The TSX P ACC 01 device connects several devices to the terminal port of Premium/Atrium PLCs. It isolates Uni-Telway signals to extend terminal port links over 10 meters and adapt the bus when connected to the end of a Uni-Telway bus. Switches configure the line end and operating mode as either a Uni-Telway master or slave.

Uploaded by

melad yousef
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
174 views18 pages

Tsxpaccc01 PDF

The TSX P ACC 01 device connects several devices to the terminal port of Premium/Atrium PLCs. It isolates Uni-Telway signals to extend terminal port links over 10 meters and adapt the bus when connected to the end of a Uni-Telway bus. Switches configure the line end and operating mode as either a Uni-Telway master or slave.

Uploaded by

melad yousef
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

Terminal port and TSX P ACC 01 device

3.4 Introduction to TSX P ACC 01

At a Glance

Subject of this This section describes the general characteristics of the TSX P ACC 01 device.
Section

What's in this This section contains the following topics:


Section?
Topic Page
Functionalities 56
External appearance 57

35006178 05 November 2006 55


Terminal port and TSX P ACC 01 device

Functionalities

General The TSX P ACC 01 unit is a cabling accessory that connects to the TER connector
of the Premium/Atrium PLC processor via an integral cable fitted with a mini-DIN
connector at one end.
This is used to:
z Connect several devices to the terminal port of Premium/Atrium PLCs. For this
purpose, it is fitted with two mini-DIN connectors, marked TER and AUX, which
are functionally identical to the TER and AUX connectors of the Premium PLC
processors.
z Isolate Uni-Telway signals in order to extend Premium PLC terminal port links to
over 10 meters for the purpose of connecting the PLC to a Uni-Telway bus.
z Adapt the bus when the unit is connected to one of the ends of the Uni-Telway
bus.
z Set the operating mode of the terminal port:
z Uni-Telway master
z Uni-Telway slave or Character Mode

Note: The TER and AUX ports of the TSX P ACC 01 unit are not isolated from one
another, nor from the TER port of the supplying PLC.

Note: We strongly recommend that, after use, you do not leave a TSX PCU 103•
or TSX PCX 1031 cable connected to the Uni-telway bus at one end and
unconnected at the other.

56 35006178 05 November 2006


Terminal port and TSX P ACC 01 device

External appearance

General This device is made from zamak and of the same type as Uni-Telway branching or
connection devices (TSX SCA 50 and TSX SCA 62). It is designed to be mounted
in a cabinet. Its protection index is IP20.

Illustration:

Terminal ports
Connection cable to TER port
for Premium PLC (length 1 m)

35006178 05 November 2006 57


Terminal port and TSX P ACC 01 device

3.5 Hardware installation

At a Glance

Aim of this This Section deals with installing hardware for connection devices TSX P ACC 01.
Section

What's in this This section contains the following topics:


Section?
Topic Page
Dimensions and mounting 59
Internal view 60
Connection to Uni-Telway Buses 61
Connecting to Premium and Atrium PLCs 62
Switch configuration 63
TSX P ACC 01 connector pin configuration 64

58 35006178 05 November 2006


Terminal port and TSX P ACC 01 device

Dimensions and mounting

General The TSX P ACC 01 device is installed on a AM1-PA••• perforated board or on a DIN
rail with a LA9 D09976 mounting plate.

Illustration:

=
65
AM1-PA...

=
2 x Ø 5.5
= 50 =
AM1-DE/DP

35006178 05 November 2006 59


Terminal port and TSX P ACC 01 device

Internal view

Illustration

S1
Z

S2
S M
1 2 3 4 5

1 2 3 4 5

JA JB

S1 Selects functioning mode (master or slave),


S2 Adapts the line end,
JA and JB Connection terminals on the Uni-Telway Bus.

60 35006178 05 November 2006


Terminal port and TSX P ACC 01 device

Connection to Uni-Telway Buses

General The TSX P ACC 01 device is connected to the Uni-Telway Bus using connection
terminals JA and JB as shown below:

Illustration:

Shielding

Insulating sleeve
(essential)
White
Red

White

Blue

35006178 05 November 2006 61


Terminal port and TSX P ACC 01 device

Connecting to Premium and Atrium PLCs

General When the TSX P ACC 01 device has to be supplied, it must be connected by its
built-in cable to the TER connector on the PLC processor.
The device can be connected and disconnected when the PLC is switched on.
Illustration:

Premium TSX RKY

Host PC

Atrium

TSX P ACC 01 TSX P ACC 01

Note:
Only one TSX P ACC 01 device can be connected to a Premium/Atrium PLC.

62 35006178 05 November 2006


Terminal port and TSX P ACC 01 device

Switch configuration

General z Configuring line end adaptation


Line ends are adapted by the S2 switch as indicated below.
z Configuring the operating mode
The operating mode is selected by switch S1 as indicated below.
Illustration:
OFF

OFF
S1
Z

S2 S M
Uni-Telway end of line Uni-Telway
position slave or
character mode
OFF

OFF
S1
Z

S2 S M
Other positions Uni-Telway master

Note: The operating mode selected only concerns the connection cable leading to
the TER connector on the PLC processor.

35006178 05 November 2006 63


Terminal port and TSX P ACC 01 device

TSX P ACC 01 connector pin configuration

General The TSX P ACC 01 device has two parallel connectors, marked TER and AUX.
The signals are given below :

1 D(B) 1 D(B)
2 D(A) 2 D(A)
3 not connected 3 not connected
4 not connected 4 not connected
5 not connected 5 not connected
6 not connected 6 not connected
7 0V 7 not connected
8 5V 8 not connected

64 35006178 05 November 2006


Terminal port and TSX P ACC 01 device

3.6 Example of topologies

At a Glance

Aim of this This Section introduces examples of how to use the TSX P ACC 01 device.
Section

What's in this This section contains the following topics:


Section?
Topic Page
Connecting devices 66
Uni-Telway master mode 68
Uni-Telway slave mode 70
Connection between two PLCs 71

35006178 05 November 2006 65


Terminal port and TSX P ACC 01 device

Connecting devices

General The two TER and AUX ports on the TSX P ACC 01 device have the same standard
functions as the TER and AUX connectors on Premium/Atrium PLC station
processors.
z The TER connector on the device is used to connect any device which supports
Uni-Telway protocol, and in particular link up devices without their own power
supply (RS 485/RS 232 cable converter, etc)
z The AUX connector on the device is only used to connect devices with a power
supply (man-machine interface console, third-party devices etc).

Note: The TSX P ACC 01 device is supplied from the TER connector on the PLC
to which is it connected. As a result, the TER connector on the device enables
devices with their own power supply (Magelis, etc) or without their own power
supply (RS 485/RS 232 cable converter, etc) to be supplied.
If the user wants to connect the terminal port of a second PLC to one of the ports
on the TSX P ACC 01 device, the AUX connectors (on the device and PLC) must
be used to avoid power supply conflicts on the two PLCs.

Example 1:
Premium master Premium slave

T FTX CB 1020/1050

TSX P ACC 01

66 35006178 05 November 2006


Terminal port and TSX P ACC 01 device

Example 2:
Premium master TSX RKY

T FTX CB 1020/1050

Atrium slave

TSX P ACC 01

35006178 05 November 2006 67


Terminal port and TSX P ACC 01 device

Uni-Telway master mode

Example A TSX P ACC 01 device is connected to a Uni-Telway link master PLC as in the
example below.
Switches S1 and S2 must be positioned on OFF (master mode).

Example on a Premium station:


PC slave
Premium master

S1=OFF
S2=OFF
Addresses 1, 2, 3 TSX PCX 1031
Uni-Telway bus
TER AUX

TSX P ACC 01
TSX SCA 50 TSX SCA 62
XBT-Z 968

TSX CSC 015

ATV 16 slave Magelis slave TSX 17-20 slave


Address 6 Addresses 4/5 Addresses 7/8

1000 meters maximum

68 35006178 05 November 2006


Terminal port and TSX P ACC 01 device

Example on an Atrium station:


TSX RKY

X Bus

PC slave
Host PC

Atrium Master

S1=OFF
S2=OFF Uni-Telway bus
Addresses 1, 2, 3 TSX PCX 1031
TER AUX
TSX P ACC 01 TSX SCA 62
TSX SCA 50
XBT-Z 968

TSX CSC 015

ATV 16 slave Magelis slave TSX 17-20 slave


Address 6 Addresses 4/5 Addresses 7/8

1000 meters maximum

35006178 05 November 2006 69


Terminal port and TSX P ACC 01 device

Uni-Telway slave mode

Example A TSX P ACC 01 device is connected to a Uni-Telway link slave PLC as in the
example below.

Note: for a PLC to be able to operate in slave mode it must be connected to


a TSX P ACC 01 device by its built-in cable.

Illustration:

PC
TSX P CX 1031

TSX 107-40 master

S1=ON TSX CSB 015 S1=ON


S2=ON S2=ON
Uni-Telway bus
TER AUX TER AUX

TSX P ACC 01 TSX P ACC 01


TSX SCA 62
Premium

XBT-Z 968 X Bus

Atrium slave

Magelis

1000 meters maximum

70 35006178 05 November 2006


Terminal port and TSX P ACC 01 device

Connection between two PLCs

Reminders If the user wants to connect the terminal port of a second PLC on one of the ports of
the TSX P ACC 01 device, the AUX port must be used to avoid power supply
conflicts in the two PLCs.

Note: for a PLC to be able to operate in slave mode it must be connected to


a TSX P ACC 01 device by its built-in cable.

In the example given below the TSX P ACC 01 device must therefore be connected
to the Uni-Telway slave PLC by the device’s integrated cable. Its S1 switch must be
positioned on ON
If the device if not placed on a Uni-Telway bus, the position of the S2 switch does
not matter.
Illustration:
Premium master Premium slave
PC

T FTX CB1 XBT-Z 968


020/050
S1=ON
S2=not significant
TSX PCX1031
TER AUX

TSX P ACC 01 Magelis

35006178 05 November 2006 71


Terminal port and TSX P ACC 01 device