Profibus Setup Yokogawa Centum ALP121 (Master) to Siemens S7 417-4 (Slave) DP Port X2
Page |2
Profibus Setup Yokogawa Centum ALP121 (Master) to Siemens S7 417-4 (Slave) DP Port X2
Setup “Send” address range from Siemens Slave to Yokogawa DCS Master (Ensure
all settings are identical at Yokogawa end before downloading and connecting
Profibus cable)
Setup “Receive” address range from Yokogawa DCS Master to Siemens Slave
(Ensure all settings are identical at Yokogawa end before downloading and
connecting Profibus cable)
WARNING: A misconfiguration at either end will cause the PLC to STOP when
connecting the Profibus cable
Yokogawa Master Setup
Page |3
Profibus Setup Yokogawa Centum ALP121 (Master) to Siemens S7 417-4 (Slave) DP Port X2
In Sycon – Import S7 GSD file for relevant processor type and drag onto the profibus
connection of the ALP121 module.
Add virtual modules of choice (must align with Simatic configuration). Input in
Yokogawa must be matched with Output on Siemens.
Page |4
Profibus Setup Yokogawa Centum ALP121 (Master) to Siemens S7 417-4 (Slave) DP Port X2
Setup as above
Ensure “Enable DPV1” is Unchecked. Having this checked caused the PLC to
STOP.
Page |5
Profibus Setup Yokogawa Centum ALP121 (Master) to Siemens S7 417-4 (Slave) DP Port X2