Water and Drainage PDF
Water and Drainage PDF
Water and Drainage PDF
DRAINAGE IN BUILDINGS
SANS10252-1
SANS10400-W
SANS10252-2
SANS10400-P
1
10:00 – 10:30 Tea/Coffee
2
WATER RETICULATION
IN BUILDINGS
LEGISLATIVE
BACKGROUND
3
Government Notice
R509 of 08 June 2001
4
13(2) If constructed or installed after promulgation of
these Regulations, a suitable water volume
measuring device or volume controlling device
must be fitted to separately measure or control the
water supply to every –
5
14. Every consumer installation must comply with
SANS 10252: Water Supply (Part 1) and Drainage
for Buildings (Part 2) and SANS 10254: The
Installation of Fixed Electric Storage Water Heating
Systems, or any similar substituting re-enactment or
amendment thereof if the consumer installation is of
a type regulated by either standard.
6
National Building Regulations
7
A2 Plans and Particulars to be Furnished
8
A7 LAYOUT DRAWING
9
A8 PLUMBING INSTALLATION DRAWINGS AND
PARTICULARS
10
(2) Any drawing of a fire installation as contemplated in
regulation A2(1)(c) shall contain as many plans,
sections and elevations as may be necessary to
show, where relevant, the following:
12
WATER RETICULATION
IN BUILDINGS
HOW TO COMPLY
(RESIDENTIAL UNITS)
13
WHAT IS IMPORTANT?
1. Water supply
2. Water pressure
3. Water quality
NOTE:
• Emergency storage
• Boosting of pressure
14
WATER QUALITY
15
c) storage tanks shall be regularly cleaned and kept
free of contamination,
d) stored cold water shall be maintained at a
temperature not exceeding 20 °C,
e) in a hot water installation, there shall be no zones
where water is stored at temperatures of between
25 °C and 45 °C,
f) the stored hot water shall be maintained at a
temperature of at least 55 °C, and
g) the quality of the water shall be such as to comply
with SANS 241-1 and SANS 241-2.
16
WATER DEMAND
• SANS10252-1: Table 1
Table 2
Table 3
17
NBR A21
18
19
SANS10252-1
20
21
22
4.2.3 Hot water demand
And
3 × 2 = 6 persons
SANS10252-1 Table 5:
6 × 140ℓ/person = 840ℓ
5. Instantaneous
- No storage
26
EXERCISE
27
EXERCISE
2 × 2 = 4 persons
4 × 50ℓ = 200ℓ
28
EXERCISE
2 × 2 = 4 people
4 × 140ℓ = 560ℓ
29
EXERCISE
2 × 2 = 4 people
4 × 140ℓ = 560ℓ
30
NATIONAL BUILDING REGULATIONS
A20 Classification: H1
A21 Occupancy: 2 persons/bedroom
Type of hot water generation: Solar with back-up element
Hot water demand (SANS10252-1): 140ℓ per day per bed
Number of Bedrooms: 10
Total demand: 10 × 2 × 140 = 2800ℓ
Hot water storage capacity required: 2800 × 50% = 1400ℓ (50% XA2)
Capacity provided: 5 × 300ℓ
32
GUIDELINE: STORAGE CAPACITY OF DOMESTIC
SOLAR GEYSERS WITH BACKUP ELEMENT
EFFICIENT XA2
33
34
SANS1307 - Domestic storage solar water heating
systems
35
4.5.5.2 Any stand or frame that will determine the angle of
the collectors or the storage tank (or both) shall comply
with the following:
36
SANS10160 - The installation, maintenance, repair
and replacement of domestic solar water heating
systems
37
Design considerations and positioning of solar
collectors
38
In the southern hemisphere, collectors should be pointed
true north and tilted at an angle above the horizontal equal
to the latitude of the site plus 10°.
The design of the absorber unit can vary from a simple flat
plate to an evacuated tube reflector type absorber.
40
The absorber and all pipes are therefore sloped in such a
way that air can escape to the tank to be vented off.
43
44
c) corrosion within the primary system can be
minimized by the use of a corrosion-inhibited heat
transfer fluid; and
d) scale formation within the primary system can be
more effectively controlled.
45
46
47
SANS1352 - The installation, maintenance,
replacement and repair of domestic air source water
heating heat pump systems
50
j) that adverse weather conditions such as high winds and
heavy rains or excessive water discharges onto the heat
pump unit do not affect the efficient and effective
operations of the heat pump unit;
k) when the heat pump unit is positioned above the storage
water heater, provision shall be made to prevent the heat
pump unit from draining of water.
51
52
53
CAUTION:
54
55
5 Materials, pipes, fittings, components and fixtures
5.1 General
56
57
58
5.1.3 If it is desired or deemed necessary to use materials,
components, fittings or fixtures not covered by this part of
SANS 10252 or by an appropriate standard, proof of
quality and performance of the material or workmanship
shall be established by tests or by reference to other
appropriate standards.
PRESENTER’NOTE:
59
5.1.4 The following factors shall be considered when
materials, components, fittings and fixtures are being
selected:
60
5.1.5 All materials, components, fittings and fixtures in
every part of a water installation shall
62
5.1.8 All rubber components that are in contact with potable
water, such as joint rings, tap washers and flange packings,
shall, in order to control the multiplication of Legionaella
pneumophila bacteria in water installations, be of a
composition that will not promote microbiological growth.
63
5.2 Pipes and pipe fittings
64
NOTE 3 Where galvanized mild steel pipes and copper
pipes are used in the same system, the corrosion rate of
galvanized steel is usually substantially increased by the
traces of copper present in the water. Dissolved copper
ions can stimulate the corrosion of zinc coatings and bare
steel surfaces, either by direct electrochemical exchange
reactions or by galvanic attack. Dissolved copper is,
however, usually only found in cases where galvanized mild
steel hot water outlet pipes are used together with copper
domestic water heaters that operate at excessively high
temperatures.
67
SANS 460 Class 1:
A half hard thin-walled tube for above ground use only.
This tube can be bent using a bending tool with inner and
outer formers. Spring bending is not advised due to the
spring being too loose in the tube and the walls of the tube
collapsing. SABS 460 Class 1 - 28mm to 108mm is ideally
suited for the drawing of “T” joints.
68
SANS 460 Class 2:
A half hard, heavy gauge tube with excellent bending
qualities. This class is also used underground under normal
conditions i.e. non-aggressive soils. This is the only class
that can be bent by using an Internal Bending Spring. Care
should be taken when installing tube underground. The
tube should be protected against external corrosion using
CXP tape. SABS 460 Class 2 - 28mm to 108mm is ideally
suited for the drawing of “T” joints.
69
SANS 460 Class 3:
This class is a heavy, thick walled, half hard copper tube
with excellent bending qualities, designed specifically for
underground use where soil movement takes place. Care
should be taken when installing tube underground and it
should be protected against external corrosion using CXP
tape.
70
5.2.1.3 Unless the water is suitably treated, copper piping
shall not be used where
71
5.2.1.4 Copper or copper alloy pipes and fittings shall not
be used, unless suitably protected against external
corrosion, where they might be in contact with materials
such as
a) ash,
c) ammonia, or
72
5.2.3.7 Plastics pipes and fittings for hot and cold water
supply systems shall comply with one of the following
standards:
75
76
ABC PIPES
77
5.2.5 Iron and steel
79
5.3.3 Taps, mixers and showers
80
5.3.3.2 Showers
Showers shall be of a type that can operate effectively at
the internal water pressure recommended by the
manufacturer.
81
8.6.3 Pipes laid in or through floors, concrete slabs
or walls
83
84
85
86
WATER SYSTEM:
87
4.2.2 Probable (or design) flow demand
Qp = (ΣQ)n
Where
ΣQ is the arithmetic sum of the design flow rates of all the individual
fittings supplied by the pipe (see table 3 for design flow rates), in
litres per minute; and
Qp = (ΣQ)n + 80
Qp = (ΣQ)n + 45
89
4.2.2.4 The probable water flow demand for pipes in
installations where all the fittings supplied by a pipe
would probably operate simultaneously (automatic shut-
off flush valves excluded) shall be calculated using the
following equation:
Qp = ΣQ
4.2.2.5 Equation (4) can be used in all cases for the final
two fittings (automatic shut-off flush valves excluded)
supplied by a branch pipe. Working upstream from this
branch, the calculated value of Qp shall be retained until
it is replaced by a new value obtained from using
equation (1), (2) or (3).
90
Table 3 — Flow rates from terminal water fittings
91
Table 3 — Flow rates from terminal water fittings
92
Table 3 — Flow rates from terminal water fittings
93
Table 3 — Flow rates from terminal water fittings
94
Table 4 — Values of na
1 2
Nature of use of building Value of n
Dwellings (economic) 0,5 - 0,70
Dwellings (low-cost) 0,5 - 0,75
Offices 0,5 - 0,70
95
7.7.1.3 Unless otherwise stated, the length of an
unheated pipe (dead leg) conveying water direct
from a fixed water heater to a terminal water
fitting, or from the point of take-off from a hot
water circulating system to a terminal water
fitting, shall be such that the internal volume of
that pipe does not exceed 4ℓ. The internal volume
of pipes and permissible lengths in terms of the
4ℓ volume limit are given in table 19 and
recommended limits are given in table 20.
96
97
98
99
EXERCISE
100
DESIGN FLOW RATES
(Table 3)
The total length of the dead leg (hot water) is less than
8m (Table 20) – less than 4ℓ of water will be wasted
before water is hot at tap - therefore no HWR required.
102
In the case of dwelling houses, it will usually not be
necessary to carry out a detailed exercise to size the
pipes for the installation. For the internal hot and cold
water supply systems, certain basic pipe sizes will be
generally applicable.
103
104
The recommended pipe sizes for installations that
incorporate a storage tank and a type 3 standard water
heater as given in SANS 151, are given in table F.2.
105
Residual water pressure in our domestic water systems
is determined by gravity, pipe size, elevation, water
volume and distance from source.
106
Drag and pipe friction reduces residual water pressure.
This is the same as any other material traveling by
another. Think about dragging your feet across the floor.
It requires more effort to drag your feet across the floor
than it does to lift them through the air. This is because
there is less friction and drag in the air than on the solid
floor.
108
TYPICAL HOUSE
109
110
EXERCISE
Typical dwelling
• 5 bedrooms
• 3 bathrooms
• 1 kitchen
• Laundry
• Scullery
114
A20 Classification: H4
A21 Occupancy: 2 persons/bedroom
Type of hot water generation: Solar with back-up element
Hot water demand (SANS10252-1): 140ℓ per day per person
Number of Bedrooms: 5
Total demand: 5 × 2 × 140 = 1400ℓ
Hot water storage capacity required: 1400 × 50% = 700ℓ(50% XA2)
Capacity provided: 300ℓ + 300ℓ + 100ℓ
115
116
117
118
119
120
PLUMBING COC
122
• A plumbing certificate of compliance will be issued
for most plumbing work, including:
123
• A Plumbing certificate of compliance shall be issued
to the relevant owner with five working days of the
completion of the said plumbing works. Only a
licensed plumber may purchase and issue
compliance certificates.
FIRE INSTALLATIONS
125
4.1 General
126
c) the fire installation is either
127
4.2 Communication pipe
128
4.4 Isolating valves
129
4.5 Fire pump connections
131
4.6 Pipework
133
PF ≥ PM – (HF – HC) – PL
where
PM is the static pressure head, in metres, at the juncture between the communication
pipe and the service pipe, and which, unless otherwise directed by the local authority,
is the minimum head measured at a point in time;
HF is the elevation of the fire pump connection or hose reel, in metres, above a
common datum (see figure 1);
HC is the elevation of the communication pipe at the juncture with the service pipe, in
metres, above or below, or on the same level as the common datum (see figure 1). If
the elevation is below the common datum, the volume between HF and HC shall be
added and not subtracted;
PL is the sum, in metres, of all the products of the length of service pipe of a
particular diameter serving the fire pump connection or hose reel, and the friction
factor obtained from table 1 based on the following:
b) fire hose reels: the simultaneous use of all fire hose reels within a division.
134
4.6.2 All fire installation pipework shall be constructed in
accordance with the relevant requirements of
SANS 2001-DP2 or SANS 2001-DP6 and shall
have a pressure rating of not less than 1 200 kPa.
135
136
137
Example of a calculation for sizing pipework
138
139
Service pipe to fire pump connection
The head loss in the service pipe from
the communication pipe to the fire pump
connection (S1 + S2) for the maximum
fire load of the two fire hydrants, is as
follows for a 75 mm diameter pipe:
PF ≥ PM – (HF – HC) – PL
= 36 – (5 – 10) – (60 × 1,91 + 30 × 1,91)
= -130,9 m
(< 5 m is unacceptable (see 4.6.1(b)))
142
Service pipe from fire pump to
hose reels in division 2
143
Therefore, if S7 is increased to 40 mm
diameter:
144
Summary
145
DRAINAGE
146
147