Lab Manual Exp 6 - Liquid Level Flow Process Control (Electronic)
Lab Manual Exp 6 - Liquid Level Flow Process Control (Electronic)
LABORATORY: SECTION of 1
REVISION NO:
CHEMICAL PROCESS
29 SEPT
EXPERIMENT: LEVEL FLOW EFFECTIVE DATE:
2014
PROCESS CONTROL
AMENDMENT
(ELECTRONIC)
DATE:
COURSE CODE
EXPERIMENT NO. EXPERIMENT 7
INTRODUCTION: /5%
PROCEDURE: /5%
RESULTS& CALCULATIONS /15%
ANALYSIS /15%
DISTRIBUTION OF MARKS FOR DISCUSSIONS: /20%
LABORATORY REPORT: ADDITIONAL QUESTIONS /15%
CONCLUSION /10%
REFERENCES: /5%
TOTAL: /100%
I hereby declare that I have prepared this report with my own efforts. I also admit to
not accept or provide any assistance in preparing this report and anything
that is in it is true.
5.0 PROCEDURE
5.1 STARTUP PROCEDURES
1. Turn on the main power supply switch. All panel instrument will lit
up
2. Check the various manual valve as follow
• All pumps (P81 & P82) suction, and discharge valves are fully
opened
• Manual by-pass valve for each pumps is shut.
• Control valve positioners (PP) must be selected.
• Bottom drain valves of tank T81 and T82 always shut
• Open overflow valves for Tank T82 and T81
3. There are two controller FIC81, LIC81 and recorder LFR81 in front of
the panel. Be familiar with their basic operation before proceed with
the experiment.
• Make sure the two controllers VIC81, LIC81 are both in their
MANUAL (M) mode
• Set the two controller FIC81, LIC81 at their DEFAULT values as
follows:
• With both controller in MANUAL (M) mode, set their control output
at 50%. Check the valve position at FCV81 and LCV 81 are both
about 50% opened.
• Start the recorder LFR81 by pressing ON the RCD pushbutton.
4. Start pump P81 and verify there is a flow into T82. Otherwise, the
manual valves are not fully opened. Make sure pump by-pass valve
B81 fully shut to provide maximum flow to T82 only.
FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 1
REVISION NO:
CHEMICAL PROCESS
29 SEPT
EXPERIMENT: LEVEL FLOW EFFECTIVE DATE:
2014
PROCESS CONTROL
AMENDMENT
(ELECTRONIC)
DATE:
5. Please noted:
• At tank T82, note the Level ruler and the Level: 0mm is just
above the bottom tip of the level probe LE81
• When the level in tank T82 is about 50%, start the outflow
pump P82 and verify its flow into T81. Otherwise the manual
valves are not fully opened. Shut fully pump bypass valve B82
for maximum flow.
• DO NOT START THE OUTFLOW PUMP P82 IF NO WATER IN
TANK T82
6. At the controller FIC81, set SV = 1.2 m3/Hr. Switch FIC81 to AUTO
(A) mode
7. Please noted:
• Tank T82 is non-Self Regulating and can overflow if the inflow
rate exceeds the Outflow rate
• With LIC81 in MANUAL (M) mode, manually adjust the control
output to LCV 81 so that the level in T82 approaches set point
400mm. Switch LIC81 to AUTO (A) mode
8. Check the recorder LFR81 and examine the level and flow response
9. If recording is no longer required, OFF the recorder by pressing RCD
pushbutton
PART A:
a) With the SP of LIC81 at 200mm in AUTO mode, wait till the level PV
in LICD81 is steady at its SP.
b) Take the level reading at LIC81 and LFR81. Also take the level
measurement at the tank ruler.
c) Mark on the chart paper on the RED color that SP=200
d) Take a second set of reading when the level is not fluctuating and PV
is about 200mm as follow:
• Stop pump P81 and P82.
• With LIC81 in MANUAL mode, shut LCV81 fully with MV= 0
• Shut one of manual valve adjacent to LCV81.
• Take the level reading again as in above state. Its does not matter
that the PV is not at its SP for this second set reading.
FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 1
REVISION NO:
CHEMICAL PROCESS
29 SEPT
EXPERIMENT: LEVEL FLOW EFFECTIVE DATE:
2014
PROCESS CONTROL
AMENDMENT
(ELECTRONIC)
DATE:
PART B
a) REMEMBER TO OPEN FULLY ALL THE MANUAL VALVE ADJACENT
TO LVC81 BEFORE PROCEEDING TO NEW SETPOINT VALUE
b) View the SP at LIC81. Change the SP = 400mm and push BLUE
button once to register the new SP
c) Start pump P81 and P82. Make sure
LIC81 = Auto (A) mode with SP = 400mm
FIC81 = Manual (M) mode with MV = 50%
PART C
a) Take the level readings as previously (SP=200mm) when;
• the tank level PV is steady at its SP (view LIC81)
• when pumps P81, P82 are OFF and LCV81 and one of the adjacent
manual valve are fully shut.
b) Repeat the procedure (PART B) with various other level set point (SP)
at LIC81, i.e SP=500 ,SP=700
c) Record all the result in the Table 2. in the Result Section 6
5.4 LEVEL CONTROL AND TUNNING
1. Do the following quick check:
• Pumps P81 and P82 are pumping.
• By-pass valve of for control valve FCV81 and level control valve
LCV81 are shut.
• Both controllers LIC81 and FIC81 in MANUAL (M) mode set with
the DEFAULT value ( Table 1 )
• Check the IAS are set accordingly
• The chart recorder LFR81 is running and indicate “RCD” at the
display panel.
2. Switch the flow controller FIC81 to Manual (M) mode and manually
adjust MV = 50% observe the Inflow in to tank T82
3. The experiment is to be conducted with LIC81 in AUTO mode using
various PID value and disturbances.
FACULTY : UniKL MICET EDITION: 1
LABORATORY: SECTION of 1
REVISION NO:
CHEMICAL PROCESS
29 SEPT
EXPERIMENT: LEVEL FLOW EFFECTIVE DATE:
2014
PROCESS CONTROL
AMENDMENT
(ELECTRONIC)
DATE:
4. Check pump P82 is ON and pumping the outflow to T81.
With LIC81 in AUTO (A) mode, SP = 400mm and PID at Default value,
and apply of disturbance describe below:
i. LIC81, SP = 400mm , 1.P = 20%, 1.I = 20sec, 1.D = OFF
a. Inflow load step change disturbance
• LIC81 must be in AUTO mode with SP and PID value above
• In AUTO mode, observe the level response until it is almost
steady or consistent at 400mm
• Step decrease the inflow rate by shutting FCV81 from MV
=50% to MV = 70% . This is an inflow load step
disturbance test
• Observe the level response of Red pen at LFR81 until it is
steady at it set point or continues to oscillate even after 3
cycles.
b. Outflow load step change or disturbance
• LIC81 still in AUTO mode, SP = 400mm with same PID
value
• Switch LIC81 to MANUAL mode, note that the SP value
display “0”. Manually step increase or decrease the output
“0” by about 30% and then switch back to AUTO mode.
This is outflow load step disturbance
• Observe the level response (Red pen)
𝐷𝑖𝑠𝑡𝑎𝑛𝑐𝑒, 𝑚𝑚 3600𝑠𝑒𝑐𝑠
𝑇𝑖𝑚𝑒 𝑡𝑎𝑘𝑒𝑛, 𝑠𝑒𝑐𝑠 = ×
500𝑚𝑚/𝐻𝑟 1𝐻𝑟
READINGS
LCV81/Manual
valve shut
B a) 400mm
b) P81,P82 OFF
LCV81/Manual
valve shut
C a) 500mm
b) P81,P82 OFF
LCV81/Manual
valve shut
D a) 600mm
b) P81,P82 OFF
LCV81/Manual
valve shut
8.0 DISCUSSIONS
Discuss the overall experiment on data obtain based on your understanding.
Discussion should relate reasons for the phenomena/results obtained,
theoretical parts, suggested reasons (if necessary but back with sound
theoretical knowledge) and your overview understanding.
9.0 CONCLUSION
Conclusion is merely a summary of the important findings already reported
in the discussion section. It also relates to the objectives stated earlier.
11.0 REFERENCES
Minimum of at least 5 references (with 3 of them are paper/book/chapter
based)