Testing For Current Transformer Parameters

The document reports the results of tests on a current transformer with the serial number KH026G located at Schneider-Electric. Tests conducted include resistance, burden, excitation, ratio, and error measurements to verify the transformer's performance against standards. The transformer was found to have a ratio of 2500.0:1.00691 with a phase displacement of 0.56 minutes and an error of 0.6908% well within allowable limits.

Uploaded by

322399mk7086
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
282 views2 pages

Testing For Current Transformer Parameters

The document reports the results of tests on a current transformer with the serial number KH026G located at Schneider-Electric. Tests conducted include resistance, burden, excitation, ratio, and error measurements to verify the transformer's performance against standards. The transformer was found to have a ratio of 2500.0:1.00691 with a phase displacement of 0.56 minutes and an error of 0.6908% well within allowable limits.

Uploaded by

322399mk7086
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Company Name: Schneider-Electric

Company Address: 10 Harris Rd, Malaga WA 6090

Order Number:

General test information: Date/Time: 2015-05-19, 12:29:20


Test device: CT-Analyzer Device Serial No.: KH026G
File name: C:\Users\sesa286234\Documents\OMICRON\CTAnalyzer\RemoteEFL\TEMP\XMLData(1).xml
Assessments: OK

Used test settings:


I-pn: 2500.0 A Location: Object:
I-sn: 1.0 A Company: Chevron Manufacturer: RS ISOLSEC
Rated burden: 20.0 VA / 0.8 Country: Australia Type: TA34
Operating burden: 20.0 VA / 0.8 Station: WDS Serial number: 13/360907/10
Applied standard: IEC 60044-1 Feeder/Bay: 0EK-12A41 Panel A1 Core number: 1
Core type (P/M): P Phase: L1-T13 Tap: S1-S2
Class: 5P IEC-ID Optional:
ALF: 20.0 Ts:
f: 50.0 Hz max. Rct: 19.056 Ω

Resistance test: Burden test:


Rmeas (17.8°C): 15.53387 Ω Burden: cos φ: Z:
Rref (75°C): 19.05562 Ω Vmeas: Imeas:

Excitation test:
V-kn: 699.418 V I-kn: 0.005341 A Result with rated burden: Result with operating burden:
V-kn 2: #N/A I-kn 2: #N/A ALF: >25.453765 ALFi: 25.25 ALF: >25.453765 ALFi: 25.25
Ls: 0.0281686H Lm: 524.9761 H Ts: 14.976s Ts: 14.976s
Kr: 80.91 %

Ratio test:
Ratio: 2500.0 : 1.00691 ε : 0.6908 % Δφ: 0.56 min Polarity: OK N: 2481.93
εc : 0.689 %

Excitation curve data


Excitation curve data

1000

100
Es / V

10

0.1
0.00001 0.0001 0.001 0.01 0.1 1 10

le / A

Series1 (I-kn,V-kn) (I-kn2,V-kn2) Series 2


Current ratio error in % at % of rated current
VA/cosPhi 1 5 10 20 50 100 120 200
20 VA/ 0.8 0.537 0.612 0.641 0.664 0.682 0.691 0.692 0.696
10 VA/ 0.8 0.644 0.662 0.679 0.694 0.700 0.702 0.705
5 VA/ 0.8 0.663 0.675 0.688 0.700 0.706 0.707 0.710
2.5 VA/ 1 0.681 0.688 0.696 0.705 0.710 0.711 0.713
VA/

Phase displacement in [min] at % rated current


VA/cosPhi 1 5 10 20 50 100 120 200
20 VA/ 0.8 8.994 3.074 1.895 1.244 0.775 0.562 0.600 0.609
10 VA/ 0.8 3.153 1.978 1.285 0.793 0.581 0.539 0.596
5 VA/ 0.8 3.152 2.019 1.325 0.809 0.595 0.550 0.482
2.5 VA/ 1 3.332 2.194 1.457 0.898 0.666 0.618 0.509
VA/

Error borders according IEC 60044-1 at % of rated current


Mult.Factor 1 5 10 Error Graph
Ratio 20 50 100 120 200
1.00 1.00 1.00
-1.00 -1.00 -1.00
0.800

0.700

0.600
Current deviation [%]

0.500 100% Load

50% Load
0.400

25% Load
0.300

0.200

0.100

0.000
0 50 100 150 200 250
% I-pn