Electrical Load List
Electrical Load List
2009.11.06
SHEET :
LOAD DATA Normal Fed by
Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power MS in
Item MCC/ASB REMARK Location
NOTE. MCC/
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive No.
ASB
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
PHASE 1
PM-0101A T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 1 3 6600 V 18.4 N 155.6 79.7 Y HT-201 MOTOR A200
PM-0101B T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 1 3 6600 V 18.4 N 155.6 79.7 Y HT-201 MOTOR A200
PM-0101C T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0.1 3 6600 V 18.4 S 15.6 8.0 Y HT-201 MOTOR A200
PM-0102A T-0102 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0.1 3 6600 V 18.4 S 15.6 8.0 Y HT-201 MOTOR A200
PM-0102B T-0102 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0.1 3 6600 V 18.4 S 15.6 8.0 Y HT-201 MOTOR A200
PM-0102C T-0102 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0.1 3 6600 V 18.4 S 15.6 8.0 Y HT-201 MOTOR A200
CM-0101A BOIL OFF GAS COMPRESSOR 810.0 kW 701.0 kW 95.0% 0.79 1 3 6600 V 94.4 N 737.9 572.7 Y HT-201 MOTOR A300
CM-0101B BOIL OFF GAS COMPRESSOR 810.0 kW 701.0 kW 95.0% 0.79 0.5 3 6600 V 94.4 I 368.9 286.3 Y HT-201 MOTOR A300
EM-0106 SUBMERGED COMBUSTION VAPORISER BLOWER 500.0 kW 450.0 kW 96.3% 0.86 0.1 3 6600 V 52.8 S 46.7 27.7 Y HT-201 MOTOR A300
PM-0104A HP SEND OUT PUMP 1629.0 kW 1241.0 kW 87.1% 0.91 1 3 6600 V 179.8 N 1424.8 649.2 Y HT-201 MOTOR A300
PM-0104B HP SEND OUT PUMP 1629.0 kW 1241.0 kW 87.1% 0.91 1 3 6600 V 179.8 N 1424.8 649.2 Y HT-201 MOTOR A300
PM-0104C HP SEND OUT PUMP 1629.0 kW 1241.0 kW 87.1% 0.91 0.1 3 6600 V 179.8 S 142.5 64.9 Y HT-201 MOTOR A300
PM-0301A GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 1 3 6600 V 82.8 N 647.4 331.7 Y HT-201 MOTOR A300
PM-0301B GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 0.1 3 6600 V 82.8 S 64.7 33.2 Y HT-201 MOTOR A300
PM-0301C GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 1 3 6600 V 82.8 N 647.4 331.7 Y HT-201 MOTOR A300
PM-0301D GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 0.1 3 6600 V 82.8 S 64.7 33.2 Y HT-201 MOTOR A300
CM-0701A AIR COMPRESSOR 250.0 kW 200.0 kW 95.9% 0.90 1 3 6600 V 25.3 N Y 208.6 101.0 Y HT-202 MOTOR A500
CM-0701B AIR COMPRESSOR 250.0 kW 200.0 kW 95.9% 0.90 0.1 3 6600 V 25.3 S Y 20.9 10.1 Y HT-202 MOTOR A500
P-1002A-LP ELECTRICAL FIRE WATER PUMP LOCAL PANEL 300.0 kW 270.8 kW 94.0% 0.90 0 3 6600 V 31.0 S 0.0 0.0 -- HT-201 POWER PNL. W/MS A700
P-1002B-LP ELECTRICAL FIRE WATER PUMP LOCAL PANEL 300.0 kW 270.8 kW 94.0% 0.90 0 3 6600 V 31.0 S 0.0 0.0 -- HT-201 POWER PNL. W/MS A700
COMPOSITION BUILDING (POWER,LTG,HVAC,ETC.) 850.0 KVA 850.0 KVA 100.0% 0.90 0.7 3 6600 V 74.4 N 535.5 259.4 (To be developed) -- HT-201 A900
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
6708.1 3541.3
PHASE 2
PM-0101D T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 1 3 6600 V 18.4 N 155.6 79.7 HT-201 MOTOR A200
PM-0101E T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 1 3 6600 V 18.4 N 155.6 79.7 HT-201 MOTOR A200
PM-0102D T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0 HT-201 MOTOR A200
PM-0102E T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0 HT-201 MOTOR A200
PM-0103A T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0 HT-201 MOTOR A200
PM-0103B T-0103 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0 HT-201 MOTOR A200
PM-0103C T-0103 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0 HT-201 MOTOR A200
PM-0103D T-0103 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0 HT-201 MOTOR A200
PM-0103E T-0103 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0 HT-201 MOTOR A200
CM-0101C BOIL OFF GAS COMPRESSOR 810.0 kW 729.0 kW 95.0% 0.79 0 3 6600 V 94.4 S 0.0 0.0 HT-201 MOTOR A300
PM-0104D HP SEND OUT PUMP 1629.0 kW 1241.0 kW 87.1% 0.91 1 3 6600 V 179.8 N 1424.8 649.2 HT-201 MOTOR A300
PM-0104E HP SEND OUT PUMP 1629.0 kW 1241.0 kW 87.1% 0.91 1 3 6600 V 179.8 N 1424.8 649.2 HT-201 MOTOR A300
PM-0301E GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 1 3 6600 V 82.8 N 647.4 331.7 HT-201 MOTOR A300
PM-0301F GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 0 3 6600 V 82.8 S 0.0 0.0 HT-201 MOTOR A300
PM-0301G GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 1 3 6600 V 82.8 N 647.4 331.7 HT-201 MOTOR A300
PM-0301H GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 0 3 6600 V 82.8 S 0.0 0.0 HT-201 MOTOR A300
kW kVAR
POWER CONSUMPTION ( PHASE 2 ) :
4455.5 2121.0
LOAD DATA Normal Fed by
Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power MS in
Item MCC/ASB REMARK Location
NOTE. MCC/
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive No.
ASB
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
Page of
ELECTRICAL LOAD SUMMARY (MV)
2009.10.21
SHEET : 1/2
LOAD DATA Normal Fed by
Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power MS in
Item REMARK Location
NOTE. MCC/
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive ASB
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
PHASE 1
B-0901 FLARE OBSTRUCTION LIGHT 4.0 kW 4.0 KW 100.0% 0.90 0.5 3 415 V 6.2 N Y 2.0 1.0 -- ELDB-301 A700
FLARE WINCH 2.2 kW 2.2 kW 84.5% 0.89 0 3 415 V 4.1 S 0.0 0.0 MC-301 To be chk. With Vendor Dwg. A700
LNG TANK
L-0101-001 T-0101 LIGHTING-01 50.0 kW 50.0 kW 100.0% 0.90 1 3 415 V 77.3 N 50.0 24.2 -- ELDB-301 A200
L-0101-002 T-0101 LIGHTING-02 50.0 kW 50.0 kW 100.0% 0.90 1 3 415 V 77.3 N 50.0 24.2 -- LDB-301 A200
L-0101-003 T-0101 LIGHTING-03 2.5 kW 2.5 kW 100.0% 0.90 1 3 415 V 3.9 N Y 2.5 1.2 -- LDB-301 A200
L-0102-001 T-0102 LIGHTING-01 50.0 kW 50.0 kW 100.0% 0.90 1 3 415 V 77.3 N 50.0 24.2 -- ELDB-301 A200
L-0102-002 T-0102 LIGHTING-02 50.0 kW 50.0 kW 100.0% 0.90 1 3 415 V 77.3 N 50.0 24.2 -- LDB-301 A200
L-0102-003 T-0102 LIGHTING-03 2.5 kW 2.5 kW 100.0% 0.90 1 3 415 V 3.9 N Y 2.5 1.2 -- LDB-301 A200
L-0101AW-001 T-0101 AIR CRAFT WARNING LIGHT PANEL 2.0 kW 2.0 kW 100.0% 0.90 0.5 3 415 V 3.1 N Y? 1.0 0.5 -- ELDB-301 A200
L-0102AW-001 T-0102 AIR CRAFT WARNING LIGHT PANEL 2.0 kW 2.0 kW 100.0% 0.90 0.5 3 415 V 3.1 N Y? 1.0 0.5 -- ELDB-301 A200
T-0101-EL T-0101 LIFT 6.9 kW 6.9 kW 84.6% 0.89 0 3 415 V 12.7 I Y? 0.0 0.0 -- EMC-301 A200
T-0101-CRANE T-0101 PUMP JIB CRANE 38.0 kW 38.0 kW 92.5% 0.92 0 3 415 V 62.1 S 0.0 0.0 -- MC-301 A200
T-0102-EL T-0102 LIFT 6.9 kW 6.9 kW 84.6% 0.89 0 3 414 V 12.8 I Y? 0.0 0.0 -- EMC-301 A200
T-0102-CRANE T-0102 PUMP JIB CRANE 38.0 kW 38.0 kW 92.5% 0.92 0 3 415 V 62.1 S 0.0 0.0 -- MC-301 A200
T-0101-DR-A T-0101 CATHODIC PROTECTION TRU-A 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9 -- MC-301 A200
T-0101-DR-B T-0101 CATHODIC PROTECTION TRU-B 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9 -- MC-301 A200
T-0101-DR-C T-0101 CATHODIC PROTECTION TRU-C 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9 -- MC-301 A200
T-0101-DR-D T-0101 CATHODIC PROTECTION TRU-D 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9 -- MC-301 A200
T-0102-DR-A T-0102 CATHODIC PROTECTION TRU-A 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9 -- MC-301 A200
T-0102-DR-B T-0102 CATHODIC PROTECTION TRU-B 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9 -- MC-301 A200
T-0102-DR-C T-0102 CATHODIC PROTECTION TRU-C 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9 -- MC-301 A200
T-0102-DR-D T-0102 CATHODIC PROTECTION TRU-D 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9 -- MC-301 A200
GTG
HM-301 CRANE FOR GTG 31.8 kW 31.8 kW 100.0% 0.85 0 3 415 V 52.0 S 0.0 0.0 -- MC-301 (Hold. To be chk) A800
HVAC FOR GTG BUILDING 50.0 KVA 50.0 KVA 100.0% 0.90 0.7 3 415 V 69.6 I 31.5 15.3 (To be developed) -- MC-301 A800
LTG FOR GTG BUILDING 16.0 KVA 16.0 KVA 100.0% 0.90 1 3 415 V 22.3 N 14.4 7.0 (To be developed) -- LDB-301 A800
EMG. LTG FOR GTG BUILDING 4.0 KVA 4.0 KVA 100.0% 0.90 1 3 415 V 5.6 N Y 3.6 1.7 (To be developed) -- ELDB-301 A800
G-0301A-MCC MCC FOR G-0301A GENERATOR 317.0 kW 100.0 kW 100.0% 0.85 1 3 415 V 518.8 N Y 100.0 62.0 -- EPC-301 POWER PNL. W/MS A800
G-0301B-MCC MCC FOR G-0301B GENERATOR 317.0 kW 100.0 kW 100.0% 0.85 1 3 415 V 518.8 N Y 100.0 62.0 -- EPC-301 POWER PNL. W/MS A800
G-0301C-MCC MCC FOR G-0301C GENERATOR 317.0 kW 100.0 kW 100.0% 0.85 0 3 415 V 518.8 S Y 0.0 0.0 -- EPC-301 POWER PNL. W/MS A800
HW
P-0307A HOT WATER PUMP 75.0 kW 61.0 kW 94.0% 0.91 0 3 415 V 122.0 S 0.0 0.0 Y PC-301 MOTOR A800
P-0307B HOT WATER PUMP 75.0 kW 61.0 kW 94.0% 0.91 0 3 415 V 122.0 S 0.0 0.0 Y PC-301 MOTOR A800
U-0521 CORROSION INHIBITOR UNIT 0.55 kW 0.4 kW 100.0% 0.85 1 3 415 V 0.9 N 0.4 0.2 -- MC-301 A800
DG
HVAC FOR DG BUILDING 3.0 KVA 3.0 KVA 100.0% 0.90 0 3 415 V 4.2 S 0.0 0.0 (To be developed) -- MC-301 A800
LTG FOR DG BUILDING 1.6 KVA 1.6 KVA 100.0% 0.90 1 3 415 V 2.2 N 1.4 0.7 (To be developed) -- LDB-301 A800
EMG. LTG FOR DG BUILDING 0.4 KVA 0.4 KVA 100.0% 0.90 1 3 415 V 0.6 N Y 0.4 0.2 (To be developed) -- ELDB-301 A800
HM-302 CRANE FOR DG 31.8 kW 31.8 kW 100.0% 0.85 0 3 415 V 52.0 S 0.0 0.0 -- MC-301 A800
G-0302-H DIESEL GENERATOR WATER HEATER 14.0 kW 11.0 kW 100.0% 1.00 0.5 3 415 V 19.5 I Y 5.5 0.0 -- EMC-301 A800
G-0302-RCP DIESEL GENERATOR CTR. PNL. 0.7 KVA 0.7 KVA 100.0% 0.85 1 1 240 V 2.9 N Y 0.6 0.4 -- EMC-301 A800
BOG COMP. -
CRANE FOR C-0101A/B 2.2 kW 2.2 kW 100.0% 0.85 0 3 415 V 3.6 S 0.0 0.0 -- MC-301 A300
C-0101A BOG COMP. OIL PUMP 5.5 kW 4.95 kW 84.6% 0.89 0 3 415 V 10.2 S 0.0 0.0 Y MC-301 MOTOR A300
C-0101B BOG COMP. OIL PUMP 5.5 kW 4.95 kW 84.6% 0.89 0 3 415 V 10.2 S 0.0 0.0 Y MC-301 MOTOR A300
C-0101A BOG COMP. OIL COOLER 0.75 kW 0.68 kW 76.0% 0.87 1 3 415 V 1.6 N 0.9 0.5 Y MC-301 MOTOR A300
C-0101B BOG COMP. OIL COOLER 0.75 kW 0.68 kW 76.0% 0.87 1 3 415 V 1.6 N 0.9 0.5 Y MC-301 MOTOR A300
C-0101A BOG COMP. TURNING DEVICE 2.2 kW 1.98 kW 84.5% 0.89 0 3 415 V 4.1 S 0.0 0.0 Y MC-301 MOTOR A300
C-0101B BOG COMP. TURNING DEVICE 2.2 kW 1.98 kW 84.5% 0.89 0 3 415 V 4.1 S 0.0 0.0 Y MC-301 MOTOR A300
E0106 SCV
PM-0106 E-0106 SCV COOLING WATER PUMP 5.5 kW 4.95 kW 84.6% 0.89 0 3 415 V 10.2 S 0.0 0.0 Y MC-301 MOTOR A300
E-0106 PANEL LIGHTING 1.0 KVA 1.0 KVA 100.0% 0.90 1 1 240 V 4.2 N 0.9 0.4 -- LDB-301 A300
E-0106 ACOUSTIC COOLING FAN 0.25 kW 0.23 kW 76.0% 0.87 0 3 415 V 0.5 S 0.0 0.0 Y MC-301 MOTOR A300
GW
PM-0302 GLYCOL WATER DRAIN PUMP 3.7 kW 2.6 kW 84.5% 0.89 0 3 415 V 6.8 S 0.0 0.0 Y MC-301 MOTOR A300
PM-0303A GLYCOL WATER PUMP 55.0 kW 44.0 KW 93.3% 0.89 0 3 415 V 92.1 S 0.0 0.0 Y MC-301 MOTOR A300
PM-0303B GLYCOL WATER PUMP 55.0 kW 44.0 KW 93.3% 0.89 0 3 415 V 92.1 S 0.0 0.0 Y MC-301 MOTOR A300
LOAD DATA Normal Fed by
Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power MS in
Item MCC/ASB REMARK Location
NOTE. MCC/
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive No.
ASB
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
EM-301A1-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-302 MOTOR A400
EM-301A1-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-302 MOTOR, w/VFD in SS A400
EM-301A2-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-302 MOTOR A400
EM-301A2-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-302 MOTOR, w/VFD in SS A400
EM-301A3-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-302 MOTOR A400
EM-301A3-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-302 MOTOR, w/VFD in SS A400
EM-301A4-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-302 MOTOR A400
EM-301A4-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-302 MOTOR, w/VFD in SS A400
EM-301A5-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-302 MOTOR A400
EM-301A5-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-302 MOTOR, w/VFD in SS A400
EM-301A6-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-302 MOTOR A400
EM-301A6-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-302 MOTOR, w/VFD in SS A400
EM-301A7-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-303 MOTOR A400
EM-301A7-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-303 MOTOR, w/VFD in SS A400
EM-301A8-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-303 MOTOR A400
EM-301A8-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-303 MOTOR, w/VFD in SS A400
EM-301A9-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-303 MOTOR A400
EM-301A9-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-303 MOTOR, w/VFD in SS A400
EM-301A10-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-303 MOTOR A400
EM-301A10-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-303 MOTOR, w/VFD in SS A400
EM-301A11-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-303 MOTOR A400
EM-301A11-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-303 MOTOR, w/VFD in SS A400
EM-301A12-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-304 MOTOR A400
EM-301A12-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-304 MOTOR, w/VFD in SS A400
EM-301A13-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-304 MOTOR A400
EM-301A13-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-304 MOTOR, w/VFD in SS A400
EM-301A14-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-304 MOTOR A400
EM-301A14-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-304 MOTOR, w/VFD in SS A400
EM-301A15-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 Y MC-304 MOTOR A400
EM-301A15-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1 -- MC-304 MOTOR, w/VFD in SS A400
EM-301A16-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0 Y MC-304 MOTOR A400
EM-301A16-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0 -- MC-304 MOTOR, w/VFD in SS A400
EM-301A17-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0 Y MC-304 MOTOR A400
ELECTRICAL LOAD SUMMARY NORMAL LTG. D.B. (LDB-301) Page of
2009.11.06
SHEET :
LOAD DATA Normal Fed by
Item Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power
NOTE.
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
PHASE 1
L-0101-002 T-0101 LIGHTING-02 20.0 kW 20.0 kW 100.0% 0.90 1 3 415 V 30.9 N 20.0 9.7
L-0101-003 T-0101 LIGHTING-03 20.0 kW 20.0 kW 100.0% 0.90 1 3 415 V 30.9 N 20.0 9.7
L-0102-002 T-0102 LIGHTING-02 20.0 kW 20.0 kW 100.0% 0.90 1 3 415 V 30.9 N 20.0 9.7
L-0102-003 T-0102 LIGHTING-03 20.0 kW 20.0 kW 100.0% 0.90 1 3 415 V 30.9 N 20.0 9.7
LTG FOR GTG BUILDING 16.0 KVA 16.0 KVA 100.0% 0.90 1 3 415 V 22.3 N 14.4 7.0 (To be developed)
LTG FOR DG BUILDING 1.6 KVA 1.6 KVA 100.0% 0.90 1 3 415 V 2.2 N 1.4 0.7 (To be developed)
E-0106 PANEL LIGHTING 1.0 KVA 1.0 KVA 100.0% 0.90 1 1 240 V 4.2 N 0.9 0.4
LTG FOR N2 ANALYSER HOUSE 0.8 kW 0.8 kW 100.0% 0.90 1 3 415 V 1.2 N 0.8 0.4 (To be developed)
LTG FOR METERING ANALYSER HOUSE 0.8 kW 0.8 kW 100.0% 0.90 1 3 415 V 1.2 N 0.8 0.4 (To be developed)
FEEDER FOR OWNER 125A(LTG,) 76.37 kW 76.37 kW 100.0% 0.90 1 3 415 V 118.1 N 76.4 37.0 (To be developed)
MAIN SUBSTATION (LTG,) 24.0 KVA 24.0 KVA 100.0% 0.90 1 3 415 V 33.4 N 21.6 10.5 (To be developed)
CONTROL BUILDING (LTG) 32.0 KVA 32.0 KVA 100.0% 0.90 1 3 415 V 44.5 N 28.8 13.9 (To be developed)
LABORATORY (LTG.) 20.0 KVA 20.0 KVA 100.0% 0.90 1 3 415 V 27.8 N Y 18.0 8.7 (To be developed)
FIRE STATION (LTG) 2.4 KVA 2.4 KVA 100.0% 0.90 1 3 415 V 3.3 N Y 2.2 1.0 (To be developed)
MAINTENNANCE BUILDING (LTG,) 16.0 KVA 16.0 KVA 100.0% 0.90 1 3 415 V 22.3 N Y 14.4 7.0 (To be developed)
FWPH SUMP AND FOAM HOUSE (LTG.) 0.8 KVA 0.8 KVA 100.0% 0.90 1 3 415 V 1.1 N Y 0.7 0.3 (To be developed)
SECURITY ROOM (LTG,) 0.25 KVA 0.25 KVA 100.0% 0.90 1 3 415 V 0.3 N Y 0.2 0.1 (To be developed)
TRUCK LOADING OPERATOR CABIN (LTG.) 1.2 KVA 1.2 KVA 100.0% 0.90 1 3 415 V 1.7 N Y 1.1 0.5 (To be developed)
AREA A300 LIGHTING 15.0 kW 15.0 kW 100.0% 0.90 1 3 415 V 23.2 N 15.0 7.3 (To be developed)
AREA A400 LIGHTING 10.0 kW 10.0 kW 100.0% 0.90 1 3 415 V 15.5 N 10.0 4.8 (To be developed)
AREA A500 LIGHTING 5.0 kW 5.0 kW 100.0% 0.90 1 3 415 V 7.7 N 5.0 2.4 (To be developed)
AREA A600 LIGHTING 2.5 kW 2.5 kW 100.0% 0.90 1 3 415 V 3.9 N Y 2.5 1.2 (To be developed)
AREA A700 LIGHTING 2.5 kW 2.5 kW 100.0% 0.90 1 3 415 V 3.9 N 2.5 1.2 (To be developed)
ROAD LIGHTING 100.0 kW 100.0 kW 100.0% 0.90 1 3 415 V 154.6 N 100.0 48.4 (To be developed)
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
396.7 192.1
PHASE 2
L-0103-002 T-0103 LIGHTING-02 20.0 kW 20.0 kW 100.0% 0.90 1 3 415 V 30.9 N 20.0 9.7
L-0103-003 T-0103 LIGHTING-03 20.0 kW 20.0 kW 100.0% 0.90 1 3 415 V 30.9 N 20.0 9.7
kW kVAR
POWER CONSUMPTION ( PHASE 2 ) :
40.0 19.4
kW kVAR
POWER CONSUMPTION ( PHASE 1 & 2 ) :
436.7 211.5
485.2 KVA
Page of
ELECTRICAL LOAD SUMMARY FOR EMG. LTG. D.B.(ELDB-301) (MV)
2009.11.06
SHEET : 1/2
LOAD DATA Normal Fed by
Item Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power
NOTE.
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
PHASE 1
B-0901 FLARE OBSTRUCTION LIGHT 4.0 kW 4.0 KW 100.0% 0.90 0.5 3 415 V 6.2 N Y 2.0 1.0
L-0101-001 T-0101 LIGHTING-01 20.0 kW 20.0 kW 100.0% 0.90 1 3 415 V 30.9 N Y(Note.2) 20.0 9.7
L-0102-001 T-0102 LIGHTING-01 20.0 kW 20.0 kW 100.0% 0.90 1 3 415 V 30.9 N Y(Note.2) 20.0 9.7
L-0101AW-001 T-0101 AIR CRAFT WARNING LIGHT PANEL 1.0 kW 1.0 kW 100.0% 0.90 0.5 3 415 V 1.5 N Y 0.5 0.2
L-0102AW-001 T-0102 AIR CRAFT WARNING LIGHT PANEL 1.0 kW 1.0 kW 100.0% 0.90 0.5 3 415 V 1.5 N Y 0.5 0.2
EMG. LTG FOR GTG BUILDING 4.0 KVA 4.0 KVA 100.0% 0.90 1 3 415 V 5.6 N 3.6 1.7 (To be developed)
EMG. LTG FOR DG BUILDING 0.4 KVA 0.4 KVA 100.0% 0.90 1 3 415 V 0.6 N 0.4 0.2 (To be developed)
EMG. LTG FOR N2 ANALYSER HOUSE 0.2 kW 0.2 kW 100.0% 0.90 1 3 415 V 0.3 N 0.2 0.1 (To be developed)
EMG. LTG FOR METERING ANALYSER HOUSE 0.2 kW 0.2 kW 100.0% 0.90 1 3 415 V 0.3 N 0.2 0.1 (To be developed)
MAIN SUBSTATION (EMG.LTG,) 6.0 KVA 6.0 KVA 100.0% 0.90 1 3 415 V 8.3 N 5.4 2.6 (To be developed)
CONTROL BUILDING (EMG.LTG) 8.0 KVA 8.0 KVA 100.0% 0.90 1 3 415 V 11.1 N 7.2 3.5 (To be developed)
LABORATORY (EMG.LTG.) 5.0 KVA 5.0 KVA 100.0% 0.90 1 3 415 V 7.0 N Y 4.5 2.2 (To be developed)
FIRE STATION (EMG.LTG) 0.6 KVA 0.6 KVA 100.0% 0.90 1 3 415 V 0.8 N Y 0.5 0.3 (To be developed)
MAINTENNANCE BUILDING (EMG.LTG,) 4.0 KVA 4.0 KVA 100.0% 0.90 1 3 415 V 5.6 N Y 3.6 1.7 (To be developed)
FWPH SUMP AND FOAM HOUSE (EMG.LTG.) 0.2 KVA 0.2 KVA 100.0% 0.90 1 3 415 V 0.3 N Y 0.2 0.1 (To be developed)
SECURITY ROOM (EMG.LTG,) 0.25 KVA 0.25 KVA 100.0% 0.90 1 3 415 V 0.3 N Y 0.2 0.1 (To be developed)
TRUCK LOADING OPERATOR CABIN (EMG.LTG.) 0.2 KVA 0.2 KVA 100.0% 0.90 1 3 415 V 0.3 N Y 0.2 0.1 (To be developed)
AREA A300 EMG. LIGHTING kW 3.0 kW 100.0% 0.90 1 3 415 V 0.0 N Y 3.0 1.5 (To be developed)
AREA A400 EMG. LIGHTING kW 2.0 kW 100.0% 0.90 1 3 415 V 0.0 N 2.0 1.0 (To be developed)
AREA A500 EMG. LIGHTING kW 1.0 kW 100.0% 0.90 1 3 415 V 0.0 N Y 1.0 0.5 (To be developed)
AREA A600 EMG LIGHTING kW 0.5 kW 100.0% 0.90 1 3 415 V 0.0 N Y 0.5 0.2 (To be developed)
AREA A700 EMG LIGHTING kW 0.5 kW 100.0% 0.90 1 3 415 V 0.0 N 0.5 0.2 (To be developed)
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
76.2 36.9
PHASE 2
L-0103AW-001 T-0103 AIR CRAFT WARNING LIGHT PANEL 1.0 kW 1.0 kW 100.0% 0.90 1 3 415 V 1.5 N 1.0 0.5
L-0103-001 T-0103 LIGHTING-01 20.0 kW 20.0 kW 100.0% 0.90 1 3 415 V 30.9 N Y(Note.2) 20.0 9.7
kW kVAR
POWER CONSUMPTION ( PHASE 2 ) :
21.0 10.2
kW kVAR
POWER CONSUMPTION ( PHASE 1 & 2 ) :
97.2 47.1
2 108.0 KVA
Transformer Rating 125.0 KVA
3 Total Amps 173.9 Amps
Bus Bar Rating 200.0 Amps
Page of
ELECTRICAL LOAD SUMMARY EMERGENCY LTG. D.B. (JETTY)
2009.11.06
SHEET : 1/1
LOAD DATA Normal FEEDER
Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by ed by
Emg. Absorbed power
Item
NOTE.
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive
Unit Unit % pu pu V A N/S kW kVAR
PHASE 1
INDOOR LIGHTING 3.0 kVA 3.0 kVA 100.0% 0.9 1 3 415 V 4.2 N Y 2.7 1.3 (To be developed)
OUTDOOR LIGHTING 10.0 kVA 10.0 kVA 100.0% 0.9 1 3 415 V 13.9 N Y 9.0 4.4 (To be developed)
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
11.7 5.7
PHASE 2
NONE
kW kVAR
POWER CONSUMPTION ( PHASE 2 ) :
0.0 0.0
kW kVAR
POWER CONSUMPTION ( PHASE 1 & 2 ) :
11.7 5.7
Page of
ELECTRICAL LOAD SUMMARY 415V EMG. MCC (EMC-301) (MV)
2009.11.06
SHEET : 1/2
LOAD DATA Normal Fed by
Item Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power
NOTE.
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
PHASE 1
T-0101-EL T-0101 LIFT 5.9 kW 5.9 kW 84.6% 0.89 0 3 415 V 10.9 I Y 0.0 0.0
T-0102-EL T-0102 LIFT 5.9 kW 5.9 kW 84.6% 0.89 0 3 414 V 10.9 I Y 0.0 0.0
G-0302-H DIESEL GENERATOR WATER HEATER 14.0 kW 11.0 kW 100.0% 1.00 0.5 3 415 V 19.5 I Y 5.5 0.0
G-0302-RCP DIESEL GENERATOR CTR. PNL. 0.7 KVA 0.7 KVA 100.0% 0.85 1 1 240 V 2.9 N Y 0.6 0.4
PM-0614A POTABLE WATER PUMP 1.5 kW 1.12 kW 82.0% 0.84 1 3 415 V 3.0 N Y 1.4 0.9
PM-0614B POTABLE WATER PUMP 1.5 kW 1.12 kW 82.0% 0.84 0 3 415 V 3.0 S Y 0.0 0.0
P-1004A-LP HI-EX FOAM PUMP LOCAL PANEL 3.7 KW 3.7 KW 100.0% 0.85 0 3 415 V 6.1 S Y 0.0 0.0
P-1004B-LP HI-EX FOAM PUMP LOCAL PANEL 3.7 KW 3.7 KW 100.0% 0.85 0 3 415 V 6.1 S Y 0.0 0.0
U-0701A INSTRUMENT AIR DRYER A 36.0 kW 28.8 kW 100.0% 0.90 1 3 415 V 55.6 N Y 28.8 13.9
U-0701B INSTRUMENT AIR DRYER B 36.0 kW 28.8 kW 100.0% 0.90 0 3 415 V 55.6 S Y 0.0 0.0
EF-0710A COOLING TOWER FAN A 11.0 kW 10.0 kW 88.1% 0.85 1 3 415 V 20.4 N Y 11.4 7.0
EF-0710B COOLING TOWER FAN B 11.0 kW 10.0 kW 88.1% 0.85 0 3 415 V 20.4 S Y 0.0 0.0
PM-0710A COOLING WATER PUMP A 11.0 kW 7.25 kW 88.1% 0.85 1 3 415 V 20.4 N Y 8.2 5.1
PM-0710B COOLING WATER PUMP B 11.0 kW 7.25 kW 88.1% 0.85 0 3 415 V 20.4 S Y 0.0 0.0
COMPOSITION BUILDING 63A Feeder (EMERGENCY POWE 36.23 kW 36.23 kW 100.0% 0.90 0.7 3 415 V 56.0 N Y 25.4 12.3 (To be developed)
MAIN SUBSTATION (EMERGENCY POWER) KVA KVA 100.0% 0.90 0.7 3 415 V 0.0 N Y 0.0 0.0 (To be developed)
LABORATORY (EMERGENCY POWER) KVA KVA 100.0% 0.90 0.7 3 415 V 0.0 N Y 0.0 0.0 (To be developed)
CONTROL BUILDING (EMERGENCY POWER) KVA KVA 100.0% 0.90 0.7 3 415 V 0.0 N Y 0.0 0.0 (To be developed)
FIRE STATION (EMERGENCY POWER) KVA KVA 100.0% 0.90 0.7 3 415 V 0.0 N Y 0.0 0.0 (To be developed)
MAINTENNANCE BUILDING (EMERGENCY POWER) KVA KVA 100.0% 0.90 0.7 3 415 V 0.0 N Y 0.0 0.0 (To be developed)
FWPH SUMP AND FOAM HOUSE (POWER) 1.0 KVA 1.0 KVA 100.0% 0.90 0 3 415 V 1.4 S Y 0.0 0.0 (To be developed)
FWPH SUMP AND FOAM HOUSE (HVAC) 1.0 KVA 1.0 KVA 100.0% 0.90 0 3 415 V 1.4 S Y 0.0 0.0 (To be developed)
SECURITY ROOM (POWER,) 0.25 KVA 0.25 KVA 100.0% 0.90 0.7 3 415 V 0.3 N Y 0.2 0.1 (To be developed)
SECURITY ROOM (HVAC.) 0.5 KVA 0.5 KVA 100.0% 0.90 0.7 3 415 V 0.7 I Y 0.3 0.2 (To be developed)
TRUCK LOADING OPERATOR CABIN (POWER.) 1.5 KVA 1.5 KVA 100.0% 0.90 0.7 3 415 V 2.1 N Y 0.9 0.5 (To be developed)
TRUCK LOADING OPERATOR CABIN (HVAC) 2.0 KVA 2.0 KVA 100.0% 0.90 0.7 3 415 V 2.8 I Y 1.3 0.6 (To be developed)
AUX. POWER FOR TR-11 2.0 kVA 2.0 kVA 100.0% 0.85 0 3 240 V 8.3 S Y 0.0 0.0
AUX. POWER FOR TR-12 2.0 kVA 2.0 kVA 100.0% 0.85 0 3 240 V 8.3 S Y 0.0 0.0
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
83.9 40.9
Page of
ELECTRICAL LOAD SUMMARY 415V NORMAL MCC(MC-301)
2009.11.06
SHEET : 1/2
LOAD DATA Normal Fed by
Item Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power
NOTE.
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
PHASE 1
FLARE WINCH 2.2 kW 2.2 kW 84.5% 0.89 0 3 415 V 4.1 S 0.0 0.0
T-0101-CRANE T-0101 PUMP JIB CRANE 38.0 kW 38.0 kW 92.5% 0.92 0 3 415 V 62.1 S 0.0 0.0
T-0102-CRANE T-0102 PUMP JIB CRANE 38.0 kW 38.0 kW 92.5% 0.92 0 3 415 V 62.1 S 0.0 0.0
T-0101-DR-A T-0101 CATHODIC PROTECTION TRU-A 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9
T-0101-DR-B T-0101 CATHODIC PROTECTION TRU-B 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9
T-0101-DR-C T-0101 CATHODIC PROTECTION TRU-C 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9
T-0101-DR-D T-0101 CATHODIC PROTECTION TRU-D 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9
T-0102-DR-A T-0102 CATHODIC PROTECTION TRU-A 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9
T-0102-DR-B T-0102 CATHODIC PROTECTION TRU-B 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9
T-0102-DR-C T-0102 CATHODIC PROTECTION TRU-C 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9
T-0102-DR-D T-0102 CATHODIC PROTECTION TRU-D 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9
HM-301 CRANE FOR GTG 31.8 kW 31.8 kW 100.0% 0.85 0 3 415 V 52.0 S 0.0 0.0
HVAC FOR GTG BUILDING 50.0 KVA 50.0 KVA 100.0% 0.90 0.7 3 415 V 69.6 I 31.5 15.3 (To be developed)
P-330A HOT WATER DRAIN PUMP 3.7 kW 2.1 kW 84.5% 0.89 1 3 415 V 6.8 N 0.0 0.0
P-330B HOT WATER DRAIN PUMP 3.7 kW 2.1 kW 84.5% 0.89 0 3 415 V 6.8 S 0.0 0.0
U-0521 CORROSION INHIBITOR UNIT 0.55 kW 0.4 kW 100.0% 0.85 1 3 415 V 0.9 N 0.4 0.2
HVAC FOR DG BUILDING 3.0 KVA 3.0 KVA 100.0% 0.90 0 3 415 V 4.2 S 0.0 0.0 (To be developed)
HM-302 CRANE FOR DG 31.8 kW 31.8 kW 100.0% 0.85 0 3 415 V 52.0 S 0.0 0.0
CRANE FOR C-0101A/B 2.2 kW 2.2 kW 100.0% 0.85 0 3 415 V 3.6 S 0.0 0.0
C-0101A BOG COMP. OIL PUMP 5.5 kW 4.95 kW 84.6% 0.89 0 3 415 V 10.2 S 0.0 0.0
C-0101B BOG COMP. OIL PUMP 5.5 kW 4.95 kW 84.6% 0.89 0 3 415 V 10.2 S 0.0 0.0
C-0101A BOG COMP. OIL COOLER 0.75 kW 0.68 kW 76.0% 0.87 1 3 415 V 1.6 N 0.9 0.5
C-0101B BOG COMP. OIL COOLER 0.75 kW 0.68 kW 76.0% 0.87 1 3 415 V 1.6 N 0.9 0.5
C-0101A BOG COMP. TURNING DEVICE 2.2 kW 1.98 kW 84.5% 0.89 0 3 415 V 4.1 S 0.0 0.0
C-0101B BOG COMP. TURNING DEVICE 2.2 kW 1.98 kW 84.5% 0.89 0 3 415 V 4.1 S 0.0 0.0
C-0101A FRAME OIL HEATER 10.0 kW 12.0 kW 100.0% 1.00 0 3 415 V 13.9 S 0.0 0.0
C-0101B FRAME OIL HEATER 10.0 kW 12.0 kW 100.0% 1.00 0 3 415 V 13.9 S 0.0 0.0
PM-0106 E-0106 SCV COOLING WATER PUMP 5.5 kW 4.95 kW 84.6% 0.89 0 3 415 V 10.2 S 0.0 0.0
E-0106 ACOUSTIC COOLING FAN 0.25 kW 0.23 kW 76.0% 0.87 0 3 415 V 0.5 S 0.0 0.0
PM-0302 GLYCOL WATER DRAIN PUMP 3.7 kW 2.6 kW 84.5% 0.89 0 3 415 V 6.8 S 0.0 0.0
PM-0303A GLYCOL WATER PUMP 55.0 kW 44.0 KW 93.3% 0.89 1 3 415 V 92.1 N 47.2 24.2
PM-0303B GLYCOL WATER PUMP 55.0 kW 44.0 KW 93.3% 0.89 0 3 415 V 92.1 S 0.0 0.0
U-0522 BIOCIDE DOESING UNIT 0.55 kW 0.4 kW 100.0% 0.85 1 3 415 V 0.9 N 0.4 0.2
U-0523 O2 SCAVENGER UNIT 0.55 kW 0.4 kW 100.0% 0.85 1 3 415 V 0.9 N 0.4 0.2
PM-0401A DIESEL OIL PUMP 0.75 kW 0.6 kW 76.0% 0.87 1 3 415 V 1.6 N 0.8 0.4
PM-0401B DIESEL OIL PUMP 0.75 kW 0.6 kW 76.0% 0.87 0 3 415 V 1.6 S 0.0 0.0
PM-402A GTG DIESEL OIL PUMP 2.2 kW 1.52 kW 84.5% 0.89 1 3 415 V 4.1 N 1.8 0.9
PM-402B GTG DIESEL OIL PUMP 2.2 kW 1.52 kW 84.5% 0.89 0 3 415 V 4.1 S 0.0 0.0
PM-0601A SERVICE WATER PUMP 15.0 kW 11.0 kW 87.0% 0.85 1 3 415 V 28.2 N 12.6 7.8
PM-0601B SERVICE WATER PUMP 15.0 kW 11.0 kW 87.0% 0.85 0 3 415 V 28.2 S 0.0 0.0
PM-0611A RAW WATER PUMP 1.5 kW 1.3 kW 82.0% 0.84 1 3 415 V 3.0 N 1.6 1.0
PM-0611B RAW WATER PUMP 1.5 kW 1.3 kW 82.0% 0.84 0 3 415 V 3.0 S 0.0 0.0
U0613 BOOSTER PUMP 0.75 kW 0.6 kW 76.0% 0.87 1 3 415 V 1.6 N 0.8 0.4
U0613 BOOSTER PUMP 0.75 kW 0.6 kW 76.0% 0.87 0 3 415 V 1.6 S 0.0 0.0
CRANE FOR FW PUMP BUILDING 13.25 kW 13.25 kW 100.0% 0.85 0 3 415 V 21.7 S 0.0 0.0
CRANE FOR AIR COMPRSSOR SHED 28.7 kW 28.7 kW 100.0% 0.85 0 3 415 V 47.0 S 0.0 0.0
CRANE FOR NITROGEN SHELTER 31.8 kW 31.8 kW 100.0% 0.85 0 3 415 V 52.0 S 0.0 0.0
HVAC FOR N2 ANALYSER HOUSE 2.0 kW 2.0 kW 100.0% 0.90 0.5 3 415 V 3.1 I 1.0 0.5 (To be developed)
CRANE FOR METERING SHED 28.7 kW 28.7 kW 100.0% 0.85 0 3 415 V 47.0 S 0.0 0.0
HVAC FOR METERING ANALYSER HOUSE 2.0 kW 2.0 kW 100.0% 0.90 0.5 3 415 V 3.1 I 1.0 0.5 (To be developed)
CRANE FOR P-104A/B/C 2.2 kW 2.2 kW 100.0% 0.85 0 3 415 V 3.6 S 0.0 0.0
PM-0503 DRAINAGE PUMP 1.5 kW 1.42 kW 82.0% 0.84 0 3 415 V 3.0 S 0.0 0.0
PM-0504 DRAINAGE PUMP 1.1 kW 1.0 kW 79.5% 0.86 0 3 415 V 2.2 S 0.0 0.0
PM-0310A CHILLED WATER PUMP BACK-UP SYSTEM 7.5 kW 6.75 kW 88.0% 0.91 0 3 415 V 13.0 S 0.0 0.0
PM-0310B CHILLED WATER PUMP BACK-UP SYSTEM 7.5 kW 6.75 kW 88.0% 0.91 0 3 415 V 13.0 S 0.0 0.0
U-0113 SAMPLING UNITS FOR GC 0.5 kVA 0.5 kVA 100.0% 0.90 0 1 240 V 2.1 N 0.0 0.0
AREA A400 RECEPTACLE kW kW 100.0% 0.90 0 3 415 V 0.0 S 0.0 0.0 (To be developed)
AREA A400 WELDING RECEPTACLE kW kW 100.0% 0.90 0 3 415 V 0.0 S 0.0 0.0 (To be developed)
AREA A500 RECEPTACLE 86.4 kW 86.4 kW 100.0% 0.90 0 3 415 V 133.6 S 0.0 0.0 (To be developed)
AREA A500 WELDING RECEPTACLE 210.0 kW 210.0 kW 100.0% 0.90 0 3 415 V 324.6 S 0.0 0.0 (To be developed)
AREA A700 RECEPTACLE 61.2 kW 61.2 kW 100.0% 0.90 0 3 415 V 94.6 S 0.0 0.0 (To be developed)
AREA A700 WELDING RECEPTACLE 175.0 kW 175.0 kW 100.0% 0.90 0 3 415 V 270.5 S 0.0 0.0 (To be developed)
WT-2 WATCH TOWER 1.0 KVA 1.0 KVA 100.0% 0.90 1 3 415 V 1.4 N 0.9 0.4 (To be developed)
WT-4 WATCH TOWER 1.0 KVA 1.0 KVA 100.0% 0.90 1 3 415 V 1.4 N 0.9 0.4 (To be developed)
WT-5 WATCH TOWER 1.0 KVA 1.0 KVA 100.0% 0.90 1 3 415 V 1.4 N 0.9 0.4 (To be developed)
WT-6 WATCH TOWER 1.0 KVA 1.0 KVA 100.0% 0.90 1 3 415 V 1.4 N 0.9 0.4 (To be developed)
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
CATHODIC PROTECTION TRU 3.75 KVA 2.5 KVA 100.0% 0.90 1 3 415 V 5.2 N 2.3 1.1
PM-0311A CONDENSATE WATER TRANSFER PUMP 15.0 kW 10.0 kW 87.0% 0.85 1 3 415 V 28.2 N 11.5 7.1
PM-0311B CONDENSATE WATER TRANSFER PUMP 15.0 kW 10.0 kW 87.0% 0.85 0 3 415 V 28.2 S 0.0 0.0
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
187.9 96.4
Page of
ELECTRICAL LOAD SUMMARY 415V NORMAL MCC(MC-302)
2009.11.06
SHEET : 1/2
LOAD DATA Normal Fed by
Item Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power
NOTE.
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
PHASE 1
EM-301A1-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A1-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A2-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A2-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A3-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A3-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A4-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A4-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A5-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A5-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A6-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A6-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
368.4 157.0
Page of
ELECTRICAL LOAD SUMMARY 415V NORMAL MCC(MC-303)
2009.11.06
SHEET : 1/2
PHASE 1
EM-301A7-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A7-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A8-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A8-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A9-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A9-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A10-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A10-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A11-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A11-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
307.0 130.8
Page of
ELECTRICAL LOAD SUMMARY 415V NORMAL MCC(MC-304)
2009.11.06
SHEET : 1/2
PHASE 1
EM-301A12-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A12-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A13-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A13-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A14-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A14-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A15-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A15-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301A16-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0
EM-301A16-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0
EM-301A17-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0
EM-301A17-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0
EM-301A18-A E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0
EM-301A18-B E-301A AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0
HE-163 NITROGEN PACKAGE REGENERATION HEATER 22.0 kW 22.0 kW 100.0% 1.00 1 3 415 V 30.6 N 22.0 0.0
NITROGEN PACKAGE TURBINE OIL HEATER 1.5 kW 1.5 kW 100.0% 1.00 1 3 415 V 2.1 N 1.5 0.0
HE-99 NITROGEN PACKAGE THAWING HEATER 6.0 kW 6.0 kW 100.0% 1.00 1 3 415 V 8.3 N 6.0 0.0
CONTROL BUILDING POWER 20.0 KVA 20.0 KVA 100.0% 0.90 0.7 3 415 V 27.8 N 12.6 6.1 (To be developed)
PM-141A NITROGEN PACKAGE CHILLED WATER PUMP 3.7 kW 3.33 kW 84.5% 0.89 1 3 415 V 6.8 N 3.9 2.0
PM-141B NITROGEN PACKAGE CHILLED WATER PUMP 3.7 kW 3.33 kW 84.5% 0.89 0 3 415 V 6.8 S 0.0 0.0
PM-911A NITROGEN PACKAGE COOLING WATER PUMP 3.7 kW 0.0 kW 84.5% 0.89 1 3 415 V 6.8 N 0.0 0.0
PM-911B NITROGEN PACKAGE COOLING WATER PUMP 3.7 kW 0.0 kW 84.5% 0.89 0 3 415 V 6.8 S 0.0 0.0
NITROGEN PACKAGE TURBINE OIL PUMP & AUX 3.7 kW 3.33 kW 84.5% 0.89 1 3 415 V 6.8 N 3.9 2.0
NITROGEN PACKAGE REFRIGERATION UNIT 7.5 kW 6.75 kW 88.0% 0.91 1 3 415 V 13.0 N 7.7 3.5
NITROGEN PACKAGE REFRIGERATION UNIT 7.5 kW 6.75 kW 88.0% 0.91 0 3 415 V 13.0 S 0.0 0.0
FA-CT-91 NITROGEN PACKAGE COOLING TOWER FAN 1.1 kW 0.0 kW 79.5% 0.86 1 3 415 V 2.2 N 0.0 0.0
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
303.3 118.3
Page of
ELECTRICAL LOAD SUMMARY 415V NORMAL MCC(MC-305)
2009.11.06
SHEET : 1/2
PHASE 1
EM-301B1-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B1-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B2-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B2-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B3-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B3-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B4-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B4-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B5-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B5-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B6-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B6-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
368.4 157.0
PHASE 1
EM-301B7-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B7-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B8-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B8-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B9-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B9-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B10-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B10-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B11-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B11-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
307.0 130.8
PHASE 1
EM-301B13-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B13-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B12-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B12-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B14-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B14-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B15-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B15-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 1 3 415 V 60.5 N 30.7 13.1
EM-301B16-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0
EM-301B16-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0
EM-301B17-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0
EM-301B17-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0
EM-301B18-A E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0
EM-301B18-B E-301B AIR HEATER FAN 37.0 kW 28.4 kW 92.5% 0.92 0 3 415 V 60.5 S 0.0 0.0
MAIN SUBSTATION (POWER) 20.0 KVA 20.0 KVA 100.0% 0.90 0.7 3 415 V 27.8 N 12.6 6.1 (To be developed)
MAIN SUBSTATION (HVAC,ETC.) 30.0 KVA 30.0 KVA 100.0% 0.90 0.7 3 415 V 41.7 I 18.9 9.2 (To be developed)
PM-1101A SANITARY WATER PUMP A 3.7 kW 3.0 kW 84.5% 0.89 1 3 415 V 6.8 N 0.0 0.0
PM-1101B SANITARY WATER PUMP B 3.7 kW 3.0 kW 84.5% 0.89 0 3 415 V 6.8 S 0.0 0.0
AREA A200 RECEPTACLE 39.6 kW 39.6 kW 100.0% 0.90 0 3 415 V 61.2 S 0.0 0.0 (To be developed)
AREA A200 WELDING RECEPTACLE 35.0 kW 35.0 kW 100.0% 0.90 0 3 415 V 54.1 S 0.0 0.0 (To be developed)
AREA A300 RECEPTACLE 75.6 kW 75.6 kW 100.0% 0.90 0 3 415 V 116.9 S 0.0 0.0 (To be developed)
AREA A300 WELDING RECEPTACLE 315.0 kW 315.0 kW 100.0% 0.90 0 3 415 V 486.9 S 0.0 0.0 (To be developed)
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
277.1 119.9
Page of
ELECTRICAL LOAD SUMMARY 415V AUX. SWBD.(ASB-01), MAINTENANCE BUILDING
2009.11.06
SHEET : 1/2
PHASE 1
LABORATORY (POWER) 25.0 KVA 25.0 KVA 100.0% 0.90 0.7 3 415 V 34.8 N 15.8 7.6 (To be developed)
LABORATORY (HVAC.) 50.0 KVA 50.0 KVA 100.0% 0.90 0.7 3 415 V 69.6 I 31.5 15.3 (To be developed)
FIRE STATION (POWER) 3.0 KVA 3.0 KVA 100.0% 0.90 0.7 3 415 V 4.2 N 1.9 0.9 (To be developed)
FIRE STATION (HVAC) 4.0 KVA 4.0 KVA 100.0% 0.90 0.7 3 415 V 5.6 I 2.5 1.2 (To be developed)
MAINTENNANCE BUILDING (POWER) 20.0 KVA 20.0 KVA 100.0% 0.90 0.7 3 415 V 27.8 N 12.6 6.1 (To be developed)
MAINTENNANCE BUILDING (HVAC) 10.0 KVA 10.0 KVA 100.0% 0.90 0.7 3 415 V 13.9 I 6.3 3.1 (To be developed)
MEDITATION HALL (POWER,LTG,HVAC,ETC.) 5.0 KVA 5.0 KVA 100.0% 0.90 0.7 3 415 V 7.0 N 3.2 1.5 (To be developed)
RECEPTION CENTER (POWER,LTG,HVAC,ETC.) 10.0 KVA 10.0 KVA 100.0% 0.90 0.7 3 415 V 13.9 N 6.3 3.1 (To be developed)
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
80.0 38.8
Rev. Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power
Item
NOTE.
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
G-0301A-MCC MCC FOR G-0301A GENERATOR 100.0 kW 100.0 kW 100.0% 0.85 1 3 415 V 163.7 N Y 100.0 62.0
G-0301B-MCC MCC FOR G-0301B GENERATOR 100.0 kW 100.0 kW 100.0% 0.85 1 3 415 V 163.7 N Y 100.0 62.0
G-0301C-MCC MCC FOR G-0301C GENERATOR 100.0 kW 100.0 kW 100.0% 0.85 0 3 415 V 163.7 S Y 0.0 0.0
P-1001A-LP FIRE WATER JOCKEY PUMP LOCAL PANE 82.1 kW 71.4 kW 100.0% 0.85 1 3 415 V 134.4 N Y 71.4 44.2
P-1001B-LP FIRE WATER JOCKEY PUMP LOCAL PANE 82.1 kW 71.4 kW 100.0% 0.85 0 3 415 V 134.4 S Y 0.0 0.0
SUB. DC CHARGER (NORMAL 1) 10.0 KVA 10.0 KVA 100.0% 0.85 0.2 3 415 V 13.9 N Y 1.7 1.1
SUB. DC CHARGER (NORMAL 2) 10.0 KVA 10.0 KVA 100.0% 0.85 0.2 3 415 V 13.9 N Y 1.7 1.1
CONTROL BUILDING UPS (NORMAL 1) 100.0 KVA 100.0 KVA 100.0% 0.85 0.2 3 415 V 139.1 N Y 17.0 10.5
CONTROL BUILDING UPS (NORMAL 2) 100.0 KVA 100.0 KVA 100.0% 0.85 0.2 3 415 V 139.1 N Y 17.0 10.5
CONTROL BUILDING UPS (BYPASS) 100.0 KVA 100.0 KVA 100.0% 0.85 0 3 415 V 139.1 S Y 0.0 0.0
415V EMG. MCC (EMC-301) 83.88 kW 83.88 kW 100.0% 0.85 0.5 3 415 V 137.3 N Y 41.9 26.0
415V EMG. MCC (EMC-301) 83.88 kW 83.88 kW 100.0% 0.85 0.5 3 415 V 137.3 N Y 41.9 26.0
EMG. LTG. D.B.(ELDB-301) 97.19 kW 97.19 kW 100.0% 0.85 1 3 415 V 159.1 N Y 97.2 60.2
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
489.9 303.6
Page of
ELECTRICAL LOAD SUMMARY 415V PMCC(PC-301)
2009.11.06
SHEET : 1/2
P-0307A HOT WATER PUMP 75.0 kW 61.0 kW 94.0% 0.91 0 3 415 V 122.0 S 0.0 0.0
P-0307B HOT WATER PUMP 75.0 kW 61.0 kW 94.0% 0.91 0 3 415 V 122.0 S 0.0 0.0
PM-0308A CHILLED WATER PUMP A 90.0 kW 78.0 kW 94.0% 0.90 1 3 415 V 148.0 N 83.0 40.2
MP-0308B CHILLED WATER PUMP B 90.0 kW 78.0 kW 94.0% 0.90 1 3 415 V 148.0 N 83.0 40.2
PM-0308C CHILLED WATER PUMP C 90.0 kW 78.0 kW 94.0% 0.90 0 3 415 V 148.0 S 0.0 0.0
U-0310 CHILLER FOR BACK-UP REFRIGERATIO 380.0 kW 350.0 kW 100.0% 0.88 0 3 415 V 600.7 S 0.0 0.0
CONTROL BUILDING (HVAC.) 100.0 KVA 100.0 KVA 0.7 3 139.1 I 63.0 30.5
100.0% 0.90 415 V (To be developed)
MC-301 415V NORMAL MCC(MC-301) 187.95 kW 187.95 kW 100.0% 0.85 0.5 3 415 V 307.6 N 94.0 58.2
MC-301 415V NORMAL MCC(MC-301) 187.95 kW 187.95 kW 100.0% 0.85 0.5 3 415 V 307.6 N 94.0 58.2
MC-306 415V NORMAL MCC(MC-306) 307.03 kW 307.03 kW 100.0% 0.85 0.5 3 415 V 502.5 N 153.5 95.1
MC-306 415V NORMAL MCC(MC-306) 307.03 kW 307.03 kW 100.0% 0.85 0.5 3 415 V 502.5 N 153.5 95.1
MC-307 415V NORMAL MCC(MC-307) 277.12 kW 277.12 kW 100.0% 0.85 0.5 3 415 V 453.6 N 138.6 85.9
MC-307 415V NORMAL MCC(MC-307) 277.12 kW 277.12 kW 100.0% 0.85 0.5 3 415 V 453.6 N 138.6 85.9
MC-305 415V NORMAL MCC(MC-305) 368.43 kW 368.43 kW 100.0% 0.85 0.5 3 415 V 603.0 N 184.2 114.2
MC-305 415V NORMAL MCC(MC-305) 368.43 kW 368.43 kW 100.0% 0.85 0.5 3 415 V 603.0 N 184.2 114.2
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
1369.5 817.7
1595.044
Page of
ELECTRICAL LOAD SUMMARY 415V PMCC(PC-302)
2009.11.06
SHEET : 1/2
U-0310 CHILLER FOR BACK-UP REFRIGERATION 500.0 kW 450.0 kW 100.0% 0.89 0 3 415 V 781.6 S 0.0 0.0
ASB-01 SWBD.(ASB-01), MAINTENANCE BUILDING 80.01 kW 80.01 kW 0.5 3 123.7 N 40.0 19.4 (To be
100.0% 0.90 415 V
developed)
ASB-01 SWBD.(ASB-01), MAINTENANCE BUILDING 80.01 kW 80.01 kW 0.5 3 123.7 N 40.0 19.4 (To be
100.0% 0.90 415 V
developed)
MC-302 415V NORMAL MCC(MC-302) 368.43 kW 368.43 kW 100.0% 0.85 0.5 3 415 V 603.0 N 184.2 114.2
MC-302 415V NORMAL MCC(MC-302) 368.43 kW 368.43 kW 100.0% 0.85 0.5 3 415 V 603.0 N 184.2 114.2
MC-303 415V NORMAL MCC(MC-303) 307.03 kW 307.03 kW 100.0% 0.85 0.5 3 415 V 502.5 N 153.5 95.1
MC-303 415V NORMAL MCC(MC-303) 307.03 kW 307.03 kW 100.0% 0.85 0.5 3 415 V 502.5 N 153.5 95.1
MC-304 415V NORMAL MCC(MC-304) 303.27 kW 303.27 kW 100.0% 0.85 0.5 3 415 V 496.4 N 151.6 94.0
MC-304 415V NORMAL MCC(MC-304) 303.27 kW 303.27 kW 100.0% 0.85 0.5 3 415 V 496.4 N 151.6 94.0
LDB-301 ELECTRICAL LOAD SUMMARY NORMAL LTG. D. 436.7 kW 436.7 kW 100.0% 0.85 1 3 415 V 714.7 N 436.7 270.6
LDB-301 ELECTRICAL LOAD SUMMARY NORMAL LTG. D. 436.7 kW 436.7 kW 100.0% 0.85 0 3 415 V 714.7 N 0.0 0.0
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
1495.4 916.0
Page of
ELECTRICAL LOAD SUMMARY 415V PMCC(PC-303) JETTY AREA
2009.11.06
SHEET : 1/2
LOAD DATA Normal Fed by
Rev. Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power
Item
NOTE.
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
QUICK RELEASE HOOK LOCAL PNL 18.0 kW 18.0 kW 100.0% 1.00 0 3 415 V 25.0 S Y 0.0 0.0 Cabling by Marine Contractor
QUICK RELEASE HOOK LOCAL PNL 18.0 kW 18.0 kW 100.0% 1.00 0 3 415 V 25.0 S Y 0.0 0.0 Cabling by Marine Contractor
QUICK RELEASE HOOK LOCAL PNL 18.0 kW 18.0 kW 100.0% 1.00 0 3 415 V 25.0 S Y 0.0 0.0 Cabling by Marine Contractor
QUICK RELEASE HOOK LOCAL PNL 18.0 kW 18.0 kW 100.0% 1.00 0 3 415 V 25.0 S Y 0.0 0.0 Cabling by Marine Contractor
QUICK RELEASE HOOK LOCAL PNL 18.0 kW 18.0 kW 100.0% 1.00 0 3 415 V 25.0 S Y 0.0 0.0 Cabling by Marine Contractor
QUICK RELEASE HOOK LOCAL PNL 18.0 kW 18.0 kW 100.0% 1.00 0 3 415 V 25.0 S Y 0.0 0.0 Cabling by Marine Contractor
JETTY SUBSTATION UPS (NORMAL 1) 15.0 kVA 12.0 kVA 100.0% 0.85 0.2 3 415 V 20.9 N Y 2.0 1.3
JETTY SUBSTATION UPS (NORMAL 2) 15.0 kVA 12.0 kVA 100.0% 0.85 0.2 3 415 V 20.9 N Y 2.0 1.3
JETTY SUBSTATION UPS (BYPASS) 15.0 kVA 12.0 kVA 100.0% 0.85 0 3 415 V 20.9 S Y 0.0 0.0
FEEDERIRE ALARM 0.5 kVA 0.5 kVA 100.0% 0.85 1 3 415 V 0.7 N Y 0.4 0.3
AUX. POWER FOR TR-29 0.5 kVA 0.5 kVA 100.0% 0.85 0.5 1 240 V 2.1 N Y 0.2 0.1
HVAC 40.0 kVA 40.0 kVA 100.0% 0.85 1 3 415 V 55.6 N Y 34.0 21.1
INDOOR/OUTDOOR RECEPT. 2.0 kVA 2.0 kVA 100.0% 0.9 0 3 415 V 2.8 S Y 0.0 0.0 (To be developed)
QUICK RELEASE HOOK LOCAL PNL 18.0 kW 18.0 kW 100.0% 1.00 0 3 415 V 25.0 S Y 0.0 0.0 Cabling by Marine Contractor
QUICK RELEASE HOOK LOCAL PNL 18.0 kW 18.0 kW 100.0% 1.00 0 3 415 V 25.0 S Y 0.0 0.0 Cabling by Marine Contractor
QUICK RELEASE HOOK LOCAL PNL 18.0 kW 18.0 kW 100.0% 1.00 0 3 415 V 25.0 S Y 0.0 0.0 Cabling by Marine Contractor
QUICK RELEASE HOOK LOCAL PNL 18.0 kW 18.0 kW 100.0% 1.00 0 3 415 V 25.0 S Y 0.0 0.0 Cabling by Marine Contractor
QUICK RELEASE HOOK LOCAL PNL 18.0 kW 18.0 kW 100.0% 1.00 0 3 415 V 25.0 S Y 0.0 0.0 Cabling by Marine Contractor
QUICK RELEASE HOOK LOCAL PNL 18.0 kW 18.0 kW 100.0% 1.00 0 3 415 V 25.0 S Y 0.0 0.0 Cabling by Marine Contractor
63A WELDING RECEPTACLE 30.0 kVA 30.0 kVA 100.0% 0.80 0 3 415 V 41.7 S Y 0.0 0.0
AUX. POWER FOR TR-30 0.5 kVA 0.5 kVA 100.0% 0.85 0.5 1 240 V 2.1 N Y 0.2 0.1
JETTY INSTRUMENT PDP (NON-UPS) 6.0 kVA 6.0 kVA 100.0% 0.85 0.2 3 415 V 8.3 N Y 1.0 0.6
POWER, LIGHTING AT TUG BIRTH 100.0 kVA 100.0 kVA 100.0% 0.85 0.7 3 415 V 139.1 N Y 59.5 36.9 (To be developed)
JETTY GANGWAY 15.0 kW 15.0 kW 100.0% 0.85 0 3 415 V 24.6 S Y 0.0 0.0 Cabling by Marine Contractor
HYDRAULIC UNIT FEEDEROR LNG UNLOADING ARM 7.5 kW 7.5 kW 100.0% 0.90 0.5 3 415 V 11.6 N Y 3.8 1.8
MARITIME AREA GUARD HOUSE (POWER,LTG,HVAC,ETC.) 5.0 kVA 5.0 kVA 100.0% 0.90 1 3 415 V 7.0 N Y 4.5 2.2 (To be developed)
WT-1 WATCH TOWER (POWER,LTG,HVAC,ETC.) 1.0 kVA 1.0 kVA 100.0% 0.90 1 3 415 V 1.4 N Y 0.9 0.4 (To be developed)
WT-3 WATCH TOWER (POWER,LTG,HVAC,ETC.) 1.0 kVA 1.0 kVA 100.0% 0.90 1 3 415 V 1.4 N Y 0.9 0.4 (To be developed)
U-0111 UNLOADED LNG SAMPLING UNITS 0.5 kVA 0.5 kVA 100.0% 0.90 0 1 240 V 2.1 S Y 0.0 0.0
P-1004C-LP HI-EX FEEDEROAM PUMP LOCAL PANEL 3.7 KW 3.7 KW 100.0% 0.85 0 3 415 V 6.1 S Y 0.0 0.0
P-1004D-LP HI-EX FEEDEROAM PUMP LOCAL PANEL 3.7 KW 3.7 KW 100.0% 0.85 0 3 415 V 6.1 S Y 0.0 0.0
MOV FEEDEROR Z-1002A 1.5 KW 1.5 KW 100.0% 0.85 0 3 415 V 2.5 S Y 0.0 0.0
MOV FEEDEROR Z-1002B 1.5 KW 1.5 KW 100.0% 0.85 0 3 415 V 2.5 S Y 0.0 0.0
Z-1002A TOWER MONITOR 1.0 KW 1.0 KW 100.0% 0.80 0 3 415 V 1.7 S Y 0.0 0.0
Z-1002B TOWER MONITOR 1.0 KW 1.0 KW 100.0% 0.80 0 3 415 V 1.7 S Y 0.0 0.0
P-1003A-LP DRY CHEMICAL HYDRALIC OIL PUMP LOCAL PANEL 3.7 KW 3.7 KW 100.0% 0.85 0 3 415 V 6.1 S Y 0.0 0.0
CATHODIC PROTECTION TRU 62.0 KW 62.0 KW 100.0% 0.85 1 3 415 V 101.5 N Y 62.0 38.4 Cabling by Marine Contractor
EMERGENCY LTG. D.B. (JETTY) 11.7 KW 11.7 KW 100.0% 0.85 1 3 415 V 19.1 N Y 11.7 7.3
AREA A100 RECEPTACLE 10.8 kW 10.8 kW 100.0% 0.90 0 3 415 V 16.7 S 0.0 0.0 (To be developed)
AREA A100 WELDING RECEPTACLE 35.0 kW 35.0 kW 100.0% 0.90 0 3 415 V 54.1 S 0.0 0.0 (To be developed)
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
183.2 112.2
Page of
ELECTRICAL LOAD SUMMARY 415V FUTURE MCC(MC-308)
2009.11.06
SHEET : 1/2
LOAD DATA Normal Fed by
Item Rev. Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power
NOTE.
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
PHASE 2
C-0101C C-0101C BOG 26.0 kW 26.0 kW 100.0% 0.85 0 3 415 V 42.6 S 0.0 0.0
EM-301C-1~18-A AIR HEATER E 37.0 kW 28.4 kW 92.5% 0.92 15 3 415 V 60.5 N 460.5 196.2
kW kVAR
POWER CONSUMPTION ( PHASE 2 ) :
460.5 196.2
Page of
ELECTRICAL LOAD SUMMARY 415V FUTURE MCC(MC-309)
2009.11.06
SHEET : 1/2
LOAD DATA Normal Fed by
Rev. Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power
Item
NOTE.
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
PHASE 2
EM-301C-1~18-B AIR HEATER E-3 37.0 kW 28.4 kW 92.5% 0.92 15 3 415 V 60.5 N 460.5 196.2
T-0103-CRANE T-0103 PUMP JI 38.0 kW 38.0 kW 92.5% 0.92 0 3 415 V 62.1 S 0.0 0.0
T-0103-DR-A T-0103 CATHOD 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9
kW kVAR
POWER CONSUMPTION ( PHASE 2 ) :
462.5 197.1
Page of
ELECTRICAL LOAD SUMMARY 415V FUTURE MCC(MC-310)
2009.11.06
SHEET : 1/2
LOAD DATA Normal Fed by
Rev. Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power
Item
NOTE.
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
PHASE 2
EM-301D-1~18-A AIR HEATER E-301D FAN 37.0 kW 28.4 kW 92.5% 0.92 15 3 415 V 60.5 N 460.5 196.2
T-0103-EL T-0103 LIFT 5.9 kW 5.9 kW 84.6% 0.89 0 3 415 V 10.9 S 0.0 0.0
T-0103-DR-B T-0103 CATHODIC PROTEC 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9
kW kVAR
POWER CONSUMPTION ( PHASE 2 ) :
462.5 197.1
Page of
ELECTRICAL LOAD SUMMARY 415V FUTURE MCC(MC-311)
2009.11.06
SHEET : 1/2
PHASE 2
EM-301D-1~18-B AIR HEATER E-301D FAN 37.0 kW 28.4 kW 92.5% 0.92 15 3 415 V 60.5 N 460.5 196.2
T-0103-DR-C T-0103 CATHODIC PROTE 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9
T-0103-DR-D T-0103 CATHODIC PROTE 2.4 kW 2.4 kW 100.0% 0.90 0.8 3 415 V 3.7 N 1.9 0.9
kW kVAR
POWER CONSUMPTION ( PHASE 2 ) :
464.4 198.0
Page of
ELECTRICAL LOAD SUMMARY 415V FUTURE PMCC(PC-304)
2009.11.06
SHEET : 1/2
PHASE 2
MC-308 FUTURE MCC (MC-308) 460.54 kW 460.54 kW 100.0% 0.89 0.5 3 415 V 719.9 N 230.3 118.0
MC-308 FUTURE MCC (MC-308) 460.54 kW 460.54 kW 100.0% 0.89 0.5 3 415 V 719.9 N 230.3 118.0
MC-309 FUTURE MCC (MC-309) 462.46 kW 462.46 kW 100.0% 0.90 0.5 3 415 V 714.9 N 231.2 112.0
MC-309 FUTURE MCC (MC-309) 462.46 kW 462.46 kW 100.0% 0.90 0.5 3 415 V 714.9 N 231.2 112.0
MC-310 FUTURE MCC (MC-310) 462.46 kW 462.46 kW 100.0% 0.90 0.5 3 415 V 714.9 N 231.2 112.0
MC-310 FUTURE MCC (MC-310) 462.46 kW 462.46 kW 100.0% 0.90 0.5 3 415 V 714.9 N 231.2 112.0
MC-311 FUTURE MCC (MC-311) 464.38 kW 464.38 kW 100.0% 0.90 0.5 3 415 V 717.8 N 232.2 112.5
MC-311 FUTURE MCC (MC-311) 464.38 kW 464.38 kW 100.0% 0.90 0.5 3 415 V 717.8 N 232.2 112.5
kW kVAR
POWER CONSUMPTION ( PHASE 2 ) :
1849.8 908.8
Page of
ELECTRICAL LOAD SUMMARY 6.6KV EMERGENCY SWBD. (HT-202)
2009.11.06
SHEET :
PHASE 1
CM-0701A AIR COMPRESSOR 250.0 kW 200.0 kW 95.9% 0.90 1 3 6600 V 25.3 N Y 208.6 101.0
CM-0701B AIR COMPRESSOR 250.0 kW 200.0 kW 95.9% 0.90 0 3 6600 V 25.3 S Y 0.0 0.0
EPC-301 415V PMCC(EPC-301) 489.86 kW 489.86 kW 100.0% 0.89 0.5 3 6600 V 48.1 N Y 244.9 125.5
EPC-301 415V PMCC(EPC-301) 489.86 kW 489.86 kW 100.0% 0.89 0.5 3 6600 V 48.1 N Y 244.9 125.5
PC-303 415V PMCC(PC-303) JETTY AREA 183.2 kW 183.2 kW 100.0% 0.88 0.5 3 6600 V 18.2 N Y 91.6 49.4
PC-303 415V PMCC(PC-303) JETTY AREA 183.2 kW 183.2 kW 100.0% 0.88 0.5 3 6600 V 18.2 N Y 91.6 49.4
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
881.6 450.9
PHASE 2
EPC-301 1250.0 kVA 23.0 kVA 100.0% 0.89 1 3 6600 V 109.3 N Y 20.5 10.5
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
20.5 10.5
Page of
ELECTRICAL LOAD SUMMARY (HV)
2009.11.06
SHEET :
Rev. Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Emg. Absorbed power
Item
NOTE.
No. Power Consumption factor factor Voltage Current Mode Gen. Active Reactive
PHASE 1
PM-0101A T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 1 3 6600 V 18.4 N 155.6 79.7
PM-0101B T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 1 3 6600 V 18.4 N 155.6 79.7
PM-0101C T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0
PM-0102A T-0102 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0
PM-0102B T-0102 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0
PM-0102C T-0102 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0
CM-0101A BOIL OFF GAS COMPRESSOR 810.0 kW 701.0 kW 95.0% 0.79 1 3 6600 V 94.4 N 737.9 572.7
CM-0101B BOIL OFF GAS COMPRESSOR 810.0 kW 701.0 kW 95.0% 0.79 0.5 3 6600 V 94.4 N 368.9 286.3
EM-0106 SUBMERGED COMBUSTION VAPORISER BLOWER 500.0 kW 450.0 kW 96.3% 0.86 0 3 6600 V 52.8 S 0.0 0.0
PM-0104A HP SEND OUT PUMP 1629.0 kW 1241.0 kW 87.1% 0.91 1 3 6600 V 179.8 N 1424.8 649.2
PM-0104B HP SEND OUT PUMP 1629.0 kW 1241.0 kW 87.1% 0.91 1 3 6600 V 179.8 N 1424.8 649.2
PM-0104C HP SEND OUT PUMP 1629.0 kW 1241.0 kW 87.1% 0.91 0 3 6600 V 179.8 S 0.0 0.0
PM-0301A GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 1 3 6600 V 82.8 N 647.4 331.7
PM-0301B GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 0 3 6600 V 82.8 S 0.0 0.0
PM-0301C GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 1 3 6600 V 82.8 N 647.4 331.7
PM-0301D GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 0 3 6600 V 82.8 S 0.0 0.0
P-1002A-LP ELECTRICAL FIRE WATER PUMP LOCAL PANEL 300.0 kW 270.8 kW 94.0% 0.90 0 3 6600 V 31.0 S 0.0 0.0
P-1002B-LP ELECTRICAL FIRE WATER PUMP LOCAL PANEL 300.0 kW 270.8 kW 94.0% 0.90 0 3 6600 V 31.0 S 0.0 0.0
PC-301 415V PMCC(PC-301) 1369.49 kW 1369.49 kW 100.0% 0.89 0.5 3 6600 V 134.6 N 684.7 350.8
PC-301 415V PMCC(PC-301) 1369.49 kW 1369.49 kW 100.0% 0.89 0.5 3 6600 V 134.6 N 684.7 350.8
PC-302 415V PMCC(PC-302) 1495.44 kW 1495.44 kW 100.0% 0.89 0.5 3 6600 V 147.0 N 747.7 383.1
PC-302 415V PMCC(PC-302) 1495.44 kW 1495.44 kW 100.0% 0.89 0.5 3 6600 V 147.0 N 747.7 383.1
HT-202 6.6KV EMERGENCY SWBD. (HT-202) 881.61 kW 881.61 kW 100.0% 0.89 1 3 6600 V 86.7 N 881.6 451.7
COMPOSITION BUILDING (POWER,LTG,HVAC,ETC.) 850.0 KVA 850.0 KVA 100.0% 0.90 0.35 3 6600 V 74.4 N 267.8 129.7 (To be developed)
COMPOSITION BUILDING (POWER,LTG,HVAC,ETC.) 850.0 KVA 850.0 KVA 100.0% 0.90 0.35 3 6600 V 74.4 N 267.8 129.7 (To be developed)
kW kVAR
9844.4 5158.8
5562.3
6097.8
PHASE 2
PM-0101D T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 1 3 6600 V 18.4 N 155.6 79.7
PM-0101E T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 1 3 6600 V 18.4 N 155.6 79.7
PM-0102D T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0
PM-0102E T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0
PM-0103A T-0101 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0
PM-0103B T-0103 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0
PM-0103C T-0103 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0
PM-0103D T-0103 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0
PM-0103E T-0103 IN TANK PUMP 160.0 kW 132.7 kW 85.3% 0.89 0 3 6600 V 18.4 S 0.0 0.0
CM-0101C BOIL OFF GAS COMPRESSOR 810.0 kW 729.0 kW 95.0% 0.79 0 3 6600 V 94.4 S 0.0 0.0
PM-0104D HP SEND OUT PUMP 1629.0 kW 1241.0 kW 87.1% 0.91 1 3 6600 V 179.8 N 1424.8 649.2
PM-0104E HP SEND OUT PUMP 1629.0 kW 1241.0 kW 87.1% 0.91 1 3 6600 V 179.8 N 1424.8 649.2
PM-0301E GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 1 3 6600 V 82.8 N 647.4 331.7
PM-0301F GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 0 3 6600 V 82.8 S 0.0 0.0
PM-0301G GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 1 3 6600 V 82.8 N 647.4 331.7
PM-0301H GLYCOL WATER PUMP 800.0 kW 615.0 kW 95.0% 0.89 0 3 6600 V 82.8 S 0.0 0.0
HT-202
PC-302
PC-304 FUTURE PMCC(PC-305) 1849.84 kW 1849.84 kW 100.0% 0.89 0.5 3 6600 V 181.8 N 924.9 473.9
PC-304 FUTURE PMCC(PC-305) 1849.84 kW 1849.84 kW 100.0% 0.89 0.5 3 6600 V 181.8 N 924.9 473.9
kW kVAR
POWER CONSUMPTION ( PHASE 2 ) :
6305.3 3068.7
kW kVAR
POWER CONSUMPTION ( PHASE 1 & 2 ) :
16149.7 8227.5
#REF!
18124.68 KVA
1585.545
792.8
ELECTRICAL CONSUMER LIST & LOAD BALANCE Page 1 of
SPACE HEATER LIST 12
REV. 1A
DD-CAL-TS-EL-0000-23A01 SHEET : 1/1
2008.12.5
LOAD DATA Normal
Item Rev. Equip. No. Designation Rated BHP / Power Efficiency Power Run Ph Nominal Rated Stand-by Absorbed power MCC MCC LOAD Location
NOTE.
No. Power Consumption factor factor Voltage Current Mode Active Reactive TYPE No. TYPE (Unit/Build.)
(estimated) Unit (estimated) Unit % pu pu V A N/S kW kVAR
PHASE 1
PHASE 1
1 P-0307A-H HOT WATER PUMP SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A800
2 P-0307B-H HOT WATER PUMP SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 1 1 240 V 1.7 N 0.4 0.0 FEEDER A800
3 C-0101A-H C-0101A COMP. MOTOR SPACE HEATER 1.2 kW 1.2 kW 100.0% 1.00 0 1 240 V 5.0 S 0.0 0.0 FEEDER A300
4 C-0101B-H C-0101B COMP. MOTOR SPACE HEATER 1.2 kW 1.2 kW 100.0% 1.00 0 1 240 V 5.0 S 0.0 0.0 FEEDER A300
5 E-0106-H E-0106 SCV BLOWER SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A300
6 P-301A-H GW PUMP SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A300
7 P-301B-H GW PUMP SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A300
8 P-301C-H GW PUMP SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A300
9 P-301D-H GW PUMP SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A300
10 P-0303A-H GLYCOL WATER PUMP SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A300
11 P-0303B-H GLYCOL WATER PUMP SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A300
12 EM-301A1~18-A-H SPACE HEATER FOR FANS FOR AIR HEATER E-301A 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A400
13 EM-301A1~18-B-H SPACE HEATER FOR FANS FOR AIR HEATER E-301A 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A400
14 EM-301B1~18-A-H SPACE HEATER FOR FANS FOR AIR HEATER E-301B 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A400
15 EM-301B1~18-B-H SPACE HEATER FOR FANS FOR AIR HEATER E-301B 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A400
16 P-0308A-H CHILLED WATER PUMP A SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A500
17 P-0308B-H CHILLED WATER PUMP B SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A500
18 P-0308C-H CHILLED WATER PUMP C SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER A500
19 P-1002A-H ELECTRICAL FIRE WATER PUMP MOTOR SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER SUPPLIED BY LP ?(HOLD) A700
20 P-1002B-H ELECTRICAL FIRE WATER PUMP MOTOR SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER SUPPLIED BY LP ?(HOLD) A700
21 P-1001A-H FIRE WATER JOCKEY PUMP SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER SUPPLIED BY LP ?(HOLD) A700
22 P-1001B-H FIRE WATER JOCKEY PUMP SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 1 1 240 V 1.7 N 0.4 0.0 FEEDER SUPPLIED BY LP ?(HOLD) A700
23 C-0701A-H INSTRUMENT AIR COMPRESSOR SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 0 1 240 V 1.7 S 0.0 0.0 FEEDER SUPPLIED BY LP ?(HOLD) A500
24 C-0701B-H INSTRUMENT AIR COMPRESSOR SPACE HEATER 0.4 kW 0.4 kW 100.0% 1.00 1 1 240 V 1.7 N 0.4 0.0 FEEDER SUPPLIED BY LP ?(HOLD) A500
kW kW
kW
kW kVAR
POWER CONSUMPTION ( PHASE 1 ) :
0.4 0.0
FLSN non sparking motors - IP 55 - Cl. F - 400V +/- 10 % (Source Leroy Sommer)
Mechanical 3000 rpm 1500 rpm 1000 rpm
Rated Power P.F. h P.F. h P.F. h
0.64 52.3%
0.64 52.3%
0.64 52.3%
0.64 52.3%
0.60 54.5%
0.63 64.0%
0.66 60.0%
0.68 70.9%
0.62 67.1%
0.63 71.7%
0.56 72.7%
0.56 72.7%
0.66 83.9%
0.65 82.6%
0.68 86.3%
0.72 88.1%
0.74 89.4%
0.74 91.1%
0.67 90.8%
0.79 92.8%
0.80 93.1%
0.79 93.5%
0.82 94.0%
0.81 94.0%
0.81 94.0%
0.80 94.0%
0.80 94.0%
0.80 94.0%
0.80 94.0%
0.82 94.0%
0.82 94.0%
0.82 94.0%
0.82 94.0%
0.82 94.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%
0.82 95.0%