Open Building With Gable Roof: Procedure
Open Building With Gable Roof: Procedure
Open Building
with Gable Roof
Wind pressures for a typical open storage building are determined. Fig. G10-1
shows the dimensions and framing of the open buildings. The physical data
are as listed in Table G10-1.
Procedure
Wind loads on MWFRS are obtained using the Analytical (Directional)
Procedure of chapter 27, part 1, because the example building is an open
building. Even though the building height is h < 60 ft and qualifies as a
low-rise building by definition, adaptation of the low-rise “pseudo pressure”
coefficients of chapter 28, part 1, is not appropriate for this example building.
Therefore, the Directional Procedure of Section 27.4.1 is used.
C&C wind loads are obtained using provisions of chapter 30, part 5,
for open buildings.
Exposure
The building is located in a wooded area. Section 26.7.2 of the Standard
defines terrain roughness as Exposure B.
Enclosure Classification
The building has all walls open; it qualifies as an open building. Value of
(GCpi) = 0.0 (see Table 26.11-1 in the Standard).
Fig. G10-1
Building characteristics
for open building with
gable roof
Velocity Pressures
Velocity pressure is determined using equations from the Standard: Eq.
27.3-1 for MWFRS and Eq. 30.3-1 for C&C. The equation is the same for
MWFRS and C&C.
where
qz = velocity pressure at height z
Kz = exposure coefficient at height z and Kh at mean roof height
Kzt = 1.0 for homogeneous terrain (Section 26.8 of the Standard)
Kd = 0.85 for buildings (Table 26.6-1 of the Standard)
V = 105 mph (Fig. 26.5-1C of the Standard)
122 Wind Loads: Guide to the Wind Load Provisions of ASCE 7-10
Since Kz is constant in the 0 to 15 ft region, from Table 27.3-1 of the Standard
for MWFRS and Table 30.3-1 for C&C:
For MWFRS Kz = Kh = 0.57
For C&C Kz = Kh = 0.70
For MWFRS qh = 0.00256 (0.57) (1.0) (0.85) (105)2 = 13.7 psf
For C&C qh = 0.00256 (0.7) (1.0) (0.85) (105)2 = 16.8 psf
where
qh = velocity pressure evaluated at mean roof height h
G = gust effect factor
CN = net pressure coefficient value obtained from Fig. 27.4-4 through
Fig. 27.4-7 of the Standard.
Wind Loads: Guide to the Wind Load Provisions of ASCE 7-10 123
Wind Pressure for MWFRS
Calculated wind pressures for MWFRS are summarized in Table G10-3.
Figures G10-2 and G10-3 illustrate the design pressures (Case A and Case B)
for wind direction γ = 0° or 180° and γ = 90°, respectively.
where
qh = velocity pressure evaluated at mean roof height h
G = gust effect factor value determined from Section 26.9 of the
Standard
CN = net pressure coefficient value obtained from Fig. 30.8-2 of the
Standard
Table G10-3 Design Wind Pressures for MWFRS for Two Cases (psf )
Distance from
Wind direction, γ windward edge Case A Case B
Normal to ridge
γ = 0° or 180°
Windward 12.8 1.2
Leeward –4.6 –12.8
Parallel to ridge
γ = 90° 0 to 12 ft –9.3 9.3
12 to 14 ft –7.0 5.8
24 to 60 ft –3.5 3.5
Note: Positive numbers mean toward the surface; negative numbers mean away from
the surface.
124 Wind Loads: Guide to the Wind Load Provisions of ASCE 7-10
Fig. G10-2
Design pressures for
MWFRS for wind direction
γ = 0° or 180°
Zones for the pitched roof of this open building are shown in Fig. G10-4.
The panels and trusses are designed for the pressures indicated.
For trusses, two loading combinations need to be considered. The two
loading cases are shown in Fig. G10-5. Loading Case 1 is for Wind Directions
1 and 2 while Loading Case 2 is for Wind Direction 2. The loadings shown
for trusses are used for the design of truss and individual members. For
anchorage of the truss to frame support members, you may use MWFRS
loading.
126 Wind Loads: Guide to the Wind Load Provisions of ASCE 7-10
Table G10-5 Roof Component Design Pressure by Zone (psf )
Component Zone 3 Zone 2 Zone 1
Panel 31.4 –31.4 24.3 –24.3 15.7 –15.7
Truss 15.7 –15.7 15.7 –15.7 15.7 –15.7
Note: Positive numbers mean toward the surface; negative numbers mean away from
the surface. Note that Section 30.2.2 requires that a minimum pressure of 16 psf be
used.
Fig. G10-4
Pressure zones for panels
and trusses
Fig. G10-5
Loading cases for room
trusses
Comment
The pressures determined are limit state design pressures for strength design.
Section 2.3 of the Standard indicates load factor for wind load to be 1.0W for
loads determined in this example. If allowable stress design is to be used, the
load factor for wind load is 0.6W as shown in Section 2.4 of the Standard.
Wind Loads: Guide to the Wind Load Provisions of ASCE 7-10 127