents into motors,
and simultaneous demand from many other loads because the normal load diversity has been lost.
This feature can be used to change protection element settings when (by changing to another settings group) a cold load
condition is expected to occur. During the cold load condition, the current level can be above the pickup setting of some
protection elements, so this feature can be used to prevent the tripping that is otherwise caused by the normal settings.
Without historical data on a particular feeder, some utilities assume an initial cold load current of about 500% of normal
load, decaying to 300% after 1 second, 200% after 2 seconds, and 150% after 3 seconds.
5
Figure 5-169: Typical cold load pickup characteristics
500
Current (% of normal)
400
300
NORMAL TRIP SETTING
200
X
PICKUP PICKUP
100
OUTAGE
0
-1 0 1 2 3 4 5 6
time (seconds)
LOAD ENERGIZED 832760A1.CDR
SETTING
COLD LOAD PICKUP
AND
FUNCTION:
Enabled
SETTING
AND
COLD LOAD PICKUP 1
BLK:
Off
SETTING OR
RUN FLEXLOGIC-OPERAND
IC IC < 2% NOMINAL CT
OR CLD LOAD OP1
SETTING
COLD LOAD PICKUP 1
AND SETTING
INIT: RUN
IA > 2% NOMINAL CT ON-LOAD TIME BEFORE
Off
RESET 1:
RUN
OR 100
IB > 2% NOMINAL CT
RUN
IC > 2% NOMINAL CT
827064A6.CDR
The F35 is provided with this optional feature, specified as an option at the time of ordering. Using the order
code for your device, see the order codes in chapter 2 for details.
1
Tt
+ -
w
832031A1.cdr
where
y is the process signal
r is the setpoint signal
w is the tracking signal
u is the regulator output
K is the proportional gain
b is the setpoint weighting
Td is the derivative time constant
Eq. 5-28
where
TS is the sampling time
AW is a flag which enables anti-windup
The incremental form of this equation is:
Eq. 5-29
where
Eq. 5-30
SETTING SETTING
u>0 FLEXLOGIC OPERAND
FUNCTION: DEAD TIME:
AND PID 1 LOWER
Enabled = 1 Tdead
u > Tmin AND
|u| ms
SETTING AND FLEXLOGIC OPERAND
BLOCKED: AND PID 1 RAISE
Off = 0 SETTING u<0
Ts, K, b,
SETTING Ti, Tt, Td, N
Run FLEXLOGIC OPERAND
ANTIWINDUP: u
PID 1 DELTA OUT
Enabled = 1 AW
PID
SETTING
PROCESS SIGNAL: SETTING
SETPOINT SIGNAL: max, min ACTUAL VALUE
u
TRACKING SIGNAL: Out=MAX(min,MIN(max,u)) PID 1 OUT
ACTUAL VALUE
SETPOINT
832029A1.cdr
5.9 Inputs/outputs
5.9.1 Contact inputs
SETTINGS INPUTS/OUTPUTS CONTACT INPUTS
CONTACT INPUTS
CONTACT INPUT
THRESHOLDS
A contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Wet and dry contacts
are supported.
The contact inputs menu contains configuration settings for each contact input as well as voltage thresholds for each
group of four contact inputs. Upon startup, the relay processor determines (from an assessment of the installed modules)
which contact inputs are available and then display settings for only those inputs.
An alphanumeric ID can be assigned to a contact input for diagnostic, setting, and event recording purposes. The CONTACT
IP X On (Logic 1) FlexLogic operand corresponds to contact input “X” being closed, while CONTACT IP X Off corresponds to
contact input “X” being open. The CONTACT INPUT DEBNCE TIME defines the time required for the contact to overcome
‘contact bouncing’ conditions. As this time differs for different contact types and manufacturers, set it as a maximum
contact debounce time (per manufacturer specifications) plus some margin to ensure proper operation. If CONTACT INPUT
EVENTS is set to “Enabled,” every change in the contact input state triggers an event.
A raw status is scanned for all Contact Inputs synchronously at the constant rate of 0.5 ms as shown in the following
figure. The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a
user-settable debounce time in order for the F35 to validate the new contact state. In the following figure, the debounce
time is set at 2.5 ms; thus the 6th sample in a row validates the change of state (mark no. 1 in the diagram). Once validated
(de-bounced), the contact input asserts a corresponding FlexLogic operand and logs an event as per user setting.
A time stamp of the first sample in the sequence that validates the new state is used when logging the change of the
contact input into the Event Recorder (mark no. 2 in the figure).
Protection and control elements, as well as FlexLogic equations and timers, are executed eight times in a power system
cycle. The protection pass duration is controlled by the frequency tracking mechanism. The FlexLogic operand reflecting
the debounced state of the contact is updated at the protection pass following the validation (marks no. 3 and 4 on the
figure that follows). The update is performed at the beginning of the protection pass so all protection and control functions,
as well as FlexLogic equations, are fed with the updated states of the contact inputs.
The FlexLogic operand response time to the contact input change is equal to the debounce time setting plus up to one
protection pass (variable and depending on system frequency if frequency tracking enabled). If the change of state occurs
just after a protection pass, the recognition is delayed until the subsequent protection pass; that is, by the entire duration
of the protection pass. If the change occurs just prior to a protection pass, the state is recognized immediately. Statistically
a delay of half the protection pass is expected. Owing to the 0.5 ms scan rate, the time resolution for the input contact is
below 1 ms.
For example, eight protection passes per cycle on a 60 Hz system correspond to a protection pass every 2.1 ms. With a
contact debounce time setting of 3.0 ms, the FlexLogic operand-assert time limits are: 3.0 + 0.0 = 3.0 ms and 3.0 + 2.1 = 5.1
ms. These time limits depend on how soon the protection pass runs after the debouncing time.
Regardless of the contact debounce time setting, the contact input event is time-stamped with a 1 s accuracy using the
time of the first scan corresponding to the new state (mark no. 2 shown). Therefore, the time stamp reflects a change in the
DC voltage across the contact input terminals that was not accidental as it was subsequently validated using the
debounce timer. Keep in mind that the associated FlexLogic operand is asserted/de-asserted later, after validating the
change.
The debounce algorithm is symmetrical: the same procedure and debounce time are used to filter the LOW-HIGH (marks
no.1, 2, 3, and 4 in the figure) and HIGH-LOW (marks no. 5, 6, 7, and 8) transitions.
Figure 5-173: Input contact debouncing mechanism and time stamp sample timing
5
VOLTAGE
INPUT
USER-PROGRAMMABLE THRESHOLD
6
2 1 3 5
Time stamp of the first
TM
Time stamp of the first At this time, the The FlexLogic scan corresponding to the
At this time, the new
scan corresponding to new (HIGH) operand is going to new validated state is
(LOW) contact state is
the new validated state is contact state is be asserted at this logged in the SOE record
validated
logged in the SOE record validated protection pass
7
RAW CONTACT
The FlexLogicTM
operand is going to be
STATE
de-asserted at this
protection pass
DEBOUNCE TIME
(user setting)
4
The FlexLogicTM operand
DEBOUNCE TIME
The FlexLogicTM operand changes reflecting the
SCAN TIME (user setting)
changes reflecting the validated contact state
FLEXLOGICTM
PROTECTION PASS
(8 times a cycle controlled by the
frequency tracking mechanism)
842709A1.cdr
Contact inputs are isolated in groups of four to allow connection of wet contacts from different voltage sources for each
group. The CONTACT INPUT THRESHOLDS determine the minimum voltage required to detect a closed contact input. This
value is selected according to the following criteria: 17 for 24 V sources, 33 for 48 V sources, 84 for 110 to 125 V sources
and 166 for 250 V sources.
For example, to use contact input H5a as a status input from the breaker 52b contact to seal-in the trip relay and record it
in the Event Records menu, make the following settings changes:
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic equations used to customize the
device. Virtual outputs can also serve as virtual inputs to FlexLogic equations.
There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (via the
COMMANDS menu) and communications protocols. All virtual input operands are defaulted to “Off” (logic 0) unless the
appropriate input signal is received.
If the VIRTUAL INPUT x FUNCTION is to “Disabled,” the input is forced to off (logic 0) regardless of any attempt to alter the
input. If set to “Enabled,” the input operates as shown on the logic diagram and generates output FlexLogic operands in
response to received input signals and the applied settings.
5
There are two types of operation: self-reset and latched. If VIRTUAL INPUT x type is “Self-Reset,” when the input signal
transits from off to on, the output operand is set to on for only one evaluation of the FlexLogic equations and then return to
off. If set to “Latched,” the virtual input sets the state of the output operand to the same state as the most recent received
input.
The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic equations. If the
operand is to be used anywhere other than internally in a FlexLogic equation, it likely needs to be lengthened in time. A
FlexLogic timer with a delayed reset can perform this function.
Figure 5-174: Virtual inputs logic
SETTING
VIRTUAL INPUT 1
FUNCTION:
Enabled=1 S
AND
Latch
“Virtual Input 1 to ON = 1”
SETTING
“Virtual Input 1 to OFF = 0” R VIRTUAL INPUT 1 ID:
AND
SETTING (Flexlogic Operand)
OR
Virt Ip 1
VIRTUAL INPUT 1
TYPE:
Latched AND
Self - Reset 827080A3.CDR
A contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Wet and dry contacts
are supported.
Upon startup of the relay, the main processor determines from an assessment of the modules installed in the chassis
which contact outputs are available and then presents the settings for only these outputs. Where the contact input is non-
latching, the settings are as shown.
An ID can be assigned to each contact output. The signal that can OPERATE a contact output can be any FlexLogic
operand (virtual output, element state, contact input, or virtual input). An additional FlexLogic operand can be used to
SEAL-IN the relay. Any change of state of a contact output can be logged as an Event if programmed to do so.
For example, the trip circuit current is monitored by providing a current threshold detector in series with some Form-A
5 contacts (see the trip circuit example in the Digital Elements section). The monitor sets a flag (see the specifications for
Form-A). The name of the FlexLogic operand set by the monitor, consists of the output relay designation, followed by the
name of the flag; for example, Cont OP 1 IOn.
In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact used to interrupt current
flow after the breaker has tripped, to prevent damage to the less robust initiating contact. This can be done by monitoring
an auxiliary contact on the breaker which opens when the breaker has tripped, but this scheme is subject to incorrect
operation caused by differences in timing between breaker auxiliary contact change-of-state and interruption of current in
the trip circuit. The most dependable protection of the initiating contact is provided by directly measuring current in the
tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in.
This can be realized using the Cont OP 1 IOn FlexLogic operand to seal-in the contact output as follows:
CONTACT OUTPUT H1 ID: “Cont Op 1"
OUTPUT H1 OPERATE: any suitable FlexLogic operand
OUTPUT H1 SEAL-IN: “Cont Op 1 IOn”
CONTACT OUTPUT H1 EVENTS: “Enabled”
H1b
H1c
859743A1.vsd
The latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such
they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and
populates the setting menu accordingly. On power up, the relay reads positions of the latching contacts from the hardware
before executing any other functions of the relay (such as protection and control features or FlexLogic).
The latching output modules, either as part of the relay or as individual modules, are shipped from the factory with all
latching contacts open. It is highly recommended to double-check the programming and positions of the latching contacts
when replacing a module.
Since the relay asserts the output contact and reads back its position, it is possible to incorporate self-monitoring
capabilities for the latching outputs. If any latching outputs exhibits a discrepancy, the LATCHING OUTPUT ERROR self-test
error is declared. The error is signaled by the LATCHING OUT ERROR FlexLogic operand, event, and target message.
OUTPUT H1a OPERATE — This setting specifies a FlexLogic operand to operate the ‘close coil’ of the contact. The relay seals- 5
in this input to safely close the contact. Once the contact is closed and the RESET input is logic 0 (off), any activity of the
OPERATE input, such as subsequent chattering, does not have any effect. With both the OPERATE and RESET inputs active
(logic 1), the response of the latching contact is specified by the OUTPUT H1a TYPE setting.
OUTPUT H1a RESET — This setting specifies a FlexLogic operand to operate the ‘trip coil’ of the contact. The relay seals-in
this input to safely open the contact. Once the contact is opened and the OPERATE input is logic 0 (off), any activity of the
RESET input, such as subsequent chattering, does not have any effect. With both the OPERATE and RESET inputs active (logic
1), the response of the latching contact is specified by the OUTPUT H1a TYPE setting.
OUTPUT H1a TYPE — This setting specifies the contact response under conflicting control inputs; that is, when both the
OPERATE and RESET signals are applied. With both control inputs applied simultaneously, the contact closes if set to
“Operate-dominant” and opens if set to “Reset-dominant.”
Figure 5-176: Contact input/output module type 4L contact 1 logic
SETTING
CONTACT OUTPUT H1a Non-volatile,
OPERATE = On Set-dominant
AND S
SETTING OR Latch On
CONTACT OUTPUT H1a TYPE Close
= Operate-dominant R
H1b
= Reset-dominant
Non-volatile,
SETTING OR Set-dominant
H1a
CONTACT OUTPUT H1a RESET AND S
= On Open
Latch
R
FLEXLOGIC OPERAND
Cont Op 1 Closed
859744A1.vsd
Application example 1
A latching output contact H1a is to be controlled from two user-programmable pushbuttons (buttons number 1 and 2). The
following settings are applied.
Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT
OUTPUTS CONTACT OUTPUT H1a menu (assuming an H4L module):
OUTPUT H1a OPERATE: “PUSHBUTTON 1 ON”
OUTPUT H1a RESET: “PUSHBUTTON 2 ON”
Program the pushbuttons by making the following changes in the PRODUCT SETUP USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1 and USER PUSHBUTTON 2 menus:
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.00 s”
PUSHBUTTON 2 FUNCTION: “Self-reset”
PUSHBTN 2 DROP-OUT TIME: “0.00 s”
Application example 2
A relay, having two latching contacts H1a and H1c, is to be programmed. The H1a contact is to be a Type-a contact, while
the H1c contact is to be a Type-b contact (Type-a means closed after exercising the operate input; Type-b means closed
after exercising the reset input). The relay is to be controlled from virtual outputs: VO1 to operate and VO2 to reset.
Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT
OUTPUTS CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1”
OUTPUT H1a RESET: “VO2”
OUTPUT H1c OPERATE: “VO2”
OUTPUT H1c RESET: “VO1”
Since the two physical contacts in this example are mechanically separated and have individual control inputs, they do not
operate at exactly the same time. A discrepancy in the range of a fraction of a maximum operating time can occur.
5 Therefore, a pair of contacts programmed to be a multi-contact relay do not guarantee any specific sequence of operation
(such as make before break). If required, the sequence of operation must be programmed explicitly by delaying some of the
control inputs as shown in the next application example.
Application example 3
A make before break functionality must be added to the preceding example. An overlap of 20 ms is required to implement
this functionality.
Write the following FlexLogic equation (EnerVista example shown).
Application example 4
A latching contact H1a is to be controlled from a single virtual output VO1. The contact is to remain closed as long as VO1
is high, and is to remain opened when VO1 is low. Program the relay as follows.
Write the following FlexLogic equation (EnerVista example shown).
Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT
OUTPUTS CONTACT OUTPUT H1a menu (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1”
OUTPUT H1a RESET: “VO2”
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic equations used to customize the
device. Virtual outputs can also serve as virtual inputs to FlexLogic equations.
There are 96 virtual outputs that can be assigned using FlexLogic. If not assigned, the output is forced to ‘OFF’ (Logic 0). An
ID also can be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the
FlexLogic equations. Any change of state of a virtual output can be logged as an event if programmed to do so.
For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings is
programmed as follows:
VIRTUAL OUTPUT 1 ID: "Trip"
VIRTUAL OUTPUT 1 EVENTS: "Disabled"
5.9.5 Resetting
Some events can be programmed to latch the front panel LED event indicators, target messages, and/or graphical front
panel annunciator windows. Once set, the latching mechanism holds the latched indicators, messages, or windows in the
set state after the initiating condition has cleared until a RESET command is received to return these latches (not including
FlexLogic latches) to the reset state where the initiating condition has cleared. The RESET command can be sent from the
front panel RESET button, a remote device via a communications channel, or any selected operand. The Modbus execute
function 05h with operation code 1 command is also available to perform the same function as the front panel RESET key.
RESET OPERAND — The three sources of RESET commands each activates the RESET OP FlexLogic operand. Each individual
source of a RESET command also activates its individual operand RESET OP (PUSHBUTTON), RESET OP (COMMS), or RESET OP
(OPERAND) to identify the source of the command. Each of these three operands generates an event in the event record
when activated. The RESET OPERAND setting here selects the operand that activates the RESET OP (OPERAND) operand.
RESET ANNUNCIATOR — Used to select a FlexLogic operand that when activated acknowledges/resets all annunciator
windows on the graphical front panel. The other methods to acknowledge/reset annunciator windows include:
• On the displayed page, press the RESET pushbutton with none of the annunciator windows selected to acknowledge/
reset all annunciator windows on that page
• To acknowledge/reset a specific annunciator window, use the Up, Down, Left and Right pushbuttons to select the
window, and press the RESET or ENTER pushbutton
5 • All annunciator windows can be reset remotely by programming a Virtual Input (for example Virtual Input 1) as the
input to the RESET ANNUNCIATOR setting. Then the Modbus execute function 05h with operation code 1000h command
(or function 10h with address 400h) is used to set the state of Virtual Input 1.
For the RESET ANNUNCIATOR setting, the RESET ANCTR OP FlexLogic operand is activated by the two sources of RESET
command, operand source and manual source. Each individual source of a RESET ANNUNCIATOR command also activates
its individual operand RESET OP (OPRD) or RESET ANCTR OP (MNUL) to identify the source of the command. Each of these two
operands generates an event in the event record when activated. The setting here selects the operand that activates the
RESET ANCTR OP (OPRD) operand. The RESET pushbutton on the front panel or the reset command from the software
activates the RESET ANCTR OP (MNUL) operand.
DIRECT INPUT 1 DEVICE ID — Represents the source of direct input 1. The specified direct input is driven by the device
identified here.
DIRECT INPUT 1 BIT NUMBER — The bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
identified as DIRECT INPUT 1 BIT NUMBER. This corresponds to the direct output number of the sending device.
DIRECT INPUT 1 DEFAULT STATE — Represents the state of the direct input when the associated direct device is offline. The
following choices are available:
• On — Defaults the input to Logic 1
• Off — Defaults the input to Logic 0
• Latest/On — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 1. When communication resumes,
the input becomes fully operational.
• Latest/Off — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 0. When communication resumes,
the input becomes fully operational.
TX1
UR IED 1
RX1
TX1
UR IED 2
RX1
842711A1.CDR
Assume that contact input 1 from UR IED 2 is to be used by UR IED 1. The following settings are applied (Direct Input 5 and
bit number 12 are used, as an example).
UR IED 1:
UR IED 1 BLOCK
842712A1.CDR
5 Assume that Phase Instantaneous Overcurrent 1 is used by Devices 2, 3, and 4 to block Device 1. If not blocked, Device 1
trips the bus upon detecting a fault and applying a short coordination time delay.
The following settings are applied (assume Bit 3 is used by all 3 devices to send the blocking signal and Direct Inputs 7, 8,
and 9 are used by the receiving device to monitor the three blocking signals).
UR IED 2:
DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"
UR IED 3:
DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"
UR IED 4:
DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"
UR IED 1:
DIRECT INPUT 7 DEVICE ID: "2"
DIRECT INPUT 7 BIT NUMBER: "3"
DIRECT INPUT 7 DEFAULT STATE: select "On" for security, select "Off" for dependability
UR IED 1 UR IED 2
UR IED 3 842713A1.CDR
Assume the Hybrid Permissive Overreaching Transfer Trip (Hybrid POTT) scheme is applied using the architecture shown as
follows. The scheme output operand HYB POTT TX1 is used to key the permission.
Figure 5-180: Single-channel open-loop configuration
5
RX1
UR IED 3
TX1
842714A1.CDR
In this architecture, Devices 1 and 3 do not communicate directly. Therefore, Device 2 must act as a ‘bridge’. The following
settings are applied:
UR IEC 1:
DIRECT OUT 2 OPERAND: "HYB POTT TX1"
DIRECT INPUT 5 DEVICE ID: "2"
DIRECT INPUT 5 BIT NUMBER: "2" (this is a message from IED 2)
DIRECT INPUT 6 DEVICE ID: "2"
DIRECT INPUT 6 BIT NUMBER: "4" (effectively, this is a message from IED 3)
UR IED 3:
DIRECT OUT 2 OPERAND: "HYB POTT TX1"
DIRECT INPUT 5 DEVICE ID: "2"
DIRECT INPUT 5 BIT NUMBER: "2" (this is a message from IED 2)
DIRECT INPUT 6 DEVICE ID: "2"
DIRECT INPUT 6 BIT NUMBER: "3" (effectively, this is a message from IED 1)
UR IED 2:
DIRECT INPUT 5 DEVICE ID: "1"
DIRECT INPUT 5 BIT NUMBER: "2"
DIRECT INPUT 6 DEVICE ID: "3"
DIRECT INPUT 6 BIT NUMBER: "2"
UR IED 1 UR IED 2
DIRECT OUT 2 = HYB POTT TX1 DIRECT INPUT 5
DIRECT INPUT 5 DIRECT OUT 2 = HYB POTT TX1
DIRECT INPUT 6 DIRECT OUT 4 = DIRECT INPUT 6
DIRECT OUT 3 = DIRECT INPUT 5
DIRECT INPUT 6
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 are ANDed in FlexLogic and the resulting operand configured as the permission to trip (HYB POTT RX1
5 setting).
5.9.7 Teleprotection
5.9.7.1 Overview
The relay provides 16 teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and 16
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only,
numbered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by
assigning FlexLogic operands to be sent via the selected communications channel. This allows the user to create
distributed protection and control schemes via dedicated communications channels. Some examples are directional
comparison pilot schemes and direct transfer tripping. Note that failures of communications channels affect
teleprotection functionality. The teleprotection function must be enabled to utilize the inputs.
Setting the TELEPROT INPUT ~~ DEFAULT setting to “On” defaults the input to logic 1 when the channel fails. A value of “Off”
defaults the input to logic 0 when the channel fails.
The “Latest/On” and “Latest/Off” values freeze the input in case of lost communications. If the latest state is not known,
such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for “Latest/
On” and logic 0 for “Latest/Off.”
As the following figure demonstrates, processing of the teleprotection inputs/outputs is dependent on the number of
communication channels and terminals. On two-terminal two-channel systems, they are processed continuously on each
channel and mapped separately per channel. Therefore, to achieve redundancy, the user must assign the same operand
on both channels (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end).
On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of
channel failure between any pair of relays.
5
Figure 5-182: Teleprotection input/output processing
UR-1 UR-2
ACTUAL VALUES SETTING
CHANNEL 1 STATUS: TELEPROT INPUT 1-1
DEFAULT:
SETTING (same for 1-2...1-16)
TELEPROT OUTPUT 1-1:
(same for 1-2...1-16) On FLEXLOGIC OPERAND
Fail
Off (Flexlogic Operand) Off TELEPRO INPUT 1-1 On
OK OR
(same for 1-2...1-16)
UR-2 or UR-3
ACTUAL VALUES SETTING
CHANNEL 2 STATUS: TELEPROT INPUT 2-1
DEFAULT:
SETTING (same for 2-2...2-16)
TELEPROT OUTPUT 2-1:
(same for 1-2...1-16) On FLEXLOGIC OPERAND
Fail
Off TELEPRO INPUT 2-1 On
Off (Flexlogic Operand) OK OR
(same for 2-2...2-16)
842750A2.CDR
The F35 is provided with optional DCmA capability. This feature is specified as an option at the time of
ordering. See the Order Codes section in chapter 2 for details.
5 Hardware and software are provided to receive signals from external transducers and to convert these signals into a
digital format for use as required. The relay accepts inputs in the range of –1 to +20 mA DC, suitable for use with most
common transducer output ranges; all inputs are assumed to be linear over the complete range. Hardware details are
contained in chapter 3.
Before the DCmA input signal can be used, the value of the signal measured by the relay must be converted to the range
and quantity of the external transducer primary input parameter, such as DC voltage or temperature. The relay simplifies
this process by internally scaling the output from the external transducer and displaying the actual primary parameter.
DCmA input channels are arranged in a manner similar to CT and VT channels. Configure the individual channels with the
settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay automatically generates configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8
inclusive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are generated automatically for every channel available in the specific relay as shown above for the first channel
of a type 5F transducer module installed in slot H.
The function of the channel can be “Enabled” or “Disabled.” If “Disabled,” no actual values are created for the channel. An
alphanumeric “ID” is assigned to each channel; this ID is included in the channel actual value, along with the programmed
units associated with the parameter measured by the transducer, such as volts, °C, megawatts, and so on. This ID is also
used to reference the channel as the input parameter to features designed to measure this type of parameter. The DCMA
INPUT H1 RANGE setting specifies the mA DC range of the transducer connected to the input channel.
The DCMA INPUT H1 MIN VALUE and DCMA INPUT H1 MAX VALUE settings are used to program the span of the transducer in
primary units. For example, a temperature transducer might have a span from 0 to 250 °C; in this case the DCMA INPUT H1
MIN VALUE value is “0” and the DCMA INPUT H1 MAX VALUE value is “250.” Another example is a watts transducer with a span
from –20 to +180 MW; in this case the DCMA INPUT H1 MIN VALUE value is “–20” and the DCMA INPUT H1 MAX VALUE value is
“180.” Intermediate values between the minimum and maximum values are scaled linearly.
RTD INPUT H1 TYPE: Range: 100Ω Nickel, 10Ω Copper, 100Ω Platinum,
100Ω Platinum 120Ω Nickel
Hardware and software is provided to receive signals from external resistance temperature detectors and convert these
signals into a digital format for use as required. These channels are intended to be connected to any of the RTD types in
common use. Specific hardware details are contained in chapter 3.
RTD input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels with
the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay automatically generates configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8
inclusive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel
of a type 5C transducer module installed in the first available slot.
The function of the channel can be either “Enabled” or “Disabled.” If “Disabled,” there is not an actual value created for the
channel. An alphanumeric ID is assigned to the channel; this ID is included in the channel actual values. It is also used to
reference the channel as the input parameter to features designed to measure this type of parameter. Selecting the type of
RTD connected to the channel configures the channel.
5
Actions based on RTD overtemperature, such as trips or alarms, are done in conjunction with the FlexElements feature. In
FlexElements, the operate level is scaled to a base of 100°C. For example, a trip level of 150°C is achieved by setting the
operate level at 1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output
contact directly.
See the following table for reference temperature values for each RTD type.
Hardware and software is provided to generate DCmA signals that allow interfacing with external equipment. Hardware
details are contained in chapter 3. The DCmA output channels are arranged in a manner similar to transducer input or CT
and VT channels. The user configures individual channels with the settings as follows.
The channels are arranged in sub-modules of two channels, numbered 1 through 8 from top to bottom. On power-up, the
relay automatically generates configuration settings for every channel, based on the order code, in the same manner used
for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclusive, which is used as
the channel number.
Both the output range and a signal driving a given output are user-programmable via the following settings menu (an
example for channel M5 is shown).
The relay checks the driving signal (x in equations below) for the minimum and maximum limits, and subsequently re-
scales so the limits defined as MIN VAL and MAX VAL match the output range of the hardware defined as RANGE. The
following equation is applied:
Eq. 5-31
where
x is a driving signal specified by the SOURCE setting
Imin and Imax are defined by the RANGE setting
k is a scaling constant calculated as:
Eq. 5-32
The feature is intentionally inhibited if the MAX VAL and MIN VAL settings are entered incorrectly, for example when MAX VAL
5
– MIN VAL < 0.1 pu. The resulting characteristic is illustrated in the following figure.
Figure 5-183: DCmA output characteristic
Imax
OUTPUT CURRENT
Imin
DRIVING SIGNAL
842739A1.CDR MIN VAL MAX VAL
Settings
DCMA OUTPUT H1 SOURCE — This setting specifies an internal analog value to drive the analog output. Actual values
(FlexAnalog parameters) such as power, current amplitude, voltage amplitude, power factor, etc. can be configured as
sources driving DCmA outputs. See Appendix A for a list of FlexAnalog parameters.
DCMA OUTPUT H1 RANGE — This setting allows selection of the output range. Each DCmA channel can be set independently
to work with different ranges. The three most commonly used output ranges are available.
DCMA OUTPUT H1 MIN VAL — This setting allows setting the minimum limit for the signal that drives the output. This setting
is used to control the mapping between an internal analog value and the output current. The setting is entered in per-unit
values. The base units are defined in the same manner as the FlexElement base units.
DCMA OUTPUT H1 MAX VAL — This setting allows setting the maximum limit for the signal that drives the output. This setting
is used to control the mapping between an internal analog value and the output current. The setting is entered in per-unit
values. The base units are defined in the same manner as the FlexElement base units.
The DCMA OUTPUT H1 MIN VAL and DCMA OUTPUT H1 MAX VAL settings are ignored for power factor base units (i.e. if
the DCMA OUTPUT H1 SOURCE is set to FlexAnalog value based on power factor measurement).
Eq. 5-33
The base unit for power (refer to the FlexElements section in this chapter for additional details) is:
Eq. 5-35
The minimum and maximum power values to be monitored (in pu) are:
Eq. 5-36
Eq. 5-37
The base unit for current (see the FlexElements section in this chapter for additional details) is:
Eq. 5-38
The minimum and maximum power values to be monitored (in pu) are:
Eq. 5-39
Eq. 5-40
The base unit for voltage (see the FlexElements section in this chapter for additional details) is:
Eq. 5-41
The minimum and maximum voltage values to be monitored (in pu) are:
Eq. 5-42
5.11 Testing
5.11.1 Test mode function
SETTINGS TESTING TEST MODE FUNCTION
TESTING TEST MODE Range: Disabled, Isolated, Forcible
FUNCTION: Disabled
The F35 provides a test facility to verify the functionality of contact inputs and outputs, some communication functions
and the Phasor Measurement Unit (PMU, where applicable), using simulated conditions. It is accessible in the software and
graphical front panel.
The TEST MODE FUNCTION can be in one of three states: Disabled, Isolated, or Forcible. In UR 7.7 and later, as outlined in the
Simulation section that follows, the UR test mode and GOOSE simulation mode are Isolated, and they no longer depend on
the UR TEST MODE FUNCTION.
The Disabled mode is intended for normal in service operation; the relay protection, control, and communication function
is normal. Test features are disabled, except channel tests and Phasor Measurement Unit tests remain usable when
provided.
The Isolated mode is intended to allow the relay to be quickly placed in a state where the relay cannot negatively impact
the power system or other parts of the substation automation system. This is to allow changing settings, loading new
firmware, changing hardware modules, and changing communication connections. As far as practical all relay output
signals are blocked. Contact outputs are de-energized, latching outputs are frozen. Commands to HardFiber Bricks are
blocked. GOOSE transmissions have their "simulation" flag (also known as "test" flag) set, which results in the messages not
5 being accepted by compliant receiving devices that do not have a "Sim" data attribute set. The quality attribute of values
that can be output via IEC 61850 MMS services are set to "invalid," which results in the values not being used for
operational purposes by compliant receiving devices. Direct I/O channel tests and PMU tests are usable on applicable
models.
The Forcible mode is intended for testing involving forcing relay operation by test signal injection and verifying correct
relay output. This mode is also for tests to verify the relay outputs (both contact and communications) have the intended
impact on specific power system devices or on specific other substation automation devices. Contact outputs can be
selectively enabled or forced as described in the following two sections. Shared outputs to Bricks have their test mode flag
raised, which results in their value only being accepted by relays also in forcible mode. GOOSE transmissions have the
"simulation" flag set, which results in these only being accepted by other devices that have their "Sim" data attribute set.
The "Sim" data attribute in the relay is set, so that if GOOSE messages are received with the "simulation" flag set, these are
used in place of the normal messages. The quality attribute of values that are output via IEC 61850 MMS services are set to
"valid" + "test," which signals that the values are not to be used for operational purposes.
Otherwise, the UR remains fully operational while in the Forcible test mode, allowing for various testing procedures. In
particular, the protection and control elements, and FlexLogic function normally. Other than the IEC 61850 protocol,
communications based inputs and outputs remain fully operational. The test procedure must take this into account. Direct
I/O channel tests and PMU tests are usable on applicable models.
The test mode can be selected through the front panel, EnerVista UR Setup software, or IEC 61850 control to LLN0.Mod.
LLN0.Mod.ctlVal "on" selects Disabled, "test/blocked" selects Isolated, and "test" selects Forcible. The TEST MODE FUNCTION
setting can only be changed by a direct user command. Following a restart, power up, settings upload, or firmware
upgrade, the test mode remains at the last programmed value. This allows a UR that has been placed in isolated mode to
remain isolated during testing and maintenance activities.
When in Forcible mode, the operand selected by the TEST MODE FORCING setting dictates further response of the F35 to
testing conditions, as described in the following two sections.
The test mode state is indicated on the relay front panel by a combination of the Test Mode LED indicator, the In-Service
LED indicator, and by the critical fail relay, as shown in the following table.
Table 5-36: Test mode operation
TEST MODE In-service Test mode Critical fail TEST MODE Contact input and output behavior
FUNCTION LED LED relay FORCING
Disabled Unaffected Off Normal No effect Normal
Isolated Off On De-energized No effect Contact outputs disabled
Forcible Off Flashing De-energized Off Normal
On Controlled by forcing features
On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings revert to
their default states.
The force contact inputs feature provides a method of performing checks on the function of all contact inputs.
While in Forcible test mode, the relay contact inputs can be pre-programmed to respond in the following ways:
• If set to “Normal,” the input remains fully operational. It is controlled by the voltage across its input terminals and can
be turned on and off by external circuitry. Select this value if a given input must be operational during the test. This
includes, for example, an input initiating the test, or being a part of a user pre-programmed test sequence.
• If set to “Open,” the input is forced to report as opened (Logic 0) while the operand selected by TEST MODE FORCING
setting is On, regardless of the voltage across the input terminals. While the selected operand is Off, the input behaves
as it does when in service.
• If set to “Closed,” the input is forced to report as closed (Logic 1) while the operand selected by TEST MODE FORCING
setting is On regardless of the voltage across the input terminals. While the selected operand is Off, the input behaves
as it does when in service.
On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings revert to
their default states.
The force contact outputs feature provides a method of performing checks on the function of all contact outputs.
While in Forcible test mode, the relay contact outputs can be pre-programmed to respond in the following ways:
• If set to “Normal,” the contact output remains fully operational. It operates when its control operand is logic 1 and
resets when its control operand is logic 0.
• If set to “Energized,” the output closes and remains closed while the operand selected by the TEST MODE FORCING
setting is On, regardless of the status of the operand configured to control the output contact. While the selected
operand is Off, the output behaves as it does when in service.
• If set to “De-energized,” the output opens and remains opened while the operand selected by the TEST MODE FORCING
setting is On, regardless of the status of the operand configured to control the output contact. While the selected
operand is Off, the output behaves as it does when in service.
• If set to “Freeze,” the output retains its position at the instant before the TEST MODE FUNCTION was Forcible and the
operand selected by the TEST MODE FORCING setting was On, regardless of later changes in the status of the operand
configured to control the output contact. While the selected operand is Off, the output behaves as it does when in
service.
On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings revert to
their default states.
5
5.12 Simulation
5.12.1 GOOSE
SETTINGS SIMULATION GOOSE
GOOSE Tx GOOSE SIM MODE: Range: Enabled, Disabled
Disabled
Prior to UR 7.7, when the UR TEST MODE FUNCTION is set to "Isolated" or "Forcible," the sim bit in the header of all
transmitted GOOSE messages is set to "TRUE," so that the UR plays the simulator role during the testing and
commissioning phases. The "Sim" data attribute in the relay is set (<MasterLD>/LPHD1.Sim.stVal = TRUE), so that if GOOSE
messages are received with the "simulation" flag set, these are used in place of the normal messages. The quality attribute
values that are transmitted via GOOSE services are set to "valid" + "test."
In UR 7.7 and later, the UR test mode and GOOSE simulation mode are isolated. The sim bit in the transmitted GOOSE
messages and the relay "Sim" attribute (<MasterLD>/LPHD1.Sim.stVal) are controlled via new Modbus settings and MMS
control requests. They no longer depend on the UR TEST MODE FUNCTION.
When the F35 is set to IEC 61850 Edition 2, the settings display in the software and front panel. When using IEC 61850
Edition 1, the settings display in the software and are read-only.
Tx GOOSE SIM MODE — When set to Disabled, the sim bit in all transmitted GOOSE messages are set to FALSE. When set to
Enabled, the sim bit in all transmitted GOOSE messages are set to TRUE. This setting also is accessible from IEC 61850
client control to <MasterLD>/LPHD1.TxGoSim.
SIM q.VALIDITY — This setting simulates the validity bits of the quality attribute values included in all transmitted GOOSE
messages. This setting is used when Tx GOOSE SIM MODE is set to Enabled. When this setting is set to None, the q.Validity
bits are set based on the logical node behavior value. When set to any other value, the q.Validity bits of quality attributes
included in all transmitted GOOSE messages are set to the selected value.
SIM q.TEST — This setting simulates the Test bit of the quality attribute values included in all transmitted GOOSE messages.
This setting is used when Tx GOOSE SIM MODE is set to Enabled. When this setting is set to None, the q.Test bit is set based
on the relay TEST MODE FUNCTION. When set to any other value, the q.Test bit of quality attributes included in all
transmitted GOOSE messages is set to the selected value.
ACCEPT SIM GOOSE & SV — When set to Disabled, the relay "Sim" attribute (<MasterLD>/LPHD1.Sim.stVal) is set to False and
the GOOSE messages received with simulation flag set are ignored. When set to Enabled, the relay "Sim" attribute
(<MasterLD>/LPHD1.Sim.stVal) is set to True, so that if GOOSE messages are received with the "simulation" flag set, these
are used in place of the normal messages. This setting also is accessible from IEC 61850 client control to <MasterLD>/
LPHD1.Sim.
Actual values
This chapter outlines viewing of data on the front panel and in the software.
SOURCE SRC 2
SOURCE SRC 3
SOURCE SRC 4
SOURCE SRC 5
SOURCE SRC 6
WATTMETRIC
GROUND FAULT 5
For status reporting, ‘On’ represents Logic 1 and ‘Off’ represents Logic 0.
6 Annunciator alarms can be acknowledged and reset, and LEDs and pushbuttons can be viewed.
To view alarms for the graphical front panel in EnerVista:
1. Access Actual Values > Graphical Panel > Annunciator Panel. Alarms are listed, allowing remote acknowledgement/
reset.
2. Click the Acknowledge or Reset button for an alarm.
Figure 6-2: Annunciator alarms displayed in the software)
6.3 Status
6.3.1 Contact inputs
ACTUAL VALUES STATUS CONTACT INPUTS
CONTACT INPUTS Cont Ip 1 Range: On, Off
Off
Cont Ip xx Range: On, Off
Off
The present status of the contact inputs is shown here. The first line of a message display indicates the ID of the contact
input. For example, ‘Cont Ip 1’ refers to the contact input in terms of the default name-array index. The second line of the
display indicates the logic state of the contact input.
The present status of the 64 virtual inputs is shown here. The first line of a message display indicates the ID of the virtual
input. For example, ‘Virt Ip 1’ refers to the virtual input in terms of the default name. The second line of the display indicates
the logic state of the virtual input.
6
6.3.3 RxGOOSE boolean inputs
ACTUAL VALUES STATUS RxGOOSE BOOLEANS
RxGOOSE BOOLEANS RxGOOSE BOOLEAN 1 Range: On, Off
STATUS: Off
RxGOOSE BOOLEAN 256 Range: On, Off
STATUS: Off
The F35 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
The F35 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
The present state of teleprotection inputs from communication channels 1 and 2 are shown here. The state displayed is
that of corresponding remote output unless the channel is declared failed.
The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn, and VOn.
For form-C contact outputs, the state is displayed as Off or On.
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.
6.3.8 Autoreclose
ACTUAL VALUES STATUS AUTORECLOSE AUTORECLOSE 1(6)
AUTORECLOSE 1 AUTORECLOSE 1 Range: 0, 1, 2, 3, 4
SHOT COUNT: 0
The F35 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
The All RxGOOSE Online actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
Input.
The F35 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
stNum — State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
sqNum — Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.
IGMP — Multicast (SSM and ASM) modes of R-GOOSE reception require that the F35 device subscribe to a multicast group
over the Internet Group Management Protocol (IGMP) enabled network. R-RxGOOSE## IGMP status On indicates that IGMP
negotiation with a network device (for example a router) was successful. In the case where setting R-RxGOOSE1 DST IP is
configured to a multicast address and this status indicates Off, R-GOOSE reception cannot be successful, and therefore
communication network diagnosis needs to be carried out. This status is relevant to R-GOOSE reception when configured
for SSM or ASM reception modes. It is not relevant for GOOSE or for R-GOOSE in unicast reception mode.
Counter 1 FROZEN:
0
The present status of the eight digital counters displays here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label also appears). Also included, is the date and time
stamp for the frozen count. The COUNTER 1 MICROS value refers to the microsecond portion of the time stamp.
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
6.3.13 FlexStates
6 ACTUAL VALUES STATUS FLEX STATES
FLEX STATES PARAM 1: Off Range: On, Off
Off
PARAM 256: Off Range: On, Off
Off
There are 256 FlexStateTM bits available. The second line value indicates the state of the given FlexState bit.
6.3.14 Ethernet
ACTUAL VALUES STATUS ETHERNET
ETHERNET ETHERNET PRI LINK Range: Fail, OK
STATUS: Fail
These values indicate the status of the first, second, and third Ethernet links.
This item displays in the software when the product includes an IEEE 1588 software option.
RTC SYNC SOURCE actual value is the time synchronizing source the relay is using at present. Possible sources are: Port 1
PTP Clock, Port 2 PTP Clock, Port 3 PTP Clock, IRIG-B, SNTP1, SNTP2, and None. An actual value displays when the relay
includes the IEEE 1588 software option.
The GRANDMASTER ID is the grandmasterIdentity code being received from the present PTP grandmaster, if any. When the
relay is not using any PTP grandmaster, this actual value is zero. The grandmasterIdentity code is specified by PTP to be
globally unique, so one can always know which clock is grandmaster in a system with multiple grandmaster-capable
clocks.
ACCURACY is the estimated maximum time error at present in the RTC, considering the quality information imbedded in the
6
received time signal. The value 999,999,999 indicates that the magnitude of the estimated error is one second or more, or
that the error cannot be estimated.
PORT 1…3 PTP STATE is the present state of the port’s PTP clock. The PTP clock state is:
• Disabled is the port’s function setting is Disabled
• No Signal if enabled but no signal from an active master has been found and selected
• Calibrating if an active master has been selected but lock is not at present established
• Synch’d (No Pdelay) if the port is synchronized, but the peer delay mechanism is non-operational
• Synchronized if synchronized
PTP - IRIG-B DELTA is the time difference, measured in nanoseconds, between the fractional seconds portion of the time
being received via PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to IRIG-
B time.
UNRETURNED MSG
COUNT CH1: 0
UNRETURNED MSG
COUNT CH2: 0
DIRECT INPUT 1:
On
DIRECT INPUT 32:
On
The AVERAGE MSG RETURN TIME is the time taken for direct output messages to return to the sender in a direct input/output
ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last
ten messages. There are two return times for dual-channel communications modules.
The UNRETURNED MSG COUNT values (one per communications channel) count the direct output messages that do not
make the trip around the communications ring. The CRC FAIL COUNT values (one per communications channel) count the
direct output messages that have been received but fail the CRC check. High values for either of these counts can indicate
on a problem with wiring, the communication channel, or one or more relays. The UNRETURNED MSG COUNT and CRC FAIL
COUNT values can be cleared using the CLEAR DIRECT I/O COUNTERS command.
The DIRECT INPUT 1 to DIRECT INPUT (32) values represent the state of each direct input.
These actual values represent the state of direct devices 1 through 16.
FAST EXCHANGE 1
DATA LENGTH: 0
These values provide information for debugging an Ethernet Global Data (EGD) network. The EGD signature and packet size
for the fast EGD exchange display.
SLOW EXCHANGE 1
DATA LENGTH: 0
These values provide information for debugging an EGD network. The EGD signature and packet size for the slow EGD
exchanges display.
The number of detected incipient faults for each incipient fault element are displayed here for each phase. These values
can be reset to zero with the COMMANDS CLEAR RECORDS CLEAR INCIPENT FAULT COUNTERS command.
These values specify the remaining number of TCP connections still available for each protocol. The display depends on the
options applicable to your device. Each time a connection is used, the remaining number of connections decrements.
When released, the remaining number of connections increments. If no connection is made over the specific protocol, the
number equals the maximum number available for the specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP
status shows 4.
For the graphical front panel, the remaining connections refer to TCP connections only.
MMS TCP — The number of IEC 61850 connections remaining.
The F35 is provided with optional PRP capability. This feature is specified as a software option at the time of
ordering. See the Order Codes section in chapter 2 for details.
Total Received Port A is a counter for total messages received (either from DANPs or from SANs) on Port A.
Total Received Port B is a counter for total messages received (either from DANPs or from SANs) on Port B.
Total Errors is a counter for total messages received with an error (bad port code, frame length too short).
Mismatches Port A is a counter for total messages received with an error on Port A (PRP frame, but port received through
and LAN ID in the frame do not match).
Mismatches Port B is a counter for total messages received with an error on Port B (PRP frame, but port received through
and LAN ID in the frame do not match).
The F35 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
This status is relevant to R-GOOSE reception when configured for SSM or ASM reception modes. It is not relevant for GOOSE
or for R-GOOSE in unicast reception mode.
ARP — The unicast mode of R-GOOSE transmission requires Address Resolution Protocol (ARP) for the resolution of the
network layer address into the MAC layer address. R-TxGOOSE## ARP status On indicates that ARP responses are being
received and the destination MAC address for R-GOOSE transmissions has been obtained. This status remains Off if
TxGOOSE## is not configured for R-GOOSE. It also remains Off if setting R-TxGOOSE1 DST IP is set to a multicast address. In
the case where setting R-TxGOOSE1 DST IP is configured with a unicast address and this status indicates Off, TxGOOSE##
transmission will be off, and therefore communication network diagnosis needs to be carried out.
This status is only applicable for R-GOOSE transmission with setting R-TxGOOSE1 DST IP set to a unicast IP address. It is not
applicable for GOOSE or for R-GOOSE when setting R-TxGOOSE1 DST IP is multicast.
6.3.24 Protocol
ACTUAL VALUES STATUS PROTOCOL 6
PROTOCOL IEC61850 EDITION: Range: Edition1, Edition2
Edition2
The F35 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
Displays the IEC 61850 edition currently being used, as set under Settings > Product Setup > Communications > Protocol
> IEC61850 SCL Edition. This value displays only on the front panel.
6.4 Metering
6.4.1 Metering conventions
Figure 6-3: Flow direction of signed values for watts and VARs
Voltage +Q
VCG
Watts = Positive IC
PF = Lead PF = Lag
Vars = Positive
PF = Lag IA
VAG –P +P
Current IB IA
PF = Lag PF = Lead
UR-SERIES IED
VBG
–Q
M LOAD –Θ1°
Inductive Resistive S=VI
Generator
G
VCG +Q
Voltage
PF = Lead PF = Lag
Watts = Positive IA
Vars = Negative IC
PF = Lead VAG –P +P
IA
Current
PF = Lag PF = Lead
IB
UR-SERIES IED
VBG –Q
S=VI
LOAD
–Θ2°
Resistive
Inductive Resistive
M LOAD
VCG +Q
6 PF = Lag
Current IC
IA
PF = Lag PF = Lead
VBG
–Q
UR-SERIES IED
G S=VI
–Θ3°
Generator
Resistive
LOAD
+Q
VCG
Voltage IB
PF = Lead PF = Lag
Watts = Negative IA
Vars = Positive VAG –P +P
PF = Lead
IA IC
The relay first determines if any “Phase VT” bank is indicated in the source. If it is, voltage channel VA of that bank is used
as the angle reference. Otherwise, the relay determines if any “Aux VT” bank is indicated; if it is, the auxiliary voltage
channel of that bank is used as the angle reference. If neither of the two conditions is satisfied, then two more steps of this
hierarchical procedure to determine the reference signal include “Phase CT” bank and “Ground CT” bank.
If the AC signal pre-selected by the relay upon configuration is not measurable, the phase angles are not referenced. The
phase angles are assigned as positive in the leading direction, and are presented as negative in the lagging direction, to
more closely align with power system metering conventions. The figure illustrates this.
Figure 6-4: UR phase angle measurement convention
-270o
-225o -315o
positive
angle
direction
-180o 0o
UR phase angle
reference
-135o -45o
-90o
827845A1.CDR
The zero-sequence voltage is not measurable under the Delta connection of instrument transformers and is defaulted to
zero. The table below shows an example of symmetrical components calculations for the ABC phase rotation.
Table 6-1: Symmetrical components calculation example
SYSTEM VOLTAGES, sec. V * VT conn. relay INPUTS, sec. V SYMM. COMP, sec. V
VAG VBG VCG VAB VBC VCA F5ac F6ac F7ac V0 V1 V2
13.9 76.2 79.7 84.9 138.3 85.4 WYE 13.9 76.2 79.7 19.5 56.5 23.3
0° –125° –250° –313° –97° –241° 0° –125° –250° –192° –7° –187°
UNKNOWN (only V1 and V2 84.9 138.3 85.4 DELTA 84.9 138.3 85.4 N/A 56.5 23.3
can be determined) 0° –144° –288° 0° –144° –288° –54° –234°
* The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a
relative matter. It is important to remember that the F35 displays are always referenced as specified under SETTINGS
SYSTEM SETUP POWER SYSTEM FREQUENCY AND PHASE REFERENCE.
The example above is illustrated in the following figure.
Figure 6-5: Measurement convention for symmetrical components
System voltages Symmetrical
components
UR-series phase
angle reference
6
UR-series phase
angle reference
1
A
Wye VTs
C
B
0
2
UR
an -s
gl eri
e es
re p
fe ha
re s
nc e
e
U 1
A an R-s
gl eri
e es
re p
fe ha
re s
Delta VTs nc e
e
C
B
2
827844A1.CDR
6.4.2 Sources
6.4.2.1 Menu
ACTUAL VALUES METERING SOURCE SRC 1
SOURCE SRC 1 PHASE CURRENT See below
SRC 1
This menu displays the metered values available for each source.
Metered values presented for each source depend on the phase and auxiliary VTs and phase and ground CTs assignments
for this particular source. For example, if no phase VT is assigned to this source, then any voltage, energy, and power 6
values are unavailable.
The metered phase current values are displayed in this menu. The "SRC 1" text gets replaced by whatever name was
programmed by the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
The metered ground current values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by
the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
The metered phase voltage values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by
the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
The metered auxiliary voltage values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by
the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
This menu displays metered values for real, reactive, and apparent power, as well as power factor. The "SRC 1" text is
replaced by the name programmed by the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL
SOURCES).
When VTs are configured in wye, the F35 calculates power in each phase and three-phase power is measured as
S = VA x ÎA + VB x ÎB + VC x ÎC Eq. 6-1
When VTs are configured in delta, the F35 does not calculate power in each phase and three-phase power is measured as
S = VAB x ÎA + VCB x ÎC Eq. 6-2
where
S is the apparent power
VA, VB, VC, IA, IB, IC are phase voltage and phase current phasors
VAB and VCB are phase-to-phase voltage phasors
Î is the conjugate of I
This menu displays metered values for real and reactive energy. The "SRC 1" text is replaced by the name programmed by
the user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES). Because energy values are
accumulated, record them and then reset them immediately prior to changing CT or VT characteristics.
SRC 1 DMD W:
0.000 W
The metered frequency values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by the
user for the associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES).
SOURCE FREQUENCY is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the SYSTEM SETUP POWER SYSTEM settings). The signal used for frequency estimation is low-pass filtered. The final
frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
This menu displays metered current harmonics values. The "SRC 1" text is replaced by the name was programmed for the
associated source (see SETTINGS SYSTEM SETUP SIGNAL SOURCES). Current harmonics are measured for each source
for the total harmonic distortion (THD) and 2nd to 25th harmonics per phase.
6 This menu displays metered voltage harmonics values. The “SRC 1” text is replaced by the programmed name for the
associated source (see the SETTINGS SYSTEM SETUP SIGNAL SOURCES menu).
To extract the 2nd to 25th voltage harmonics, each harmonic is computed on a per-phase basis, where:
N = 64 is the number of samples per cycle
0 = 2f is the angular frequency based on the system frequency (50 or 60 Hz)
k = 1, 2,..., N – 1 is the index over one cycle for the Fast Fourier Transform (FFT)
m is the last sample number for the sliding window
h = 1, 2,..., 25 is the harmonic number
The short-time Fourier transform is applied to the unfiltered signal:
Eq. 6-3
The harmonics are a percentage of the fundamental signal obtained as a ratio of harmonic amplitude to fundamental
amplitude multiplied by 100%. The total harmonic distortion (THD) is the ratio of the total harmonic content to the
fundamental:
Eq. 6-4
Voltage harmonics are calculated only for Wye connected phase VTs. Ensure that the SYSTEM SETUP AC INPUTS
VOLTAGE BANK F5 PHASE VT XX CONNECTION setting is “Wye” to enable voltage harmonics metering.
The tracking frequency displays here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE setting in the SETTINGS SYSTEM SETUP POWER SYSTEM menu. See the Power
System section of chapter 5 for details.
6.4.4 FlexElements
ACTUAL VALUES METERING FLEXELEMENTS FLEXELEMENT 1(16)
FLEXELEMENT 1 FLEXELEMENT 1
OpSig: 0.000
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6-2: FlexElement base units
Base unit Description
BREAKER ACC ARCING AMPS BASE = 2000 kA2 cycle
(Brk X Acc Arc Amp A, B, and C)
BREAKER ARCING AMPS BASE = 1 kA2 cycle
(Brk X Arc Amp A, B, and C)
DCmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
FAULT LOCATION
under the +IN and –IN inputs.
BASE = Line Length as specified in Fault Report
6
FREQUENCY fBASE = 1 Hz
PHASE ANGLE BASE = 360 degrees (see the UR angle referencing convention)
POWER FACTOR PFBASE = 1.00
RTDs BASE = 100°C
SOURCE CURRENT IBASE = maximum nominal primary RMS value of the +IN and –IN inputs
SOURCE ENERGY EBASE = 10000 MWh or MVAh, respectively
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER PBASE = maximum value of VBASE IBASE for the +IN and –IN inputs
SOURCE THD & HARMONICS BASE = 1%
SOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputs
The F35 is provided with optional GOOSE communications capability. This feature is specified as a software
option at the time of ordering. See the Order Codes section of chapter 2 for details.
The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE
messages sent from other devices.
This menu displays the wattmetric zero-sequence directional element operating power values.
Actual values for each DCmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
ACTUAL VALUES METERING TRANSDUCER I/O RTD INPUTS RTD INPUT xx
RTD INPUT xx RTD INPUT xx
-50 °C
Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value.
6
6.5 Records
6.5.1 Fault reports
ACTUAL VALUES RECORDS FAULT REPORTS FAULT REPORT 1(15)
NO FAULTS TO REPORT
or
FAULT REPORT 1 FAULT 1 Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
LINE ID: SRC 1
FAULT 1 TYPE: Range: not available if the source VTs are in the
ABG “Delta” configuration
FAULT 1 LOCATION Range: not available if the source VTs are in the
00.0 km “Delta” configuration
The latest 15 fault reports can be stored. The most recent fault location calculation (when applicable) is displayed in this
menu, along with the date and time stamp of the event which triggered the calculation. See the SETTINGS PRODUCT
SETUP FAULT REPORTS menu for assigning the source and trigger for fault calculations. See the COMMANDS CLEAR
RECORDS menu for manual clearing of the fault reports and to the SETTINGS PRODUCT SETUP CLEAR RELAY RECORDS
menu for automated clearing of the fault reports.
The FAULT 1 LOOP RESISTANCE and REACTANCE are expressed in secondary ohms, which are calculated as per the following
equation.
Zloop = Vloop / Iloop Eq. 6-5
The table defines the loop voltage and current.
Table 6-3: Quantities used to calculate fault loop impedances
Fault type Vloop Iloop
AG VA IA + (Z0/Z1-1)*I0 + Z0M/Z1*IG/3
BG VB IB + (Z0/Z1-1)*I0 + Z0M/Z1*IG/3
CG VC IC + (Z0/Z1-1)*I0 + Z0M/Z1*IG/3
AB, ABG VA – VB IA - IB
BC, BCG VB – VC IB - IC
CA, CAG VC – VA IC - IA
ABC Average of AB, BC, CA loop impedances
Where VA, VB, VC are phase voltage phasors in secondary volts; IA, IB, IC are current phasors in secondary amps, I0 is the
zero sequence current phasors in secondary amps; and IG is the ground current from the parallel line scaled to the source
phase CT in secondary amps. Z0/Z1 is the zero sequence impedance to positive sequence impedance ratio, and Z0M/Z1 is
6
mutual zero sequence impedance to positive sequence impedance ratio.
VTs of the FAULT REPORT 1 SOURCE must be connected in Wye or VT SUBSTITUTION must be set correctly for the Delta
connected VT to display the loop impedance and fault resistance for single phase-to-ground faults.
For the application of partially parallel circuits and in the case of single phase-to-ground faults, the reported fault
resistance and fault loop impedance may not be accurate even the compensation method is applied.
EVENT: 3 EVENT 3
POWER ON DATE: 2000/07/14
EVENT: 2 EVENT 3
POWER OFF TIME: 14:53:00.03405
EVENT: 1
EVENTS CLEARED
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological
order from most recent to oldest. When all 1024 event records have been filled, the oldest record is removed as a new
record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated
with the event trigger. See the COMMANDS CLEAR RECORDS menu for clearing event records.
Only major output operands generate events, not every operand. Elements that assert output per phase, for example, log
operating phase output only without asserting the common three-phase operand event.
See also the system log (syslog) information in the previous chapter.
The event records are viewable in the software and in a web browser. The figure shows the event records in the software.
Figure 6-6: Event records viewed in EnerVista software
6
To view events in a web browser:
1. Enter the IP address of the device.
To download an oscillography waveform:
1. Click the arrow icon in the Data column.
6.5.3 Oscillography
NUMBER OF TRIGGERS:
0
AVAILABLE RECORDS:
0
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The cycles
per record value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillography
section of chapter 5 for details.
A trigger can be forced here at any time by setting “Yes” to the FORCE TRIGGER? command. See the COMMANDS CLEAR
RECORDS menu for information on clearing the oscillography records.
To view a waveform:
2. Access Actual Values > Records > Oscillography in the EnerVista software.
3. In the window that opens, select the record number. The highest number is the most recent record (Newest Record
Number).
4. Click the Read button to get the waveform. When available, waveforms are displayed graphically, and otherwise error
messages display.
5. In the waveform window that opens, you can save the file, for example with the CFG extension.
The OLDEST SAMPLE TIME represents the time at which the oldest available samples were taken. It is static until the log gets
full, at which time it starts counting at the defined sampling rate.
The NEWEST SAMPLE TIME represents the time the most recent samples were taken. It counts up at the defined sampling
rate. If the data logger channels are defined, then both values are static.
See the COMMANDS CLEAR RECORDS menu for clearing data logger records.
BKR 1 OPERATING
TIME: 0 ms
The order code, serial number, Ethernet MAC address, date and time of manufacture, and operating time are shown here.
The rear panel on the device contains similar information. The information is read-only in the software and modifiable on 6
the front panel. For example, the order code can be corrected using the front panel.
ETHERNET MAC ADDRESS — UR devices with firmware 7.0x and above have three Ethernet ports that can be used on three
networks. The MAC address displays for port 1. The MAC address for port 2 is one higher. The MAC address for port 3 is one
higher than port 2. In redundant mode, the MAC addresses for ports 2 and 3 are the same as port 2.
The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been
installed.
The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been
installed. The date format reflects the format specified for the clock and can vary from that shown here.
This chapter outlines the Commands and Targets menus and self-tests/error messages. Commands related to the IEC
61850 protocol are outlined in the IEC 61850 section of the Settings chapter. Log/error messages for IEC 61850 are
outlined in the UR Family Communications Guide.
COMMANDS
COMMANDS
VIRTUAL INPUTS
COMMANDS
CLEAR RECORDS
COMMANDS
SET DATE AND TIME
COMMANDS
RELAY MAINTENANCE
COMMANDS
SECURITY
The commands menu contains relay directives intended for operations personnel. All commands can be protected from
unauthorized access via the command password; see the Security section of chapter 5 for details. The following flash
message appears after successfully command entry.
COMMAND
EXECUTED
The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The
second line indicates the current or selected status of the virtual input. This status is a state off (logic 0) or on (logic 1).
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a
command setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to
“No.”
COMMANDS CLEAR RECORDS CLEAR IEC61850 XWSI OPCNT
CLEAR IEC61850 CLEAR XSWI 1 Range: No, Yes
XWSI OPCNT OpCnt? No
CLEAR XSWI 24 Range: No, Yes
OpCnt? No
The Clear XSWI commands clear the disconnect operation counters for each phase and the three-phase counter. Similarly,
the Clear XCBR commands clear the circuit breaker operation counters for each phase and the three-phase counter.
The date and time can be entered on the front panel keypad. The time setting is based on the 24-hour clock. The complete
date, as a minimum, must be entered to allow execution of this command. The new time and date take effect when the
ENTER key is pressed.
The clock also can be synchronized to the local computer time among several UR devices. Use the Synchronize Devices
entry in the Online Window area of the EnerVista software. (Click the button at the top of the window that opens.)
When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time or the
manually synchronized time is over-written.
The timescale of the entered time is local time, including daylight savings time where and when applicable.
7
7.1.4 Relay maintenance
COMMANDS RELAY MAINTENANCE
COMMANDS PERFORM LAMP TEST? Range: No, Yes
RELAY MAINTENANCE No
PERFORM LCD TEST? Range: Off, Red, Green, Blue, White & Text Pattern,
Off Black & Text Pattern, TV Test Pattern
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are
activated by changing a command setting to “Yes” and pressing the ENTER key. The command setting then automatically
reverts to “No.” The service command is activated by entering a numerical code and pressing the ENTER key.
Not all commands display in the software; use the front panel when required.
PERFORM LAMP TEST — Turns on all front panel LEDs and display pixels for a short duration.
PERFORM LCD TEST — This command detects either stuck-ON or stuck-OFF pixels (dead pixels) in the display screen on the
graphical front panel. RED/GREEN/BLUE is to display the solid background color in the whole screen. WHITE & TEXT
PATTERN shows the white background and black texts. BLACK & TEXT PATTERN shows the black background and white
texts. TV TEST PATTERN displays a standard television test pattern (SMPTE color bars). The test screen can be canceled by
pressing any pushbutton or after 30 seconds of inactivity.
PERFORM PUSHBUTTON TEST — This command tests the pushbuttons on the graphical front panel. During testing, press the
corresponding pushbutton according to the prompt text. A failure message is given if the expected action is not detected
in one minute. Holding the ESCAPE button for five seconds to interrupt the test sequence. The designated function of a
specific pushbutton is bypassed in the test.
UPDATE ORDER CODE — Use this command to read and update the order code, for example when hardware modules have
been changed inside the relay. It causes the relay to scan the backplane for the modules and update the order code to
match. All settings are defaulted with an update. When an update occurs, the following message displays and the relay
restarts.
UPDATING...
PLEASE WAIT
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER
CODE NOT UPDATED message displays.
REBOOT RELAY — Restarts the relay so that changes to configuration settings can take effect. In most cases, if changes are
made to the configuration settings these changes do not take effect unless the relay is rebooted.
With the CyberSentry option, the Administrator and Operator roles can initiate the Reboot Relay command.
7 SERVICE COMMAND — Performs specific F35 service actions. Presently, there are two service actions available. Code "20511"
returns all settings to their factory default value and restarts the relay (then you re-enter IP address, restart, set unit to
"Programmed"). Code “101” is used to clear factory diagnostic information stored in the non-volatile memory. If a code
other than these two is entered, the command is ignored and no action is taken. Various self-checking diagnostics are
performed in the background while the F35 is running, and diagnostic information is stored on the non-volatile memory
from time to time based on the self-checking result. Although the diagnostic information is cleared before the F35 is
shipped from the factory, the user can want to clear the diagnostic information for themselves under certain
circumstances. For example, you clear diagnostic information after replacement of hardware. Once the diagnostic
information is cleared, all self-checking variables are reset to their initial state and diagnostics restart from scratch.
SAVE VOLATILE DATA — Saves this data to compact flash memory prior to shutdown. This allows the saved data to be as
recent as possible instead of relying on the periodic timer to save the data.
7.1.5 Security
COMMANDS SECURITY
SECURITY ADMINISTRATOR Range: Yes, No
LOGOFF: No
With the CyberSentry option, this setting is available to enable or disable the following commands.
ADMINISTRATOR LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an administrator session.
ENGINEER LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an engineer session.
OPERATOR LOGOFF — Selecting ‘Yes’ allows the Supervisor to forcefully logoff an operator session.
CLEAR SECURITY DATA — Selecting ‘Yes’ allows the Supervisor to forcefully clear all the security logs and clears all the
operands associated with the self-tests.
7.2 Targets
TARGETS
PHASE TOC4 Displayed only if targets for this element are active.
OP: A B - Example shown.
DIGITAL ELEMENT 48: Displayed only if targets for this element are active.
LATCHED Example shown.
A target enables the EnerVista UR Setup software to monitor automatically and display the status of any active target
messages of all the devices inserted into that site.
Each F35 element with a TARGET setting has a target message that when activated by its element is displayed in sequence
with any other currently active target messages in the TARGETS menu. In the example shown, the Phase TOC4 and Digital
Element 48 target settings are active and so have their targets displayed. The down arrow below the two elements
indicates that there can be other active elements beyond these two. 7
For more information, see the description of target messages in the next section, and the Introduction to Elements section
in the Settings chapter for instructions on TARGET setting.
When no targets are active, the display reads NO ACTIVE TARGETS.
If a self test error is detected, a message appears indicating the cause of the error. For example UNIT NOT PROGRAMMED
indicates that the minimal relay settings have not been programmed.
7.2.2.1 Description
The relay performs a number of self-test diagnostic checks to ensure device integrity. The two types of self-tests (major
and minor) are listed in the following tables. When either type of error occurs, the Trouble LED Indicator turns on and a
target message displays. All errors record an event in the event recorder. Latched errors can be cleared by pressing the
RESET key, providing the condition is no longer present.
Major self-test errors also result in the following:
• The critical fail relay on the power supply module de-energizes
• All other output relays de-energize and are prevented from further operation
• The front panel In Service LED indicator turns off
• A RELAY OUT OF SERVICE event is recorded
To view error messages in EnerVista software:
1. Access Actual Values > Records > Event Records.
Messages display on the front panel with one or two lines of text. An example is as follows. In the tables that follow,
messages are grouped using the first line of text. For example, MAINTENANCE ALERT, then a row for 4L Discrepancy, then a
row for Bad IRIG-B Signal.
MAINTENANCE ALERT:
4L Discrepancy
MAINTENANCE ALERT:
Bad IRIG-B Signal
The consequence of an
incorrect SFP can range from
damage to the F35 to no
power information for the F35
on its web page (enter IP
address in a web browser,
then click the SFP
Transceiver Information —
only the type of SFP displays
and not power data).
Chapter 8: Commissioning
Commissioning
8.1 Testing
8.1.1 Testing underfrequency elements
Underfrequency and overfrequency protection requires techniques with subtle testing implications. Whereas most
protection is designed to detect changes from normal to fault conditions that occur virtually instantaneously, power
system inertia requires frequency protection to pick up while the frequency is changing slowly. Frequency measurement is
inherently sensitive to noise, making high precision in combination with high speed challenging for both relays and test
equipment.
Injection to a particular F35 frequency element must be to its configured source and to the channels that the source uses
for frequency measurement. For frequency measurement, a source uses the first quantity configured in the following
order:
1. Phase voltages
2. Auxiliary voltage
3. Phase currents
4. Ground current
For example, if auxiliary voltage and phase currents are configured, the source uses the auxiliary voltage, not the phase
voltages or any of the currents.
When phase voltages or phase currents are used, the source applies a filter that rejects the zero-sequence component. As
such, the same signal must not be injected to all three phases, or the injected signal is completely filtered out. For an
underfrequency element using phase quantities, the phase A signal must be above the MIN VOLT/AMP setting value.
Therefore, either inject into phase A only, or inject a balanced three-phase signal.
Source frequency
Tracking frequency
Pickup
frequency
Time
Underfrequency element detection time
The static accuracy of the frequency threshold is determined by slowly adjusting the frequency of the injected signal about
the set pickup. If the F35 frequency metering feature is used to determine the injected frequency, verify the metering
accuracy by checking it against a known standard (for example, the power system).
To accurately measure the time delay of a frequency element, a test emulating realistic power system dynamics is
required. Let the injected frequency ramp smoothly through the set threshold, with the ramp starting frequency sufficiently
outside the threshold so that the relay becomes conditioned to the trend before operation. For typical interconnected
power systems, the recommended testing ramp rate is 0.20 Hz/s.
The required delay time is the interval from the point the frequency crosses the set threshold to the point that the element
operates. Some test sets can measure only the time from the ramp start to element operation, necessitating the
subtraction of the pre-threshold ramp time from the reading. For example, with a ramp rate of 0.20 Hz/s, start the ramp
0.20 Hz before the threshold and subtract 1 second from the test set time reading of ramp start to relay operation.
Note that the F35 event records only show the “pickup delay” component, a definite time timer. This is exclusive of the time
taken by the frequency responding component to pickup.
F35 oscillography can be used to measure the time between the calculated source frequency crossing the threshold and
8 element operation; however, this method omits the delay in the calculated source frequency. The security features of the
source frequency measurement algorithm result in the calculated frequency being delayed by two to four cycles (or longer
with noise on the input). In addition, oscillography resolution is 0.004 Hz, which at 0.20 Hz/s corresponds to a delay of 20
ms. Do not use the tracking frequency in timing measurements, as its algorithm involves phase locking, which purposely
sets its frequency high or low to allow the F35 sample clock to catch-up or wait as necessary to reach synchronism with
the power system.
Theory of operation
distance to fault
Remote
Local bus bus
ZA IA mZ (1-m)Z IB ZB
IF
EA VF RF EB
VA VB
842780A2.CDR
Eq. 9-1
where
Eq. 9-2
where
d is the current distribution factor, which is a complex value
Substituting the second equation into the first equation and multiplying both sides by the complex conjugate of IAF,
Eq. 9-3
where
* denotes complex conjugate
Assuming the system is homogeneous, d is then a real number. The fault resistance does not have any imaginary part. The
preceding equation solved for the unknown m yields the following fault location algorithm:
Eq. 9-4
where
Im( ) stands for the imaginary part of a complex number
Depending on the fault type, appropriate voltage and current signals are selected from the phase quantities before
applying the preceding equation (the superscripts denote phases, the subscripts denote stations).
For AG faults:
Eq. 9-5
For BG faults:
Eq. 9-6
For CG faults:
Eq. 9-7
Eq. 9-8
9 Eq. 9-9
Eq. 9-10
where K0 is the zero sequence compensation factor (for the first six equations)
Z0M is the mutual zero sequence impedance
I0M = IG/3 and IG is the ground current of the adjacent line. The I0M compensation term is applied for the entirely parallel
line.
For ABC faults, all three AB, BC, and CA loops are analyzed and the final result is selected based upon consistency of the
results.
The element calculates the distance to the fault (with m in miles or kilometers) and the phases involved in the fault.
The relay allows locating faults from delta-connected VTs. If the FAULT REPORT 1 VT SUBSTITUTION setting is set to “None,”
and the VTs are connected in wye, the fault location is performed based on the actual phase to ground voltages. If the VTs
are connected in delta, fault location is suspended.
If the FAULT REPORT 1 VT SUBSTITUTION setting value is “V0” and the VTs are connected in a wye configuration, the fault
location is performed based on the actual phase to ground voltages. If the VTs are connected in a delta configuration, fault
location is performed based on the delta voltages and externally supplied neutral voltage:
Eq. 9-11
If the FAULT REPORT 1 VT SUBSTITUTION setting value is “I0” and the VTs are connected in a wye configuration, the fault
location is performed based on the actual phase to ground voltages. If the VTs are connected in a delta configuration, fault
location is performed based on the delta voltages and zero-sequence voltage approximated based on the zero-sequence
current:
Eq. 9-12
where ZSYS0 is the equivalent zero-sequence impedance behind the relay as entered under the fault report setting menu.
SETTINGS
FAULT REPORT 1 Z1
MAG:
FAULT REPORT 1 Z1
ANGLE:
FAULT REPORT 1 Z0
MAG:
FAULT REPORT 1 Z0
ANGLE:
FAULT REPORT 1
LENGTH UNITS:
FAULT REPORT 1
LENGTH:
SHOT # FROM
AUTO RECLOSURE
859748A1.CDR
Maintenance
This chapter outlines monitoring, maintenance, repair, storage, and disposal of the hardware and software.
10.1 Monitoring
Devices and data can be monitored.
The first row in the figure shows that Contact Output 1 operation is being monitored. Its Modbus address is CAFA. The
actual value read from the device is 0, which means that it is off.
The second row in the figure shows the Contact Output 1 Name. It has a Modbus address of CAF0 and a default value of
"Cont Op 1." None of Selection column settings render this value because they present the information based on
numbering systems.
Figure 10-2: Modbus Analyzer used to monitor actual values on a UR
Address (HEX) — Modbus address in hexadecimal. See the Modbus memory map in the UR Family Communications Guide
or in the web interface (enter IP address of UR device in a web browser).
Modbus Type
Actual Value — To read the data in the UR device
Setting — To read a setting in the UR device
Coil — To read a command in the UR device
# of — Element, input, or output to read. An example is 1 for Contact Output 1.
Selection (examples demonstrate various ways to represent 0)
Hex — A decimal numbering system based on 16 possible values, from 0 to 9 and A to F. An example is 0x0000.
Char — A single unicode character, such as C. An example is 0.
Int — A 32-bit number, either positive or negative. An example is 0.
UInt — Unsigned 32-bit integer, which means that it cannot be negative but can be twice as large as a signed integer. An
example is 0.
Long — A 64-bit number, either positive or negative. An example is 0.
ULong — Unsigned 64-bit number, which means that it cannot be negative but can be twice as large as a signed 64-bit
number. An example is 0.
Float — A numbering system with no fixed number of digits before or after the decimal point. An example is 0.000000.
Binary — A numbering system using 0 and 1. An example is 0000-0000-0000-0000.
10
To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized
state once per year, for one hour continuously.
5. Click the Read File button. The file is saved to the destination folder. The EnerVista window remains open to download
additional files.
Do not unplug the USB drive while copying is in progress, else the USB drive can be compromised.
4. When done, to exit unplug the USB drive or press the ESCAPE pushbutton.
0 = None
1 = Keypad
2 = Front port
3 = COM1 (not used)
4 = COM2 (RS485)
5 = Ethernet
GE recommends converting settings in firmware steps, for example when converting from 6.0 to 7.4x, convert first to
7.0 then 7.4 in order to follow embedded conversion rules and keep settings.
The settings convert and a report generates.
Figure 10-5: Upgrade settings
4. Review the conversion report. The values of all settings that have been defaulted during conversion are not listed in
the conversion report; to find the value of a setting before conversion, inspect the device backup file made before
conversion.
In the example shown here, settings have been reset to factory defaults and several settings are new in firmware
version 7.6 under Settings > System Setup > Switches and Breakers.
Figure 10-6: Conversion report
5. Change settings in the new file, for example by looking at the original file.
6. Write the converted file to the device, for example by dragging and dropping from the Offline Window to the Online
Window.
7. Check settings and operation.
10
10
There are two ways to compare devices: devices in the Offline area or between Online and Offline devices.
To compare settings of two devices in the Offline Window area:
1. Right-click a first device in the Offline Window area and select Compare Two Devices.
2. In the window that opens, select a second device and click the Receive button. The file generates and the number of
differences displays.
3. To save the report, click File > Save As, select the TXT, PDF, or CSV format from the drop-down list, and enter a name
for the file.
10 UR device settings can be saved in a backup URS file using the EnerVista UR Setup software. The URS file is the standard
UR settings file. For an introduction to settings files in the URS format, see the beginning of the Interfaces chapter.
When the IEC 61850 option is present, the settings can be saved alternatively in a backup IID file either using the EnerVista
UR Setup software in online mode or by using any of the supported file transfer protocols. The IID file is one of several IEC
61850 Substation Configuration Language (SCL) file types; see the IEC 61850 chapter in the UR Series Communications
Guide for an introduction to SCL.
"TBD" displays when a setting in a modeled element is configured with a non-modeled operand. For example, Phase IOC is
modeled in a firmware release, while the LED operands are not modeled. If the block setting of the Phase IOC is configured
with LED operands, its displays as TBD in IID and CID files, the web interface, or in an MMS client.
The options that display in the EnerVista software when right-clicking depend on device options.
Preferences are set in the File > Preferences > IEC 61850 menu. There are two options as follows:
• Preserve custom attributes when importing SCD/CID files — Applies to the Add Device to Offline Window option.
When enabled, the IID file also is to be copied to the computer. The IID file that is retrieved from the relay is therefore
assumed to be in synchronization with the resulting .urs file, and in fact in this situation the IID file on the computer is
a copy of the IID file that was read from the online device. When disabled, the IID file on the computer is to be left
unchanged. The location of the IID file is C:\ProgramData\GE Power Management\urpc\Offline, for example.
• Do not update IID file when updating SCL files — When enabled (default), an IID file is not to be created on the
computer and if one is already present there, it is neither removed nor updated. Have this option enabled when you
want to keep the IID file from the UR device instead of from another tool. The location of the file is C:\ProgramData\GE
Power Management\urpc\Offline, for example.
An Environment backup stores a list of sites and devices in the Online and Offline Window areas. Settings files are not
contained within the environment file. If a settings file is moved, renamed, or deleted after the backup, it is removed from
the Offline Window during the restore.
To create a new settings file in the URS format in EnerVista Offline Window:
1. In EnerVista, right-click in the Offline Window area and select New Device. A window opens.
2. Change the file name at the end of the Path field, keeping the .urs extension.
3. From the Associate File with Device drop-down list, select the UR device. Other fields complete automatically.
Otherwise, when you do not select a device from the drop-down list, all fields need to be completed manually and
only devices that match the entered order code and version display in the list.
4. The Serial # Lock field is the serial number of the intended device. It ensures that the settings file is sent only to the
specific relay that matches the serial number.
5. Click the OK button to create the .urs file in the Offline Window area.
No file is generated. The IID file on the computer is copied to the location specified.
3. If the Do not update IID file when updating SCL files preference is enabled under File > Preferences > IEC 61850,
then a message displays to that effect. This means that there is no IID file available on the computer to be copied, so
a new one is generated.
10
3. Two prompts are possible, first that the URS file does not include the complete IEC 61850 configuration and that it
needs to be recreated if you continue. This means that the URS file is from UR version 7.30 or higher, has the IEC 61850
software option in the order code, but any IEC 61850 content will be compromised and will need to be configured.
Second, a message can display that the URS file is part of a device folder and to use the device’s CID file. This means
that the URS file is from UR version 7.3 or higher, has the IEC 61850 software option in the order code, and is part of the
device folder. The user is trying to add a URS file from inside a device’s folder. Instead, the user needs to use the CID file
from the device folder.
These messages display because the roles of the protection engineer and network engineer can be separate. The
former can require a URS file, while the latter can require stored Modbus settings and protection schemes. 10
4. Navigate to and select the file with .cid extension. When prompted, enter a file name to give to an intermediate URS
file. The URS file is added to the Offline Window area.
5. Drag the imported file in the Offline Window to the device in the Online Window. Note that the RELAY SETTINGS value
also is written to a device, and the accepting relay is put into "Programmed" or "Not Programmed" mode as
configured in the offline file.
6. Manually copy the remaining settings, outlined as follows.
The field-programmable gate array (FPGA) can be upgraded under Maintenance > Update FPGA when the device
is connected via serial cable and the firmware revision is 7.0 or higher.
Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (that is, default
values, minimum/maximum values, data type, and item size) can change slightly from version to version of
firmware. The addresses are rearranged when new features are added or existing features are enhanced or
modified. The EEPROM DATA ERROR message displayed after upgrading/downgrading the firmware is a resettable,
self-test message intended to inform users that the Modbus addresses have changed with the upgraded firmware.
This message does not signal any problems when appearing after firmware upgrades.
Withdraw or insert a module only when control power has been removed from the unit, and be
sure to insert only the correct module type into a slot, else personal injury, damage to the unit or
connected equipment, or undesired operation can result.
To avoid damage to the equipment, use proper electrostatic discharge protection (for example, a
static strap) when coming in contact with modules while the relay is energized.
The following procedure can be used for the Rev. 1 and Rev. 2 enhanced front panels, with Rev. 1 is documented here. The
Rev. 2 enhanced horizontal front panel introduced starting November 2017 uses a screw to close it and internal hinge
screws as per the graphical front panel.
To remove an enhanced or basic front panel:
1. In the EnerVista software or on the front panel, access Settings > Product Setup > Communications > Network and
record the IP address and subnet mask of the port(s) being used. Record the gateway address under Default IPv4
Route.
2.
3.
Turn off power to the unit. Hot-swapping of the front panel is not supported.
For an enhanced front panel, loosen the thumb screw and open slightly the front panel.
10
For a basic front panel, lift up the black plastic latch on the right side of the front panel and open slightly the front
panel.
Figure 10-12: Loosen thumb screw on enhanced front panel to open
4. With a Phillips screwdriver, unscrew and remove the mounting bracket on the right side of the unit. The bracket for the
enhanced front panel looks similar to that for the graphical front panel, but they are not the same.
10
Figure 10-14: Remove enhanced front panel mounting bracket on right side
Figure 10-15: Remove basic front panel mounting bracket on right side
5. Open the front panel. Unplug or unscrew the grey ground cable from the front panel. Unplug the RJ45 connector from
the CPU module in the second slot on the left.
10
6. Unscrew and remove the mounting bracket with the front panel from the left side.
Figure 10-17: Unscrew enhanced front panel mounting bracket on left side
Figure 10-18: Unscrew basic front panel mounting bracket on left side
10
(note riveted hinges with red arrows - cannot replace this front panel)
2. Screw the right mounting bracket to the right side of the relay. 10
3. Attach the graphical front panel hinge to the left mounting bracket using the nuts provided.
Figure 10-21: Attach to left mounting bracket inside relay
4. Close the front panel without tightening the screw to the mounting bracket.
5. Optionally remove the protective plastic film on the graphical front panel. It is normally peeled off, but also can be left
on.
The graphical front panel has been installed but not connected.
10
2. At the front of the relay, insert the new CPU module in the second slot. The new CPU has two connection slots on the
front. Ensure that the RS485 connector and the black cover plate are not on the back of the CPU module before sliding
the module into the front of the relay.
Figure 10-23: Rear of a CPU module before insertion without RS485 connector or cover plate
10
3. Once the module is in place, connect the graphical front panel to the CPU module (ground and upper connector) and
close the front panel. There are two connections possible on the front of the CPU module: upper for the graphical front
panel and lower for the enhanced and basic front panels. The upper connection is black with holes, similar to the
cover, so it is difficult to see.
Figure 10-24: Connect graphical front panel to top connection on CPU module
4. Tighten the embedded screw on the right side of the graphical front panel to the mounting bracket.
Figure 10-25: Screw to attach graphical front panel to mounting bracket
5. At the back of the CPU module, attach the new black cover plate to the back of the relay, then connect the new RS485
connector.
10 6.
Insert the silver SFP connector(s) at the back of the CPU module, then connect any Ethernet connection(s).
Power up the relay. If the graphical front panel does not power up immediately, disconnect power, open the front
panel, then check that the graphical front panel is plugged into the upper connection, not the lower silver connection
on the CPU module.
Withdraw or insert a module only when control power has been removed from the unit, and be
sure to insert only the correct module type into a slot, else personal injury, damage to the unit or
connected equipment, or undesired operation can result.
To avoid damage to the equipment, use proper electrostatic discharge protection (for example, a
static strap) when coming in contact with modules while the relay is energized.
The relay, being modular in design, allows for the withdrawal and insertion of modules. Replace modules only with like
modules in their original factory configured slots.
Two procedures follow: replace a module with the same module, and upgrade a module.
To replace a module with the same module:
1. Open the enhanced front panel to the left once the thumb screw has been removed. This allows for easy access of the
modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and
allows easy access to all modules in the F35.
10
Figure 10-26: Modules inside relay with front cover open (enhanced front panel)
The basic front panel can be opened to the left once the black plastic sliding latch on the right side has been pushed
up, as shown below.
Figure 10-27: Removing module (basic front panel)
2. With power to the unit off, disconnect individually the connections at the front and back of the module before
removing the module from the chassis.
For any Process Card/process bus module in slot H for use with a HardFiber Brick, also remove the two screws at the
back that attach the module to the chassis.
3. To properly remove a module, pull simultaneously the ejector/inserter clips, located at the top and bottom of the
module. Record the original location of the module to ensure that the same or replacement module is inserted into the
correct slot. While modules with current input provide automatic shorting of external CT circuits, for CT/VT modules it
is recommended to short/isolate external circuits accordingly for maximum safety.
4. To properly insert a module, ensure that the correct module type is inserted into the correct slot position. The ejector/
inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module
is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the clips
simultaneously. When the clips have locked into position, the module is fully inserted.
When adding a module (versus replacing a module), check that settings have not changed. Depending on the
module, settings can reset to default values.
10
The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with old
CPUs. In the event that there is a mismatch between the CPU and CT/VT module, the relay does not function and a
DSP ERROR or HARDWARE MISMATCH error displays.
An upgrade example is replacing the CPU module with a more recent one, such as swapping 9G/9H/9N with 9T/9U/9V/9W.
A power supply module upgrade does not affect an order code.
To upgrade a module:
1. Back up settings by sending the device to the Offline Window area. Convert the settings to the new order code by
right-clicking in the Offline Window area. Replace the module as outlined in the previous procedure. In the Online
Window area, reset all settings to factory defaults and read the new order code from the device using Commands >
Relay Maintenance > Update Order Code. Send the saved settings from the Offline Window area to the online device.
Refresh the order code in the Device Setup window and set the device to "Programmed" under Settings > Product
Setup > Installation.
10.12 Battery
A battery powers the real time clock on startup of the device.
When required, the battery can be replaced. The battery type is 3 V cylindrical.
The power supply module contains the battery. The power supply modules were upgraded in 2014 to SH/SL from RH/RL,
but the order code when purchasing a UR with redundant power supply remained as RH/RL so that customers can
continue to use the same order codes. The order code can read RH or RL, while the module inside the unit reads SH or SL.
The order code for replacement redundant power supply modules was changed to SH/SL.
To avoid injury, ensure that the unit has been powered off for a minimum of three minutes before
replacing the battery.
Risk of fire if battery is replaced with incorrect type or polarity.
To replace the battery:
1. Turn off the power to the unit.
2. Wait a minimum of three minutes to ensure that there is no power to the battery.
3. As outlined in the previous section, open the unit by sliding up the plastic latch on the right side of the front panel
(basic front panel) or unscrewing the panel (enhanced front panel).
4. For the basic front panel, it needs to be removed in order to access the power supply module, which is typically in the
first slot on the left side and blocked by the hinge of the front panel. To remove the front panel, unscrew the bracket on
the left side of the unit.
5. Remove the power supply module by simultaneously pulling the ejector clips at the top and bottom of the module and
sliding it out.
6. Unscrew all four screws (not three) that attach the metal cover to the module. The fourth screw is at the back end of
the module, on the opposite side from the clips, beside the white electronics part (see figure).
7. Slide the metal cover away from the clips about 0.5 cm (1/8 inch) and remove the cover.
8. Unclip the black plastic holder that keeps the battery in place. The plastic clips into the socket at the bottom on both
sides—pull the plastic away from the battery. Use a flat-head screwdriver if you cannot unclip the plastic with your
fingers.
9. Replace the battery with the identical make and model. For example, do not use a rechargeable battery. Observe the
+ and - polarity of the battery and replace it with the same polarity as marked on the battery holder. 10
10. Reinstall the battery holder and the metal cover, and reinsert the power supply module into the unit.
11. Power on the unit.
12. Dispose of the old battery as outlined in the next section.
10
10
10
10.14 Repairs
The battery and modules inside the case can be replaced without return of the device to the factory. The firmware and
software can be upgraded without return of the device to the factory.
Fuses in the power supply module are not field-replaceable.
Files can be requested for use by technical support staff, for example the Service Report (click the icon in the software or
connect a USB drive to the graphical front panel) or under Maintenance > Retrieve File, as outlined elsewhere in this
document.
For issues not solved by troubleshooting, the process to return the device to the factory for repair is as follows:
• Contact a GE Grid Solutions Technical Support Center. Contact information is found in the first chapter.
• Obtain a Return Materials Authorization (RMA) number from the Technical Support Center.
• Verify that the RMA and Commercial Invoice received have the correct information.
• Tightly pack the unit in a box with bubble wrap, foam material, or styrofoam inserts or packaging peanuts to cushion
the item(s). You may also use double boxing whereby you place the box in a larger box that contains at least 5 cm of
cushioning material.
• Ship the unit by courier or freight forwarder, along with the Commercial Invoice and RMA, to the factory.
GE GRID SOLUTIONS
650 MARKLAND STREET
MARKHAM, ONTARIO
CANADA L6C 0M1
ATTN: SERVICE DEPT.
RMA# : ______________
Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty.
• Fax a copy of the shipping information to the GE Grid Solutions service department in Canada at +1 905 927 5098.
Use the detailed return procedure outlined at
https://www.gegridsolutions.com/multilin/support/ret_proc.htm
The current warranty and return information are outlined at
https://www.gegridsolutions.com/multilin/warranty.htm
10.15 Storage
Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow the storage temperature range
outlined in the Specifications.
10
To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized
state once per year, for one hour continuously.
10.16 Disposal
Other than the battery, there are no special requirements for disposal of the unit at the end its service life. For customers
located in the European Union, dispose of the battery as outlined earlier. To prevent non-intended use of the unit, remove
the modules, dismantle the unit, and recycle the metal when possible.
10
10
Appendices
FlexAnalog operands
A
6283 SRC 3 Ib Mag Amps Source 3 phase B current magnitude
6285 SRC 3 Ib Angle Degrees Source 3 phase B current angle
6286 SRC 3 Ic Mag Amps Source 3 phase C current magnitude
6288 SRC 3 Ic Angle Degrees Source 3 phase C current angle
6289 SRC 3 In Mag Amps Source 3 neutral current magnitude
6291 SRC 3 In Angle Degrees Source 3 neutral current angle
6292 SRC 3 Ig RMS Amps Source 3 ground current RMS
6294 SRC 3 Ig Mag Amps Source 3 ground current magnitude
6296 SRC 3 Ig Angle Degrees Source 3 ground current angle
6297 SRC 3 I_0 Mag Amps Source 3 zero-sequence current magnitude
6299 SRC 3 I_0 Angle Degrees Source 3 zero-sequence current angle
6300 SRC 3 I_1 Mag Amps Source 3 positive-sequence current magnitude
6302 SRC 3 I_1 Angle Degrees Source 3 positive-sequence current angle
6303 SRC 3 I_2 Mag Amps Source 3 negative-sequence current magnitude
6305 SRC 3 I_2 Angle Degrees Source 3 negative-sequence current angle
6306 SRC 3 Igd Mag Amps Source 3 differential ground current magnitude
6308 SRC 3 Igd Angle Degrees Source 3 differential ground current angle
6336 SRC 4 Ia RMS Amps Source 4 phase A current RMS
6338 SRC 4 Ib RMS Amps Source 4 phase B current RMS
6340 SRC 4 Ic RMS Amps Source 4 phase C current RMS
6342 SRC 4 In RMS Amps Source 4 neutral current RMS
6344 SRC 4 Ia Mag Amps Source 4 phase A current magnitude
6346 SRC 4 Ia Angle Degrees Source 4 phase A current angle
6347 SRC 4 Ib Mag Amps Source 4 phase B current magnitude
6349 SRC 4 Ib Angle Degrees Source 4 phase B current angle
6350 SRC 4 Ic Mag Amps Source 4 phase C current magnitude
6352 SRC 4 Ic Angle Degrees Source 4 phase C current angle
6353 SRC 4 In Mag Amps Source 4 neutral current magnitude
6355 SRC 4 In Angle Degrees Source 4 neutral current angle
6356 SRC 4 Ig RMS Amps Source 4 ground current RMS
6358 SRC 4 Ig Mag Amps Source 4 ground current magnitude
6360 SRC 4 Ig Angle Degrees Source 4 ground current angle
6361 SRC 4 I_0 Mag Amps Source 4 zero-sequence current magnitude
6363 SRC 4 I_0 Angle Degrees Source 4 zero-sequence current angle
6364 SRC 4 I_1 Mag Amps Source 4 positive-sequence current magnitude
6366 SRC 4 I_1 Angle Degrees Source 4 positive-sequence current angle
6367 SRC 4 I_2 Mag Amps Source 4 negative-sequence current magnitude
6369 SRC 4 I_2 Angle Degrees Source 4 negative-sequence current angle
6370 SRC 4 Igd Mag Amps Source 4 differential ground current magnitude
6372 SRC 4 Igd Angle Degrees Source 4 differential ground current angle
6400 SRC 5 Ia RMS Amps Source 5 phase A current RMS
6402 SRC 5 Ib RMS Amps Source 5 phase B current RMS
6404 SRC 5 Ic RMS Amps Source 5 phase C current RMS
6406 SRC 5 In RMS Amps Source 5 neutral current RMS
6408 SRC 5 Ia Mag Amps Source 5 phase A current magnitude
6410 SRC 5 Ia Angle Degrees Source 5 phase A current angle
6411 SRC 5 Ib Mag Amps Source 5 phase B current magnitude
A
6670 SRC 1 Vcg Angle Degrees Source 1 phase CG voltage angle
6671 SRC 1 Vab RMS Volts Source 1 phase AB voltage RMS
6673 SRC 1 Vbc RMS Volts Source 1 phase BC voltage RMS
6675 SRC 1 Vca RMS Volts Source 1 phase CA voltage RMS
6677 SRC 1 Vab Mag Volts Source 1 phase AB voltage magnitude
6679 SRC 1 Vab Angle Degrees Source 1 phase AB voltage angle
6680 SRC 1 Vbc Mag Volts Source 1 phase BC voltage magnitude
6682 SRC 1 Vbc Angle Degrees Source 1 phase BC voltage angle
6683 SRC 1 Vca Mag Volts Source 1 phase CA voltage magnitude
6685 SRC 1 Vca Angle Degrees Source 1 phase CA voltage angle
6686 SRC 1 Vx RMS Volts Source 1 auxiliary voltage RMS
6688 SRC 1 Vx Mag Volts Source 1 auxiliary voltage magnitude
6690 SRC 1 Vx Angle Degrees Source 1 auxiliary voltage angle
6691 SRC 1 V_0 Mag Volts Source 1 zero-sequence voltage magnitude
6693 SRC 1 V_0 Angle Degrees Source 1 zero-sequence voltage angle
6694 SRC 1 V_1 Mag Volts Source 1 positive-sequence voltage magnitude
6696 SRC 1 V_1 Angle Degrees Source 1 positive-sequence voltage angle
6697 SRC 1 V_2 Mag Volts Source 1 negative-sequence voltage magnitude
6699 SRC 1 V_2 Angle Degrees Source 1 negative-sequence voltage angle
6720 SRC 2 Vag RMS Volts Source 2 phase AG voltage RMS
6722 SRC 2 Vbg RMS Volts Source 2 phase BG voltage RMS
6724 SRC 2 Vcg RMS Volts Source 2 phase CG voltage RMS
6726 SRC 2 Vag Mag Volts Source 2 phase AG voltage magnitude
6728 SRC 2 Vag Angle Degrees Source 2 phase AG voltage angle
6729 SRC 2 Vbg Mag Volts Source 2 phase BG voltage magnitude
6731 SRC 2 Vbg Angle Degrees Source 2 phase BG voltage angle
6732 SRC 2 Vcg Mag Volts Source 2 phase CG voltage magnitude
6734 SRC 2 Vcg Angle Degrees Source 2 phase CG voltage angle
6735 SRC 2 Vab RMS Volts Source 2 phase AB voltage RMS
6737 SRC 2 Vbc RMS Volts Source 2 phase BC voltage RMS
6739 SRC 2 Vca RMS Volts Source 2 phase CA voltage RMS
6741 SRC 2 Vab Mag Volts Source 2 phase AB voltage magnitude
6743 SRC 2 Vab Angle Degrees Source 2 phase AB voltage angle
6744 SRC 2 Vbc Mag Volts Source 2 phase BC voltage magnitude
6746 SRC 2 Vbc Angle Degrees Source 2 phase BC voltage angle
6747 SRC 2 Vca Mag Volts Source 2 phase CA voltage magnitude
6749 SRC 2 Vca Angle Degrees Source 2 phase CA voltage angle
6750 SRC 2 Vx RMS Volts Source 2 auxiliary voltage RMS
6752 SRC 2 Vx Mag Volts Source 2 auxiliary voltage magnitude
6754 SRC 2 Vx Angle Degrees Source 2 auxiliary voltage angle
6755 SRC 2 V_0 Mag Volts Source 2 zero-sequence voltage magnitude
6757 SRC 2 V_0 Angle Degrees Source 2 zero-sequence voltage angle
6758 SRC 2 V_1 Mag Volts Source 2 positive-sequence voltage magnitude
6760 SRC 2 V_1 Angle Degrees Source 2 positive-sequence voltage angle
6761 SRC 2 V_2 Mag Volts Source 2 negative-sequence voltage magnitude
6763 SRC 2 V_2 Angle Degrees Source 2 negative-sequence voltage angle
6784 SRC 3 Vag RMS Volts Source 3 phase AG voltage RMS
A
6883 SRC 4 V_0 Mag Volts Source 4 zero-sequence voltage magnitude
6885 SRC 4 V_0 Angle Degrees Source 4 zero-sequence voltage angle
6886 SRC 4 V_1 Mag Volts Source 4 positive-sequence voltage magnitude
6888 SRC 4 V_1 Angle Degrees Source 4 positive-sequence voltage angle
6889 SRC 4 V_2 Mag Volts Source 4 negative-sequence voltage magnitude
6891 SRC 4 V_2 Angle Degrees Source 4 negative-sequence voltage angle
6912 SRC 5 Vag RMS Volts Source 5 phase AG voltage RMS
6914 SRC 5 Vbg RMS Volts Source 5 phase BG voltage RMS
6916 SRC 5 Vcg RMS Volts Source 5 phase CG voltage RMS
6918 SRC 5 Vag Mag Volts Source 5 phase AG voltage magnitude
6920 SRC 5 Vag Angle Degrees Source 5 phase AG voltage angle
6921 SRC 5 Vbg Mag Volts Source 5 phase BG voltage magnitude
6923 SRC 5 Vbg Angle Degrees Source 5 phase BG voltage angle
6924 SRC 5 Vcg Mag Volts Source 5 phase CG voltage magnitude
6926 SRC 5 Vcg Angle Degrees Source 5 phase CG voltage angle
6927 SRC 5 Vab RMS Volts Source 5 phase AB voltage RMS
6929 SRC 5 Vbc RMS Volts Source 5 phase BC voltage RMS
6931 SRC 5 Vca RMS Volts Source 5 phase CA voltage RMS
6933 SRC 5 Vab Mag Volts Source 5 phase AB voltage magnitude
6935 SRC 5 Vab Angle Degrees Source 5 phase AB voltage angle
6936 SRC 5 Vbc Mag Volts Source 5 phase BC voltage magnitude
6938 SRC 5 Vbc Angle Degrees Source 5 phase BC voltage angle
6939 SRC 5 Vca Mag Volts Source 5 phase CA voltage magnitude
6941 SRC 5 Vca Angle Degrees Source 5 phase CA voltage angle
6942 SRC 5 Vx RMS Volts Source 5 auxiliary voltage RMS
6944 SRC 5 Vx Mag Volts Source 5 auxiliary voltage magnitude
6946 SRC 5 Vx Angle Degrees Source 5 auxiliary voltage angle
6947 SRC 5 V_0 Mag Volts Source 5 zero-sequence voltage magnitude
6949 SRC 5 V_0 Angle Degrees Source 5 zero-sequence voltage angle
6950 SRC 5 V_1 Mag Volts Source 5 positive-sequence voltage magnitude
6952 SRC 5 V_1 Angle Degrees Source 5 positive-sequence voltage angle
6953 SRC 5 V_2 Mag Volts Source 5 negative-sequence voltage magnitude
6955 SRC 5 V_2 Angle Degrees Source 5 negative-sequence voltage angle
6976 SRC 6 Vag RMS Volts Source 6 phase AG voltage RMS
6978 SRC 6 Vbg RMS Volts Source 6 phase BG voltage RMS
6980 SRC 6 Vcg RMS Volts Source 6 phase CG voltage RMS
6982 SRC 6 Vag Mag Volts Source 6 phase AG voltage magnitude
6984 SRC 6 Vag Angle Degrees Source 6 phase AG voltage angle
6985 SRC 6 Vbg Mag Volts Source 6 phase BG voltage magnitude
6987 SRC 6 Vbg Angle Degrees Source 6 phase BG voltage angle
6988 SRC 6 Vcg Mag Volts Source 6 phase CG voltage magnitude
6990 SRC 6 Vcg Angle Degrees Source 6 phase CG voltage angle
6991 SRC 6 Vab RMS Volts Source 6 phase AB voltage RMS
6993 SRC 6 Vbc RMS Volts Source 6 phase BC voltage RMS
6995 SRC 6 Vca RMS Volts Source 6 phase CA voltage RMS
6997 SRC 6 Vab Mag Volts Source 6 phase AB voltage magnitude
6999 SRC 6 Vab Angle Degrees Source 6 phase AB voltage angle
A
7236 SRC 3 Pb Watts Source 3 phase B real power
7238 SRC 3 Pc Watts Source 3 phase C real power
7240 SRC 3 Q Vars Source 3 three-phase reactive power
7242 SRC 3 Qa Vars Source 3 phase A reactive power
7244 SRC 3 Qb Vars Source 3 phase B reactive power
7246 SRC 3 Qc Vars Source 3 phase C reactive power
7248 SRC 3 S VA Source 3 three-phase apparent power
7250 SRC 3 Sa VA Source 3 phase A apparent power
7252 SRC 3 Sb VA Source 3 phase B apparent power
7254 SRC 3 Sc VA Source 3 phase C apparent power
7256 SRC 3 PF --- Source 3 three-phase power factor
7257 SRC 3 Phase A PF --- Source 3 phase A power factor
7258 SRC 3 Phase B PF --- Source 3 phase B power factor
7259 SRC 3 Phase C PF --- Source 3 phase C power factor
7264 SRC 4 P Watts Source 4 three-phase real power
7266 SRC 4 Pa Watts Source 4 phase A real power
7268 SRC 4 Pb Watts Source 4 phase B real power
7270 SRC 4 Pc Watts Source 4 phase C real power
7272 SRC 4 Q Vars Source 4 three-phase reactive power
7274 SRC 4 Qa Vars Source 4 phase A reactive power
7276 SRC 4 Qb Vars Source 4 phase B reactive power
7278 SRC 4 Qc Vars Source 4 phase C reactive power
7280 SRC 4 S VA Source 4 three-phase apparent power
7282 SRC 4 Sa VA Source 4 phase A apparent power
7284 SRC 4 Sb VA Source 4 phase B apparent power
7286 SRC 4 Sc VA Source 4 phase C apparent power
7288 SRC 4 PF --- Source 4 three-phase power factor
7289 SRC 4 Phase A PF --- Source 4 phase A power factor
7290 SRC 4 Phase B PF --- Source 4 phase B power factor
7291 SRC 4 Phase C PF --- Source 4 phase C power factor
7296 SRC 5 P Watts Source 5 three-phase real power
7298 SRC 5 Pa Watts Source 5 phase A real power
7300 SRC 5 Pb Watts Source 5 phase B real power
7302 SRC 5 Pc Watts Source 5 phase C real power
7304 SRC 5 Q Vars Source 5 three-phase reactive power
7306 SRC 5 Qa Vars Source 5 phase A reactive power
7308 SRC 5 Qb Vars Source 5 phase B reactive power
7310 SRC 5 Qc Vars Source 5 phase C reactive power
7312 SRC 5 S VA Source 5 three-phase apparent power
7314 SRC 5 Sa VA Source 5 phase A apparent power
7316 SRC 5 Sb VA Source 5 phase B apparent power
7318 SRC 5 Sc VA Source 5 phase C apparent power
7320 SRC 5 PF --- Source 5 three-phase power factor
7321 SRC 5 Phase A PF --- Source 5 phase A power factor
7322 SRC 5 Phase B PF --- Source 5 phase B power factor
7323 SRC 5 Phase C PF --- Source 5 phase C power factor
7328 SRC 6 P Watts Source 6 three-phase real power
A
7684 SRC 1 Demand Ic Amps Source 1 phase C current demand
7686 SRC 1 Demand Watt Watts Source 1 real power demand
7688 SRC 1 Demand var Vars Source 1 reactive power demand
7690 SRC 1 Demand VA VA Source 1 apparent power demand
7696 SRC 2 Demand Ia Amps Source 2 phase A current demand
7698 SRC 2 Demand Ib Amps Source 2 phase B current demand
7700 SRC 2 Demand Ic Amps Source 2 phase C current demand
7702 SRC 2 Demand Watt Watts Source 2 real power demand
7704 SRC 2 Demand var Vars Source 2 reactive power demand
7706 SRC 2 Demand VA VA Source 2 apparent power demand
7712 SRC 3 Demand Ia Amps Source 3 phase A current demand
7714 SRC 3 Demand Ib Amps Source 3 phase B current demand
7716 SRC 3 Demand Ic Amps Source 3 phase C current demand
7718 SRC 3 Demand Watt Watts Source 3 real power demand
7720 SRC 3 Demand var Vars Source 3 reactive power demand
7722 SRC 3 Demand VA VA Source 3 apparent power demand
7728 SRC 4 Demand Ia Amps Source 4 phase A current demand
7730 SRC 4 Demand Ib Amps Source 4 phase B current demand
7732 SRC 4 Demand Ic Amps Source 4 phase C current demand
7734 SRC 4 Demand Watt Watts Source 4 real power demand
7736 SRC 4 Demand var Vars Source 4 reactive power demand
7738 SRC 4 Demand VA VA Source 4 apparent power demand
7744 SRC 5 Demand Ia Amps Source 5 phase A current demand
7746 SRC 5 Demand Ib Amps Source 5 phase B current demand
7748 SRC 5 Demand Ic Amps Source 5 phase C current demand
7750 SRC 5 Demand Watt Watts Source 5 real power demand
7752 SRC 5 Demand var Vars Source 5 reactive power demand
7754 SRC 5 Demand VA VA Source 5 apparent power demand
7760 SRC 6 Demand Ia Amps Source 6 phase A current demand
7762 SRC 6 Demand Ib Amps Source 6 phase B current demand
7764 SRC 6 Demand Ic Amps Source 6 phase C current demand
7766 SRC 6 Demand Watt Watts Source 6 real power demand
7768 SRC 6 Demand var Vars Source 6 reactive power demand
7770 SRC 6 Demand VA VA Source 6 apparent power demand
8064 SRC 1 Va THD % Source 1 phase A voltage total harmonic distortion (THD)
8065 SRC 1 Va Harm[2] % Source 1 phase A voltage second harmonic
8066 SRC 1 Va Harm[3] % Source 1 phase A voltage third harmonic
8067 SRC 1 Va Harm[4] % Source 1 phase A voltage fourth harmonic
8068 SRC 1 Va Harm[5] % Source 1 phase A voltage fifth harmonic
8069 SRC 1 Va Harm[6] % Source 1 phase A voltage sixth harmonic
8070 SRC 1 Va Harm[7] % Source 1 phase A voltage seventh harmonic
8071 SRC 1 Va Harm[8] % Source 1 phase A voltage eighth harmonic
8072 SRC 1 Va Harm[9] % Source 1 phase A voltage ninth harmonic
8073 SRC 1 Va Harm[10] % Source 1 phase A voltage tenth harmonic
8074 SRC 1 Va Harm[11] % Source 1 phase A voltage eleventh harmonic
8075 SRC 1 Va Harm[12] % Source 1 phase A voltage twelfth harmonic
8076 SRC 1 Va Harm[13] % Source 1 phase A voltage thirteenth harmonic
A
8124 SRC 1 Vc Harm[11] % Source 1 phase C voltage eleventh harmonic
8125 SRC 1 Vc Harm[12] % Source 1 phase C voltage twelfth harmonic
8126 SRC 1 Vc Harm[13] % Source 1 phase C voltage thirteenth harmonic
8127 SRC 1 Vc Harm[14] % Source 1 phase C voltage fourteenth harmonic
8128 SRC 1 Vc Harm[15] % Source 1 phase C voltage fifteenth harmonic
8129 SRC 1 Vc Harm[16] % Source 1 phase C voltage sixteenth harmonic
8130 SRC 1 Vc Harm[17] % Source 1 phase C voltage seventeenth harmonic
8131 SRC 1 Vc Harm[18] % Source 1 phase C voltage eighteenth harmonic
8132 SRC 1 Vc Harm[19] % Source 1 phase C voltage nineteenth harmonic
8133 SRC 1 Vc Harm[20] % Source 1 phase C voltage twentieth harmonic
8134 SRC 1 Vc Harm[21] % Source 1 phase C voltage twenty-first harmonic
8135 SRC 1 Vc Harm[22] % Source 1 phase C voltage twenty-second harmonic
8136 SRC 1 Vc Harm[23] % Source 1 phase C voltage twenty-third harmonic
8137 SRC 1 Vc Harm[24] % Source 1 phase C voltage twenty-fourth harmonic
8138 SRC 1 Vc Harm[25] % Source 1 phase C voltage twenty-fifth harmonic
8139 SRC 2 Va THD % Source 2 phase A voltage total harmonic distortion (THD)
8140 SRC 2 Va Harm[2] % Source 2 phase A voltage second harmonic
8141 SRC 2 Va Harm[3] % Source 2 phase A voltage third harmonic
8142 SRC 2 Va Harm[4] % Source 2 phase A voltage fourth harmonic
8143 SRC 2 Va Harm[5] % Source 2 phase A voltage fifth harmonic
8144 SRC 2 Va Harm[6] % Source 2 phase A voltage sixth harmonic
8145 SRC 2 Va Harm[7] % Source 2 phase A voltage seventh harmonic
8146 SRC 2 Va Harm[8] % Source 2 phase A voltage eighth harmonic
8147 SRC 2 Va Harm[9] % Source 2 phase A voltage ninth harmonic
8148 SRC 2 Va Harm[10] % Source 2 phase A voltage tenth harmonic
8149 SRC 2 Va Harm[11] % Source 2 phase A voltage eleventh harmonic
8150 SRC 2 Va Harm[12] % Source 2 phase A voltage twelfth harmonic
8151 SRC 2 Va Harm[13] % Source 2 phase A voltage thirteenth harmonic
8152 SRC 2 Va Harm[14] % Source 2 phase A voltage fourteenth harmonic
8153 SRC 2 Va Harm[15] % Source 2 phase A voltage fifteenth harmonic
8154 SRC 2 Va Harm[16] % Source 2 phase A voltage sixteenth harmonic
8155 SRC 2 Va Harm[17] % Source 2 phase A voltage seventeenth harmonic
8156 SRC 2 Va Harm[18] % Source 2 phase A voltage eighteenth harmonic
8157 SRC 2 Va Harm[19] % Source 2 phase A voltage nineteenth harmonic
8158 SRC 2 Va Harm[20] % Source 2 phase A voltage twentieth harmonic
8159 SRC 2 Va Harm[21] % Source 2 phase A voltage twenty-first harmonic
8160 SRC 2 Va Harm[22] % Source 2 phase A voltage twenty-second harmonic
8161 SRC 2 Va Harm[23] % Source 2 phase A voltage twenty-third harmonic
8162 SRC 2 Va Harm[24] % Source 2 phase A voltage twenty-fourth harmonic
8163 SRC 2 Va Harm[25] % Source 2 phase A voltage twenty-fifth harmonic
8164 SRC 2 Vb THD % Source 2 phase B voltage total harmonic distortion (THD)
8165 SRC 2 Vb Harm[2] % Source 2 phase B voltage second harmonic
8166 SRC 2 Vb Harm[3] % Source 2 phase B voltage third harmonic
8167 SRC 2 Vb Harm[4] % Source 2 phase B voltage fourth harmonic
8168 SRC 2 Vb Harm[5] % Source 2 phase B voltage fifth harmonic
8169 SRC 2 Vb Harm[6] % Source 2 phase B voltage sixth harmonic
8170 SRC 2 Vb Harm[7] % Source 2 phase B voltage seventh harmonic
A
8218 SRC 3 Va Harm[5] % Source 3 phase A voltage fifth harmonic
8219 SRC 3 Va Harm[6] % Source 3 phase A voltage sixth harmonic
8220 SRC 3 Va Harm[7] % Source 3 phase A voltage seventh harmonic
8221 SRC 3 Va Harm[8] % Source 3 phase A voltage eighth harmonic
8222 SRC 3 Va Harm[9] % Source 3 phase A voltage ninth harmonic
8223 SRC 3 Va Harm[10] % Source 3 phase A voltage tenth harmonic
8224 SRC 3 Va Harm[11] % Source 3 phase A voltage eleventh harmonic
8225 SRC 3 Va Harm[12] % Source 3 phase A voltage twelfth harmonic
8226 SRC 3 Va Harm[13] % Source 3 phase A voltage thirteenth harmonic
8227 SRC 3 Va Harm[14] % Source 3 phase A voltage fourteenth harmonic
8228 SRC 3 Va Harm[15] % Source 3 phase A voltage fifteenth harmonic
8229 SRC 3 Va Harm[16] % Source 3 phase A voltage sixteenth harmonic
8230 SRC 3 Va Harm[17] % Source 3 phase A voltage seventeenth harmonic
8231 SRC 3 Va Harm[18] % Source 3 phase A voltage eighteenth harmonic
8232 SRC 3 Va Harm[19] % Source 3 phase A voltage nineteenth harmonic
8233 SRC 3 Va Harm[20] % Source 3 phase A voltage twentieth harmonic
8234 SRC 3 Va Harm[21] % Source 3 phase A voltage twenty-first harmonic
8235 SRC 3 Va Harm[22] % Source 3 phase A voltage twenty-second harmonic
8236 SRC 3 Va Harm[23] % Source 3 phase A voltage twenty-third harmonic
8237 SRC 3 Va Harm[24] % Source 3 phase A voltage twenty-fourth harmonic
8238 SRC 3 Va Harm[25] % Source 3 phase A voltage twenty-fifth harmonic
8239 SRC 3 Vb THD % Source 3 phase B voltage total harmonic distortion (THD)
8240 SRC 3 Vb Harm[2] % Source 3 phase B voltage second harmonic
8241 SRC 3 Vb Harm[3] % Source 3 phase B voltage third harmonic
8242 SRC 3 Vb Harm[4] % Source 3 phase B voltage fourth harmonic
8243 SRC 3 Vb Harm[5] % Source 3 phase B voltage fifth harmonic
8244 SRC 3 Vb Harm[6] % Source 3 phase B voltage sixth harmonic
8245 SRC 3 Vb Harm[7] % Source 3 phase B voltage seventh harmonic
8246 SRC 3 Vb Harm[8] % Source 3 phase B voltage eighth harmonic
8247 SRC 3 Vb Harm[9] % Source 3 phase B voltage ninth harmonic
8248 SRC 3 Vb Harm[10] % Source 3 phase B voltage tenth harmonic
8249 SRC 3 Vb Harm[11] % Source 3 phase B voltage eleventh harmonic
8250 SRC 3 Vb Harm[12] % Source 3 phase B voltage twelfth harmonic
8251 SRC 3 Vb Harm[13] % Source 3 phase B voltage thirteenth harmonic
8252 SRC 3 Vb Harm[14] % Source 3 phase B voltage fourteenth harmonic
8253 SRC 3 Vb Harm[15] % Source 3 phase B voltage fifteenth harmonic
8254 SRC 3 Vb Harm[16] % Source 3 phase B voltage sixteenth harmonic
8255 SRC 3 Vb Harm[17] % Source 3 phase B voltage seventeenth harmonic
8256 SRC 3 Vb Harm[18] % Source 3 phase B voltage eighteenth harmonic
8257 SRC 3 Vb Harm[19] % Source 3 phase B voltage nineteenth harmonic
8258 SRC 3 Vb Harm[20] % Source 3 phase B voltage twentieth harmonic
8259 SRC 3 Vb Harm[21] % Source 3 phase B voltage twenty-first harmonic
8260 SRC 3 Vb Harm[22] % Source 3 phase B voltage twenty-second harmonic
8261 SRC 3 Vb Harm[23] % Source 3 phase B voltage twenty-third harmonic
8262 SRC 3 Vb Harm[24] % Source 3 phase B voltage twenty-fourth harmonic
8263 SRC 3 Vb Harm[25] % Source 3 phase B voltage twenty-fifth harmonic
8264 SRC 3 Vc THD % Source 3 phase C voltage total harmonic distortion (THD)
A
8312 SRC 4 Va Harm[24] % Source 4 phase A voltage twenty-fourth harmonic
8313 SRC 4 Va Harm[25] % Source 4 phase A voltage twenty-fifth harmonic
8314 SRC 4 Vb THD % Source 4 phase B voltage total harmonic distortion (THD)
8315 SRC 4 Vb Harm[2] % Source 4 phase B voltage second harmonic
8316 SRC 4 Vb Harm[3] % Source 4 phase B voltage third harmonic
8317 SRC 4 Vb Harm[4] % Source 4 phase B voltage fourth harmonic
8318 SRC 4 Vb Harm[5] % Source 4 phase B voltage fifth harmonic
8319 SRC 4 Vb Harm[6] % Source 4 phase B voltage sixth harmonic
8320 SRC 4 Vb Harm[7] % Source 4 phase B voltage seventh harmonic
8321 SRC 4 Vb Harm[8] % Source 4 phase B voltage eighth harmonic
8322 SRC 4 Vb Harm[9] % Source 4 phase B voltage ninth harmonic
8323 SRC 4 Vb Harm[10] % Source 4 phase B voltage tenth harmonic
8324 SRC 4 Vb Harm[11] % Source 4 phase B voltage eleventh harmonic
8325 SRC 4 Vb Harm[12] % Source 4 phase B voltage twelfth harmonic
8326 SRC 4 Vb Harm[13] % Source 4 phase B voltage thirteenth harmonic
8327 SRC 4 Vb Harm[14] % Source 4 phase B voltage fourteenth harmonic
8328 SRC 4 Vb Harm[15] % Source 4 phase B voltage fifteenth harmonic
8329 SRC 4 Vb Harm[16] % Source 4 phase B voltage sixteenth harmonic
8330 SRC 4 Vb Harm[17] % Source 4 phase B voltage seventeenth harmonic
8331 SRC 4 Vb Harm[18] % Source 4 phase B voltage eighteenth harmonic
8332 SRC 4 Vb Harm[19] % Source 4 phase B voltage nineteenth harmonic
8333 SRC 4 Vb Harm[20] % Source 4 phase B voltage twentieth harmonic
8334 SRC 4 Vb Harm[21] % Source 4 phase B voltage twenty-first harmonic
8335 SRC 4 Vb Harm[22] % Source 4 phase B voltage twenty-second harmonic
8336 SRC 4 Vb Harm[23] % Source 4 phase B voltage twenty-third harmonic
8337 SRC 4 Vb Harm[24] % Source 4 phase B voltage twenty-fourth harmonic
8338 SRC 4 Vb Harm[25] % Source 4 phase B voltage twenty-fifth harmonic
8339 SRC 4 Vc THD % Source 4 phase C voltage total harmonic distortion (THD)
8340 SRC 4 Vc Harm[2] % Source 4 phase C voltage second harmonic
8341 SRC 4 Vc Harm[3] % Source 4 phase C voltage third harmonic
8342 SRC 4 Vc Harm[4] % Source 4 phase C voltage fourth harmonic
8343 SRC 4 Vc Harm[5] % Source 4 phase C voltage fifth harmonic
8344 SRC 4 Vc Harm[6] % Source 4 phase C voltage sixth harmonic
8345 SRC 4 Vc Harm[7] % Source 4 phase C voltage seventh harmonic
8346 SRC 4 Vc Harm[8] % Source 4 phase C voltage eighth harmonic
8347 SRC 4 Vc Harm[9] % Source 4 phase C voltage ninth harmonic
8348 SRC 4 Vc Harm[10] % Source 4 phase C voltage tenth harmonic
8349 SRC 4 Vc Harm[11] % Source 4 phase C voltage eleventh harmonic
8350 SRC 4 Vc Harm[12] % Source 4 phase C voltage twelfth harmonic
8351 SRC 4 Vc Harm[13] % Source 4 phase C voltage thirteenth harmonic
8352 SRC 4 Vc Harm[14] % Source 4 phase C voltage fourteenth harmonic
8353 SRC 4 Vc Harm[15] % Source 4 phase C voltage fifteenth harmonic
8354 SRC 4 Vc Harm[16] % Source 4 phase C voltage sixteenth harmonic
8355 SRC 4 Vc Harm[17] % Source 4 phase C voltage seventeenth harmonic
8356 SRC 4 Vc Harm[18] % Source 4 phase C voltage eighteenth harmonic
8357 SRC 4 Vc Harm[19] % Source 4 phase C voltage nineteenth harmonic
8358 SRC 4 Vc Harm[20] % Source 4 phase C voltage twentieth harmonic
A
8406 SRC 5 Vb Harm[18] % Source 5 phase B voltage eighteenth harmonic
8407 SRC 5 Vb Harm[19] % Source 5 phase B voltage nineteenth harmonic
8408 SRC 5 Vb Harm[20] % Source 5 phase B voltage twentieth harmonic
8409 SRC 5 Vb Harm[21] % Source 5 phase B voltage twenty-first harmonic
8410 SRC 5 Vb Harm[22] % Source 5 phase B voltage twenty-second harmonic
8411 SRC 5 Vb Harm[23] % Source 5 phase B voltage twenty-third harmonic
8412 SRC 5 Vb Harm[24] % Source 5 phase B voltage twenty-fourth harmonic
8413 SRC 5 Vb Harm[25] % Source 5 phase B voltage twenty-fifth harmonic
8414 SRC 5 Vc THD % Source 5 phase C voltage total harmonic distortion (THD)
8415 SRC 5 Vc Harm[2] % Source 5 phase C voltage second harmonic
8416 SRC 5 Vc Harm[3] % Source 5 phase C voltage third harmonic
8417 SRC 5 Vc Harm[4] % Source 5 phase C voltage fourth harmonic
8418 SRC 5 Vc Harm[5] % Source 5 phase C voltage fifth harmonic
8419 SRC 5 Vc Harm[6] % Source 5 phase C voltage sixth harmonic
8420 SRC 5 Vc Harm[7] % Source 5 phase C voltage seventh harmonic
8421 SRC 5 Vc Harm[8] % Source 5 phase C voltage eighth harmonic
8422 SRC 5 Vc Harm[9] % Source 5 phase C voltage ninth harmonic
8423 SRC 5 Vc Harm[10] % Source 5 phase C voltage tenth harmonic
8424 SRC 5 Vc Harm[11] % Source 5 phase C voltage eleventh harmonic
8425 SRC 5 Vc Harm[12] % Source 5 phase C voltage twelfth harmonic
8426 SRC 5 Vc Harm[13] % Source 5 phase C voltage thirteenth harmonic
8427 SRC 5 Vc Harm[14] % Source 5 phase C voltage fourteenth harmonic
8428 SRC 5 Vc Harm[15] % Source 5 phase C voltage fifteenth harmonic
8429 SRC 5 Vc Harm[16] % Source 5 phase C voltage sixteenth harmonic
8430 SRC 5 Vc Harm[17] % Source 5 phase C voltage seventeenth harmonic
8431 SRC 5 Vc Harm[18] % Source 5 phase C voltage eighteenth harmonic
8432 SRC 5 Vc Harm[19] % Source 5 phase C voltage nineteenth harmonic
8433 SRC 5 Vc Harm[20] % Source 5 phase C voltage twentieth harmonic
8434 SRC 5 Vc Harm[21] % Source 5 phase C voltage twenty-first harmonic
8435 SRC 5 Vc Harm[22] % Source 5 phase C voltage twenty-second harmonic
8436 SRC 5 Vc Harm[23] % Source 5 phase C voltage twenty-third harmonic
8437 SRC 5 Vc Harm[24] % Source 5 phase C voltage twenty-fourth harmonic
8438 SRC 5 Vc Harm[25] % Source 5 phase C voltage twenty-fifth harmonic
8439 SRC 6 Va THD % Source 6 phase A voltage total harmonic distortion (THD)
8440 SRC 6 Va Harm[2] % Source 6 phase A voltage second harmonic
8441 SRC 6 Va Harm[3] % Source 6 phase A voltage third harmonic
8442 SRC 6 Va Harm[4] % Source 6 phase A voltage fourth harmonic
8443 SRC 6 Va Harm[5] % Source 6 phase A voltage fifth harmonic
8444 SRC 6 Va Harm[6] % Source 6 phase A voltage sixth harmonic
8445 SRC 6 Va Harm[7] % Source 6 phase A voltage seventh harmonic
8446 SRC 6 Va Harm[8] % Source 6 phase A voltage eighth harmonic
8447 SRC 6 Va Harm[9] % Source 6 phase A voltage ninth harmonic
8448 SRC 6 Va Harm[10] % Source 6 phase A voltage tenth harmonic
8449 SRC 6 Va Harm[11] % Source 6 phase A voltage eleventh harmonic
8450 SRC 6 Va Harm[12] % Source 6 phase A voltage twelfth harmonic
8451 SRC 6 Va Harm[13] % Source 6 phase A voltage thirteenth harmonic
8452 SRC 6 Va Harm[14] % Source 6 phase A voltage fourteenth harmonic
A
8500 SRC 6 Vc Harm[12] % Source 6 phase C voltage twelfth harmonic
8501 SRC 6 Vc Harm[13] % Source 6 phase C voltage thirteenth harmonic
8502 SRC 6 Vc Harm[14] % Source 6 phase C voltage fourteenth harmonic
8503 SRC 6 Vc Harm[15] % Source 6 phase C voltage fifteenth harmonic
8504 SRC 6 Vc Harm[16] % Source 6 phase C voltage sixteenth harmonic
8505 SRC 6 Vc Harm[17] % Source 6 phase C voltage seventeenth harmonic
8506 SRC 6 Vc Harm[18] % Source 6 phase C voltage eighteenth harmonic
8507 SRC 6 Vc Harm[19] % Source 6 phase C voltage nineteenth harmonic
8508 SRC 6 Vc Harm[20] % Source 6 phase C voltage twentieth harmonic
8509 SRC 6 Vc Harm[21] % Source 6 phase C voltage twenty-first harmonic
8510 SRC 6 Vc Harm[22] % Source 6 phase C voltage twenty-second harmonic
8511 SRC 6 Vc Harm[23] % Source 6 phase C voltage twenty-third harmonic
8512 SRC 6 Vc Harm[24] % Source 6 phase C voltage twenty-fourth harmonic
8513 SRC 6 Vc Harm[25] % Source 6 phase C voltage twenty-fifth harmonic
8692 Brk 3 Arc Amp A kA2-cyc Breaker 3 arcing amp phase A
8694 Brk 3 Arc Amp B kA2-cyc Breaker 3 arcing amp phase B
8696 Brk 3 Arc Amp C kA2-cyc Breaker 3 arcing amp phase C
8698 Brk 3 Op Time A ms Breaker 3 operating time phase A
8699 Brk 3 Op Time B ms Breaker 3 operating time phase B
8700 Brk 3 Op Time C ms Breaker 3 operating time phase C
8701 Brk 3 Op Time ms Breaker 3 operating time
8702 Brk 4 Arc Amp A kA2-cyc Breaker 4 arcing amp phase A
8704 Brk 4 Arc Amp B kA2-cyc Breaker 4 arcing amp phase B
8706 Brk 4 Arc Amp C kA2-cyc Breaker 4 arcing amp phase C
8708 Brk 4 Op Time A ms Breaker 4 operating time phase A
8709 Brk 4 Op Time B ms Breaker 4 operating time phase B
8710 Brk 4 Op Time C ms Breaker 4 operating time phase C
8711 Brk 4 Op Time ms Breaker 4 operating time
9024 Prefault Ia Mag [1] Amps Fault 1 pre-fault phase A current magnitude
9026 Prefault Ia Ang [1] Degrees Fault 1 pre-fault phase A current angle
9027 Prefault Ib Mag [1] Amps Fault 1 pre-fault phase B current magnitude
9029 Prefault Ib Ang [1] Degrees Fault 1 pre-fault phase B current angle
9030 Prefault Ic Mag [1] Amps Fault 1 pre-fault phase C current magnitude
9032 Prefault Ic Ang [1] Degrees Fault 1 pre-fault phase C current angle
9033 Prefault Va Mag [1] Volts Fault 1 pre-fault phase A voltage magnitude
9035 Prefault Va Ang [1] Degrees Fault 1 pre-fault phase A voltage angle
9036 Prefault Vb Mag [1] Volts Fault 1 pre-fault phase B voltage magnitude
9038 Prefault Vb Ang [1] Degrees Fault 1 pre-fault phase B voltage angle
9039 Prefault Vc Mag [1] Volts Fault 1 pre-fault phase C voltage magnitude
9041 Prefault Vc Ang [1] Degrees Fault 1 pre-fault phase C voltage angle
9042 Fault Ia Mag [1] Amps Fault 1 post-fault phase A current magnitude
9044 Fault Ia Ang [1] Degrees Fault 1 post-fault phase A current angle
9045 Fault Ib Mag [1] Amps Fault 1 post-fault phase B current magnitude
9047 Fault Ib Ang [1] Degrees Fault 1 post-fault phase B current angle
9048 Fault Ic Mag [1 Amps Fault 1 post-fault phase C current magnitude
9050 Fault Ic Ang [1] Degrees Fault 1 post-fault phase C current angle
9051 Fault Va Mag [1] Volts Fault 1 post-fault phase A voltage magnitude
A
9121 Fault Ib Mag [3] Amps Fault 3 post-fault phase B current magnitude
9123 Fault Ib Ang [3] Degrees Fault 3 post-fault phase B current angle
9124 Fault Ic Mag [3] Amps Fault 3 post-fault phase C current magnitude
9126 Fault Ic Ang [3] Degrees Fault 3 post-fault phase C current angle
9127 Fault Va Mag [3] Volts Fault 3 post-fault phase A voltage magnitude
9129 Fault Va Ang [3] Degrees Fault 3 post-fault phase A voltage angle
9130 Fault Vb Mag [3] Volts Fault 3 post-fault phase B voltage magnitude
9132 Fault Vb Ang [3] Degrees Fault 3 post-fault phase B voltage angle
9133 Fault Vc Mag [3] Volts Fault 3 post-fault phase C voltage magnitude
9135 Fault Vc Ang [3] Degrees Fault 3 post-fault phase C voltage angle
9136 Fault Type [3] --- Fault 3 type
9137 Fault Location [3] --- Fault 3 location
9138 Prefault Ia Mag [4] Amps Fault 4 pre-fault phase A current magnitude
9140 Prefault Ia Ang [4] Degrees Fault 4 pre-fault phase A current angle
9141 Prefault Ib Mag [4] Amps Fault 4 pre-fault phase B current magnitude
9143 Prefault Ib Ang [4] Degrees Fault 4 pre-fault phase B current angle
9144 Prefault Ic Mag [4] Amps Fault 4 pre-fault phase C current magnitude
9146 Prefault Ic Ang [4] Degrees Fault 4 pre-fault phase C current angle
9147 Prefault Va Mag [4] Volts Fault 4 pre-fault phase A voltage magnitude
9149 Prefault Va Ang [4] Degrees Fault 4 pre-fault phase A voltage angle
9150 Prefault Vb Mag [4] Volts Fault 4 pre-fault phase B voltage magnitude
9152 Prefault Vb Ang [4] Degrees Fault 4 pre-fault phase B voltage angle
9153 Prefault Vc Mag [4] Volts Fault 4 pre-fault phase C voltage magnitude
9155 Prefault Vc Ang [4] Degrees Fault 4 pre-fault phase C voltage angle
9156 Fault Ia Mag [4] Amps Fault 4 post-fault phase A current magnitude
9158 Fault Ia Ang [4] Degrees Fault 4 post-fault phase A current angle
9159 Fault Ib Mag [4] Amps Fault 4 post-fault phase B current magnitude
9161 Fault Ib Ang [4] Degrees Fault 4 post-fault phase B current angle
9162 Fault Ic Mag [4] Amps Fault 4 post-fault phase C current magnitude
9164 Fault Ic Ang [4] Degrees Fault 4 post-fault phase C current angle
9165 Fault Va Mag [4] Volts Fault 4 post-fault phase A voltage magnitude
9167 Fault Va Ang [4] Degrees Fault 4 post-fault phase A voltage angle
9168 Fault Vb Mag [4] Volts Fault 4 post-fault phase B voltage magnitude
9170 Fault Vb Ang [4] Degrees Fault 4 post-fault phase B voltage angle
9171 Fault Vc Mag [4] Volts Fault 4 post-fault phase C voltage magnitude
9173 Fault Vc Ang [4] Degrees Fault 4 post-fault phase C voltage angle
9174 Fault Type [4] --- Fault 4 type
9175 Fault Location [4] --- Fault 4 location
9176 Prefault Ia Mag [5] Amps Fault 5 pre-fault phase A current magnitude
9178 Prefault Ia Ang [5] Degrees Fault 5 pre-fault phase A current angle
9179 Prefault Ib Mag [5] Amps Fault 5 pre-fault phase B current magnitude
9181 Prefault Ib Ang [5] Degrees Fault 5 pre-fault phase B current angle
9182 Prefault Ic Mag [5] Amps Fault 5 pre-fault phase C current magnitude
9184 Prefault Ic Ang [5] Degrees Fault 5 pre-fault phase C current angle
9185 Prefault Va Mag [5] Volts Fault 5 pre-fault phase A voltage magnitude
9187 Prefault Va Ang [5] Degrees Fault 5 pre-fault phase A voltage angle
9188 Prefault Vb Mag [5] Volts Fault 5 pre-fault phase B voltage magnitude
A
10278 SRC 1 Ib Harm[6] % Source 1 phase B current sixth harmonic
10279 SRC 1 Ib Harm[7] % Source 1 phase B current seventh harmonic
10280 SRC 1 Ib Harm[8] % Source 1 phase B current eighth harmonic
10281 SRC 1 Ib Harm[9] % Source 1 phase B current ninth harmonic
10282 SRC 1 Ib Harm[10] % Source 1 phase B current tenth harmonic
10283 SRC 1 Ib Harm[11] % Source 1 phase B current eleventh harmonic
10284 SRC 1 Ib Harm[12] % Source 1 phase B current twelfth harmonic
10285 SRC 1 Ib Harm[13] % Source 1 phase B current thirteenth harmonic
10286 SRC 1 Ib Harm[14] % Source 1 phase B current fourteenth harmonic
10287 SRC 1 Ib Harm[15] % Source 1 phase B current fifteenth harmonic
10288 SRC 1 Ib Harm[16] % Source 1 phase B current sixteenth harmonic
10289 SRC 1 Ib Harm[17] % Source 1 phase B current seventeenth harmonic
10290 SRC 1 Ib Harm[18] % Source 1 phase B current eighteenth harmonic
10291 SRC 1 Ib Harm[19] % Source 1 phase B current nineteenth harmonic
10292 SRC 1 Ib Harm[20] % Source 1 phase B current twentieth harmonic
10293 SRC 1 Ib Harm[21] % Source 1 phase B current twenty-first harmonic
10294 SRC 1 Ib Harm[22] % Source 1 phase B current twenty-second harmonic
10295 SRC 1 Ib Harm[23] % Source 1 phase B current twenty-third harmonic
10296 SRC 1 Ib Harm[24] % Source 1 phase B current twenty-fourth harmonic
10297 SRC 1 Ib Harm[25] % Source 1 phase B current twenty-fifth harmonic
10306 SRC 1 Ic THD % Source 1 phase C current total harmonic distortion
10307 SRC 1 Ic Harm[2] % Source 1 phase C current second harmonic
10308 SRC 1 Ic Harm[3] % Source 1 phase C current third harmonic
10309 SRC 1 Ic Harm[4] % Source 1 phase C current fourth harmonic
10310 SRC 1 Ic Harm[5] % Source 1 phase C current fifth harmonic
10311 SRC 1 Ic Harm[6] % Source 1 phase C current sixth harmonic
10312 SRC 1 Ic Harm[7] % Source 1 phase C current seventh harmonic
10313 SRC 1 Ic Harm[8] % Source 1 phase C current eighth harmonic
10314 SRC 1 Ic Harm[9] % Source 1 phase C current ninth harmonic
10315 SRC 1 Ic Harm[10] % Source 1 phase C current tenth harmonic
10316 SRC 1 Ic Harm[11] % Source 1 phase C current eleventh harmonic
10317 SRC 1 Ic Harm[12] % Source 1 phase C current twelfth harmonic
10318 SRC 1 Ic Harm[13] % Source 1 phase C current thirteenth harmonic
10319 SRC 1 Ic Harm[14] % Source 1 phase C current fourteenth harmonic
10320 SRC 1 Ic Harm[15] % Source 1 phase C current fifteenth harmonic
10321 SRC 1 Ic Harm[16] % Source 1 phase C current sixteenth harmonic
10322 SRC 1 Ic Harm[17] % Source 1 phase C current seventeenth harmonic
10323 SRC 1 Ic Harm[18] % Source 1 phase C current eighteenth harmonic
10324 SRC 1 Ic Harm[19] % Source 1 phase C current nineteenth harmonic
10325 SRC 1 Ic Harm[20] % Source 1 phase C current twentieth harmonic
10326 SRC 1 Ic Harm[21] % Source 1 phase C current twenty-first harmonic
10327 SRC 1 Ic Harm[22] % Source 1 phase C current twenty-second harmonic
10328 SRC 1 Ic Harm[23] % Source 1 phase C current twenty-third harmonic
10329 SRC 1 Ic Harm[24] % Source 1 phase C current twenty-fourth harmonic
10330 SRC 1 Ic Harm[25] % Source 1 phase C current twenty-fifth harmonic
10339 SRC 2 Ia THD % Source 2 phase A current total harmonic distortion
10340 SRC 2 Ia Harm[2] % Source 2 phase A current second harmonic
A
10396 SRC 2 Ib Harm[25] % Source 2 phase B current twenty-fifth harmonic
10405 SRC 2 Ic THD % Source 2 phase C current total harmonic distortion
10406 SRC 2 Ic Harm[2] % Source 2 phase C current second harmonic
10407 SRC 2 Ic Harm[3] % Source 2 phase C current third harmonic
10408 SRC 2 Ic Harm[4] % Source 2 phase C current fourth harmonic
10409 SRC 2 Ic Harm[5] % Source 2 phase C current fifth harmonic
10410 SRC 2 Ic Harm[6] % Source 2 phase C current sixth harmonic
10411 SRC 2 Ic Harm[7] % Source 2 phase C current seventh harmonic
10412 SRC 2 Ic Harm[8] % Source 2 phase C current eighth harmonic
10413 SRC 2 Ic Harm[9] % Source 2 phase C current ninth harmonic
10414 SRC 2 Ic Harm[10] % Source 2 phase C current tenth harmonic
10415 SRC 2 Ic Harm[11] % Source 2 phase C current eleventh harmonic
10416 SRC 2 Ic Harm[12] % Source 2 phase C current twelfth harmonic
10417 SRC 2 Ic Harm[13] % Source 2 phase C current thirteenth harmonic
10418 SRC 2 Ic Harm[14] % Source 2 phase C current fourteenth harmonic
10419 SRC 2 Ic Harm[15] % Source 2 phase C current fifteenth harmonic
10420 SRC 2 Ic Harm[16] % Source 2 phase C current sixteenth harmonic
10421 SRC 2 Ic Harm[17] % Source 2 phase C current seventeenth harmonic
10422 SRC 2 Ic Harm[18] % Source 2 phase C current eighteenth harmonic
10423 SRC 2 Ic Harm[19] % Source 2 phase C current nineteenth harmonic
10424 SRC 2 Ic Harm[20] % Source 2 phase C current twentieth harmonic
10425 SRC 2 Ic Harm[21] % Source 2 phase C current twenty-first harmonic
10426 SRC 2 Ic Harm[22] % Source 2 phase C current twenty-second harmonic
10427 SRC 2 Ic Harm[23] % Source 2 phase C current twenty-third harmonic
10428 SRC 2 Ic Harm[24] % Source 2 phase C current twenty-fourth harmonic
10429 SRC 2 Ic Harm[25] % Source 2 phase C current twenty-fifth harmonic
10438 SRC 3 Ia THD % Source 3 phase A current total harmonic distortion
10439 SRC 3 Ia Harm[2] % Source 3 phase A current second harmonic
10440 SRC 3 Ia Harm[3] % Source 3 phase A current third harmonic
10441 SRC 3 Ia Harm[4] % Source 3 phase A current fourth harmonic
10442 SRC 3 Ia Harm[5] % Source 3 phase A current fifth harmonic
10443 SRC 3 Ia Harm[6] % Source 3 phase A current sixth harmonic
10444 SRC 3 Ia Harm[7] % Source 3 phase A current seventh harmonic
10445 SRC 3 Ia Harm[8] % Source 3 phase A current eighth harmonic
10446 SRC 3 Ia Harm[9] % Source 3 phase A current ninth harmonic
10447 SRC 3 Ia Harm[10] % Source 3 phase A current tenth harmonic
10448 SRC 3 Ia Harm[11] % Source 3 phase A current eleventh harmonic
10449 SRC 3 Ia Harm[12] % Source 3 phase A current twelfth harmonic
10450 SRC 3 Ia Harm[13] % Source 3 phase A current thirteenth harmonic
10451 SRC 3 Ia Harm[14] % Source 3 phase A current fourteenth harmonic
10452 SRC 3 Ia Harm[15] % Source 3 phase A current fifteenth harmonic
10453 SRC 3 Ia Harm[16] % Source 3 phase A current sixteenth harmonic
10454 SRC 3 Ia Harm[17] % Source 3 phase A current seventeenth harmonic
10455 SRC 3 Ia Harm[18] % Source 3 phase A current eighteenth harmonic
10456 SRC 3 Ia Harm[19] % Source 3 phase A current nineteenth harmonic
10457 SRC 3 Ia Harm[20] % Source 3 phase A current twentieth harmonic
10458 SRC 3 Ia Harm[21] % Source 3 phase A current twenty-first harmonic
A
10522 SRC 3 Ic Harm[19] % Source 3 phase C current nineteenth harmonic
10523 SRC 3 Ic Harm[20] % Source 3 phase C current twentieth harmonic
10524 SRC 3 Ic Harm[21] % Source 3 phase C current twenty-first harmonic
10525 SRC 3 Ic Harm[22] % Source 3 phase C current twenty-second harmonic
10526 SRC 3 Ic Harm[23] % Source 3 phase C current twenty-third harmonic
10527 SRC 3 Ic Harm[24] % Source 3 phase C current twenty-fourth harmonic
10528 SRC 3 Ic Harm[25] % Source 3 phase C current twenty-fifth harmonic
10537 SRC 4 Ia THD % Source 4 phase A current total harmonic distortion
10538 SRC 4 Ia Harm[2] % Source 4 phase A current second harmonic
10539 SRC 4 Ia Harm[3] % Source 4 phase A current third harmonic
10540 SRC 4 Ia Harm[4] % Source 4 phase A current fourth harmonic
10541 SRC 4 Ia Harm[5] % Source 4 phase A current fifth harmonic
10542 SRC 4 Ia Harm[6] % Source 4 phase A current sixth harmonic
10543 SRC 4 Ia Harm[7] % Source 4 phase A current seventh harmonic
10544 SRC 4 Ia Harm[8] % Source 4 phase A current eighth harmonic
10545 SRC 4 Ia Harm[9] % Source 4 phase A current ninth harmonic
10546 SRC 4 Ia Harm[10] % Source 4 phase A current tenth harmonic
10547 SRC 4 Ia Harm[11] % Source 4 phase A current eleventh harmonic
10548 SRC 4 Ia Harm[12] % Source 4 phase A current twelfth harmonic
10549 SRC 4 Ia Harm[13] % Source 4 phase A current thirteenth harmonic
10550 SRC 4 Ia Harm[14] % Source 4 phase A current fourteenth harmonic
10551 SRC 4 Ia Harm[15] % Source 4 phase A current fifteenth harmonic
10552 SRC 4 Ia Harm[16] % Source 4 phase A current sixteenth harmonic
10553 SRC 4 Ia Harm[17] % Source 4 phase A current seventeenth harmonic
10554 SRC 4 Ia Harm[18] % Source 4 phase A current eighteenth harmonic
10555 SRC 4 Ia Harm[19] % Source 4 phase A current nineteenth harmonic
10556 SRC 4 Ia Harm[20] % Source 4 phase A current twentieth harmonic
10557 SRC 4 Ia Harm[21] % Source 4 phase A current twenty-first harmonic
10558 SRC 4 Ia Harm[22] % Source 4 phase A current twenty-second harmonic
10559 SRC 4 Ia Harm[23] % Source 4 phase A current twenty-third harmonic
10560 SRC 4 Ia Harm[24] % Source 4 phase A current twenty-fourth harmonic
10561 SRC 4 Ia Harm[25] % Source 4 phase A current twenty-fifth harmonic
10570 SRC 4 Ib THD % Source 4 phase B current total harmonic distortion
10571 SRC 4 Ib Harm[2] % Source 4 phase B current second harmonic
10572 SRC 4 Ib Harm[3] % Source 4 phase B current third harmonic
10573 SRC 4 Ib Harm[4] % Source 4 phase B current fourth harmonic
10574 SRC 4 Ib Harm[5] % Source 4 phase B current fifth harmonic
10575 SRC 4 Ib Harm[6] % Source 4 phase B current sixth harmonic
10576 SRC 4 Ib Harm[7] % Source 4 phase B current seventh harmonic
10577 SRC 4 Ib Harm[8] % Source 4 phase B current eighth harmonic
10578 SRC 4 Ib Harm[9] % Source 4 phase B current ninth harmonic
10579 SRC 4 Ib Harm[10] % Source 4 phase B current tenth harmonic
10580 SRC 4 Ib Harm[11] % Source 4 phase B current eleventh harmonic
10581 SRC 4 Ib Harm[12] % Source 4 phase B current twelfth harmonic
10582 SRC 4 Ib Harm[13] % Source 4 phase B current thirteenth harmonic
10583 SRC 4 Ib Harm[14] % Source 4 phase B current fourteenth harmonic
10584 SRC 4 Ib Harm[15] % Source 4 phase B current fifteenth harmonic
A
10648 SRC 5 Ia Harm[13] % Source 5 phase A current thirteenth harmonic
10649 SRC 5 Ia Harm[14] % Source 5 phase A current fourteenth harmonic
10650 SRC 5 Ia Harm[15] % Source 5 phase A current fifteenth harmonic
10651 SRC 5 Ia Harm[16] % Source 5 phase A current sixteenth harmonic
10652 SRC 5 Ia Harm[17] % Source 5 phase A current seventeenth harmonic
10653 SRC 5 Ia Harm[18] % Source 5 phase A current eighteenth harmonic
10654 SRC 5 Ia Harm[19] % Source 5 phase A current nineteenth harmonic
10655 SRC 5 Ia Harm[20] % Source 5 phase A current twentieth harmonic
10656 SRC 5 Ia Harm[21] % Source 5 phase A current twenty-first harmonic
10657 SRC 5 Ia Harm[22] % Source 5 phase A current twenty-second harmonic
10658 SRC 5 Ia Harm[23] % Source 5 phase A current twenty-third harmonic
10659 SRC 5 Ia Harm[24] % Source 5 phase A current twenty-fourth harmonic
10660 SRC 5 Ia Harm[25] % Source 5 phase A current twenty-fifth harmonic
10669 SRC 5 Ib THD % Source 5 phase B current total harmonic distortion
10670 SRC 5 Ib Harm[2] % Source 5 phase B current second harmonic
10671 SRC 5 Ib Harm[3] % Source 5 phase B current third harmonic
10672 SRC 5 Ib Harm[4] % Source 5 phase B current fourth harmonic
10673 SRC 5 Ib Harm[5] % Source 5 phase B current fifth harmonic
10674 SRC 5 Ib Harm[6] % Source 5 phase B current sixth harmonic
10675 SRC 5 Ib Harm[7] % Source 5 phase B current seventh harmonic
10676 SRC 5 Ib Harm[8] % Source 5 phase B current eighth harmonic
10677 SRC 5 Ib Harm[9] % Source 5 phase B current ninth harmonic
10678 SRC 5 Ib Harm[10] % Source 5 phase B current tenth harmonic
10679 SRC 5 Ib Harm[11] % Source 5 phase B current eleventh harmonic
10680 SRC 5 Ib Harm[12] % Source 5 phase B current twelfth harmonic
10681 SRC 5 Ib Harm[13] % Source 5 phase B current thirteenth harmonic
10682 SRC 5 Ib Harm[14] % Source 5 phase B current fourteenth harmonic
10683 SRC 5 Ib Harm[15] % Source 5 phase B current fifteenth harmonic
10684 SRC 5 Ib Harm[16] % Source 5 phase B current sixteenth harmonic
10685 SRC 5 Ib Harm[17] % Source 5 phase B current seventeenth harmonic
10686 SRC 5 Ib Harm[18] % Source 5 phase B current eighteenth harmonic
10687 SRC 5 Ib Harm[19] % Source 5 phase B current nineteenth harmonic
10688 SRC 5 Ib Harm[20] % Source 5 phase B current twentieth harmonic
10689 SRC 5 Ib Harm[21] % Source 5 phase B current twenty-first harmonic
10690 SRC 5 Ib Harm[22] % Source 5 phase B current twenty-second harmonic
10691 SRC 5 Ib Harm[23] % Source 5 phase B current twenty-third harmonic
10692 SRC 5 Ib Harm[24] % Source 5 phase B current twenty-fourth harmonic
10693 SRC 5 Ib Harm[25] % Source 5 phase B current twenty-fifth harmonic
10702 SRC 5 Ic THD % Source 5 phase C current total harmonic distortion
10703 SRC 5 Ic Harm[2] % Source 5 phase C current second harmonic
10704 SRC 5 Ic Harm[3] % Source 5 phase C current third harmonic
10705 SRC 5 Ic Harm[4] % Source 5 phase C current fourth harmonic
10706 SRC 5 Ic Harm[5] % Source 5 phase C current fifth harmonic
10707 SRC 5 Ic Harm[6] % Source 5 phase C current sixth harmonic
10708 SRC 5 Ic Harm[7] % Source 5 phase C current seventh harmonic
10709 SRC 5 Ic Harm[8] % Source 5 phase C current eighth harmonic
10710 SRC 5 Ic Harm[9] % Source 5 phase C current ninth harmonic
A
10774 SRC 6 Ib Harm[7] % Source 6 phase B current seventh harmonic
10775 SRC 6 Ib Harm[8] % Source 6 phase B current eighth harmonic
10776 SRC 6 Ib Harm[9] % Source 6 phase B current ninth harmonic
10777 SRC 6 Ib Harm[10] % Source 6 phase B current tenth harmonic
10778 SRC 6 Ib Harm[11] % Source 6 phase B current eleventh harmonic
10779 SRC 6 Ib Harm[12] % Source 6 phase B current twelfth harmonic
10780 SRC 6 Ib Harm[13] % Source 6 phase B current thirteenth harmonic
10781 SRC 6 Ib Harm[14] % Source 6 phase B current fourteenth harmonic
10782 SRC 6 Ib Harm[15] % Source 6 phase B current fifteenth harmonic
10783 SRC 6 Ib Harm[16] % Source 6 phase B current sixteenth harmonic
10784 SRC 6 Ib Harm[17] % Source 6 phase B current seventeenth harmonic
10785 SRC 6 Ib Harm[18] % Source 6 phase B current eighteenth harmonic
10786 SRC 6 Ib Harm[19] % Source 6 phase B current nineteenth harmonic
10787 SRC 6 Ib Harm[20] % Source 6 phase B current twentieth harmonic
10788 SRC 6 Ib Harm[21] % Source 6 phase B current twenty-first harmonic
10789 SRC 6 Ib Harm[22] % Source 6 phase B current twenty-second harmonic
10790 SRC 6 Ib Harm[23] % Source 6 phase B current twenty-third harmonic
10791 SRC 6 Ib Harm[24] % Source 6 phase B current twenty-fourth harmonic
10792 SRC 6 Ib Harm[25] % Source 6 phase B current twenty-fifth harmonic
10801 SRC 6 Ic THD % Source 6 phase C current total harmonic distortion
10802 SRC 6 Ic Harm[2] % Source 6 phase C current second harmonic
10803 SRC 6 Ic Harm[3] % Source 6 phase C current third harmonic
10804 SRC 6 Ic Harm[4] % Source 6 phase C current fourth harmonic
10805 SRC 6 Ic Harm[5] % Source 6 phase C current fifth harmonic
10806 SRC 6 Ic Harm[6] % Source 6 phase C current sixth harmonic
10807 SRC 6 Ic Harm[7] % Source 6 phase C current seventh harmonic
10808 SRC 6 Ic Harm[8] % Source 6 phase C current eighth harmonic
10809 SRC 6 Ic Harm[9] % Source 6 phase C current ninth harmonic
10810 SRC 6 Ic Harm[10] % Source 6 phase C current tenth harmonic
10811 SRC 6 Ic Harm[11] % Source 6 phase C current eleventh harmonic
10812 SRC 6 Ic Harm[12] % Source 6 phase C current twelfth harmonic
10813 SRC 6 Ic Harm[13] % Source 6 phase C current thirteenth harmonic
10814 SRC 6 Ic Harm[14] % Source 6 phase C current fourteenth harmonic
10815 SRC 6 Ic Harm[15] % Source 6 phase C current fifteenth harmonic
10816 SRC 6 Ic Harm[16] % Source 6 phase C current sixteenth harmonic
10817 SRC 6 Ic Harm[17] % Source 6 phase C current seventeenth harmonic
10818 SRC 6 Ic Harm[18] % Source 6 phase C current eighteenth harmonic
10819 SRC 6 Ic Harm[19] % Source 6 phase C current nineteenth harmonic
10820 SRC 6 Ic Harm[20] % Source 6 phase C current twentieth harmonic
10821 SRC 6 Ic Harm[21] % Source 6 phase C current twenty-first harmonic
10822 SRC 6 Ic Harm[22] % Source 6 phase C current twenty-second harmonic
10823 SRC 6 Ic Harm[23] % Source 6 phase C current twenty-third harmonic
10824 SRC 6 Ic Harm[24] % Source 6 phase C current twenty-fourth harmonic
10825 SRC 6 Ic Harm[25] % Source 6 phase C current twenty-fifth harmonic
12032 Brk 1 Acc Arc Amp A kA2-cyc Breaker 1 Acc arcing amp phase A
12034 Brk 1 Acc Arc Amp B kA2-cyc Breaker 1 Acc arcing amp phase B
12036 Brk 1 Acc Arc Amp C kA2-cyc Breaker 1 Acc arcing amp phase C
A
13550 DCmA Ip 24 mA DCmA input 24 actual value
13552 RTD Ip 1 --- RTD input 1 actual value
13553 RTD Ip 2 --- RTD input 2 actual value
13554 RTD Ip 3 --- RTD input 3 actual value
13555 RTD Ip 4 --- RTD input 4 actual value
13556 RTD Ip 5 --- RTD input 5 actual value
13557 RTD Ip 6 --- RTD input 6 actual value
13558 RTD Ip 7 --- RTD input 7 actual value
13559 RTD Ip 8 --- RTD input 8 actual value
13560 RTD Ip 9 --- RTD input 9 actual value
13561 RTD Ip 10 --- RTD input 10 actual value
13562 RTD Ip 11 --- RTD input 11 actual value
13563 RTD Ip 12 --- RTD input 12 actual value
13564 RTD Ip 13 --- RTD input 13 actual value
13565 RTD Ip 14 --- RTD input 14 actual value
13566 RTD Ip 15 --- RTD input 15 actual value
13567 RTD Ip 16 --- RTD input 16 actual value
13568 RTD Ip 17 --- RTD input 17 actual value
13569 RTD Ip 18 --- RTD input 18 actual value
13570 RTD Ip 19 --- RTD input 19 actual value
13571 RTD Ip 20 --- RTD input 20 actual value
13572 RTD Ip 21 --- RTD input 21 actual value
13573 RTD Ip 22 --- RTD input 22 actual value
13574 RTD Ip 23 --- RTD input 23 actual value
13575 RTD Ip 24 --- RTD input 24 actual value
13576 RTD Ip 25 --- RTD input 25 actual value
13577 RTD Ip 26 --- RTD input 26 actual value
13578 RTD Ip 27 --- RTD input 27 actual value
13579 RTD Ip 28 --- RTD input 28 actual value
13580 RTD Ip 29 --- RTD input 29 actual value
13581 RTD Ip 30 --- RTD input 30 actual value
13582 RTD Ip 31 --- RTD input 31 actual value
13583 RTD Ip 32 --- RTD input 32 actual value
13584 RTD Ip 33 --- RTD input 33 actual value
13585 RTD Ip 34 --- RTD input 34 actual value
13586 RTD Ip 35 --- RTD input 35 actual value
13587 RTD Ip 36 --- RTD input 36 actual value
13588 RTD Ip 37 --- RTD input 37 actual value
13589 RTD Ip 38 --- RTD input 38 actual value
13590 RTD Ip 39 --- RTD input 39 actual value
13591 RTD Ip 40 --- RTD input 40 actual value
13592 RTD Ip 41 --- RTD input 41 actual value
13593 RTD Ip 42 --- RTD input 42 actual value
13594 RTD Ip 43 --- RTD input 43 actual value
13595 RTD Ip 44 --- RTD input 44 actual value
13596 RTD Ip 45 --- RTD input 45 actual value
13597 RTD Ip 46 --- RTD input 46 actual value
A
45594 RxGOOSE Analog 6 --- RxGOOSE analog input 6
45596 RxGOOSE Analog 7 --- RxGOOSE analog input 7
45598 RxGOOSE Analog 8 --- RxGOOSE analog input 8
45600 RxGOOSE Analog 9 --- RxGOOSE analog input 9
45602 RxGOOSE Analog 10 --- RxGOOSE analog input 10
45604 RxGOOSE Analog 11 --- RxGOOSE analog input 11
45606 RxGOOSE Analog 12 --- RxGOOSE analog input 12
45608 RxGOOSE Analog 13 --- RxGOOSE analog input 13
45610 RxGOOSE Analog 14 --- RxGOOSE analog input 14
45612 RxGOOSE Analog 15 --- RxGOOSE analog input 15
45614 RxGOOSE Analog 16 --- RxGOOSE analog input 16
45616 RxGOOSE Analog 17 --- RxGOOSE analog input 17
45618 RxGOOSE Analog 18 --- RxGOOSE analog input 18
45620 RxGOOSE Analog 19 --- RxGOOSE analog input 19
45622 RxGOOSE Analog 20 --- RxGOOSE analog input 20
45624 RxGOOSE Analog 21 --- RxGOOSE analog input 21
45626 RxGOOSE Analog 22 --- RxGOOSE analog input 22
45628 RxGOOSE Analog 23 --- RxGOOSE analog input 23
45630 RxGOOSE Analog 24 --- RxGOOSE analog input 24
45632 RxGOOSE Analog 25 --- RxGOOSE analog input 25
45634 RxGOOSE Analog 26 --- RxGOOSE analog input 26
45636 RxGOOSE Analog 27 --- RxGOOSE analog input 27
45638 RxGOOSE Analog 28 --- RxGOOSE analog input 28
45640 RxGOOSE Analog 29 --- RxGOOSE analog input 29
45642 RxGOOSE Analog 30 --- RxGOOSE analog input 30
45644 RxGOOSE Analog 31 --- RxGOOSE analog input 31
45646 RxGOOSE Analog 32 --- RxGOOSE analog input 32
This appendix outlines how to set up a RADIUS server for user authentication.
VENDOR GE 2910
# Management authorization
BEGIN-VENDOR GE
# Role ID
ATTRIBUTE GE-UR-Role 1 integer
# GE-UR-ROLE values
VALUE GE-UR-Role Administrator 1
VALUE GE-UR-Role Supervisor 2
VALUE GE-UR-Role Engineer 3
B VALUE GE-UR-Role
VALUE GE-UR-Role
Operator
Observer
4
5
END-VENDOR GE
#############################################################
6. In the dictionary file in the <Path_to_Radius>\etc\raddb folder, add the following line.
$INCLUDE dictionary.ge
For example, the file can look like the following:
$INCLUDE ../shareéfreeradius/dictionary
$INCLUDE dictionary.ge
7. For the first start, run the RADIUS server in debug mode to ensure that there are no compiling errors.
<Path_to_Radius>/start_radiusd_debug.bat
8. Set up the RADIUS parameters on the UR as follows.
8.1. If logging in, select Device for the Authentication Type, and use Administrator for the User Name. The default
password is "ChangeMe1#".
8.2. Access Settings > Product Setup > Security. Configure the IP address and ports for the RADIUS server. Leave
the GE vendor ID field at the default of 2910. Update the RADIUS shared secret as specified in the clients.conf
file. Restart the relay for the IP address and port changes to take effect.
9. Verify operation. Log in to the UR software as follows. In the login window, select Server as the Authentication Type,
enter the user name entered (for example user name Tester and password "testpw"). Check that the RADIUS server log
file shows the access with an "Access-Accept" entry.
Recall that if you tried another third-party tool and it did not work, you can use the FreeRADIUS software from
freeradius.net.
SetupCLI -h
Display help.
It displays the content outline here.
SetupCLI <Application> login -d <device> [-A <authentication type>] [-a <account>] -w <password> [-s]
Authenticate with device <device> using password <password>.
For non-CyberSentry devices — Set <authentication type> to "traditional". Note that <authentication type> defaults to
"traditional" if not specified. Set <account> to "COMMANDS" or "SETTINGS". If not specified, the SETTINGS account is
used.
Example: SetupCLI URPC login -d "C30 Melbourne" -A traditional -a SETTINGS -w 1password1
Example of a batch file that checks for an error (this batch file uses standard batch file operations to check the return
code (ERRORLEVEL) and jump to an error handler):
SetupCLI URPC start
SetupCLI URPC login -d demoDevice -a SETTINGS -w WrongPassword -A traditional
IF NOT ERRORLEVEL 0 GOTO FAILED
SetupCLI URPC putsettings -d demoDevice -f "example file.urs"
SetupCLI URPC inservice -d demoDevice
SetupCLI URPC reboot -d demoDevice
SetupCLI URPC exit
exit
:FAILED
echo Please try again C
exit
For CyberSentry devices with local authentication — Set <authentication type> to "local" . Set <account> to
"Supervisor", "Administrator", "Engineer", "Operator", or "Observer".
For CyberSentry devices with RADIUS authentication — Set <authentication type> to "radius". Set <account> to the
user's account on the RADIUS server.
The device is named as DEV@SETUP_CLI, which is used as the device name required by the <device> parameter of other
SetupCLI commands.
The device name DEV@SETUP_CLI is always assigned to the device that is connected most recently by performing
'adddevice' command. It means that the Application only keeps up to one device named as DEV@SETUP_CLI, the
'adddevice' command disconnects/deletes the device DEV@SETUP _CLI that was connected previously by performing
'adddevice' command.
The device name DEV@SETUP_CLI is never used to configure/connect to a device through the graphical user interface.
Example of a batch file using a device IP address to retrieve its settings file:
SetupCLI URPC start
SetupCLI URPC adddevice -I 192.168.140.113 -S 113 -P 502
SetupCLI URPC getsettings -d DEV@SETUP_CLI -f C:\example.urs
SetupCLI URPC exit
After connecting the device using IP address, the device name DEV@SETUP_CLI is used to identify this device in
'getsettings' command.
Example of a batch file using a device IP address to retrieve a settings file when RADIUS authentication is required: C
SetupCLI URPC start
SetupCLI URPC adddevice -I 192.168.140.113 -S 113 -P 502
SetupCLI URPC login -d DEV@SETUP_CLI -a %1 -w %2 -A radius
SetupCLI URPC getsettings -d DEV@SETUP_CLI -f "example file.urs"
SetupCLI URPC logout -d DEV@SETUP_CLI
SetupCLI URPC exit
DEV@SETUP_CLI has to be used as the device name in the commands followed by the 'adddevice' command.
Appendix D: Miscellaneous
Miscellaneous
D.1 Warranty
For products shipped as of 1 October 2013, GE Grid Solutions warrants most of its GE manufactured products for 10 years.
For warranty details including any limitations and disclaimers, see the Terms and Conditions at
http://www.gegridsolutions.com/multilin/warranty.htm
For products shipped before 1 October 2013, the standard 24-month warranty applies.
D 1601-0106-M2
1601-0106-N1
4.9x
5.0x
27 February 2006
31 March 2006
URX-214
URX-217
1601-0106-N2 5.0x 26 May 2006 URX-220
1601-0106-P1 5.2x 23 October 2006 URX-230
1601-0106-P2 5.2x 24 January 2007 URX-232
1601-0106-R1 5.4x 26 June 2007 URX-242
1601-0106-R2 5.4x 31 August 2007 URX-246
1601-0106-R3 5.4x 17 October 2007 URX-251
1601-0106-S1 5.5x 7 December 2007 URX-253
1601-0106-S2 5.5x 22 February 2008 URX-258
1601-0106-S3 5.5x 12 March 2008 URX-260
1601-0106-T1 5.6x 27 June 2008 08-0390
1601-0106-U1 5.7x 29 May 2009 09-0938
1601-0106-U2 5.7x 30 September 2009 09-1165
1601-0106-V1 5.8x 29 May 2010 09-1457
1601-0106-V2 5.8x 04 January 2011 11-2237
1601-0106-W1 5.9x 12 January 2011 11-2227
1601-0106-X1 6.0x 21 December 2011 11-2840
1601-0106-X2 6.0x 5 April 2012 12-3254
1601-0106-Y1 7.0x 30 September 2012 12-3529
1601-0106-Y2 7.0x 11 November 2012 12-3601
1601-0106-Z1 7.1x 30 March 2013 13-0126
1601-0106-AA1 7.2x 1 August 2013 13-0401
1601-0106-AB1 7.3x 7 November 2014 14-1408
1601-0106-AB2 7.3x 1 September 2015 15-2215
1601-0106-AC1 7.40x 8 December 2016 16-3319
1601-0106-AE1 7.41x 31 January 2017 17-3427
1601-0106-AE3 7.4x 28 April 2017 17-3561
1601-0106-AF1 7.6x 30 June 2017 17-3779
1601-0106-AF2 7.6x 31 October 2017 17-3935
1601-0106-AG1 7.7x 31 March 2018 18-4430
1601-0106-AG2 7.7x 4 May 2018 18-4517
Table D-2: Major changes for F35 manual version AG2 (English)
Page Description
--- General revision. Improved figure quality by using conditional text to switch between PDF and PNG figures.
--- Updated maximum number of Wattmetric Ground Fault elements for F35 from 4 to 5 in Settings and Actual Values chapters
Table D-3: Major changes for F35 manual version AG1 (English)
Page Description
--- General revision
2-8 Updated order codes from SH / SL to RH / RL for the redundant power supply for horizontal units. The power supply modules
were upgraded in 2014 to SH and SL, but the order codes when purchasing a UR remain as RH and RL so that customers do
not need to change order codes. The order codes for the power supply replacement modules are correct as SH and SL.
3-58 Added IP and subnet mask address rules to the Set IP Address in UR section
5-57 Added IEC 61850 Editions 1 and 2 section
5-150 Added support for a redundant SNTP server as a time source
5-214 Added GOOSE simulation operands to FlexLogic operands table
5-330 Added Settings > Simulation > GOOSE section
6-4 Added Actual Values > Graphical Panel > LEDs and Pushbuttons information D
6-13 Added Actual Values > Status > Protocol section
Table D-4: Major changes for F35 manual version AF2 (English)
Page Description
--- General revision
--- Added type W CPU module to order codes in chapter 2, installation chapter 3, Replace Front Panel section in chapter 10
--- Added Japanese and Polish languages and modules 6W and 6X to order codes in chapter 2. Module 6W allows 30 contact
inputs, and Module 6X allows 18 outputs.
3-17 Added contact input and contact output modules 6W and 6X to Table 3-3 Contact Input and Output Module Assignments and
to Figure 3-17 Contact Input and Output Module Wiring (Sheet 3 of 3)
5-300 Updated Thermal Overload Protection Logic diagram
Table D-5: Major changes for F35 manual version AF1 (English)
Page Description
--- General revision
--- Updated "faceplate" to "front panel" for consistency and to reflect web site
--- Added graphical front panel option to order codes and specifications in chapter 2, Interfaces chapter 4, Settings chapter 5,
Actual Values chapter 6
--- Added PEAP-GTC and PAP protocols for authenticating user logins when using a RADIUS server. Added to Settings > Product
Setup > Security > RADIUS Authentication Method and to Modbus memory map and F codes.
--- Updated Contact Inputs from 96 to 120 and Contact Outputs from 64 to 72 in Product Description in chapter 2 and FlexLogic
operands table in chapter 5
--- Updated Breaker Restrike number from 6 to 3 in specifications, FlexLogic operands table, settings, features per product table,
Modbus memory map
3-36 Updated RS422 and Fiber Interface Connection figure for the clock channels (from 7a and 7b to 1a and 1b)
3-67 Added Connect to a D400 Gateway section
4-43 Updated LED Labelling instructions for the new Front Panel Label Designer
4-50 Added Standard Front Panel section for labelling LEDs and pushbuttons
5-122 Updated User-programmable Pushbuttons section as per specifications
5-143 Added USB Port section to enable/disable the USB port on the graphical front panel
5-144 Updated Breakers section as per specifications
5-149 Updated Disconnect Switches section as per specifications
Page Description
10-5 Added Convert Device Settings section
10-7 Added Copy Settings to Other Device section
10-15 Added Replace Front Panel section for retrofit with the new graphical front panel
Table D-6: Major changes for F35 manual version AE3 (English)
Page Description
--- General revision
2- Updated order codes
10-5 Added Copy Settings to Other Device section
Table D-7: Major changes for F35 manual version AE1 (English)
Page Description
--- General revision
--- Added routable GOOSE content in chapters 2 and 5
3-36 Updated RS422 and Fiber Interface Connection figure for the clock channels (from 7a and 7b to 1a and 1b)
4- Added Engineer content
D 5- Updated IEC 61850 content
A- Updated FlexAnalog table for most UR products
Table D-8: Major changes for F35 manual version AC1 (English)
Page Description
--- General revision. Added online help and updated generic online help.
--- Deleted EAC logo from title page and deleted EAC certification from Approvals specifications because document not
translated into Russian
--- Updated Breaker Arcing Current content, including FlexLogic operands table, settings, logic diagram, actual values, Modbus
memory map
--- Updated Fault Report and Fault Location content, including settings, actual values, and theory of operation chapters
--- Added Voltage Transformer Fuse Failure (VTFF) element, including to product description table, FlexLogic operands table,
settings, FlexAnalog table, Features per Product table, Modbus memory map, and IMD content
--- Added Source Current THD and Harmonics content to specifications, actual values, Modbus memory map
--- Added Phase Overvoltage content to product description, specifications, FlexLogic operands table, settings, features per
product table, Modbus memory map, IMD table
--- Updated number of Breaker Restrike elements, increasing from three to six, in FlexLogic operands table, settings, features per
product table, Modbus memory map
--- Added Cold Load Pickup content to product description, FlexLogic operands table, settings, features per product table,
Modbus memory map, IMD table
--- Added Breaker Flashover content to product description, specifications, FlexLogic operands table, settings, features per
product table, Modbus memory map, IMD table
2- Updated several specifications, such as TOC, IOC, number of FlexLogic lines
4-30 Added FlexLogic Design and Monitoring using Engineer section to end of Interfaces chapter
5-38 Added PRT FUNCTION settings in Network section to enable/disable each Ethernet port
5-49 Updated IEC 61850 section
5-61 Added Support for Routable GOOSE section
5-169 Updated number of FlexLogic lines from 512 to 1024 in FlexLogic Equation Editor settings section
10-1 Added Monitoring section
10-2 Added Retrieve Files section
C- Added Command Line Interface appendix
Abbreviations
A Ampere
AC Alternating Current CRC Cyclic Redundancy Code/Check
A/D Analog to Digital CRL Certificate Revocation List
AE Accidental Energization, Application Entity CRT, CRNT Current
AMP Ampere CSA Canadian Standards Association
ANG Angle CT Current Transformer
ANSI American National Standards Institute CVT Capacitive Voltage Transformer
AR Automatic Reclosure
ARP Address Resolution Protocol D/A Digital to Analog
ASDU Application-layer Service Data Unit DC (dc) Direct Current
ASYM Asymmetry DCE Data Communications Equipment
AUTO Automatic DCS Distributed Control System
AUX Auxiliary DD Disturbance Detector
AVG Average DFLT Default
AWG American Wire Gauge DGNST Diagnostics
DIFF Differential
BCS Best Clock Selector DIR Directional
BER Bit Error Rate DISCREP Discrepancy
BF Breaker Fail DIST Distance
BFI Breaker Failure Initiate DMD Demand
BKR Breaker DNP Distributed Network Protocol
BLK Block DPO Dropout
BLKG Blocking DPS Double-Point Status
BNC Bayonet Neill-Concelman DSP Digital Signal Processor
BPNT Breakpoint of a characteristic DST Daylight Savings Time
BRKR Breaker dt Rate of Change
DTT Direct Transfer Trip
CA Certificate Authority DUTT Direct Under-reaching Transfer Trip
CAP Capacitor
CC Coupling Capacitor EGD Ethernet Global Data
CCVT Coupling Capacitor Voltage Transformer ENCRMNT Encroachment
CFG Configure / Configurable EPRI Electric Power Research Institute
.CFG Filename extension for oscillography files .EVT Filename extension for event recorder files
CHK Check EXT Extension, External
CHNL Channel
CID Configured IED Description F Field
CLS Close FAIL Failure
CLSD Closed FD Fault Detector
CMND Command FDH Fault Detector high-set
CMPRSN Comparison FDL Fault Detector low-set
CO Contact Output FIR Finite Impulse Response
COM Communication FLA Full Load Current
COMM Communications FO Fiber Optic
COMP Compensated, Comparison FPGA Field-programmable Gate Array
CONN Connection FREQ Frequency
CONT Continuous, Contact FSK Frequency-Shift Keying
CO-ORD Coordination FTP File Transfer Protocol
FxE FlexElement™
T Time, transformer
TC Thermal Capacity
TCP Transmission Control Protocol
TCU Thermal Capacity Used
TD MULT Time Dial Multiplier
TEMP Temperature
TFTP Trivial File Transfer Protocol
THD Total Harmonic Distortion
TMR Timer
TOC Time Overcurrent
TOV Time Overvoltage
TRANS Transient
Index
Index
Administrator
Numerics add user account ............................................................................. 5-14
10BASE-F settings ...............................................................................5-45 command to force logoff ................................................................7-4
4L Discrepancy message .................................................................. 7-8 no automatic logout from front panel ................................... 5-21
7R module ................................................................................................3-41 role for CyberSentry ...........................................................................2-4
7S module ................................................................................................3-40 Alarm LEDs ............................................................................................5-163
8-bit switch Alarms
FlexLogic operands .......................................................................5-209 acknowledge ....................................................................4-33, 6-3, 6-4
settings ...............................................................................................5-282 add .............................................................................................. 4-34, 5-36
specifications ......................................................................................2-23 messages ................................................................................................7-6
overview ............................................................................................... 4-31
reset ...............................................................................................4-33, 6-4
AND gate explained ........................................................................... 4-82
A Annunciator editor ............................................................................. 4-34
AC current inputs ANSI device numbers ...........................................................................2-2
explained ..............................................................................................3-17 Apparent power
settings ...............................................................................................5-184 actual values ...................................................................................... 6-19
specifications ......................................................................................2-26 specifications ..................................................................................... 2-25
AC voltage input specifications ...................................................2-26 Application examples
Accents ......................................................................................................4-55 breaker trip circuit integrity .......................................................5-279
Access Violation message ..............................................................3-68 contact inputs ..................................................................................5-312
Acknowledge alarm ............................................................................. 6-4 direct inputs and outputs ...........................................................5-319
Activate relay .........................................................................................3-53 latching outputs ..............................................................................5-315
Active setting group ........................................................................5-230 Apply settings to other device ..................................................... 10-7
Actual values ............................................................................................ 6-1 Approvals ................................................................................................. 2-35
alarms for graphical front panel ................................................. 6-3 Architecture, relay ............................................................................5-206
display on graphical front panel ...................................4-34, 4-35 Arcing current ......................................................................5-284, 5-288
monitor with Modbus Analyzer ..................................................10-1 Audit list of port numbers ............................................................... 5-45
not activated graphical front panel .........................................4-52 Authentication by device or server ........................................... 5-16
Add Device from File option Automatic discovery of UR devices .......................................... 3-67
restore settings to online device ............................................10-11
Autoreclose
save to Offline Window ..................................................................3-72
actual values .........................................................................................6-7
Add Device to Offline Window preferences .........................10-9 FlexLogic operands .......................................................................5-209
Add module, check settings not defaulted ........................10-24 logic diagram ...................................................................................5-274
Add relay ...................................................................................................3-57 settings ...............................................................................................5-270
single shot sequence ....................................................................5-276
B C
Back up settings .......................................................... 5-59, 5-97, 10-8 C37.94 communications ..................................................... 3-48, 3-51
Bad IRIG-B Signal message ............................................................. 7-8 Cannot log in .............................................................................................2-4
Bad PTP Signal message ................................................................... 7-8 Caution symbol in Offline Window ............................................ 4-68
Banks ............................................................................................. 5-7, 5-184 CE certification ...................................................................................... 2-35
Basic front panel Certification ............................................................................................ 2-35
dimensions ............................................................................................. 3-2 Changes ...................................................................................................... D-1
FlexLogic ............................................................................................5-209 Channel
interface ............................................................................................... 4-15 banks ................................................................................................... 5-184
IP rating ................................................................................................ 2-33 tests ........................................................................................................ 6-11
keypad .................................................................................................. 4-37 Check Settings message ....................................................................7-7
labels ...................................................................................................... 4-47 Chinese limited to 10 character input ..................................... 5-27
LEDs ..........................................................................................4-39, 5-163 CID file, SCD file ................5-76, 5-77, 5-78, 5-114, 5-115, 5-116
navigation ........................................................................................... 4-49 CID files
order codes ............................................................................................ 2-7 create ......................................................................................... 5-59, 5-97
pushbuttons .....................................................................................5-166 explained .............................................................................................. 3-72
specifications ..................................................................................... 2-23 import ..................................................................................... 3-72, 10-12
use, change setting ......................................................................... 4-51 import preferences .......................................................................... 10-9
Battery view ............................................................................................. 5-59, 5-97
disposal ..............................................................................................10-26 Circuit monitoring applications ................................................ 5-278
replace ................................................................................................10-25 Cleaning .................................................................................................... 2-35
Baud rate ................................................................................................. 5-42 Clear
Blinking alarm ....................................................................................... 4-33 files and records ............................................................................ 10-29
Block setting ............................................................................................. 5-5 LEDs ..................................................................................................... 5-317
Breaker arcing current relay records using IEC 61850 ................................................ 5-133
actual values ...................................................................................... 6-28 relay records using settings ........................................................ 5-40
clearing ........................................................................................ 5-41, 7-2 security logs ...........................................................................................7-4
FlexAnalogs ............................................................................ A-21, A-33
FlexLogic operands .......................................................................5-210
logic diagram .................................................................... 5-287, 5-290
measurement ................................................................... 5-286, 5-289
settings ................................................................................ 5-284, 5-288
specifications ..................................................................................... 2-21
Digital elements
D application example .................................................................... 5-279
D400 connection ................................................................................. 3-73 FlexLogic operands ...................................................................... 5-211
Dark graphical front panel ............................................................ 5-31 logic diagram .................................................................................. 5-278
Data logger settings ............................................................................................... 5-277
actual values ...................................................................................... 6-27 Digital outputs
clearing ........................................................................................ 5-41, 7-2 see Contact outputs
settings ...............................................................................................5-157 Dimensions ................................................................................................3-2
specifications ..................................................................................... 2-24 Direct Device Off message ...............................................................7-8
Data, reading values ............................................................................ 6-1 Direct devices
Dataset member is empty message .........................5-68, 5-106 settings ............................................................................................... 5-318
Date status ..................................................................................................... 6-10
firmware ............................................................................................... 6-29 Direct I/O
last cleared oscillography date ................................................. 6-27 application example .................................................................... 5-319
last settings change ....................................................................... 6-29 configuration examples ............................................................. 5-176
manufacturing date ....................................................................... 6-29 settings ............................................................................................... 5-318
set .................................................................................... 5-29, 5-148, 7-3 Direct inputs
DCmA inputs .......................................................................................... 6-24 actual values .........................................................................................6-9
actual values ...................................................................................... 6-24 application example .................................................................... 5-319
FlexAnalogs ........................................................................................ A-34 clearing counters ................................................................................7-2
settings ...............................................................................................5-324 FlexLogic operands ...................................................................... 5-215
specifications ..................................................................................... 2-26 settings ............................................................................................... 5-318
DCmA outputs specifications ..................................................................................... 2-27
description .......................................................................................... 3-31 Direct outputs
settings ...............................................................................................5-326 application example .................................................................... 5-319
specifications ..................................................................................... 2-30 clearing counters ................................................................................7-2
Decommission ....................................................................................10-29 settings ............................................................................................... 5-319
Default password ............................................................................... 5-14 specifications ..................................................................................... 2-30
Default settings ........................................................................ 10-7, 10-8 Direct Ring Break message ..............................................................7-8
Default settings to factory default ............................................... 7-3 Disconnect switch
Definite time curve ............................................................ 5-236, 5-253 FlexLogic operands ...................................................................... 5-214
Delete files and records ....................................................5-40, 10-29 logic ..................................................................................................... 5-197
Demand metering settings ............................................................................................... 5-194
actual values ...................................................................................... 6-20 Discover button .................................................................................... 3-67
specifications ..................................................................................... 2-26 Disk space required ........................................................................... 3-55
Demand records, clearing .................................................... 5-41, 7-2 Display settings .................................................................................... 5-26
Demand, current ...............................................................................5-158 Disposal ................................................................................................. 10-31
Deploy relay .............................................................................................. 8-1 Dispose of battery ............................................................................ 10-26
Deploy settings ..................................................................................... 10-7 Disturbance detector
Device authentication ...................................................................... 5-16 FlexLogic operands ...................................................................... 5-213
Device Connectivity Report in Engineer ................................ 4-76 internal ............................................................................................... 5-187
Device information files ......................................................... 1-2, 4-76 DNP
connections remaining .................................................................. 6-12
Device overview .................................................................................. 10-1
select protocol ................................................................................... 5-51
Device setup .......................................................................................... 3-67
settings .................................................................................................. 5-52
Diagnostic Alarm COP message ................................................... 7-7
view Points List in web browser ................................................ 5-55
Diagnostic Alarm DSP message .................................................... 7-7
DOS Partition Alarm message ........................................................7-8
Diagnostic Failure message ............................................................ 7-6
Downgrade
Diagnostics Failure message .......................................................... 7-8 firmware ............................................................................................ 10-14
Dielectric strength .............................................................................. 3-15 software ............................................................................................. 10-13
Digital counters Download
actual values ......................................................................................... 6-8 files from relay ................................................................................... 10-3
FlexLogic operands .......................................................................5-211 settings to relay ................................................................................ 10-7
logic diagram ...................................................................................5-282 Drag and drop files ................................................................................4-3
settings ...............................................................................................5-280
Duplicate
device settings ................................................................................... 10-7
settings for upgrading ................................................................... 10-5
GOOSE
actual values .......................................................................................6-23 H
FlexAnalogs ........................................................................................ A-36 HardFiber
routable, explained ...........................................................5-66, 5-104 interface module described ........................................................ 3-18
settings ...................................................................................5-66, 5-104 order codes for compatible URs ..................................................2-7
simulation operands ....................................................................5-217 self-test errors ................................................................................... 7-11
simulation settings ........................................................................5-332 Harmonic content ............................................................................... 6-22
Graphical front panel .....................................................................10-15 Harmonics
actual value menu not activated ..............................................4-52 actual values ...................................................................................... 6-22
actual values, phasors ...................................................................4-56 FlexAnalogs ......................................................................................... A-11
alarm acknowledge, reset .........................................4-33, 6-3, 6-4 specifications ..................................................................................... 2-25
alarm setup .........................................................................................5-36 Heartbeat messages ...............................5-67, 5-70, 5-105, 5-108
annunciator editor ...........................................................................4-34 Help, getting ..............................................................................................1-2
date and time .....................................................................................5-30 Home page configuration .............................................................. 5-29
explained ..............................................................................................4-18 HTTP ..........................................................................................................5-138
FlexLogic ............................................................................................5-209 port, close ..........................................................................................5-138
Home page configuration ............................................................5-29
Humidity specifications ................................................................... 2-33
interface ................................................................................................4-17
Hysteresis ..............................................................................................5-226
IP rating .................................................................................................2-33
labels ......................................................................................................4-48
LEDs .........................................................................................4-42, 5-163
Metering Editor ..................................................................................4-35 I
navigation ............................................................................................4-50 IAC curves ..............................................................................................5-234
navigation keys ..................................................................................4-37 ICD file .................................... 5-76, 5-77, 5-78, 5-114, 5-115, 5-116
no display .............................................................................................5-31 IEC 60870-5-103 protocol
order codes ........................................................................................... 2-7 explained ............................................................................................5-142
phasor diagram .....................................................................4-56, 5-32 select protocol ................................................................................... 5-51
plastic protective film ..................................................................10-20 settings ...............................................................................................5-142
pushbutton testing ............................................................................ 7-3 IEC 60870-5-104 protocol
pushbuttons .....................................................................................5-166 connections remaining ................................................................. 6-12
pushbuttons 9 to 16 ........................................................................4-29 port, close ..........................................................................................5-140
settings ..................................................................................................5-28 select protocol ................................................................................... 5-51
settings, breaker ............................................................................5-190 settings ...............................................................................................5-139
settings, switch ...............................................................................5-196 IEC 61850 protocol
single-line diagrams ........................................................................4-20 Edition 1 and 2 support ................................................................. 5-57
specifications ..........................................................................2-30, 2-32 explained .................................................................................. 5-57, 5-95
time .........................................................................................................5-30 file transfer ........................................................................................5-137
USB port .............................................................................................5-147 heartbeat messages .............................5-67, 5-70, 5-105, 5-108
use, change setting .........................................................................4-52 IID file ..................................................................................................... 10-8
view LEDs and pushbuttons in software ................................. 6-4 settings in EnerVista ....................................................................... 5-56
Ground current metering ................................................................6-18 specifications ..................................................................................... 2-30
Ground IOC IEC CID files ................................................................................. 5-59, 5-97
FlexLogic operands .......................................................................5-211 IED setup .................................................................................................. 3-56
logic diagram ...................................................................................5-250 IEEE C37.94 communications .......................................... 3-48, 3-51
settings ...............................................................................................5-249 IEEE curves ............................................................................................5-232
specifications ......................................................................................2-19 IID file ..................................................................... 3-72, 5-59, 5-97, 10-8
Ground TOC import preferences .......................................................................... 10-9
FlexLogic operands .......................................................................5-212 Import settings file .............................................................................. 3-72
logic diagram ...................................................................................5-249 Import settings from SCD or CID file ......................................10-12
settings ...............................................................................................5-248 In service indicator ................................................................................7-6
specifications ......................................................................................2-19
In Service LED ........................................................................................ 3-53
Group 1 switch after powerup ..................................................5-231
Incipient cable fault detector
Grouped elements ...........................................................................5-230 actual values ...................................................................................... 6-11
Guarantee ..................................................................................................D-1 clear counter .........................................................................................7-2
FlexLogic operands .......................................................................5-212
logic diagram ...................................................................................5-300
settings ...............................................................................................5-298
specifications ..................................................................................... 2-22
J
Japanese limited to 10 character input ................................ 5-27
Modules
M add and check settings not defaulted .................................10-24
MAC address communications ............................................................................... 3-34
actual values .......................................................................................6-29 CT/VT .............................................................................................3-16, 5-7
examples ..............................................................................................5-43 order codes ......................................................................................... 2-14
RxGOOSE ................................................................................5-73, 5-111 power supply ...................................................................................... 3-15
settings for redundancy ................................................................5-46 replace ................................................................................................10-23
TxGOOSE ................................................................................5-69, 5-107 transducer I/O ................................................................................... 3-32
Maintenance Monitor
actual values .......................................................................................6-28 actual values ...................................................................................... 10-1
alert error message ........................................................................... 7-8 actual values with Metering Editor .......................................... 5-32
battery replacement ....................................................................10-25 devices .................................................................................................. 10-1
cleaning .................................................................................................2-35 use alarms ........................................................................................... 5-36
commands ............................................................................................. 7-3 Monitoring elements settings ....................................................5-284
module replacement ....................................................................10-23 Mounting .....................................................................................................3-2
upgrade or downgrade ...............................................................10-14
Manufacturing date ...........................................................................6-29
Maximum 6X, 6X wire size ..............................................................3-21 N
Maximum CT/VT wire size ...............................................................3-17 Nameplate, rear ......................................................................................3-1
Measurements of UR and panel cutout ................................... 3-2 NAND gate explained ....................................................................... 4-82
Media storage alarm message ....................................................7-10 Navigation keys ................................................................................... 4-37
Memory low message ......................................................................... 7-8 Negative sequence IOC
Memory requirements ......................................................................3-55 FlexLogic operands .......................................................................5-212
Menu navigation ..................................................................................4-49 logic diagram ...................................................................................5-252
Message about upgrade over Internet ................................10-14 settings ...............................................................................................5-251
Messages specifications ..................................................................................... 2-20
clear front panel .............................................................................5-317 Negative sequence TOC
error .......................................................................................................... 7-6 FlexLogic operands .......................................................................5-212
errors and warnings in Engineer ...............................................4-68 logic diagram ...................................................................................5-251
Metering settings ...............................................................................................5-250
conventions .............................................................................6-13, 6-14 specifications ..................................................................................... 2-19
demand specifications ...................................................................2-26 Network settings migration .......................................................... 3-72
editor in graphical front panel ....................................................4-35 Neutral IOC
frequency specifications ...............................................................2-25 FlexLogic operands .......................................................................5-212
power specifications .......................................................................2-25 logic diagram ...................................................................................5-243
THD specifications ............................................................................2-25 settings ...............................................................................................5-242
voltage specifications .....................................................................2-25 specifications ..................................................................................... 2-19
Microsoft Windows requirement ................................................3-55 Neutral overvoltage
Mimic diagrams ....................................................................................4-20 FlexLogic operands .......................................................................5-212
Missing messages, RxGOOSE fail ................................................7-10 logic diagram ...................................................................................5-257
MMS connections remaining ........................................................6-12 settings ...............................................................................................5-256
Modbus specifications ..................................................................................... 2-21
connections remaining ..................................................................6-12 Neutral TOC
Flex State parameters .................................................................5-172 FlexLogic operands .......................................................................5-212
Modbus Analyzer window ............................................................10-1 logic diagram ...................................................................................5-242
port, close .............................................................................................5-51 settings ...............................................................................................5-241
register entry ...................................................................................5-147 specifications ..................................................................................... 2-19
settings ..................................................................................................5-51 No connection ....................................................................................... 5-45
user map ............................................................................................5-147 Non-volatile data storage .............................................................. 3-16
Model information, view ..................................................................6-29 Non-volatile latches
Model number ......................................................................................... 3-1 FlexLogic operands .......................................................................5-212
Modem connection .............................................................................3-66 settings ...............................................................................................5-229
Modification file number .................................................................6-29 specifications ..................................................................................... 2-23
Module 7R ................................................................................................3-41 NOR gate explained ........................................................................... 4-82
Module 7S .................................................................................................3-40 NOT gate explained ........................................................................... 4-82
Module Failure message .................................................................7-12
User-programmable LEDs
U custom labels ..................................................................................... 4-43
UDP for TFTP ........................................................................................5-139 defaults ................................................................................................. 4-41
UL certification ......................................................................................2-35 settings ...............................................................................................5-163
Unable to connect to relay .................................................3-68, 5-45 specifications ..................................................................................... 2-23
Unable to put relay in flash mode ...........................................10-14 User-programmable pushbuttons
Unauthorized access FlexLogic operands .......................................................................5-217
commands ...........................................................................................5-41 graphical front panel buttons 9 to 16 .................................... 4-29
resetting .................................................................................................. 7-2 logic diagrams .................................................................................5-171
Underfrequency settings ...............................................................................................5-166
FlexLogic operands .......................................................................5-214 specifications ..................................................................................... 2-23
logic diagram ...................................................................................5-270 testing .......................................................................................................7-3
settings ...............................................................................................5-269 User-programmable self-test settings .................................5-164
specifications ......................................................................................2-21
testing ...................................................................................................... 8-1
Undervoltage V
auxiliary .................................................................................................2-20 VAR hour
characteristics .................................................................................5-253 actual values ...................................................................................... 6-20
phase .......................................................................................2-20, 5-254 specifications ..................................................................................... 2-25
settings ...............................................................................................5-254 Vibration testing specifications .................................................. 2-34
Uninstall .................................................................................................10-29 Virtual inputs
Unit Not Calibrated message .......................................................7-10 actual values .........................................................................................6-5
Unit not programmed ...........................................................5-182, 7-7 commands .............................................................................................7-2
Unpacking the relay ............................................................................. 3-1 explained ............................................................................................5-313
Unreturned messages alarm .....................................................5-181 FlexLogic operands .......................................................................5-215
Update SCL files prompt ..................................................................4-68 logic diagram ...................................................................................5-313
Update settings with Convert Device Settings ...................10-5 settings ...............................................................................................5-313
Updates Virtual outputs
device not recognized .................................................................10-13 actual values .........................................................................................6-6
firmware .............................................................................................10-14 explained ............................................................................................5-317
FPGA .....................................................................................................10-15 FlexLogic operands .......................................................................5-215
instruction manual ............................................................................. 3-1 settings ...............................................................................................5-317
order code .............................................................................................. 7-3 Voltage banks .....................................................................................5-184
single-line diagrams not retained .............................................4-24 Voltage deviation specifications ................................................ 2-34
software .............................................................................................10-13 Voltage elements ..............................................................................5-253
Upgrade device settings ..................................................................10-5 Voltage metering
Upgrade over Internet message ..............................................10-14 actual values ...................................................................................... 6-18
Upload settings to relay ...................................................................10-7 specifications ..................................................................................... 2-25
URS file does not include IEC 61850 configuration .......10-11 Voltage Monitor message .............................................................. 7-11
URS file is part of a device folder .............................................10-11 Voltage restraint characteristic ................................................5-237
URS settings file ................................................3-72, 5-59, 5-97, 10-8 VT fuse failure
USB port FlexAnalogs ......................................................................................... A-36
graphical front panel .......................................................4-17, 5-147 FlexLogic operands .......................................................................5-214
Quick Connect ....................................................................................3-70 logic diagram ...................................................................................5-301
specifications ......................................................................................2-30 settings ...............................................................................................5-300
User accounts VT inputs ............................................................... 3-16, 3-17, 5-7, 5-184
add ...........................................................................................................5-14 VT wiring ................................................................................................... 3-17
authentication by device or server ..........................................5-16 VTFF .............................................................................................. 5-300, A-36
multiple login limitation CyberSentry ........................................ 2-4
passwords for settings and commands ....................4-58, 5-10
permissions by role ............................................................................ 2-4 W
permissions, set .................................................................................5-14
Warning messages in Engineer .................................................. 4-70
User-definable displays
Warning symbol in Offline Window .......................................... 4-68
example ..............................................................................................5-174
Warning, firmware upload not supported ..........................10-14
invoking and scrolling ..................................................................5-173
settings ...............................................................................................5-173
Warranty .................................................................................................... D-1
specifications ......................................................................................2-23
Watt-hour
actual values ...................................................................................... 6-20
specifications ..................................................................................... 2-25
Wattmetric zero-sequence directional
actual values ...................................................................................... 6-24
FlexLogic operands .......................................................................5-215
logic diagram ...................................................................................5-247
settings ...............................................................................................5-243
specifications ..................................................................................... 2-20
Waveform
view in actual values window .................................................... 6-27
view in event record ....................................................................... 6-25
Waveform files, view ......................................................................... 4-79
Web access port ...............................................................................5-138
Web server protocol ........................................................................5-138
Windows requirement ..................................................................... 3-55
Wire size
CT/VT ...................................................................................................... 3-17
F485 converter .................................................................................. 3-55
G.703 and fiber interface ............................................................. 3-47
G.703 interface .................................................................................. 3-40
module 7S ........................................................................................... 3-40
modules 6X, 6W ................................................................................ 3-21
modules 7E, 7F, 7G, 7Q, 75 .......................................................... 3-47
modules 7L, 7M, 7N, 7P, 74 ......................................................... 3-46
modules 7T, 7W ................................................................................ 3-44
power supply module .................................................................... 3-16
RS422 and fiber interface ............................................................ 3-46
RS422 interface ................................................................................ 3-44
Wiring diagram .................................................................................... 3-14
Withdraw UR from operation ....................................................10-29
Wrong Transceiver message ....................................................... 7-11
X
XOR gate explained ........................................................................... 4-82
Y
Yellow caution icon in Offline Window ................................... 4-68
Z
Zero-sequence core balance ....................................................... 3-17