First Floor RCP
First Floor RCP
First Floor RCP
UJVN LIMITED
Approval Stamp:
Approved by:
Date
Refer to protection notice ISO 16016
TABLE OF CONTENT
1. INTRODUCTION ................................................................................................................. 3
2. DESCRIPTION .................................................................................................................... 4
District Palwal - 121102 (Haryana) INDIA
Area/Equipment to be pro-
Detection system Suppression system
tected
Heat Detector Co2 flooding System
Hydro-Generators
(Existing system) (Existing system)
Automatic High Velocity Water Spray
Quartzite Bulb Detector
Generator Transformers System
(New supplied)
(New supplied)
Automatic High Velocity Water Spray
Quartzite Bulb Detector
System
25 MVA Power Transformers (1 No. – Existing
(1 No. – Existing
1 No. - New supplied)
1 No. - New supplied)
Automatic High Velocity Water Spray
Quartzite Bulb Detector
3.5 MVA Power Transformers System
(New supplied)
(New supplied)
Smoke Detection System &
Cable Tunnel Between Power Medium Velocity Water Spray Sys-
Manual Pull Stations At The
House And Outdoor tem
Exit Of The Tunnel.
Switchyard (New supplied)
(New supplied)
Smoke Detection System &
Control Room @ El. 1122.85 Portable Fire Extinguishers
Manual Pull Stations
(New supplied)
(New supplied)
Smoke Detection System &
Portable Fire Extinguishers
Office @ El. 1129.00 Manual Pull Stations
(New supplied)
(New supplied)
Foam Type Fire Extinguisher & Fire
Smoke Detection System &
Area of Oil Pressure Unit Of Hydrant At Suitable Point In The
Manual Pull Stations
Governor & MIV Turbine Floor.
(New supplied)
(New supplied)
Smoke Detection System & Fire Hydrants & Portable Fire Extin-
Power House Floors Manual Pull Stations. guishers
(New supplied) (New supplied)
Smoke Detection System & Portable Fire Extinguishers
Switchgear Room in
Refer to protection notice ISO 16016
2. DESCRIPTION
The firefighting system can be divided in following sub systems:
2.1. Water based firefighting system
2.2. C02 flooding system for generators
District Palwal - 121102 (Haryana) INDIA
This drawing is the PROPERTY of
2.1.3.Hydrant System
The water for the hydrant system of the power plant will be taken out of the water supply line. The water
will be leaded through a pipeline with a nominal diameter of 150mm to the hydrants.
Total 3 no. single headed outdoor hydrants (0SGA10 AA201 to 203) are installed in the power house out-
Refer to protection notice ISO 16016
side & other associated area. These will be replaced with the new supplied hydrants. Piping for these hy-
drants is in good condition and will be retained.
The fire hose cabinets (0SGA10 BU001 to 003) are installed near each outdoor hydrant. These will be re-
placed with new cabinets. The hose cabinet will be equipped with fire hose that could be served with wa-
ter out of the hydrant system and shall be 30m as a minimum.
Inside the power plant, no hydrant is installed currently. 8 nos. new hose cabinets (0SGX20 BU001 to
008) will be installed, to ensure that all areas of each floor could be reached by a water based fire extin-
guishing system. Each cabinet shall be equipped with and fire hose reel with 30m of hose and single head-
ed hydrant valve.
Piping containing water for filling and supply header will be heavy duty carbon steel ERW pipes as per
IS:1239.
Client UJVN LIMITED Internal N° =
Plant TILOTH HEP C-90-826477-018-02 +
File C-90-826477-018-02 Drawing N° Index Sheet 4
SaveDate 22-12-2017 TLH-FPS-2000 0 of 9 A4
DESIGN MEMORANDUM & CONTROL PHILOSOPHY
FIRE FIGHTING SYSTEM COMMON
2.1.4.HVWS system for generator transformer, 25 MVA power transformer & 3.5 MVA power trans-
former
1 no. 25 MVA transformer is provided with wet pilot type deluge valve station, spray & detection network
which is installed recently and is in good working condition. This will be retained. Other 3 nos. generator
District Palwal - 121102 (Haryana) INDIA
transformer, 1 no. 25 MVA transformer and 2 no. 3.5 MVA transformers are provided with dry pilot type
This drawing is the PROPERTY of
pneumatic operated deluge valve stations which will be replaced with wet pilot type deluge stations.
3 nos. generator transformers, 1 no. 25 MVA and 2 no. 3.5 MVA power transformers will be surrounded by
new supplied spray header ring and detection header ring. Spray header ring will be fitted with open high
velocity spray nozzles. The ring main will be connected to the water source header through a wet pilot del-
uge valve station (0SGC10 QH001, 0SGC11 QH001, 0SGC12 QH001, 0SGC21 QH001, 0SGC30 QH001
& 0SGC31 QH001). Deluge valve station will house the deluge valve, y strainer, valves, right angle cock,
water motor gong, pressure gauge, pressure switch etc.).
The spray header will remain charged with water under pressure up to the inlet of the deluge valve. Detec-
tion header ring will be pressurized with water tapped from the upstream of the deluge valve upto the
quartzite bulb (QB) detectors, rated at 79 Deg. C.
Density of discharge will be 10.2 lpm/m2 and the pressure at the hydraulically remotest nozzle will not be
less than 3.5 Kg/cm2 as per NFPA requirement.
The water motor gong will give the local alarm (mechanical) whenever spray system operates. The water
motor gong is a hydraulically driven mechanical bell, which makes continuous alarm when the spray sys-
tem operates.
All piping after new supplied deluge valve station (Spray & detection header piping) will also be
supplied new, water feed pipes upto deluge valve station will be hydro tested and retained if found
ok in hydro test, otherwise will be replaced.
Manual Release
Manual release is accomplished by pressing the push button at manual release station provided at DV
LCP.
The water motor gong will give the local alarm (mechanical) whenever spray system operates. The water
This drawing is the PROPERTY of
motor gong is a hydraulically driven mechanical bell, which makes continuous alarm when the spray sys-
tem operates.
2.1.7.Operation Philosophy of MVWS system for cable tunnel & cable tray room
The system is capable of automatic actuation by following Signals:
Multi-criteria smoke cum heat Detector installed in the cable tunnel will provide the fire signal. OR
Manual Release
Manual release is accomplished by pressing the push button at manual release station provided at DV
LCP.
Existing system will be connected with main fire alarm system so that it is show the fire alarm at main fire
alarm panel also.
Refer to protection notice ISO 16016
The detailed positions and dimensions of the different extinguishers shall be shown at the layout drawings
This drawing is the PROPERTY of
in detail.
Circuits for the call points and the detectors shall be same and those shall be shown separately
during detail engineering
The method of operation of all the call points shall be identical unless there is a special need for
differentiation.
The delay between the operation of a call point and the giving of general alarm shall not exceed 3
seconds.
Manual pull stations shall be fixed at a height of 1.4 meters above the floor level.
Manual pull station shall be break glass type and in fire red color.
3.4. Horn cum strobe.
3.5. Cabling.
This drawing is the PROPERTY of
All power and control cable of main fire alarm looping cable shall be FRLS copper conductor,
For power cable 2Cx2.5 sq.mm and for control 2Cx1.5 sq.mm cable respectively shall be provided.
Following alarm signal for unit shall be consider for HVAC interface
Common fire signal to HVAC control panel to close the air supply system.
For above signals necessary monitor and control relay module shall be provided and its detail shall be pro-
vided during detail engineering.
e) Deluge Valve
Body : Cast Steel – ASTM A216
Clapper : Bronze LTB-II
Seat : Bronze
Diaphragm : Neoprene
Valve assembly : Gun Metal
f) QB Detector
Frame : Bronze (Cr plated)
Button : Brass/copper
Bulb : Glass
Material of liquid : High expansion liquid
g) Hydrant valve
Body : LTB-318-II
Spindle : Brass Rod
Female outlet : LTB – 318 –II
Hand wheel : Cast Iron
Blank cap : LTB
h) Hose Pipe & Accessories
Hose : Reinforced Rubber Linend (RRL)
Branch Pipe : Gun Metal / Stainless Steel
Refer to protection notice ISO 16016
xxxxxxxxxxxxxxxxx